Hoshizaki KMS1402MLJ User Manual

Page 1
Service Manual
Modular Crescent Cuber
Model
KMS-1402MLJ
Including Condensing Unit Models SRK-15J/3
hoshizakiamerica.com
Number: 73224 Issued: 5-16-2018
Page 2
WARNING
Only qualied service technicians should install and service the appliance. To obtain the name and phone number of your local Hoshizaki Certied Service Representative, visit www.hoshizaki.com. No installation or service should be undertaken until the technician has thoroughly read this Service Manual. Likewise, the owner/manager should not proceed to operate the appliance until the installer has instructed them on its proper operation. Failure to install, operate, and maintain the appliance in accordance with this manual will adversely affect safety, performance, component life, and warranty coverage and may result in costly water damage. Proper installation is the responsibility of the installer. Product failure or property damage due to improper installation is not covered under warranty.
Hoshizaki provides this manual primarily to assist qualied service technicians in the installation, maintenance, and service of the appliance.
Should the reader have any questions or concerns which have not been satisfactorily addressed, please call, send an e-mail message, or write to the Hoshizaki Technical Support Department for assistance.
Phone: 1-800-233-1940; (770) 487-2331 Fax: 1-800-843-1056; (770) 487-3360
E-mail: techsupport@hoshizaki.com
618 Highway 74 South Peachtree City, GA 30269 Attn: Hoshizaki Technical Support Department
NOTE: To expedite assistance, all correspondence/communication MUST include the
following information:
• Model Number
• Serial Number
• Complete and detailed explanation of the problem.
2
Page 3
IMPORTANT
This manual should be read carefully before the icemaker is serviced. Read the warnings and guidelines contained in this booklet carefully as they provide essential information for the continued safe use, service, and maintenance of the icemaker. Retain this booklet for any further reference that may be necessary.
CONTENTS
Important Safety Information ................................................................................................. 5
I. Construction and Water/Refrigeration Circuit Diagrams ..................................................... 7
A. Construction ................................................................................................................. 7
1. Icemaker ................................................................................................................. 7
2. Condensing Unit ..................................................................................................... 8
B. Water Circuit/Refrigeration Circuit Diagram ................................................................... 9
II. Sequence of Operation and Service Diagnosis ............................................................... 10
A. Sequence of Operation Flow Chart ............................................................................. 10
1. Operation Flow Chart ............................................................................................ 10
2. Shutdown Flow Chart .............................................................................................11
3. Freeze-Time Correction Chart ............................................................................... 12
B. Service Diagnosis ....................................................................................................... 13
C. Freeze-Time Correction Cycle (90 min.) ..................................................................... 22
D. Control Board Check ................................................................................................... 24
E. Bin Control Check ....................................................................................................... 26
F. Float Switch Check and Cleaning ................................................................................ 28
G. Thermistor Check ........................................................................................................ 30
H. Switches ...................................................................................................................... 31
1. Control Switch ........................................................................................................ 31
2. Service Switch ....................................................................................................... 31
I. Diagnostic Tables .......................................................................................................... 32
J. Freeze-Up Check List .................................................................................................. 36
III. Settings and Adjustments ............................................................................................... 37
A. Control Board Layout .................................................................................................. 38
B. LED Lights and Audible Alarm Safeties ....................................................................... 39
C. Settings and Adjustments ............................................................................................ 40
1. Default Dip Switch Settings .................................................................................... 40
2. Harvest Time (S4 dip switch 1 & 2)........................................................................ 41
3. Pump-Out Time/Harvest Time During Pump-Out (S4 dip switch 3 & 4) ................. 41
4. Pump-Out Frequency Control (S4 dip switch 5) ..................................................... 42
5. Harvest Pump Time (Harvest Assist Duration) (S4 dip switch 6) ........................... 42
6. Harvest Pump Time (Harvest Assist)/Freeze-Time Correction (S4 dip switch 7) .. 43
7. Factory Use (S4 dip switch 8)................................................................................. 43
8. Freeze Timer (S4 dip switch 9 & 10) ...................................................................... 44
9. Float Switch Control Selector (S5 dip switch 1) ..................................................... 44
10. Rell Counter (S5 dip switch 2 and 3) .................................................................. 45
11. Minimum Harvest Time (S5 dip switch 4) ............................................................. 45
12. Anti-Slush (S5 dip switch 5) ................................................................................. 45
3
Page 4
IV. Refrigeration Circuit and Component Service Information.............................................. 46
A. Refrigeration Circuit Service Information .................................................................... 46
B. Component Service Information .................................................................................. 49
V. Maintenance .................................................................................................................... 50
VI. Preparing the Appliance for Periods of Non-Use ............................................................ 51
VII. Disposal ......................................................................................................................... 53
VIII. Technical Information .................................................................................................... 54
A. Specication and Performance Data Sheets ............................................................... 54
1. KMS-1402MLJ with SRK-15J ................................................................................. 54
2. KMS-1402MLJ with SRK-15J3 .............................................................................. 55
3. SRK-15J ................................................................................................................ 56
4. SRK-15J3 .............................................................................................................. 57
B. Wiring Diagrams .......................................................................................................... 58
1. Wire Harness Connections ..................................................................................... 58
2. KMS-1402MLJ with SRK-15J ................................................................................ 59
3. KMS-1402MLJ with SRK-15J3 .............................................................................. 60
4
Page 5

Important Safety Information

Throughout this manual, notices appear to bring your attention to situations which could result in death, serious injury, damage to the appliance, or damage to property.
WARNING Indicates a hazardous situation which could result in death or
serious injury.
NOTICE Indicates a situation which could result in damage to the
appliance or property.
IMPORTANT Indicates important information about the use and care of the
appliance.
WARNING
This appliance should be destined only to the use for which it has been expressly conceived. Any other use should be considered improper and therefore dangerous. The manufacturer cannot be held responsible for injury or damage resulting from improper, incorrect, and unreasonable use. Failure to service and maintain the appliance in accordance with this manual will adversely affect safety, performance, component life, and warranty coverage and may result in costly water damage.
To reduce the risk of death, electric shock, serious injury, or re, follow basic precautions including the following:
• Only qualied service technicians should install and service this appliance.
• This appliance must be installed in accordance with applicable national, state, and local codes and regulations. Failure to meet these code requirements could result in death, electric shock, serious injury, re, or damage to the appliance.
• To reduce the risk of electric shock, do not touch the control switch or service switch with damp hands.
• Before Servicing the KMS or SRK: To reduce the risk of electric shock, move the control switch to the "OFF" position and turn off the power supply to the SRK condensing unit. Place the KMS disconnect (if applicable) in the "OFF" position. Lockout/Tagout to prevent the power supply from being turned back on inadvertently.
• Do not make any alterations to the appliance. Alterations could result in electric shock, injury, re, or damage to the appliance.
• This appliance is not intended for use by persons (including children) with reduced physical, sensory, or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
• Children should be properly supervised around this appliance.
• Do not climb, stand, or hang on the appliance or allow children or animals to do so. Serious injury could occur or the appliance could be damaged.
• Do not use combustible spray or place volatile or ammable substances near the appliance. They might catch re.
• Keep the area around the appliance clean. Dirt, dust, or insects in the appliance could cause harm to individuals or damage to the appliance.
5
Page 6
WARNING, continued
For KMS
• Power supply and ground connection are supplied from the SRK remote condensing
Failure to properly ground the appliance
• Risk of electric shock. Control switch in "OFF" position does not de-energize all loads.
unit via the wire harness provided. Do not connect the wire harness leads to an external power source.
• Wire harness routing (conduit) and disconnect (if required) must meet national, state, and local electrical code requirements. Failure to meet these code requirements could result in death, electric shock, serious injury, re, or damage to the appliance.
THE APPLIANCE MUST BE GROUNDED. could result in death, serious injury, or damage to the appliance.
For SRK
• Electrical connection must be hard-wired and must meet national, state, and local electrical code requirements. Failure to meet these code requirements could result in death, electric shock, serious injury, re, or damage to the appliance.
• The remote condensing unit requires an independent power supply of proper capacity. See the nameplate for electrical specications. Failure to use an independent power supply of proper capacity can result in a tripped breaker, blown fuses, damage to existing wiring, or component failure. This could lead to heat generation or re.
THE REMOTE CONDENSING UNIT MUST BE GROUNDED. Failure to properly ground the remote condensing unit could result in death, serious injury, or damage to the appliance.
NOTICE
• Follow the instructions in this manual carefully to reduce the risk of costly water damage.
• In areas where water damage is a concern, install in a contained area with a oor drain.
• Install the appliance in a location that stays above freezing. Normal operating ambient temperature must be within 45°F to 100°F (7°C to 38°C).
• Do not leave the appliance on during extended periods of non-use, extended absences, or in sub-freezing temperatures. To properly prepare the appliance for these occasions, follow the instructions in "VI. Preparing the Appliance for Periods of Non-Use."
• Do not place objects on top of the appliance.
• The dispenser unit/storage bin is for ice use only. Do not store anything else in the dispenser unit/storage bin.
6
Page 7

I. Construction and Water/Refrigeration Circuit Diagrams

A. Construction

1. Icemaker

Harvest Water Valve (WV2)
Evaporator
Spray Tubes
Wash Valve
Hot Gas Valve
Liquid Line Valve
Liquid Line Shutoff Valve
Drier
Suction Line Shutoff Valve
Thermistor
Control Board
Control Box
Fill/Rell Water Valve (WV1)
Control Switch
Service Switch
Drain Water Valve
Fuse
Switch Box
Switch Cover
Switch Mount
Extension Bracket
Bin Control
Pump Motor
Float Switch
Bin Control
Switch Bracket
7
Page 8

2. Condensing Unit

Liquid Line Valve
Suction Line Shutoff Valve
Liquid Line Shutoff Valve
SRK-15J Control Box
Headmaster (C.P.R.)
Fuse
Condenser
Hot Gas Valves
SRK-15J3 Control Box
Fuse
Check Valve
Receiver
Accumulator
Fan Motors and Fan Blades
Liquid Line Shutoff Valve 2
Discharge Line Shutoff Valve
Thermostat (Discharge Pipe)
Crankcase Heater
Compressor
High Pressure Switch
8
Page 9

B. Water Circuit/Refrigeration Circuit Diagram

Discharge Line
Shutoff Valve
Discharge Line
Headmaster
(C.P. R.)
Condenser
Check Valve
Access Valve
Thermostat
Strainers
Hot Gas Valves
Liquid Line Valve
Service Valve
Strainer
High-Pressure
Switch
SRK-15J/3
Wash Valve
Drier
Liquid Line Valve Body
Receiver
Fan
Suction Line
Thermistor
Liquid Line
Shutoff Valve
Service Valve
Service Valve
Liquid Line
Shutoff Valve
Strainer
Discharge
Line
Hot Gas
Valve Body
Compressor
Accumulator
Check Valves
Float Switch
Expansion Valves
Drain Valve
Water Supply
KMS-1402MLJ
Harvest Water
Valve (WV 2)
Spray Tube
Evaporator
Fill/Rell Water
Valve (WV (WV 1)
9
Drain
Pump Motor
Water Tank
Page 10

