Hoshizaki America FS-1500MLH-C Service Manual

Hoshizaki
Modular Cubelet Serenity Series with "F-A" Control Board
Models FS-1001MLH-C with SRC-10H
“A Superior Degree
of Reliability”
www.hoshizaki.com
FS-1022MLH-C with SRC-10H FS-1500MLH-C with SRC-14H
SERVICE MANUAL
Number: 73203 Issued: 1-5-2015 Revised: 1-7-2015
WARNING
Only qualied service technicians should install and service the appliance. To obtain the name and phone number of your local Hoshizaki Certied Service Representative, visit www.hoshizaki.com. No service should be undertaken until the technician has thoroughly read this Service Manual. Failure to service and maintain the appliance in accordance with this manual will adversely affect safety, performance, component life, and warranty coverage and may result in costly water damage. Proper installation is the responsibility of the installer. Product failure or property damage due to improper installation is not covered under warranty.
Hoshizaki provides this manual primarily to assist qualied service technicians in the service of the appliance.
Should the reader have any questions or concerns which have not been satisfactorily addressed, please call, send an e-mail message, or write to the Hoshizaki Technical Support Department for assistance.
Phone: 1-800-233-1940; (770) 487-2331 Fax: 1-800-843-1056; (770) 487-3360
E-mail: techsupport@hoshizaki.com
HOSHIZAKI AMERICA, INC. 618 Highway 74 South Peachtree City, GA 30269 Attn: Hoshizaki Technical Support Department
Web Site: www.hoshizaki.com
NOTE: To expedite assistance, all correspondence/communication MUST include the
following information:
• Model Number
• Serial Number
• Complete and detailed explanation of the problem.
2
IMPORTANT
This manual should be read carefully before the appliance is serviced. Read the warnings and guidelines contained in this manual carefully as they provide essential information for the continued safe use, service, and maintenance of the appliance. Retain this manual for any further reference that may be necessary.
CONTENTS
Important Safety Information ................................................................................................. 5
I. Construction and Water/Refrigeration Circuit Diagram ....................................................... 8
A. Construction .................................................................................................................. 8
1. Icemaker .................................................................................................................. 8
2. Condensing Unit ...................................................................................................... 9
3. Icemaking Unit ....................................................................................................... 10
B. Water/Refrigeration Circuit Diagram .............................................................................11
II. Sequence of Operation and Service Diagnosis ............................................................... 12
A. Sequence of Operation Flow Chart ............................................................................. 12
1. Icemaking and Drain Cycle .................................................................................... 12
2. Shutdown .............................................................................................................. 13
B. Service Diagnosis ....................................................................................................... 14
C. Control Board Check ................................................................................................... 22
D. Bin Control Check ....................................................................................................... 27
E. Float Switch Check and Cleaning ............................................................................... 31
F. Diagnostic Tables ......................................................................................................... 33
III. Controls and Adjustments ............................................................................................... 36
A. Control Board .............................................................................................................. 36
1. Control Board Layout ............................................................................................. 37
2. LED Lights and Audible Alarm Safeties ................................................................. 38
3. Ice Purge Cycle Bypass ......................................................................................... 39
B. Controls and Adjustments ........................................................................................... 39
1. Default Dip Switch Settings .................................................................................... 39
2. BC1 (Infrared Sensor) Shutdown Delay (S1 dip switch 1, 2, 3) ............................ 40
3. Drain Frequency Control (S1 dip switch 4) ............................................................ 40
4. Continuous Dispensing Timer (S1 dip switch 5 & 6) .............................................. 40
5. Bin Control Selector (S1 dip switch 7) ................................................................... 41
6. BC (Mechanical Stand-Alone) Shutdown Delay (S1 dip switch 8) ......................... 41
7. Factory Use (S1 Dip Switch 9 & 10) ....................................................................... 41
C. Power Switch and Control Switch ................................................................................ 42
IV. Refrigeration Circuit and Component Service Information.............................................. 43
A. Refrigeration Circuit Service Information .................................................................... 43
B. Component Service Information .................................................................................. 46
V. Maintenance .................................................................................................................... 55
VI. Disposal .......................................................................................................................... 57
3
VII. Technical Information ..................................................................................................... 58
A. Specication and Performance Data ........................................................................... 58
1. FS-1001MLH-C with SRC-10H ............................................................................... 58
2. FS-1022MLH-C with SRC-10H .............................................................................. 59
3. FS-1500MLH-C with SRC-14H .............................................................................. 60
4. SRC-10H and SRC-14H ........................................................................................ 61
B. Wiring Diagram ............................................................................................................ 62
1. Icemaker ................................................................................................................ 62
2. Condensing Unit .................................................................................................... 63
4

Important Safety Information

Throughout this manual, notices appear to bring your attention to situations which could result in death, serious injury, damage to the appliance, or damage to property.
WARNING Indicates a hazardous situation which could result in death or
serious injury.
NOTICE Indicates a situation which could result in damage to the
appliance or property.
IMPORTANT Indicates important information about the use and care of the
appliance.
WARNING
The appliance should be destined only to the use for which it has been expressly conceived. Any other use should be considered improper and therefore dangerous. The manufacturer cannot be held responsible for injury or damage resulting from improper, incorrect, and unreasonable use. Failure to service and maintain the appliance in accordance with this manual will adversely affect safety, performance, component life, and warranty coverage and may result in costly water damage.
To reduce the risk of death, electric shock, serious injury, or re, follow basic precautions including the following:
• Only qualied service technicians should install and service the appliance.
• The appliance must be installed in accordance with applicable national, state, and local codes and regulations. Failure to meet these code requirements could result in death, electric shock, serious injury, re, or damage to the appliance.
• The appliance must be installed in accordance with applicable national, state, and local codes and regulations.
• To reduce the risk of electric shock, do not touch the icemaker power switch or plug with damp hands. Make sure the icemaker power switch is in the "OFF" position before plugging in or unplugging the icemaker.
Before Servicing: FS: Move the icemaker's power switch to the "OFF" position. Unplug the icemaker from the electrical outlet. SRC: Turn off the power supply to the remote condensing unit. Place the disconnect (if applicable) in the off position. Lockout/Tagout to prevent the power supply from being turned back on inadvertently.
• Do not make any alterations to the icemaker or condensing unit. Alterations could result in electric shock, injury, re, or damage to the appliance.
5
WARNING, continued
FS
• The icemaker requires an independent power supply of proper capacity. See the nameplate for electrical specications. Failure to use an independent power supply of proper capacity can result in a tripped breaker, blown fuse, damage to existing wiring, or component failure. This could lead to heat generation or re.
THE ICEMAKER MUST BE GROUNDED. The icemaker is equipped with a NEMA5-15 three-prong grounding plug to reduce the risk of potential shock hazards. It must be plugged into a properly grounded, independent 3-prong wall outlet. If the outlet is a 2-prong outlet, it is your personal responsibility to have a qualied electrician replace it with a properly grounded, independent 3-prong wall outlet. Do not remove the ground prong from the power cord and do not use an adapter plug. Failure to properly ground the icemaker could result in death or serious injury.
• Do not use an extension cord.
• Do not use an icemaker with a damaged power cord. The power cord should not be altered, jerked, bundled, weighed down, pinched, or tangled. Such actions could result in electric shock or re. To unplug the icemaker, be sure to pull the plug, not the cord, and do not jerk the cord.
• Do not place ngers or any other objects into the ice discharge opening.
SRC
• The remote condensing unit requires an independent power supply of proper capacity. See the nameplate for electrical specications. Failure to use an independent power supply of proper capacity can result in a tripped breaker, blown fuse, damage to existing wiring, or component failure. This could lead to heat generation or re.
• Electrical connection must be hard-wired to the remote condensing unit and must meet national, state, and local electrical code requirements. Failure to meet these code requirements could result in death, electric shock, serious injury, re, or damage.
THE REMOTE CONDENSER UNIT MUST BE GROUNDED. The power supply and ground connection to the remote condenser unit are supplied from the icemaker. Failure to properly ground the remote condenser unit could result in death or serious injury.
• Wire routing (conduit) and disconnect (if required) must meet national, state, and local electrical code requirements. Failure to meet these code requirements could result in death, electric shock, serious injury, re, or damage.
6
NOTICE
• Follow the instructions in this manual carefully to reduce the risk of costly water damage.
• In areas where water damage is a concern, install in a contained area with a oor drain.
• Install the appliance in a location that stays above freezing. Normal operating ambient temperature must be within 45°F to 100°F (7°C to 38°C).
• Do not leave the icemaker on during extended periods of non-use, extended absences, or in sub-freezing temperatures. To properly prepare the icemaker for these occasions, follow the instructions provided in the instruction manual.
• Do not place objects on top of the appliance.
• The dispenser unit/ice storage bin is for ice use only. Do not store anything else in the dispenser unit/ice storage bin.
7