II. Sequence of Operation and Service Diagnosis

A. Sequence of Operation Flow Chart

1. Operation Flow Chart

cycle
(S4 dip switch 5)
4. Pump-Out Cycle
• Factory set for every 10th
FS in control
FS opens or freeze
timer terminates
Comp energized
FMRs energized
HGVs energized
DV energized
PM stops for 2 sec., then
Anti-Slush
Thermistor temperature
reaches 36°F (2.2°C)
(5.8 kΩ).
PM de-energized for
energized for 10/20 sec.
LLV de-energized
10 sec.
When freeze time differential exceeded,
freeze-time correction cycle starts.
See "II.A.3. Freeze-Time Correction Chart."
• Min. freeze time: 5 min.
• Max. freeze time: freeze timer setting
(S4 dip switch 9 & 10).
5-min minimum
freeze timer in
control
3. Freeze Cycle
Harvest Pump
Time
Operation Flow Chart
1 to 3-min. harvest timer in
control (S4 dip switch 1 & 2)
Thermistor
in control
setting (S4 dip switch 6), whichever is shorter.
• WV time: 6 min. or the length of harvest minus HPT
• Max. harvest time: 20 min.
2. Harvest Cycle
Rell
1 min.
50 sec.
FS closed
FS check
PM energized
WV2 de-energized
FS closed
Comp energized
FMRs energized
Thermistor temperature reaches
Comp energized
FMRs energized
PM energized
48°F (9°C) (3.9 kΩ or less). Harvest
HGVs energized
LLVs energized
WV1 energized rst
1 min. of freeze
HGVs de-energized
FS open
Power is supplied to the pump and drain valve. This drains the water tank.
Power is supplied to the pump only. This operation can be used to circulate cleaner and
sanitizer over the outside surface of the evaporator for extended periods of time.
Power is supplied to the pump and wash valve. This operation is used to circulate cleaner
and sanitizer over both the inside and outside surfaces of the evaporator.
DRAIN
CIRC.
Components Energized when the Control Switch is in the "SERVICE" Position
When in the "SERVICE" position, the control switch supplies power to the service switch and the icemaker is in service mode.
timer starts.
WV2 energized
WV1 de-energized
The service switch has three positions: "DRAIN," "CIRC." and "WASH." See the information below for details of each function.
WASH
WV1 energized
FS open
If FS is open, Comp stops and cycle
returns to 1-Min. ll.
Legend:
Comp-compressor
DV-drain valve
FMRs-fan motors-remote
F/S-oat switch
HGVs-hot gas valves (KMS and SRK)
LLVs-liquid line valves (KMS and SRK)
PM-pump motor
WV1-ll/rell water valve
WV2-harvest water valve
Fill Cycle
FS check
1. 1-Minute
10
Cycle
Steps
Startup
Page 11

2. Shutdown Flow Chart

3. Ice Level Lowered
2. Icemaker Off
Icemaker starts at
All components
"1. 1-Minute Fill Cycle."
de-energized.
To 1. 1-Minute Fill Cycle
BC closed
(BC actuator paddle disengaged)
Green "BC CLOSED" LED on
Yellow "BC OPEN" LED off
Yellow "BC OPEN" LED continues. All
components de-energized.
Shutdown Flow Chart
Note: Control board retains freeze-time correction count
data between bin control restarts.
to 15 sec. into the freeze cycle if
activated at the end of the harvest cycle.
15 sec. before the 5-min. short cycle protection
timer terminates. Otherwise, at the end of the next
harvest cycle.
Freeze Cycle–15 sec. after activation if activated at least
BC open (BC actuator paddle engaged)
Green "BC CLOSED" LED off
Yellow "BC OPEN" LED on
BC Operation
Legend:
BC–bin control
1. Bin Full
Shutdown
Shutdown Delay:
and Restart
Fill Cycle–15 sec. after activation.
Harvest Cycle–At the end of the harvest cycle, or up
11
Page 12

3. Freeze-Time Correction Chart

Overow
2. 10-Minute Fill/
WV energized
Comp de-energized
FMRs de-energized
HGVs de-energized
PM de-energized
After 5th 10-Minute Harvest Pump Cycle with WV
Freeze-Time Correction Cycle Complete.
Go to Step "3. Freeze Cycle" in Operation Flow Chart.
step 1 for 5th and nal time.
• Do not adjust S4 dip switch 7 out of the factory position.
• After step 2 completes 4th sequence (80 min. completed), repeat
1. 10-Minute Harvest Cycle with WV
Comp energized
FMRs energized
HGVs energized
PM energized
WV energized
Freeze-Time Correction Flow Chart
Cycle Steps
Steps 1 and 2 repeat
4 times (total 80 min.),
then step 1 repeats for
a 5th time to complete
Freeze-Time Correction
Start
Legend:
Comp–compressor
FM–fan motor
FMRs–fan motor-remote
HGVs–hot gas valve
PM–pump motor
WV–inlet water valve
Appliance Cycle Reset and Alarm Reset:
Cycle Reset: Power Supply or Control Switch Turned Off and On again:
Appliance turns off, then re-starts at 1.Fill Cycle.
Alarm Reset: CB "ALARM RESET" pressed during or after a freeze-time
correction cycle with power supply on:
Appliance continues cycle with no interruption or reset.
CB red "POWER OK" LED blinking:
CB red "POWER OK" LED resets to solid.
CB yellow "EXT HARVEST" LED blinking:
Cycle.
Differential
Value in Sec.
3 254
4 309
5 349
6 380
7 406
8 427
9 446
10 462
CB yellow "EXT HARVEST: LED turns off.
Number of
Freeze Time Differential Exceeded.
Minimum and Maximum Freeze times have
exceeded differential parameters.
Freeze-Time Correction function is enabled
when S4 Dip Switch 7 is in the "ON" position.
CB monitors freeze time. After 3freeze
cycles, CB compares the minimum and
maximum differential of the 3 freeze cycle
times. Every freeze cycle time after the third
freeze cycle time is added to the minimum/
maximum calculation.
Example: After 8 cycles, if the differential
between the shortest cycle (minimum) and
the longest cycle (maximum) is equal to or
greater than 427 sec. a freeze-time correction
cycle is initiated:
Freeze Cycles
Note: When 1st freeze-time correction cycle
is initiated, CB "POWER OK" LED starts
blinking. On 2nd freeze-time correction cycle,
if CB "POWER OK" LED has been reset,
CB "POWER OK" LED starts blinking. If CB
"POWER OK" had not been reset after 1st
freeze-time correction cycle CB "POWER
OK" LED continues to blink.
After 3rd freeze-time correction cycle in
36hours, CB yellow "EXT HARVEST" LED
starts blinking.
Appliance continues to operate and LEDs
continue to blink until ALARM RESET button
is pressed with power on.
12
Page 13