I. Construction and Water/Refrigeration Circuit Diagram

A. Construction

1. Icemaker

Top Panel
Inlet Water Valve
Cutter, Extruding Head, Evaporator
Reservoir
Ice Chute
Thermostatic Expansion Valve
Strainer
High-Side Service Valve
Low-Side Service Valve
Float Switch
Drier
BC2 (mechanical backup)
Spout
Evaporator Heater
Control Box
Power Cord
BC1 (infrared sensor)
Front Panel Right Side
Model Shown: FS-1500MLH-C
Gear Motor
Drain Valve
Panel
8

2. Condensing Unit

a) SRC-10H
Top Panel
Headmaster (C.P.R.)
Condenser
High-Side Service Valve
Low-Side Service Valve
Left Side Panel
b) SRC-14H
High-Pressure Switch
Fan Motor
Receiver
Top Panel
Compressor
Control Low-Pressure Switch
Safety Low-Pressure Switch
Right Side Panel
Control Box
Control Box Cover
Louver Panel
Condenser
Headmaster (C.P.R.)
Receiver
Left Side Panel
Fan Motors
High-Side Service Valve
Compressor
Low-Side Service Valve
Control Low-Pressure Switch
High-Pressure Switch
Right Side Panel
Control Box
Control Box Cover
Louver Panel
Safety Low-Pressure Switch
9

3. Icemaking Unit

Cutter
Extruding Head and Upper Bearing
Evaporator Heater
Auger
Mechanical Seal
O-Ring
Evaporator Flange
Seal Bolts and Washers
Evaporator
Socket Head Cap Screw and Split Lock Washer
Spline Coupling
Socket Head Cap Screw and Split Lock Washer
Housing and Lower Bearing
Hex Bolt and Washer
Gear Motor
10

B. Water/Refrigeration Circuit Diagram

Receiver
Headmaster (C.P.R.)
High-Pressure
Switch
SRC
FS
Condenser
Fan Motors
High-Side
Service
Strainer
Pump-Down
Solenoid Valve
Expansion Valve
Valves
Liquid Line
Suction Line
Drier
Drain
Low-Side
Service
Valve
Valves
Control Low-Pressure Switch
Drain Outlet
Compressor
Safety Low-Pressure Switch
Inlet
Water
Float Switch
Valve
Reservoir
Evaporator
Water Level
Gear
Motor
Overow
Water
Supply
Line
11

II. Sequence of Operation and Service Diagnosis

A. Sequence of Operation Flow Chart

1. Icemaking and Drain Cycle

WV continues
GM de-energized
Low Water Safety
Shutdown
90. sec. PT terminates
unit shuts down and
1-beep alarm continues.
When UFS closes, alarm
resets and 2. Ice Purge
Cycle starts.
Normal Operation
UFS open
WV energized
PDS de-energized
(CLPS opens)
Comp de-energized
FMR de-energized
GM continues
90 sec.
90 sec. FT exceeded, 90
sec. PT starts and 1-beep
Purge Timer
Rell
alarm sounds
FT Maximum
90 sec.
LFS closed
FT off (90 sec.)
UFS closed
FZT starts (30 min.)
FT terminated
WV de-energized
Comp continues
EH continues
FMR continues
GM continues
PDS continues
Low Water Safety
FMR-fan motor-remote
FT-ll timer (low water safety)
FZT-freeze timer
GM-gear motor
LFS-lower oat switch
PDS-pump-down solenoid valve
PT-purge timer
UFS-upper oat switch
WV-inlet water valve
to "1. Fill Cycle" above
4. Icemaker Restart
10-min. DT terminated
DV de-energized
1-in-12 DT reset
Legend:
BC1-bin control 1 (infrared sensor)
BC2-bin control 2 (mechanical backup)
CB-control board
CCH-crankcase heater
CLPS-control low-pressure switch
Comp-compressor
DC-drain cycle
DT-drain timer
DV-drain valve
EH-evaporator heater
4. 1-in-12 Drain Cycle - Although the factory default 1-in-1 drain cycle
is recommended, a 1-in-12 drain cycle is available. For 1-in-12 drain cycle
sequence, see "3. 1-in-12 Hour Drain Cycle & Restart (optional)."
3. Freeze Cycle
2. Ice Purge Cycle
1. Fill Cycle
1-in-1 drain cycle. DV opens for 2 sec.
every hour (CB S1 Dip Switch 4).
To bypass, press the
"SERVICE" button after
3. 10-Min. Drain
UFS open
LFS open (WV on)
FT starts (90 sec.)
FZT terminated
WV energized
Comp continues
EH continues
FMR continues
GM continues
PDS continues
30-min. FZT
DV de-energizes, no interruption
in ice procuction
Icemaker status does not change.
5 min.
GM starts.
5 or 30 sec.
(S1 Dip Switch 7)
and sounds a 5-beep alarm.
PDS energized
CLPS closed
Comp energized
FMR energized
EH continues
GM continues
EH energized
GM energized
FZT exceeded (LFS does not
2. Continued Operation
open): CB shuts down icemaker
2. Ice Purge Cycle
DV energized
GM de-energized
5 min.
Comp de-energized
FMR de-energized
PDS de-energized
GM continues
DV energizes for 2 sec.
operation
1. DT Initiates DC
FT Maximum
90 sec.
LFS closed
UFS closed
1. DT Initiates DC
Continued uninterrupted
FZT starts
FT terminated
WV de-energized
FS Models "F-A" Control Board Sequence of Operation Flow Chart - Icemaking and Drain Cycle
1. Startup
Power Switch "ON"
Control Switch in "ICE"
POWER OK LED on
BC1 Green LED on
Startup
BC1 Yellow LED off
BC2 Closed
WV energized
If Fill > 90 sec. FT
1-beep alarm sounds
WV continues
When UFS closes
alarm resets and
2. Ice Purge Cycle starts.
12
2. 1-in-1 Drain Cycle
(CB S1 dip switch 4 "OFF")
& Restart (optional)
(CB S1 dip switch 4 "ON")
3. 1-in-12 Drain Cycle
Note: CCH energizes when power is supplied to the
SRC. CCH de-energizes when Comp is de-energized.
See "VIII.B.2. Condensing Unit."

2. Shutdown

4. Icemaker Restart
3. Icemaker Off
to "2. Ice Purge Cycle" in
Icemaking and Drain Cycle
BC1 Green LED on
BC1 Yellow LED off
Chart
FMR-fan motor-remote
FT-ll timer (low water safety)
FZT-freeze timer
GM-gear motor
LFS-lower oat switch
PDS-pump-down solenoid valve
PT-purge timer
UFS-upper oat switch
WV-inlet water valve
BC1 de-activated
to "2. Ice Purge Cycle" in
Icemaking and Drain Cycle
Chart
2. Ice Purge Cycle
1. Bin Full
BC1 delay determined by CB S1 dip
switch 1, 2, 3
5 min.
BC1 Yellow LED (ashing or steady)
GM de-energized
PDS de-energized
(CLPS opens)
Comp de-energized
FMR de-energized
BC1 activated
GM continues
EH continues
2. Icemaker Off 3. Icemaker Restart
1. Bin Full
Ice level lowered
Legend:
BC2 de-activated (closed)
All Components de-energized
BC2 activated (open)
BC1-bin control 1 (infrared sensor)
BC2-bin control 2 (mechanical backup)
CB-control board
CLPS-control low-pressure switch
Comp-compressor
DC-drain cycle
DT-drain timer
DV-drain valve
EH-evaporator heater
"FS Models F-A" Control Board Sequence of Operation Flow Chart - Shutdown
1. BC1 (infrared sensor) Shutdown
BC1 Green LED on
BC1 Yellow LED off
BC2 Closed
If BC1 fails to shutdown the icemaker,
BC2 opens and a 9-beep alarm
sounds. See "II.D. Bin Control Check."
2. BC2 (mechanical backup) Shutdown
When BC2 is activated, a 9-beep alarm
sounds. See "II.D. Bin Control Check."
BC1 Green LED on
BC1 Yellow LED on
(ashing or steady)
BC2 Closed
13