B. Service Diagnosis

WARNING
• This appliance should be diagnosed and repaired only by qualied service personnel to reduce the risk of death, electric shock, serious injury, or re.
• Risk of electric shock. Use extreme caution and exercise safe electrical practices.
• Risk of electric shock. Control switch (KMS) in "OFF" position does not de-energize all loads.
• Moving parts (e.g., fan blade) can crush and cut. Keep hands clear.
CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews are securely in place after the appliance is serviced. Make sure that none have fallen into the dispenser unit/storage bin.
• Make sure all food zones in the icemaker and dispenser unit/storage bin are clean after service. For cleaning procedures, see "V. Maintenance."
1. Diagnostic Procedure
The diagnostic procedure is a sequence check that allows you to diagnose the electrical system and components. Before proceeding, check for correct installation, proper voltage per nameplate, and adequate water supply.
Note: • When checking high voltage (115VAC), always choose a neutral (W) to establish
a good neutral connection.
• On 3-phase models, the neutral (W) is provided through MT. To conrm a good neutral (W), check for 60VAC from neutral (W) to ground (GND). If 60VAC is present, neutral (W) is good. If 60VAC is not present, check 208-230VAC main power supply to MT. If 208-230VAC is present, check MT continuity.
• When checking voltage from the CB K1 connector (10 pin connector), pull CB K1connector out slightly to allow room for multimeter test leads contact.
1) Turn off the power supply, then access the control box. Clear any ice from BC.
2) Check that the 115VAC 10A fuses in the KMS and SRK are good.
Conrm that the location meets installation requirements:
KMS-1402MLJ:
• The appliance is not intended for outdoor use. Normal operating ambient temperature should be within 45°F to 100°F (7°C to 38°C).
• No clearance is required for proper operation
• The appliance should not be located in a corrosive environment.
SRK-15J/3:
• A dry and well ventilated area with 24" (61 cm) clearance in both front and rear for proper air circulation and ease of maintenance and/or service should they be required.
13
Page 14
3) Power On: Turn on the power supply, then move the control switch to the "ICE" position. A 5-sec. delay occurs. CB red "POWER OK" LED and CB green "BC CLOSED" LED turn on. If CB yellow "BC OPEN" LED is on (indicating a full bin), check BC. Move ice away from BC actuator paddle. If CB yellow "BC OPEN" LED stays on, see"II.E.1. Bin Control Check."
Note: • CB red "POWER OK" LED remains on unless the 10.5VAC power supply is
interrupted (K2 connector).
• Check CB using the steps in "II.D. Control Board Check."
• Conrm CB green "BC CLOSED" LED is on. If CB yellow "BC OPEN" LED is on, remove ice from BC. If no ice is around BC and CB yellow "BC OPEN" LED is on, see "II.E.1. Bin Control Check."
a) Power On Diagnosis: If CB red "POWER OK" LED is off, conrm 10A fuse on
both the KMS and the SRK are good. Conrm wire harness is connected and not damaged. Next, check SRK switches. Check for 115VAC at both HPS wires (BR) to neutral (W). If 115VAC is present on one and not the other, HPS is open. If HPS is open, see "b) HPS Diagnosis" below. If HPS is closed, check for 115VAC at both DLT wires (BR) to neutral (W). If 115VAC is present on one and not the other, DLT is open. If DLT is open, see "c) DLT Diagnosis" below. If DLT is closed, check for 115VAC at control switch #2 (BR) to neutral (W) then at control switch #3(BK) to neutral (W). If 115VAC is present on #2 (BR) and not on #3 (BK), replace control switch. If 115VAC is present on control switch #3 (BK), check for 10.5VAC at CB K2#1 red wire to CB K2 #2 red wire. If 10.5VAC is not present, check CT wire connections and CT continuity. If open, replace CT.
b) HPS Diagnosis: Check that all shutoff valves (4 total) are open and the condenser
coil is not clogged or restricted. Let refrigeration circuit pressures equalize. If HPS does not reset and pressures are equalized, replace HPS. If pressures are not equalized, reclaim refrigerant and diagnose refrigeration circuit restriction. Check that there are no restrictions in the refrigeration circuit. Harvest Cycle: HGVs, strainer, or check valve. Freeze Cycle: FMRs, TXV, HM, LLVs, strainer, check valve, drier, and damaged line set or tting.
c) DLT Diagnosis: Check that the condenser coil is not clogged or restricted. Let
discharge line thermostat cool, if DLT does not close, replace DLT. Once closed, restart appliance, once Comp starts, check voltage and amp draw. See "5a),a) Comp Diagnosis" below.
14
Page 15
4) 1-Min. Fill Cycle – LED 4 is on. WV1 energizes. After 1 min., CB checks for a closed FS. If FS is closed, the harvest cycle begins. If harvest cycle begins (Comp, HGVs, and FMRs energized), continue to step 5a. If FS is open, WV1 remains energized until FS closes (low water safety protection during initial start up and at the end of each harvest). Diagnosis: Check that water enters the water tank. If not, check that the water supply line shut-off valve is open and screens or external lters are clear. Check for 115VAC at CB K1 #6 (O) to neutral (W). If 115VAC is not present, replace CB. If 115VAC is present, and WV1 does not energize, check for 115VAC at X10 relay terminal #6 (O) to neutral (W) and X10 relay terminal #2 (W/O) to neutral (W). If 115VAC is present on relay terminal #6 (O) and not on relay terminal #2 (W/O), check for 115VAC on X10 relay terminal #8 (P) to neutral (W), if 115VAC is present replace CB. If 115VAC is not present replace X10 relay. If 115VAC is present, and WV1 does not energize, check for 115VAC at WV1. If 115VAC is present, check WV1 coil continuity. If open, replace WV1. If the water tank lls, but the appliance fails to start harvest (Comp energized), check for open FS. See "II.F. Float Switch Check and Cleaning." If FS is closed and CB fails to start the harvest cycle after 1 min., replace CB.
5a) Initial Harvest Cycle LEDs 1, 4, and 2 are on. WV1 continues. Comp, FMRs,
HGVs, WV2, X10 relay, X12 relay, and X13 relay energize. WV1 de-energizes. CB monitors the warming of the evaporator via the thermistor located on the suction line. When the thermistor reaches 48°F (9°C), CB reads 3.9 kΩ from the thermistor and turns harvest termination over to the harvest timer (S4 dip switch 1 & 2 and S5 dip switch 4). WV2 and X12 relay are energized during harvest for a maximum of 6 min. or the length of harvest minus HPT setting (S4 dip switch 6), whichever is shorter. See step 5b below. X13 remains energized throughout harvest cycle to prevent DV from energizing.
a) Comp Diagnosis: Check that evaporator is warming. If not, conrm that Comp
energizes. If not, check for 115VAC at CB K1 #1 (V) to neutral (W). If 115VAC is not present, check for 115VAC at CB K1 #10 (BR) to neutral (W). If 115VAC is present at #10 (BR) and not at #1 (V), replace CB. If 115VAC is present, check for 115VAC at MC solenoid (SRK). If 115VAC not present, check wire harness connections. If 115VAC is present, conrm contacts are closed. If not, replace MC. If MC contacts are closed, check Comp start and run capacitors, start relay (single phase), and Comp motor winding.
b) HGVs Diagnosis: If Comp is energized and evaporator is not warming, check that
HGVs energize and open. Check for 115VAC at CB K1 #2 (P) to neutral (W). If 115VAC is not present, replace CB. If 115VAC is present, check for 115VAC at HGVs coil (KMS and SRK) and check HGVs coils continuity. Replace as needed.
c) LLVs Diagnosis: Conrm that both LLVs are de-energized (KMS and SRK) and
closed (not bypassing). If energized, replace CB. If de-energized and bypassing, replace LLVs (KMS and SRK).
15
Page 16
d) Relays:
1. X10 (WV1 and WV2): If WV1 continues and WV2 does not energize, check for 115VAC between X10 relay terminal #4 (GY) to neutral (W) and X10 relay terminal #2 (W/O) to neutral (W). If 115VAC is present at relay terminal #2 (W/O) and not at relay terminal #4 (GY), check for 115VAC at relay terminal #8 (P). If 115 VAC is present at relay terminal #8 (P) and not at relay terminal #4 (GY), replace relay. If 115VAC is present at relay terminal #4 (GY) and not at relay terminal #2 (W/O) and WV1 contines, clean or replace WV1.
2. X12 Relay (DV Lockout relay 1) and X13 Relay (DV Lockout relay 2): If DV energizes (water owing down the drain) check for 115VAC at X12 relay terminal #8 (GY) to neutral (W). If 115VAC is not present see "d)1. X10 (WV1 and WV2)" above. If 115VAC is present, check X12 relay terminal #6 (Y) to neutral (W) and #4 (P) to neutral (W). If 115VAC is not present from X12 relay terminal #6 (Y) to neutral (W), check for 115VAC on X10 relay terminal #5 (V) and relay terminal #3 (Y) to neutral (W). If 115VAC is present on X10 relay terminal #5 (V) and not on relay terminal #3 (Y) replace X10 relay. If 115VAC is present on relay terminal #6 (Y) and not on X12 relay terminal #4 (P) replace X12 relay. If 115VAC is present on X12 relay terminal #4 (P), check for 115 VAC at X13 relay terminal #8 (P) to neutral (W). If 115VAC is present, check for 115VAC at X13 relay terminal #2 (W/BK) to neutral (W). If 115VAC is present at X13 relay terminal #2 (W/BK), replace X13 relay. If 115VAC is not present on X13 relay terminal #2 (W/BK) and water is going down the drain, clean or replace DV.
3. X11 (DV/HPT relay): If PM energizes during initial harvest, check X11 relay terminal #8 (DBU) to neutral (W). If 115VAC is present, and CB LED 3 is off, replace CB. If 115VAC is not present, check for 115VAC at X11 terminal #6 (R) to neutral (W). If 115VAC is present and CB LED 3 is off, replace X11 relay. Check X11 relay terminal #5 (W/BU) to neutral (W). If 115VAC is present, check X11 relay terminal #8 (DBU) to neutral (W). If 115VAC is present on X11 relay terminal #8 (DBU) and CB LED 3 is off, replace CB.
16
Page 17
5b) Harvest Pump Timer – LEDs 1, 3, and 2 are on. When the thermistor reaches 48°F
(9°C), CB reads 3.9 kΩ from the thermistor and turns harvest termination over to the harvest timer (S4 dip switch 1 & 2 and S5 dip switch 4). When WV2 de-energizes, LED 4 turns off, X12 relay de-energizes. LED 3 turns on and X11 relay energizes, allowing PM to energize. Comp, FMRs, HGVs, X10, and X13 relays continue. Diagnosis: Place a thermometer on the suction line next to the thermistor. Has it warmed to 48°F (9°C) or warmer? Conrm thermistor status. See "II.G. Thermistor Check." If the thermistor reading is in proper range, dip switch 7 is on, and PM does not energize before harvest terminates, replace CB. If WV2 continues, check for 115VAC at CB K1 #6 (O) to neutral (W). If 115VAC is present, and LED 4 is off, replace CB. If 115VAC is not present, and WV2 continues, check WV2 diaphragm for leaking by. Clean or replace. If LED 3 is on and PM is not energized, check for 115VAC at X11 relay terminal #8 (DBU) to neutral (W). If 115VAC is not present at X11 terminal relay #8 (DBU), replace CB. If 115VAC is present, check for 115VAC at X11 relay terminal #4 (P) to neutral (W) and X11 relay terminal #6 (R). If 115VAC is present at X11 relay terminal #4 (P) and not at X11 relay terminal #6 (R), replace X11 relay. If 115VAC is present at X11 relay terminal #6 (R), check control switch contact continuity between terminals #6 (R) and #5 (W/R). If contacts are open, replace control switch. If contacts are closed and 115VAC is present between control switch terminal #5 (W/R) and neutral (W), check PM capacitor and motor winding continuity.
5c) Initial Harvest Cycle Termination Diagnosis: When the thermistor reaches 48°F
(9°C), CB reads 3.9 kΩ from the thermistor and turns harvest termination over to the harvest timer (S4 dip switch 1 & 2 and S5 dip switch 4). Check discharge line temperature. For a thermistor check, see "II.G.Thermistor Check." Once harvest timer terminates, LED 3 & 2 turn off and freeze cycle starts. If 1-min. ll cycle starts after harvest timer terminates, check that FS is clean and operating properly, see "II.F. Float Switch Check and Cleaning." If FS is closed, CB proceeds to the next cycle. Ifnot, replace CB. Note: The minimum total time allowed by CB for a complete harvest cycle is based on S5 dip switch 4. Maximum harvest time allowed is 20 min.