B. Service Diagnosis

WARNING
• The appliance should be diagnosed and repaired only by qualied service personnel to reduce the risk of death, electric shock, serious injury, or re.
• Risk of electric shock. Use extreme caution and exercise safe electrical practices.
• Moving parts (e.g., fan blade) can crush and cut. Keep hands clear.
CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews are securely in place after the appliance is serviced. Make sure that none have fallen into the dispenser unit/storage bin.
• Make sure all food zones in the icemaker and dispenser unit/storage bin are clean after the unit is serviced.
1. Ice Production Check
To check production, prepare a bucket or pan to catch the ice and a set of scales to weigh the ice. After the appliance has operated for 10 to 20 min., catch the ice production for 10 min. Weigh the ice to establish the batch weight. Multiply the batch weight by 144 for the total production in 24 hours. When conrming production or diagnosing low production, reference production information found in "VIII.A. Specication and Performance Data."
14
2. Diagnostic Procedure
This diagnostic procedure is a sequence check that allows you to diagnose the electrical system and components. Before proceeding, check for correct installation, proper voltage per appliance nameplate, and adequate water pressure (10 PSIG to 113 PSIG). Check that both the 24VAC circuit fuse and the 115VAC GM fuse are good.
Note: • When checking high voltage (115VAC), always choose a neutral (W) wire to
establish a good neutral connection.
• When checking low voltage (24VAC), always choose a neutral (LBU) wire to establish a good neutral connection.
• When checking control board DC voltage (5VDC), always place the red positive test lead from the multimeter to CB K5 pin closest to CB K4 connector. See "II.C. Control Board Check."
• When checking BC1 (infrared sensor) (20VDC), check that BC1 (infrared sensor) green LED is on. This green LED conrms 20VDC power from CB K6to BC1 (infrared sensor) and remains on constantly. If green LED is not on, check for 20VDC from CB K6 #1 (DBU) to CB K6 #3 (BR). See "II.D.1. Bin Control1(infrared sensor) Check."
• To speed up the diagnostic process, the 5-min. ice purge cycle may be bypassed by pressing the "SERVICE" button on the control board after the gear motor starts. WARNING! Risk of electric shock. Care should be taken not to touch live terminals.
• If the icemaker is in alarm, see "III.A.2. LED Lights and Audible Alarm Safeties."
• EH energizes when "GM" LED turns on.
• CB X1 relay energizes PDS. After PDS energizes, CPLS closes, then MC energizes, energizing Comp and FMR.
• CB monitors the following switches with 5VDC during the icemaking process: Control Switch (CS), Compressor Control Relay/Gear Motor Protect Relay (CCR/ GMPR), Float Switch (FS), and Bin Control 2 (mechanical backup). When 5VDC is present across any of these switches, the switch is open.
1) Remove the front panel, then move the power switch to the "OFF" position. Move the control switch to the "DRAIN" position, then move the power switch back to the "ON" position. Replace the front panel in its correct position.
2) Allow the water system to drain for 5 min.
3) Remove the front panel. Move the power switch to the "OFF" position, then unplug the appliance from the electrical outlet.
4) Remove the control box cover and access CB.
5) Check the CB S1 dip switch settings, see "III.B.1. Default Dip Switch Settings" to assure that they are in the correct positions. For proper operation of BC1 (infrared sensor), conrm that S1 dip switch 7 is in the "ON" position.
15
6) Startup – CB "POWER OK" LED is on. Plug the icemaker back into the electrical outlet, then move the power switch to the "ON" position. Move the control switch to the "ICE" position. CB "POWER OK" LED and BC1 green LED turn on. Diagnosis CB "POWER OK" LED: If CB"POWER OK" LED is off, check for proper supply voltage (115VAC) input to CT. If 115VAC is not present, check the power switch and breaker. Next, check for proper 24VAC output voltage from CT. Check CBK8 #1 (W/R) to #2 (LBU) for 24VAC. If 24VAC is not present and 1A 24VAC fuse is good, replace CT. If 24VAC is present and CB "POWER OK" LED is off, replace CB. Diagnosis BC1 (infrared sensor): Check that BC1 green LED is on. If CB "POWER OK" LED is on and BC1 green LED is off, check CB K6 #3 (BR) to CB K6 #1 (DBU) for 20VDC. If20VDC is not present, conrm S1 dip switch 7 is in the "ON" position. IfS1dip switch 7 is in the "ON" position and 20VDC is not present, replace CB. IfBC1 yellow LED is on or ashing, move ice away from lens. If no ice is present, clean the lens with a warm, clean damp cloth. If BC1 yellow LED is still on or ashing after cleaning the lens, replace BC1. Diagnosis BC2 (mechanical backup): Check that the actuator paddle is properly positioned. Check continuity across BC2. If open, replace BC2. Next, check VDC at CB K8#3 (GY) to CB K8 #4 (GY). When BC2is closed 0VDC is read. Move the actuator paddle to open BC2. When open, 5VDCis present between CB K8 #3 (GY) and CB K8 #4(GY). If 5VDC is not present when BC2 is open, replace CB. Return actuator to its normal position.
7) Fill Cycle – "WTRIN" LED is on. Reservoir is empty and LFS and UFS are open. FTstarts. WV energizes and ll cycle starts. LFS closes. Nothing happens at this time. Reservoir continues to ll until UFS closes. When UFS closes, FT terminates, WV de-energizes and CB "WTRIN" LED turns off. FZTand 30-sec. GM delay timer start. IfUFS remains open longer than 90 sec. after LFS opens, FTexceeded and CB sounds a 1-beep alarm. WVremains energized until UFS closes. Alarm resets automatically when UFS closes. Diagnosis: If reservoir is empty and "WTRIN" LED is off, conrm LFS status. See "II.E.1. Float Switch Check." If LFS is open and "WTRIN" LED is off, replace CB. If "WTRIN" LED is on, check that the reservoir lls. If not, check water supply line shut-off valve, water lters, and WVscreen. If "WTRIN" LED is on and WV is off, check CB K2 #8(W/BR) to a neutral (LBU) for 24VAC. If 24VAC is not present, check CB K2#9(W/R) to a neutral (LBU) for 24VAC. If 24VAC is present on CB K2 #9(W/R)and not on CB K2 #8 (W/BR), replace CB. If 24VAC is present on CB K2 #8(W/BR), check continuity through WV solenoid. If open, replace WV. If WV is energized and rell exceeds FT with no water in the reservoir, check for DV leaking. Ifreservoir is full and overowing check for open UFS. See "II.E.1. Float Switch Check." If UFS is closed, check that WV de-energizes. If not, check CB K2 #8 (W/BR) to a neutral (LBU) for 24VAC. If 24VAC is present, replace CB. IfWV de-energizes and water continues to ll the reservoir, replace WV.
16
8) Ice Purge Cycle – "GM" LED is on. 30-sec. GM delay timer terminates, GM, EH, and CCR/GMPR energize. Once CCR/GMPR energizes, 5VDC circuit closes through CCR/GMPR terminal #3 (W/O) and terminal #5 (W/O) and CB K9 #5 (W/O) and K9 #6 (W/O). After 5VDC circuit closes, 5-min. ice purge timer starts. Tobypass the 5-min. Ice Purge Cycle, press the "SERVICE" button on CB after the "GM" LED turns on. WARNING! Risk of electric shock. Care should be taken not to touch live
terminals. Diagnosis: If "GM" LED is off, check that UFS closes and WV de-energizes. If UFS