NOTICE! S4 dip switch 7 must remain on. Otherwise, PM will not energize during the last seconds of harvest.
17
Page 18
6) Freeze Cycle – LED 1 is on. Comp, FMRs, and PM continue. LLVs energize. HGVs, X10, X11, and X13 relays de-energize. Appliance is held in freeze by a 5-min. short cycle protection timer. After 5-min. short cycle protection timer terminates and FS opens, freeze cycle terminates. Note: PM power supply switches from CB K1 #5 (DBU) in HPT to K1 #4 (R) in freeze.
Rell LEDs 1 and 4 are on. The KMS-1402MLJ uses a single F/S with a double F/S, UF/S rell initiation oat switch setting (S5 dip switch1) and is set for 1 rell (S5 dip switch 2 through 3). When the freeze cycle starts, CB monitors UF/S. No UF/S exists on the KMS-1402MLJ, therefore CB reads an open UF/S signal when the freeze cycle starts and immediately initiates a rell (CB energizes WV1 through X10 relay). Since there is no UF/S to close and terminate the rell, the rell lasts for the maximum time of 1-minute. During the 1-minute rell, LED 4 is on. Comp, FMRs, LLVs, and PM continue.
Anti-Slush: When anti-slush is enabled (S5 dip switch 5 "ON"), PM de-energizes when
thermistor reaches 36°F (2.2°C) (5.8kΩ) for 10 sec. then, energizes for the remainder of the freeze cycle.
a) Freeze Cycle Diagnosis: Conrm Comp, FMRs, and PM continue. Conrm that
LLVs energize. Next, conrm HGVs, X10, X11, and X13 relays de-energize. During the rst 5 min. of freeze, conrm evaporator is cooling. If not, conrm that WV1 and WV2 are de-energized (not leaking by), HGVs de-energized (not bypassing), LLVs energize, TXV and HM operate correctly, Comp is efficient, and refrigerant charge is correct. See "VIII.A. Specication and Performance Data Sheets."
b) Comp and FMRs Diagnosis: If Comp and FMRs de-energize once freeze begins,
check that appliance has not shut off on HPS or DLT ("POWER OK" LED off). If so, check "3)b) HPS Diagnosis" or "3)c) DLT Diagnosis" above. If CB "POWER OK" LED is on (KMS), check for 115VAC at CB K1 #9 (V) to neutral (W). If115VAC is not present and LED 1 is on, replace CB. If 115VAC is present, check for 115VAC at MC coil (SRK). If 115VAC is not present, check wire harness connections. Next, check for 115VAC at MC coil. If 115VAC is present, check MC coil and contacts continuity. Replace as needed. Next, check Comp start relay, start and run capacitors (single phase), and Comp motor winding continuity. If Comp is energized but evaporator is not cooling, check for an inefficient Comp. See "VIII.A. Specication and Performance Data Sheets." FMRs Diagnosis: If Comp is energized but FMRs are not, check for 115VAC at MC terminal "NO" black (BK) wire to neutral (W). If 115VAC is not present, and MC is energized replace MC. If 115VAC is present, check FMRs capacitors, motor windings, and fan blades for binding.
c) WV1, WV2, and HGVs Diagnosis: WV1/WV2: If WV1or WV2 energized or
bypassing, check for 115VAC at CB K1 #6 (O) to neutral (W). If 115VAC is present after PM energizes and LEDs 2 and 4 are off, replace CB. If 115VAC is not present, clean or replace WV1 or WV2 (bypassing). HGVs: If HGVs did not de-energize at the end of harvest and LED 2 is off, check for 115VAC at CB K1 #2 (P) to neutral (W). If 115VAC is present and LEDs 2 and 3 are off, replace CB. If 115VAC is not present, replace (defective) HGVs.
18
Page 19
d) PM Diagnosis: Conrm water is owing over evaporator from PM and not WV1
or WV2. IfPM de-energizes once freeze begins (except for anti-slush), check for 115VAC at CB K1 #4 (R) to neutral (W). If 115VAC is not present, replace CB. If 115VAC is present and PM is de-energized, check for 115VAC at control switch #5 (W/R) to neutral (W). If115VAC is present at CB K1 #4 (R) and not at control switch #5 (W/R), check control switch continuity between #5 (W/R) and #6 (R). Replace as needed. If115VAC is present at control switch #5 (W/R) to neutral (W), check PM capacitor and motor winding continuity.
e) LLVs Diagnosis: If LLVs do not energize, check for 115VAC at CB K1#3 (BK) to
neutral (W). If 115VAC is not present, replace CB. If 115VAC is present, check wire harness, wiring connections, coil voltage and continuity. Replace as needed.
f) Refrigerant Pressures, HM, and TXV Diagnosis: If evaporator is still not cooling,
check refrigerant pressures. See "VIII.A. Specication and Performance Data Sheets." Next, check HM operation. If refrigeration pressures are above HM setpoint and HMis bypassing, replace HM. Check TXV for proper operation. Remove TXV bulb and hold it in your hand, refrigerant low-side pressure should rise, place TXV bulb in ice water, refrigerant low-side pressure should drop. A 10 to 15 pound pressure swing between warm and cold conditions indicate a good TXV. If a 10 to 15 pound swing is not present, replace TXV.
g) Freeze Termination Diagnosis: After 5 min. in freeze, disconnect CB K5 FS
connector. 15 sec. later appliance should switch out of the freeze cycle (15 second delay after FS opens before terminating the freeze cycle). If appliance remains in freeze longer than 15 sec. after FS removed, replace CB. If appliance switches with FS removed but would previously not switch out of freeze with FS connected (long freeze - 3 beep alarm), see "II.F. Float Switch Check and Cleaning."
Note: Normal freeze cycle will last 20 to 40 min. depending on model and conditions.
Cycle times and pressures should follow performance data provided in this manual. See "VIII.A. Specication and Performance Data Sheets."
h) Short Freeze Cycle Diagnosis: Conrm water tank lls and overows during 1 min.
ll and harvest cycles. If not, check water supply lters, shut-off valve, WV1 and WV2 screens. Ifwater tank empties before 5 min. timer terminates and freeze cycle is short, check that DV is not bypassing or energized (water owing through DV). If DV is bypassing, remove and clean DV, replace as needed. If water tank is full, see "II.F. Float Switch Check and Cleaning." for erratic operating FS.
19
Page 20
7) Pump-Out Cycle – LEDs 1, 3, and 2 are on (10/20 second pump-out). Timing of the rst pump-out is determined by S4 dip switch 5. See the table below.
Control Board Settings
S4 Dip Switch Setting
No. 5
OFF Every 10 cycles After 11th freeze cycle
ON Every cycle After 2nd freeze cycle
Pump-Out Frequency Control Board
Comp and FMRs continue, HGVs energize. Note: If S4 dip switch 3 & 4 are set to 3 off and 4 on, LED 4 turns on and WV2 and X12 relay energize, energizing X13 relay. NOTICE!S4dip switch 3 & 4 must not be set to
3 off and 4 on. Otherwise, LED 4 turns on energizing WV2, X12, and X13 relays. Once X13 relay energizes, DV cannot energize.
LLVs de-energize. PM stops for 2 sec., then restarts for 10/20 sec. depending on pump-out timer (S4dip switch 3 & 4) setting. When the pump-out timer terminates, pump-out is complete. The pump-out frequency control (S4 dip switch 5) is factory set, and generally no adjustment is required. However, the pump-out frequency control can be set to have a pump-out occur every cycle. For details, see "III.C.4. Pump-Out Frequency Control (S4 dip switch 5)."
a) Pump-Out Diagnosis: In the freeze cycle before pump-out (see table above), after
5min. of freeze disconnect CB black K5 connector (FS connector). Check that CB LEDs 1, 3, and 2are on, PM stops, then restarts, DV energizes, and water is owing down the drain through DV.
b) CB Diagnosis:
PM: If PM does not stop and restart, check that CB LEDs 1, 3, and 2are on. Ifnot and pump-out is called for, replace CB. IfLEDs 1, 3, and 2are on, X11 relay energizes. If not, check for 115VAC at CB K1 #5 (DBU) to neutral(W). If115VAC is not present, replace CB. If115VAC is present at CB K1 #5 (DBU) and X11 relay is not energized, continue to "c) PM Diagnosis:" below. DV: If DV is not energized, check for 115VAC at CB K1 #1(V) to neutral(W). If LED 2 is on and 115VAC is not present at CB K1 #1 (V), replace CB. If 115VAC is present at CB K1 #1 (V) to neutral (W), continue to "d) DV Diagnosis" below.
c) PM Diagnosis: If 115VAC is present at CB K1 #5 (DBU), X11 relay energizes. Check
for 115VAC at X11 relay #8 (DBU) to neutral (W). If115VAC is not present, check wiring connections from CB K1 #5 (DBU) to X11 relay #8 (DBU). If115VAC is present at X11 relay #8 (DBU) and PM does not restart, check for 115VAC at X11 relay terminal #4 (P) and terminal #(6) to neutral (W). If115VAC is present on #4 (P) and not on #6 (R), replace X11 relay (sticking contacts). If 115VAC is present at X11 relay #6 (R) and PM is de-energized, check for 115VAC at control switch #6 (R) and #5(W/R) to neutral (W). If 115VAC is present at #6 (R) and not at #5 (W/R), replace control switch. If 115VAC is present at control #5 (W/R), check PM capacitor, motor winding, wiring connections, and impeller for binding.
20
Page 21
d) DV Diagnosis: X10 Relay: If 115VAC is present at CB K1 #1 (V) to neutral (W) and
DV is de-energized, check for 115VAC at X10 relay #5 (V) and #3 (Y) to neutral (W). If115VAC is present at #5 (V) and not at #3 (Y), conrm X10 relay is de-energized. Ifde-energized, replace X10 relay (sticking contacts). If energized, conrm LEDs 1, 2, and 3 are on. If LED 1, 3, and 2 are on and X10 relay is energized, replace CB. X13 Relay: Next, If 115VAC is present at X10 #3 (Y) to neutral (W), check for 115VAC at X13 #6 (Y) and #2 (W/BK) to neutral (W). If 115VAC is not present on #6(Y), check wiring from X10 relay #3 (Y). If 115VAC is present at X6 (Y) and not at #2 (W/BK), conrm X13 is de-energized. If energized, conrm CB LEDs 1, 2, and 3 are on. If LEDs 1, 2, and 3 are on and X13 relay is energized, X12 relay must be energized also. Replace CB. If 115VAC is present at X13 #2 (W/BK), check for 115VAC at X11 relay #3 (W/BK). X11 Relay: Check for 115VAC at X11 relay #3 (W/BK). If 115VAC is not present check wiring connections from X13 relay #2 (W/BK). If 115VAC is present at X11 #3 (W/ BK), check for 115VAC at X11 #5 (W/BU) to neutral (W). If 115VAC is present at X11 #3 (W/BK) and not at #5 (W/BU), conrm 115VAC from X11relay #8 (DBU) to #7 (W). If115VAC is present, replace X11 relay (sticking contacts). If 115VAC is present at X11 relay #5 (W/BU) and DV is de-energized, check wiring to DV from X11 relay #5 (W/BU), DV coil continuity, make sure the drain line is not clogged and that DV is clean and operating properly.
8)Normal Harvest Cycle – Same as the initial harvest cycle. Return to step 5a) above. Note: Appliance continues to cycle until BC is satised or power is switched off. The
appliance always restarts at the 1-min. ll cycle.
2. Shutdown Diagnosis
When the appliance is running, hold ice in contact with the thermostatic bulb. BC switch opens within 10 sec., shutting down the appliance. BC is factory set, and generally no adjustment is required. However, adjustment may be needed in some conditions, particularly at higher altitude locations. Diagnosis: See "II.E. Bin Control Check." CB red K4 connector must have the jumper in place. When the jumper is in place, the green "BC CLOSED" LED remains on. If the jumper is not in place, yellow "BC OPEN" LED turns on and the icemaker turns off and remains off until the jumper is replaced in its original position.
3. Freeze-Time Correction Cycle Diagnosis
1) See "II.C. Freeze-Time Correction Cycle (90 min.).""
Legend: BC–bin control; CB–control board; Comp–compressor; CT–control transformer;
CV–cleaning valve; DV–drain valve; FMRs–fan motor remote; FS–oat switch; HGVs–hot gas valve; HM–headmaster (C.P.R.); HPS–high-pressure switch; LLVs–liquid line valve; MC–magnetic contactor: MT–main transformer; PM–pump motor; TXV–thermostatic expansion valve; WV1–ll/re-ll water valve; WV2–harvest water valve
21
Page 22