is closed, 30 sec. has passed, and "GM" LED remains off, replace CB. If "GM" LED is on and GM is off, check CB K1 #3 (BR) to a neutral (W) for 115VAC. If 115VAC is not present, check 115VAC power supply. If 115VAC is present, check CB K1 #2(W/BK) to a neutral (W). If 115VAC is present on CB K1 #3 (BR) and not on CB K1 #2 (W/BK), replace CB. If 115VAC is present on CB K1 #2 (W/BK), check GM fuse, GM internal protector, GM windings and capacitor, and GM coupling between auger and GM. When GM energizes, CCR/GMPR energizes starting 5-min. ice purge timer.
9) Freeze Cycle – "COMP" and "GM" LEDs are on. Note: CB X1 relay energizes the PDS (pump-down solenoid) not the MC (magnetic contactor). The 5-min. ice purge timer terminates. GM, EH, and CCR/GMPR continue. PDS energizes. Once the refrigeration circuit low-side pressure reaches 29 PSIG, CLPS closes, energizingMC, MC then energizes Comp and FMR. CCH de-energizes. Iceproduction starts 4 to 6 min. after Comp energizes depending on ambient and water conditions. As ice is produced, the water level in the reservoir drops. UFS opens. Nothing happens at this time. When LFS opens, WV energizes and rell cycle begins, FZT terminates, and FTstarts. FZT: 30-Min. Freeze Safety Timer – FZT starts when UFS closes and terminates when LFS opens. If LFS does not open within 30 min. of UFS closing, CB shuts down the icemaker and sounds a 5-beep alarm. See "III.A.2.LED Lights and Audible Alarm Safeties." To reset, turn the power supply off and on again. See "II.F. Diagnostic Tables" for troubleshooting details. Icemaker Diagnosis (CCR/GMPR): 5-min. ice purge timer terminates, CB "COMP" LED is on and PDS energizes. If not, check for 5VDC between CB K5 connector pin closest to CB K4 connector and CB K9connector #5(W/O). If 5VDC is not present, replace CB. If 5VDC is present, check for 5VDC between CB K5 connector pin closest to CB K4 connector and CB K9connector #6(W/O). If 5VDC is present and CB "Comp" LED is off (PDS not energized), replace CB. If 5VDC is not present, check for 115VAC between CCR/GMPR terminal #7(R) to CCR/GMPR terminal #8(W) for 115VAC. If115VAC is not present (GM not energized), see step 8 above. If 115VAC is present and CCR/GMPR contacts are open (5VDCpresent between terminals #3(W/O) and #5(W/O)), check CCR/GMPR solenoid voltage and solenoid continuity. Replace CCR/GMPR if necessary. Icemaker Diagnosis (PDS): If"COMP" LED is on and PDS is not energized, check CB X1 relay BR wire to a neutral (W) and CB X1 relay DBU wire to a neutral (W) for 115VAC. If115VAC is present on CB X1BR wire and not on CBX1 DBU wire, replace CB. If115VAC is present on CBX1DBU wire and PDS is not energized, check for 115VAC at PDS (DBU) to a neutral (W) for 115VAC. If 115VAC is present and PDS is not energized, check PDS solenoid for continuity. If open or if PDS is sticking closed, replace PDS.
17
Condensing UnitDiagnosis: Conrm that CLPS closes. Once CLPS closes, MC energizes, energizing Comp and FMR. If not, check condensing unit 208-230VAC power supply, breakers, disconnets. Next, conrm 115VAC from CLPS BR wire to neutral (W). If 115VAC is not present, check wiring connections and power supply. CLPS: When PDS is energized, CLPS closes when refrigeration circuit low-side pressure reaches 29 PSIG. If CLPS is open, check that refrigeration circuit low-side pressure has reached 29 PSIG. If refrigeration circuit low-side pressure is too low, conrm proper TXV operation, check for refrigerant restrictions (drier, PDS), and correct refrigerant charge. Recover, evacuate, and recharge if necessary. If refrigeration circuit low-side pressure reaches 29 PSIG and CLPS does not close, replace CLPS. SLPS: If SLPS is open, manually reset SLPS. If manually resetting SLPS does not close contacts, replace SLPS. After resetting, conrm proper TXV operation, check for refrigerant restriction (drier, PDS), and correct refrigerant charge. Recover, evacuate, and recharge if necessary. HPS: If HPS is open, HPS automatically resets when refrigeration circuit high-side pressure is within an acceptable range. If HPS does not reset (open), allow pressures to equalize and HPS to reset. If refrigeration circuit high-side pressure does not drop, recover, evacuate, and recharge if necessary. Before restarting the appliance, check for dirty or clogged condenser. Once the appliance is restarted, check for proper FMR operation and fan blade for binding. Check receiver, service valves, PDS, and drier for refrigeration circuit restriction. Also check for proper HM operation. If high-side refrigerant pressures have returned to an acceptable range and HPS does not close, replace HPS. MC: If MC energizes and Comp does not energize, check for 115VAC at MC C2 (O) to neutral (W). If 115VAC is not present, check CLPS, SLPS, and HPS contacts. If 115VAC is present, check MC coil continuity. If open, replace MC. If closed, check MC L1 and MCL2to a neutral (W) for 115VAC. If 115VAC is not present on either L1or L2, check incoming power supply. If 115VAC is present on both L1 and L2 and Comp does not start, check MC T1 (BK) to MC T2 (R) for 208-230VAC. If 208-230VAC is not present, replace MC. If 208-230VAC is present, check Comp start relay, start capacitor, run capacitor, and Comp motor windings. If FMR does not energize, check MC T3 (DBU) to a neutral (W) for 115VAC. If 115VAC is present and FMR does not energize, check fan motor capacitors and motor windings. If 115VAC is not present, replace MC.
18
10) Rell Cycle – "GM", "COMP", and "WTRIN" LEDs are on. LFS opens. WVenergizes and FT starts. GM, CCR/GMPR, EH, PDS, MC, Comp, and FMR continue. LFS closes. Nothing happens at this time. Reservoir continues to ll until UFS closes. When UFS closes, WV de-energizes, FT terminates, and FZT starts. IfUFS remains open longer than 90 sec. after LFS opens, FT exceeded and CB sounds a 1-beep alarm. WVremains energized until UFS closes. Alarm resets automatically when UFS closes. Diagnosis – Conrm that the water level has dropped and the UFS and LFS are open. See "II.E.1. Float Switch Check." Check that "WTRIN" LED is on. IfLFS is open and "WTRIN" LED is off, replace CB. If "WTRIN" LED is on, check that the reservoir lls. Ifnot, check water supply line shut-off valve, water lters, and WVscreen. If"WTRIN" LED is on and WV is off, check CB K2 #8(W/BR) to a neutral (LBU) for 24VAC. If 24VAC is not present, check CB K2 #9(W/R) to a neutral (LBU) for 24VAC. If 24VAC is present on CB K2 #9 (W/R)and not on CB K2#8 (W/BR), replace CB. If 24VAC is present on CB K2#8(W/BR),check continuity through WV solenoid. If open, replace WV. If WV is energized and rell exceeds FT with no water in the reservoir, check for DV leaking. If reservoir is full and overowing check for open UFS. See "II.E. Float Switch Check and Cleaning." If UFS is closed, check that WVdeenergizes. If not, check CB K2 #8 (W/BR) to a neutral (LBU) for 24VAC. If 24VAC is present, replace CB. If WV de-energizes and water continues to ll the reservoir, replace WV. FT: 90-Sec. Low Water Safety Timer – When LFS opens, 90-sec. low water safety timer starts. If UFS does not close within 90 sec. after LFS opens (FTexceeded), CBsounds a 1-beep alarm and a 90-sec. shutdown cycle starts. See "III.A.2.LED Lights and Audible Alarm Safeties." PDS de-energizes. Refrigeration circuit low-side pressure drops to 9PSIG, opening CLPS. CLPS opens, de-energizing MC, which de-energizes Comp and FMR. GM, CCR/GMPR, and EH continue. 90-sec. purge timer terminates, GM, EH, and CCR/GMPR de-energize. WV and 1-beep alarm continue until UFS closes.
19
Loading...
+ 44 hidden pages