C. Freeze-Time Correction Cycle (90 min.)

Freeze-Time Correction function is enabled when S4 Dip Switch 7 is in the "ON" position and initiates when the minimum and maximum freeze times have exceeded differential parameters. Freeze-time correction timer and count starts at the beginning of the 2nd freeze cycle after startup from power off condition. Freeze-time correction timer and count continues and retains its freeze-time correction timer and count during a BC off cycle and resumes its freeze-time correction timer and count on the 2nd freeze cycle after BC restart. If freeze-time differential is exceeded (see table below), freeze-time correction cycle starts and CB red "POWER OK" LED blinks. When freeze-time correction cycle occurs 3 or more times within a 36 hour period, CB yellow "EXT HARVEST" LED blinks with CB red "POWER OK" LED. Appliance starts in freeze cycle after a freeze-time correction cycle. Toreset CB LEDs, press ALARM RESET button on CB with power on. CB resets LEDs and appliance continues cycle without interruption.
1) Freeze Time Differential Initiation: CB starts monitoring freeze times on the second freeze time. After 3freeze cycles (4th total), CBbegins to compare minimum and maximum freeze time cycles. Every freeze cycle time after the rst freeze cycle time is added to the freeze time list. Minimum and maximum freeze time differential comparisons begin on the third cycle and are monitored up to 10cycles. On the 11th cycle the rst freeze cycle time is dropped to maintain the 10 maximum number of cycles. Example: After 8 cycles (excluding rst cycle), if the differential between the shortestcycle (minimum) and the longest cycle (maximum) is equal to or greater than 427 sec. a freeze-time correction cycle is initiated:
Number of Freeze Cycles
3 254 4 309 5 349 6 380 7 406 8 427 9 446
10 462
Differential Value in Sec.
22
Page 23
2) Freeze-Time Correction Sequence: First occurrence within 36 hr., minimum and maximum freeze times have exceeded differential parameters. CB "POWER OK" LED starts blinking. Freeze-Time Correction Cycle starts. Second occurrence within 36 hr., minimum and maximum freeze times have exceeded differential parameters. If not reset, CB "POWER OK" LED continues blinking. If reset from rst occurrence, CB "POWER OK" LED starts blinking. Freeze-Time Correction Cycle starts. Third occurrence within 36 hr. minimum and maximum freeze times have exceeded differential parameters. CB yellow "EXT HARVEST" LED starts blinking. Also, If not reset, CB "POWER OK" LED continues blinking. If reset, CB "POWER OK" LED starts blinking. Freeze-Time Correction Cycle starts. Total freeze-time correction cycle last for 90min. At the end of 80min., the nal step initiates and nal Harvest Pump Time (Harvest Assist) with WV2 (10-min.) starts. Once the nal Harvest Pump Time (Harvest Assist) with WV2 (10-min.) terminates (90 min. complete), normal freeze cycle begins.
2a) 10-Min. Harvest Pump Time (Harvest Assist) with WV2: CB "POWER OK" LED
blinking. CB LEDs 1, 4, 3, and 2 are on and Comp, FMRs, HGVs, PM, and WV2 energize. 10-min. timer starts. Once 10-min. timer terminates, CB LEDs 1, 3, and 2 turn off and Comp, FMRs, HGVs, WV2 and PM de-energize. WV1 energizes.
2b) 10-Min. Fill: CB LED 4 on and WV1 energized. 10-min. timer starts.
2c) Final 10-Min. Harvest Pump Time (Harvest Assist) with WV2: CB "POWER OK"
LED blinking. Once 10-min. timer terminates, CB LEDs 1, 4, 3, and 2 are on and Comp, FMRs, HGVs, PM and WV2 energize. 10-min. timer starts. Once 10-min. timer terminates, normal freeze cycle begins. CB LED 1 on and Comp, FMRs, and PM continue. HGVs and WV2 de-energize.
Note: After 3rd Freeze-Time Correction Cycle in 36 hours, CB signals with blinking CB
yellow "EXT HARVEST" LED. Appliance continues normal operation. CB "POWER OK" LED and CB yellow "EXT HARVEST" LED continue blinking in normal operation sequence.
3) Appliance Cycle Reset and CB Alarm Reset: Cycle Reset: Power supply or control switch turned off and on again: Appliance turns off, then re-starts at 1.Fill Cycle. Alarm Reset: CB "ALARM RESET" pressed during or after a freeze-time correction cycle with power supply on: Appliance continues cycle with no interruption or reset. CB red "POWER OK" LED blinking: CB red "POWER OK" LED resets to solid. CB yellow "EXT HARVEST" LED blinking: CB yellow "EXT HARVEST: LED turns off.
Legend: BC–bin control; CB–control board; Comp–compressor; CT–control transformer;
CV–check valve; FMRs–fan motors remote; FS–oat switch; HGVs–hot gas valves; HM–headmaster (C.P.R.); HPS–high-pressure switch; LLVs–liquid line valves; MC–magnetic contactor; PM–pump motor; TXV–thermostatic expansion valve; WV1–ll/re-ll water valve; WV2–harvest water valve
23
Page 24

D. Control Board Check

Before replacing CB that does not show a visible defect and that you suspect is bad, always conduct the following check procedure. This procedure will help you verify your diagnosis.
Alarm Reset: If CB is in alarm (beeping), press the "ALARM RESET" button on CB
while CB is beeping. WARNING!Risk of electric shock. Care should be taken not to touch live terminals. Once reset, the icemaker starts at the 1-minute ll cycle. For audible alarm information, see "III.B. LED Lights and Audible Alarm Safeties."
1) Check the dip switch settings to assure that S4 dip switch 3, 4, 6, 7, 8, 9, 10 and S5 dip switch 1 through 5 are in the factory default position. S4 dip switch 1, 2, and 5 are cleaning adjustments and the settings are exible. For factory default settings, see "III.C.1. Default Dip Switch Settings."
2) Move the control switch to the "ICE" position. If the red "POWER OK" LED is on, control voltage is good, continue to step 3. If the "POWER OK" LED is off, check CT secondary circuit. CT output is 10.5VAC at 115VAC primary input. If the secondary circuit has proper voltage and the red LED is off, replace CB.
If the secondary circuit does not have proper voltage, check CT primary circuit. Check
for 115VAC at CB K1 connector pin #10 (BR) to neutral (W) for 115VAC. Always choose a white (W) neutral wire to establish a good neutral connection when checking voltages. For additional checks, see "II.I.1. No Ice Production."
3) The "OUTPUT TEST" button provides a relay sequence test. Make sure the control switch is in the "ICE" position, then press the "OUTPUT TEST" button. For the correct lighting sequence, see the table below. Note that the order of the LEDs from the outer edge of the control board is 1, 4, 3, 2. Components (e.g., compressor) cycle during the test.
Control
Board
Correct LED
Lighting Sequence
1, 4, 3, 2
Following the test, the icemaker begins operation at the 1-minute ll cycle for both. If the LEDs do not light as described above, replace CB.
24
Page 25
4) To verify voltage output from CB to the components, slide the CB K1 connector out far enough to allow multimeter lead contact. With the icemaker in the cycle to be tested, check output voltage from the corresponding pin on CB K1 connector to a neutral (W)wire. If output voltage is not found and the appropriate LED is on, replace CB.
5) Check CB control connectors K3, K4, and K5 for correct VDC per table below. Note: Pin #1 is DC ground (GND) on each connector.
K3 Thermistor
Pin # VDC
#1 to #2 5VDC
#1 to #3 5VDC
#2 to #3 0VDC
K4 Bin Control
Pin # VDC
#1 to #2 5VDC
#1 to #3 5VDC
#2 to #3 0VDC
Legend: CB–control board; CT–control transformer
CB
Thermistor
Bin Control
Float Switch
3
1
K3
3
RED WHITE
1
K4
3
BLACK
1
K5
K5 Float Switch
Pin # VDC
#1 to #2 1.2VDC
#1 to #3 2VDC
#2 to #3 1.2VDC
25
Page 26

E. Bin Control Check

1. Bin Control Check
This appliance uses a lever-actuated proximity switch to control the ice level in the storage bin. No adjustment is required.
To check BC, follow the steps below.
1) Turn off the power supply.
2) Remove the front panel, then move the control switch to the "OFF" position.
3) Remove the control box cover.
4) Remove the base cover and clear any ice away from BC.
5) Disconnect BC connector from CB K4 connector.
BC Connector
6) Check for continuity across the wires of BC connector. When the actuator paddle is
Bin Control Bracket
not engaged, BC switch is closed. Ifopen, check that the actuator paddle is not sticking. Clean if necessary. See "II.E.2. Bin Control Cleaning." If BC switch still reads open, replace BC.
7) Press and hold the actuator paddle; check for continuity across the wires
BC
of BC connector. When the actuator paddle is engaged, BC switch is open. If closed, check that the actuator paddle is not restricted. Clean if necessary. See "II.E.2.Bin Control Cleaning." If BC switch still reads closed, replace BC.
Actuator Paddle
Fig. 1
8) Reconnect BC connector to CB K4 connector, then move the control switch to the "ICE" position. Turn on the power supply.
9) Check that CB green "BC CLOSED" LED is on.
10) Allow the icemaker to cycle on. Press and hold the actuator paddle. CB yellow "BCOPEN" LED should turn on and the icemaker should shut down according to the chart below. If it does not, replace CB.
Cycle at Bin Control Activation
Fill Cycle 15 sec. after activation.
Harvest Cycle At the end of the harvest cycle, or up to 15 sec. into the freeze cycle if activated at the
Freeze Cycle 15 sec. after activation if activated at least 15 sec. before the 5-min. short cycle
Shutdown
end of the harvest cycle.
protection timer terminates. Otherwise, at the end of the next harvest cycle.
Legend: BC–bin control; CB–control board
26
Page 27
2. Bin Control Cleaning
Scale may build up on BC. Scale can cause the actuator paddle and magnet to stick. In this case, BC should be cleaned.
WARNING
CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews are
securely in place after the icemaker is serviced. Make sure that none have fallen into the dispenser unit/storage bin.
1) Turn off the power supply.
2) Remove the front panel, then move the control switch to the "OFF" position.
3) Remove the top and right side panels. Remove the control box cover, then clear any ice away from BC.
4) Disconnect BC connector from CB K4 (red) connector, then remove BC from the icemaker.
5) Remove the actuator paddle from the switch mount. See Fig. 2.
6) Wipe down BC with a mixture of 1 part Hoshizaki "Scale Away" and 25 parts warm water. Rinse the parts thoroughly with clean water.
7) Reassemble BC and replace it in its correct position. Note: If the magnet was removed for
cleaning, be sure to replace it in its correct position.
8) Reconnect BC connector to CB K4 (red) connector.
Bin Control Proximity Switch Closed (calling for ice)
To Control Board K4 (red) Connector
Bin Control
Proximity Switch
Actuator Paddle
Bin Control Proximity Switch Open (bin full, icemaker off or shutting down)
9) Move the control switch to the "ICE" position.
10) Replace the control box cover, right side, top, and front panels in their correct positions.
11) Turn on the power supply to start the automatic icemaking process.
Actuator Paddle
27
Switch Mount
Magnet
Fig. 2
Page 28

F. Float Switch Check and Cleaning

F/S is used to determine that there is sufficient water in the water tank after the 1-minute ll cycle and after each harvest cycle. F/S is also used to determine that the appropriate volume of water has been converted into ice before switching out of the freeze cycle. No adjustment is required. Note: F/S is not part of rell operation.
1. Float Switch Check
To check F/S, follow the steps below.
1) Turn off the power supply.
2) Remove the front panel.
3) Place the control switch in the "SERVICE" position. Then place the service switch in the "DRAIN" position.
4) Replace the front panel in its correct position, then turn on the power supply for 2minutes.
5) Turn off the power supply.
6) Remove the front panel, then move the control switch to the "OFF" position.
7) Remove the top and right side panels.
8) Remove the control box cover, then disconnect F/S connector from CB K5 (black) connector.
9) Check for continuity across F/S leads. With the water tank empty, F/S should be open. If open, continue to step 10. If closed, follow the steps in "II.F.2. Float Switch Cleaning." After cleaning F/S, check it again. Replace if necessary.
10) Reconnect F/S connector to CB K5 (black) connector, then replace the control box cover, right side, and top panels in their correct positions.
11) Move the control switch to "ICE" position. Replace the front panel.
12) Turn on the power supply.
13) As water lls the water tank, F/S contacts should close. After 1 minute, the 1-minute ll cycle should end and the initial harvest cycle should begin.
14) Once the harvest cycle starts, turn off the power supply.
15) Remove the front panel, then move the control switch to the "OFF" position.
16) Remove the top and right side panels.
17) Remove the control box cover, then disconnect F/S connector from CB K5 (black) connector.
18) Check for continuity across F/S leads. With the water tank full, F/S should be closed. If F/S is closed and the icemaker will not switch from the 1-minute ll cycle to the initial harvest cycle, replace CB.
19) If open, conrm that the water tank is full. If the water tank is not full, check the water supply, water lters, and ll/rell water valve. If the water tank is full, follow the steps in "II.F.2. Float Switch Cleaning." After cleaning F/S, check it again. Replace if necessary.
28
Page 29
20) Reconnect F/S connector to CB K5 (black) connector, then replace the control box cover, right side, and top panels in their correct positions.
21) Move the control switch to the "ICE" position.
22) Replace the front panel in its correct position.
23) Turn on the power supply to start the automatic icemaking process.
Legend: CB–control board; F/S–oat switch
2. Float Switch Cleaning
Depending on local water conditions, scale may build up on F/S. Scale can cause F/S to stick. In this case, F/S should be cleaned.
1) Turn off the power supply.
2) Remove the front panel.
3) Place the control switch in the "SERVICE" position. Then place the service switch in the "DRAIN" position.
4) Replace the front panel in its correct position, then turn on the power supply for 2minutes.
5) Turn off the power supply.
6) Remove the front, top, and right side panels, then move the control switch to the "OFF" position.
7) Disconnect the vent tube and the ush tube from the top of F/S housing, then remove F/S assembly. Remove the rubber boot from the bottom of F/S assembly. See Fig. 3.
8) Remove the retainer rod from the bottom of F/S assembly, then remove the oat. Be careful not to bend the retainer rod excessively when removing it.
9) Wipe down F/S assembly's housing, shaft, oat, and retainer rod with a mixture of 1 part Hoshizaki "Scale Away" and 25 parts warm water. Clean the inside of the rubber boot and hose with cleaning solution. Rinse the parts thoroughly with clean water.
10) Reassemble F/S assembly and replace it and the rubber boot in their correct positions. Reconnect the vent tube and the ush tube.
11) Replace the right side and top panels in
Flush Tube
Vent Tube
their correct positions.
12) Move the control switch to the "ICE"
Shaft
position.
13) Replace the front panel in its correct
Float Switch Housing
position.
14) Turn on the power supply to start the automatic icemaking process.
Legend: CB–control board; F/S–oat switch
29
Fig. 3
Rubber Boot and Hose
Float
Retainer Rod
Page 30

G. Thermistor Check

To check thermistor resistance, follow the steps below.
1) Turn off the power supply.
2) Remove the front panel, then move the control switch to the "OFF" position.
3) Remove the top and right side panels, then remove the control box cover.
4) Remove the thermistor.
5) Immerse the thermistor sensor portion in a glass containing ice and water for 2 or 3 minutes.
6) Disconnect the thermistor connector from CB K3 (white) connector and check resistance between thermistor leads. Normal range is 4.7 to 6.2 kΩ. If outside the normal range, replace the thermistor. See "IV.B. Component Service Information." If within the normal range, continue to next step.
7) Replace the thermistor in its correct position. See "IV.B. Component Service Information."
8) Reconnect the thermistor connector to CB K3 (white) connector.
9) Replace the control box cover, right side, and top panels in their correct positions.
10) Move the control switch to the "ICE" position.
11) Replace the front panel in its correct position.
12) Turn on the power supply.
13) Once the harvest cycle starts (Comp energizes), begin timing the harvest cycle.
14) The harvest timer and harvest cycle should terminate within 2 to 5 minutes. If the harvest cycle does not terminate within 2 to 5 minutes, replace CB.
Legend: CB–control board; Comp–compressor
Thermistor Lead Cable Tie
Foam Insulation Thermistor Holder
Fig. 4
30
Page 31

H. Switches

Two control switches are used to control operation. These switches are referred to as the control switch" and the "service switch" and are located on the control box.

1. Control Switch

The control switch has three positions: "OFF" for power off, "ICE" for icemaking, and "SERVICE" to activate the service switch. WARNING! Moving control switch to "OFF"
position does not de-energize all components.

2. Service Switch

When the control switch is in the "SERVICE" position, the control switch supplies power to the service switch and water pump. The machine is in service mode. The service switch has three positions: "DRAIN, "CIRCULATE," and "WASH." See the information below for details of each function.
Note:
1. When the service switch is activated, power is supplied to the water pump in all three positions.
2. When the control switch is in the "OFF" position or in the "ICE" position, the service switch has no power and can be left in any position.
a) DRAIN
This appliance utilizes a pump-out drain system. When the service switch is active and placed in the "DRAIN" position, power is supplied to the drain valve.
b) CIRCULATE
When the service switch is active and placed in the "CIRCULATE" position, power is supplied to the pump only. This operation can be used to circulate cleaner for extended periods of time over the outside surface of the evaporator.
c) WASH
This appliance utilizes a solenoid operated wash (bypass) valve. When the service switch is active and placed in the "WASH" position, power is supplied to the water pump and the wash valve. This operation is used to circulate cleaner and sanitizer over both the inside and outside of the evaporator.
31
Page 32

I. Diagnostic Tables

Before consulting the diagnostic tables, check for correct installation, proper voltage per nameplate, and adequate water pressure (10 to 113 PSIG). Check control board using the steps in "II.D. Control Board Check."
1. No Ice Production
No Ice Production - Possible Cause
1. Power Supply a) Off, blown fuse, or tripped breaker.
b) Not within specications.
2. Main Transformer (3 phase SRK) (208-230VAC/115VAC)
3. Water Supply a) Water supply off or improper water pressure.
4. Fuse (SRK Control Box) a) Blown.
5. High-Pressure Switch (SRK) a) Dirty condenser.
6. Discharge Line Thermostat (SRK)
7. Wire Harness (From SRK to KMS)
8. Fuse (KMS Control Box) a) Blown.
9. Control Switch a) In "SERVICE" or "OFF" position.
10. Control Transformer (115VAC/10.5VAC)
11. Control Board See "II.D. Control Board Check"
12. Bin Control See "II.E. Bin Control Check"
13. Fill/Rell (WV1) or Harvest Water Valve (WV2)
a) Voltage tap switch not set to proper voltage.
b) No neutral. White (W) wire to ground 0VAC. (White (W) wire to
ground should be 60VAC).
b) External water lters clogged.
b) Condensing unit fan(s) not operating.
c) Headmaster (C.P.R.) open.
d) Refrigerant overcharged.
e) Bad contacts.
f) Refrigerant lines or components plugged.
a) Ambient temperature too warm.
b) Compressor or compressor components defective.
c) Defective.
d) Hot gas valve(s) open.
e) Dirty condenser.
f) Condensing unit fan(s) not operating.
a) Disconnected or loose connection.
b) Bad contacts.
a) Coil winding open or shorted.
a) In alarm.
b) Yellow "BC OPEN" LED on: Bin full.
c) Defective.
a) Tripped with bin lled with ice.
b) Actuator does not move freely.
c) Defective.
a) Screen or orice clogged.
b) Coil winding open.
c) Water valve open in freeze cycle.
32
Page 33
No Ice Production - Possible Cause
14. Float Switch See "II.F. Float Switch Check and Cleaning"
15. Compressor a) Magnetic contactor contacts bad or coil winding open.
16. Hot Gas Valves (KMS & SRK) a) Closed in harvest cycle.
1 7. Thermistor
See "II.G. Thermistor Check"
18. Pump Motor a) Motor winding open.
19. Thermostatic Expansion Valve a) Bulb loose.
20. Liquid Line Valves (KMS & SRK) a) Closed in freeze cycle.
2 1. Fan Motors-Remote a) Motor winding open.
22. Headmaster a) Defective.
23. Water System a) Water leaks causing short freeze time.
a) Float does not move freely.
b) Defective.
b) Start capacitor or run capacitor defective (1 phase SRK).
c) Start relay contacts bad or coil winding open
(1 phase SRK).
d) Internal protector open.
e) Compressor defective.
b) Open in freeze cycle.
a) Loose, disconnected, or defective.
b) Bearing worn out or locked rotor.
c) Defective capacitor.
b) Operating erratically.
b) Open in harvest cycle.
b) Bearing worn out or locked rotor.
c) Defective capacitor.
33
Page 34
2. Freeze-Up
Defrost and clean the icemaker prior to diagnosing freeze-up. Fill out a freeze-up checklist. See "II.J. Freeze Up Check List," the Hoshizaki America Technician's Pocket Guide, or contact your local distributor for a copy of the freeze-up checklist.
Freeze-Up - Possible Cause
Harvest Cycle
1. Evaporator a) Scaled up.
b) Damaged.
2. Cube Guides a) Out of position.
b) Damaged.
3. Spray Tubes, Spray Guides, and Splash Guard or Splash Curtain
4. Water Supply a) Low water pressure.
5. Harvest Water Valve (WV2) a) Defective.
6. Float Switch See "II.F. Float Switch Check and Cleaning"
7. Refrigerant Charge a) Low.
8. Control Board See "III. Controls and Adjustments" and "II.D. Control Board Check"
9. Bin Control See "II.E. Bin Control Check"
10. Thermistor See "II.G. Thermistor Check"
11. Thermostatic Expansion Valve a) Defective.
12. Hot Gas Valves (KMS & SRK) a) Closed or restricted.
13. Liquid Line Valves (KMS & SRK) a) Open.
1. Evaporator a) Scaled up.
2. Spray Tubes, Spray Guides, and Splash Guard or Splash Curtain
3. Refrigerant Charge a) Low.
4. Control Board See "II.D. Control Board Check"
5. Fill/Rell (WV1) or Harvest Water Valve (WV2)
6. Float Switch See "II.F. Float Switch Check and Cleaning"
7. Pump Motor a) RPM too slow.
a) Dirty.
b) Out of position.
b) External water lters clogged.
c) Insufficient water line size.
Minimum 3/8" nominal ID copper water tubing or equivalent.
a) Float does not move freely.
b) Defective.
a) Harvest timer (S4 dip switch 1 & 2) set too short.
b) Harvest pump timer (S4 dip switch 7) not in factory default position.
c) Defective.
a) Bulb out of position.
b) Defective.
a) Loose, disconnected, or defective.
Freeze Cycle
b) Damaged.
a) Dirty.
b) Out of position.
a) Freeze timer (S4 dip switch 9 & 10) set incorrectly.
b) Defective.
a) Leaking by.
a) Float does not move freely.
b) Defective.
b) Impeller damaged.
34
Page 35
Freeze-Up - Possible Cause
8. Thermostatic Expansion Valve a) Bulb loose or defective.
9. Headmaster a) Defective.
10. Liquid Line Valves (KMS & SRK) a) Restricted.
3. Low Ice Production
Low Ice Production - Possible Cause
Long Harvest Cycle
1. Evaporator a) Scaled up.
2. Spray Tubes, Spray Guides, and Splash Guard or Splash Curtain
3. Refrigerant Charge a) Low.
4. Water Supply a) Low water pressure.
5. Control Board See "II.D. Control Board Check"
6. Thermistor See "II.G. Thermistor Check"
7. Hot Gas Valves (KMS & SRK) a) Erratic or closed.
8. Harvest Water Valve (WV2) a) Screen or orice clogged.
9. Compressor a) Inefficient or off.
10. Liquid Line Valves (KMS & SRK) a) Erratic or open.
11. Thermostatic Expansion Valve (TXV)
12. Headmaster a) Defective.
1. Evaporator a) Scaled up, dirty.
2. Float Switch See "II.F. Float Switch Check and Cleaning"
3. Fill/Rell (WV1) or Harvest Water Valve (WV2)
4. Hot Gas Valves (KMS & SRK) a) Erratic or open.
5. Condenser a) Clogged.
6. Control Board See "II.D. Control Board Check"
7. Refrigerant Charge a) Low.
8. Thermostatic Expansion Valve (TXV)
9. Compressor a) Inefficient or off.
10. Pump Motor a) RPM too slow.
11. Liquid Line Valves (KMS & SRK) a) Erratic or restricted.
12. Headmaster a) Defective.
a) Dirty.
b) Out of position.
b) External water lters clogged.
c) Insufficient water line size.
Minimum 3/8" nominal ID copper water tubing or equivalent.
d) Too cold.
a) Thermistor connection loose (K3).
b) Defective.
a) Loose, disconnected, or defective.
a) Defective.
Long Freeze Cycle
a) Scaled up, dirty.
b) Float sticking.
c) Defective switch.
a) Leaking by.
a) Float switch connection loose (K5).
b) Defective.
a) Bulb loose.
b) Defective.
35
Page 36

J. Freeze-Up Check List

Freeze-Up Check List
Please Complete When Diagnosing a Freeze-Up, Refrigerant Leak, or Low Charge
Technical Support Fax #: 770-487-3360
Make Copies And Use As Needed
Model #___________________________ Serial # _________________________Install Date______________Fail Date___________
List model and manufacture of bin or dispenser__________________________.
Date appliance was last cleaned:__________.
Freeze-Up Defrost
YES NO [ ] [ ] 1) After defrosting, was the appliance leak
checked?
[ ] [ ] 2) Were any leaks found?
If so where?_____________________.
[ ] [ ] 3) Was any refrigerant added to the unit?
If so, how much?_________________.
Set Up
[ ] [ ] 4) Is the appliance stacked? [ ] [ ] 5) Is water line independent? [ ] [ ] 6) Is water line correct size? If not________”.
3/8" Nominal ID Copper Water Tubing or Equivalent.
7) What is water pressure?___________. Water Temperature_________.
[ ] [ ] 8) Does appliance have any water ltration?
If yes please list the following: Filter brand___________________. Model________________. Filter pressure gauge reading during the ll cycle___________. Date lter was last replaced?__________________________. GPM or LPM ow rate of lter system?__________________.
9) Ambient temperature at appliance? ______________.
At remote condenser (if applicable)?________.
Appliance Status
[ ] [ ] 10) Is the appliance and/or oat switch dirty?
11) List the S4 (1-10) and S5 (1-5) DIP switch settings.
S4: 1___2___3___4___5___6___7___8___9___10____ S5: 1_____2_____3_____4_____5______ [ ] [ ] 12) Is DIP switch number 7 ON (harvest pump
time (harvest assist) all models and freeze-time correction models with control board
2A7664-02? [ ] [ ] 13) Is the cube guide positioned correctly? [ ] [ ] 14) Are the evaporator separators positioned
properly? [ ] [ ] 15) Is the thermistor properly mounted, tight, and
insulated? [ ] [ ] 16) Is the TXV bulb properly mounted, tight, and
insulated?
Appliance Operation
Fill YES NO [ ] [ ] 17) Does the water tank ll and overow?
60-90 sec. Note: Larger models may take up to
120 seconds to overow when empty. [ ] [ ] 18) If NO in step 17, is water ow 5GPM for larger? [ ] [ ] 19) Does the appliance utilize re-ll (S5 dip switch
2and 3)?
Harvest [ ] [ ] 20) Is the hot gas valve opening? [ ] [ ] 21) Is harvest pump time (harvest assist) utilized
(S4dip switch 7)? [ ] [ ] 22) Is hot gas valve opening in harvest? [ ] [ ] 23) Does water valve close completely when
de energized?
24) What was length of harvest?___________.
Freeze [ ] [ ] 25) Is pump motor energized in freeze cycle except
during 10-sec. anti-slush. If activated (S5 dip
switch 5 on)?
26) Water-cooled condenser outlet temperature 5-min. into freeze? ______________°F.
27) What was length of freeze?____________.
[ ] [ ] 28) Is the cube size consistent from inlet to outlet of
evaporator?
[ ] [ ] 29) Is ice still dropping when next freeze cycle starts?
30) What is the ice drop weight?___________.
31) What is head pressure? Freeze_________Harvest_______. (Freeze pressure should be taken 5 minutes into the cycle).
32) What is suction pressure? Freeze______Harvest_______. (Freeze pressure should be taken 5 minutes into the cycle).
[ ] [ ] 33) When activating bin control, did appliance
shutdown within 15seconds in the rst 5minutes of freeze cycle?
Freeze-Time Correction Operation
[ ] [ ] 34) Has Freeze-Time Correction been activated?
("POWER OK" LED blinking).
[ ] [ ] 35) Has more than 1 Freeze-Time Correction been
activated? (POWER OK" LED and "EXT HARVEST" LED blinking).
Note: Make copies of this form and use it when diagnosing a freeze up condition. Submit a completed copy of the checklist
along with the freeze-up labor claim form.
36
Page 37

III. Settings and Adjustments

• A Hoshizaki exclusive control board is employed in the Hoshizaki icemakers.
• All models are pretested and factory adjusted.
• For a control board check procedure, see "II.D. Control Board Check."
NOTICE
• Fragile, handle very carefully.
• The control board contains integrated circuits, which are susceptible to failure due to static discharge. It is especially important to touch the metal part of the icemaker when handling or replacing the control board.
• Do not touch the electronic devices on the control board or the back of the control board.
• Do not change wiring and connections. Do not misconnect terminals.
• Do not short out power supply to test for voltage.
• Always replace the whole control board assembly if it goes bad.
37
Page 38

A. Control Board Layout

• Bin Control Switch Closed LED (green)
• "ALARM RESET" Button
"J" Control Board
• S4 Dip Switch
• "OUTPUT TEST" Button
(used to test relays on control board)
• Bin Control Switch Open LED (yellow)
• Alarm Buzzer
• Ext. Harvest LED (yellow)
(blinks when 3rd occurrence of freeze time correction initiates within 36 hr.)
• POWER OK LED
(red) (lights when
10.5VAC is supplied to K2 connector)
• Relay LEDs
(4) (indicate which relays are energized and which K1 connector pins are energized
• LED 2 (X2 Relay)
LED 2 on: K1 Connector Pin #2 LED 2 off: K1 Connector Pin #3
• LED 3 (X3 Relay)
LED 3 on: K1 Connector Pin #5 LED 3 off: K1 Connector Pin #4 (energized in freeze)
• LED 4 (X4 Relay) K1 Connector Pin #6
• LED 1 (X1 Relay)
K1 Connector Pin #1, #9
• K3 (white) Connector
Thermistor (harvest control and high temperature safety)
• K4 (red) Connector
Bin Control
• S5 Dip Switch
• K5 (black) Connector
Float Switch (water level)
• Part Number
• K1 Connector
Pins #1 through #10 #1, 9 Magnetic Contactor, X13 Relay #2 Hot Gas Valves, X10 Relay #3 Liquid Line Valves #4 Pump Motor #5 X11 Relay (harvest pump timer and pump-out) #6 Fill/Rell water valve (WV1), Harvest water valve (WV2), X12 Relay #7, 10 Component Power Supply #8 Open
• K2 Connector
Control Transformer (10.5VAC)
"J" Control Board
Part Number 2A7664-02
38
Page 39

B. LED Lights and Audible Alarm Safeties

Beep occurs and red CB "POWER OK" LED turns on when control switch is moved to "ICE" position.
Sequence
Green LEDs 1 through 4 turn on and sequence from initial startup as listed in the table below. Order of green LEDs from the outer edge of control board is 1, 4, 3, 2.
Sequence Step LED
1-Minute Fill Cycle 4 WV Harvest Cycle 1, 4, 2 Comp, FM*, FMRs, HGVs, WV1/WV2 1 minute 20 minutes Harvest Pump Time
(harvest assist) Freeze Cycle 1 Comp, FM/FMRs, PM, LLV 5 minutes freeze timer
Anti-Slush Control 1, 3 Comp, FM/FMRs, LLV If S5 dip switch 5 on,
Pump-Out Cycle 1, 4 *FM energized if on K1 Connector Pin #9;
1, 3, 2 Comp, FM*, FMRs, HGVs, PM 0 seconds 50 seconds
, 3, 2 Comp, FM*, FMRs, WV †, PM, HGVs, DV 10 seconds 20 seconds
pump-out timer setting
Energized
Components
Time LEDs are On
Min. Max.
setting
PM off 10 sec. when thermistor at 36°F (2.2°C)
Alarms
Type Alarm Notes
1
Beep
2
Beep
3
Beep
LED Blink Freeze-Time Correction
To reset above safeties, press "ALARM RESET" button with power supply on.
6 Low Voltage
7 High Voltage
High Evaporator Temp. (temperature > 127°F) (53°C)
Harvest Backup Timer (harvest > 20 min. for two cycles in a row)
Freeze Timer (freeze > freeze timer setting for two cycles in a row)
(maximum freeze time differential exceeded)
(92Vac±5% or less)
(147Vac±5% or more)
Check for harvest problem (stuck HGV or relay), hot water entering unit, stuck HM, or shorted thermistor.
Check thermistor (open), HGV not opening, TXV or LLV leaking by, low charge, inefficient Comp, or WRV leaking by.
Check FS stuck closed (up), WV leaking by, HGV leaking by, PM not pumping, TXV defective, LLV not opening, low charge, HMnot bypassing, or inefficient Comp.
RED POWER OK LED blinks. After 3rdfreeze-time correction cycle in 36hours starts CByellow "EXT HARVEST" LED blinking. Fill out freeze-up checklist.
Red LED turns off if voltage protection operates. Control voltage safeties automatically reset when voltage is corrected.
Legend: Comp–compressor; FM–fan motor; FMR–fan motor remote; FS–oat switch;
HGV–hot gas valve; HM–headmaster (C.P.R.); L LV –liquid line valve; PM–pump motor; TXV–thermostatic expansion valve; WRV–water regulating valve;
WV1–ll/re-ll water valve; WV2–harvest water valve
Test
To perform output test, move control switch to "ICE" position. Press "OUTPUT TEST" button. Correct green LED lighting sequence is 1, 4, 3, 2. Components (e.g., compressor) cycle during test. Following test, icemaker resumes operation.
Dip switches must be adjusted per unit’s service manual or Hoshizaki Technical Support recommendation. S4 dip switch 8 must remain off.
39
Page 40

C. Settings and Adjustments

NOTICE
Dip switches are factory set. Failure to maintain factory settings may adversely affect performance and warranty coverage. For more information, contact Hoshizaki Technical Support at 1-800-233-1940.

1. Default Dip Switch Settings

The dip switches are factory-adjusted to the following positions:
S4 Dip Switch
Dip Switch No. 1 2 3 4 5 6 7 8 9 10
KMS-1402MLJ\3 OFF OFF OFF ON ON ON ON OFF OFF OFF
S5 Dip Switch (Do Not Adjust)
Dip Switch No.
KMS-1402MLJ/3 ON ON OFF OFF OFF
1 2 3 4 5
S4 Dip Switch
ON
Freeze Timer (9 & 10)
Factory Use (8) Harvest Pump Time (Harvest Assist)/Freeze-Time Correction (7) (Do Not Adjust)
Harvest Pump Time (Harvest Assist Duration) (6) (Do Not Adjust)
Pump-Out Frequency Control (5)
Pump-Out Time/Harvest Time During Pump-Out (3 & 4)
1 2 3 4 5 6 7 8 9 10
Harvest Time (1 & 2)
S5 Dip Switch
Do Not Adjust
Anti-Slush (5)
Minimum Harvest Time (4)
Rell Counter (2 and 3)
ON
1 2 3 4 5
Float Switch Selector (1)
40
Page 41

2. Harvest Time (S4 dip switch 1 & 2)

The harvest timer starts counting when the thermistor reaches 48°F (9°C) at the evaporator outlet and the control board reads 3.9 kΩ from the thermistor. The harvest timer is factory set, and generally no adjustment is required. However, a setting longer than the factory setting may be advised in cases where the drain provided at harvest needs to be prolonged for extra cleaning. Note that the pump-out timer (S4 dip switch 3 & 4) acts in place of the harvest timer during cycles with a pump out. For details, see "III.C.3. Pump-Out Timer (S4 dip switch 3& 4)."
Note: On models with a pump-out every cycle, the harvest timer is only relevant during
the initial harvest cycle since a pump out occurs every cycle thereafter.
Time
S4 Dip Switch Setting
No. 1 No. 2 S5-4 OFF S5-4 ON
OFF OFF 60 30
ON OFF 90 45
OFF ON 120 60
ON ON 180 75
(sec.)

3. Pump-Out Time/Harvest Time During Pump-Out (S4 dip switch 3 & 4)

NOTICE
Do not adjust 3 off and 4 on. Drain valve does not energize in this setting.
When a pump-out is called for, the pump motor stops for 2 sec. After 2 sec. the drain valve and pump motor energize. Water is removed from the bottom of the water tank and sent down the drain. The pump-out drains the water tank for the time determined by the pump-out timer. The pump-out timer also acts in place of the harvest timer during cycles with a pump-out. The pump-out timer is factory set, and generally no adjustment is required. However, where water quality is bad and the icemaker needs a longer pump-out time, the pump-out timer can be adjusted. The pump-out timer control can be set to pump-out for 10 or 20 sec.
S4 Dip Switch Setting Time (sec.)
T1 T2
No. 3 No. 4
OFF OFF 10 150 100 Closed Closed
ON OFF 10 180 130 Closed Closed
OFF ON 10 120 70 Open Closed
ON ON 20 180 180 Closed Closed
T1: Time to drain the water tank T2: Harvest timer at pump out
S5-4 OFF S5-4 ON S5-4 OFF S5-4 ON
Fill/Rell Water
Valve
41
Page 42

4. Pump-Out Frequency Control (S4 dip switch 5)

The pump-out frequency control is factory set to drain the water tank every 10 cycles. Generally no adjustment is required. However, where water quality is bad and the icemaker needs a pump-out more often, the pump-out frequency can be adjusted. The pump-out frequency control can be set to have a pump-out occur every cycle, or every 10 cycles.
The rst pump-out is dependent on S4 dip switch 5. See the table below.
S4 Dip Switch Setting
No. 5
OFF Every 10 cycles After 11th freeze cycle
ON Every cycle After 2nd freeze cycle
Pump-Out Frequency 1st Pump-Out

5. Harvest Pump Time (Harvest Assist Duration) (S4 dip switch 6)

NOTICE
Factory set for proper operation. Do not adjust. Adjustment outside of the factory default setting may result in damage to the appliance.
Harvest pump time (harvest assist duration) is controlled by S4 dip switch 6 and S5 dip switch 4. See table below. Harvest pump time (harvest assist duration) is only active when S4 dip switch 7 is in the "ON" position. In the factory default position, the harvest pump time (harvest assist duration) starts with 50sec. left to go in harvest cycle (S4 dip switch 6) and after the thermistor reaches 48°F (9°C) at the evaporator outlet and the control board reads 3.9kΩ from the thermistor. The harvest pump time (harvest assist duration) is factory set, and no adjustment is required.
Harvest Pump Time
S4 Dip Switch Setting
No. 6 S5-4 OFF S5-4 ON
OFF 50 sec. 25 sec.
ON 25 sec. 15 sec.
(Harvest Assist)
42
Page 43

6. Harvest Pump Time (Harvest Assist)/Freeze-Time Correction (S4 dip switch 7)

NOTICE
Factory set for proper operation. Do not adjust. Adjustment outside of the factory default setting may result in damage to the appliance.
a) Depending on the harvest pump timer setting, the pump motor either stays off or is
energized the last 50 seconds of harvest. When the pump motor is energized, water circulates over the evaporator. The harvest water valve (WV2) and X12 relay are energized during harvest for a maximum of 6 minutes or the length of harvest minus 0 or 50 seconds (determined by the harvest pump timer setting), whichever is shorter. When S4 dip switch 7 is in the on position and harvest begins, X10 relay energizes and allows the harvest water valve (WV2), X12, and X13 relays to energize. A lockout circuit is created using the X10, X12, and X13 relays. This prevents the drain valve from energizing during harvest pump timer. See "VIII.B. Wiring Diagram." 50 seconds before harvest termination, LED 4 goes off de-energizing WV2 (harvest water valve) and X12 relay. X13 relay remains energized through the holding circuit through X10 and X13 relays. Next, LED 3 on the control board turns on and X11relay energizes, allowing the pump motor to energize. The pump motor is energized the last 50seconds of harvest.
b) Freeze-Time Correction
When S4 dip switch 7 is in the on position, freeze-time correction enabled. See "II.C. Freeze-Time Correction Cycle (90 min.)."
S4 Dip Switch Setting Harvest Pump
Time (sec.)
No. 7
OFF 0 Disabled
ON 50 Enabled
(Harvest Assist)
Freeze-Time
Correction

7. Factory Use (S4 dip switch 8)

Factory set for proper operation. Do not adjust. This must be left in the factory default position.
43
Page 44

8. Freeze Timer (S4 dip switch 9 & 10)

NOTICE
Adjust to proper specication, or the icemaker may not operate correctly.
The freeze timer setting determines the maximum allowed freeze time to prevent possible freeze-up issues. Upon termination of the freeze timer, the control board initiates the harvest cycle or pump-out cycle. After 2 consecutive freeze timer terminations, the control board shuts down the icemaker. In this case, see "II.I.3. Low Ice Production" for possible solutions. The freeze timer is factory set and no adjustment is required. Before changing this setting, contact Hoshizaki Technical Support at 1-800-233-1940 for recommendations.
S4 Dip Switch Setting Time
No. 9 No. 10
OFF OFF 60
OFF ON 50
ON OFF 70
ON ON 75

9. Float Switch Control Selector (S5 dip switch 1)

(min.)
NOTICE
Do not adjust. This must be left in the factory default position or the icemaker will not operate correctly.
Float switch selector used in applications where rell is required in the freeze cycle. Rells set by S5 dip switch 2 and 3. Note: In single oat switch with upper oat operation only 1 rell allowed. (reword).
• Single oat switch application:
• With S5 dip switch 1 in the "OFF" position, control board monitors the lower oat switch for rell operation.
• With S5 dip switch 1 in the "ON" position, the control board monitors the upper oat switch for rell operation. In this case no upper oat switch exists, therefore the control board reads an open upper oat switch immediately when the freeze cycle starts and initiates a rell. Since there is no upper oat switch to close and terminate the rell, the rell lasts for a maximum of 1-min. During the 1-min. rell, LED 4 is on.
• Double oat switch application: Float switch control selector determines which oat
switch (upper or lower) the control board monitors for rell control during the freeze cycle.
S5 Dip Switch Setting
OFF Lower Float Switch Enabled
ON
Upper or Lower Float Switch
ControlNo. 1
Upper Float Switch Enabled
(this setting is ignored if rell counter
(S5 dip switch 2 and 3) set to 0)
44
Page 45
10. Rell Counter (S5 dip switch 2 and 3)
NOTICE
Do not adjust. These must be left in the factory default position or the icemaker will not operate correctly.
The rell counter determines the number of rells. The KMS-1122MLH does not rell during the freeze cycle.
S5 Dip Switch Setting Rell
No. 2 No. 3
OFF OFF 0
OFF ON 1 rell
ON OFF 9 rells
ON ON 10 rells
Counter

11. Minimum Harvest Time (S5 dip switch 4)

NOTICE
Factory set for proper operation. Do not adjust. Adjustment outside the factory default setting may result in damage to the appliance.
S5 Dip Switch Setting Minimum
No. 4
OFF 120 sec.
ON 70 sec.
Harvest Timer

12. Anti-Slush (S5 dip switch 5)

NOTICE
Factory set for proper operation. Do not adjust. Adjustment outside the factory default setting may result in damage to the appliance.
This dip switch setting provides anti-slush control during the freeze cycle. When the evaporator temperature reaches 36°F (2.2°C) the control board reads a 5.8kΩ signal from the thermistor and de-energizes the water pump for 10 sec. to melt ice slush and prevent ice slush from blocking the water supply tubing, causing irregular freeze patterns.
S5 Dip Switch Setting
Anti-SlushNo. 5
OFF Disabled
ON Enabled
45
Page 46

IV. Refrigeration Circuit and Component Service Information

WARNING
• This appliance should be diagnosed and repaired only by qualied service personnel to reduce the risk of death, electric shock, serious injury, or re.
• Move the control switch to the "OFF" position and turn off the power supply. Place the disconnect in the "OFF" position. Lockout/Tagout to prevent the power supply from being turned back on inadvertently.
CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews are securely in place after the icemaker is serviced. Make sure that none have fallen into the dispenser unit/ice storage bin.
• Make sure all food zones in the icemaker and dispenser unit/ice storage bin are clean after service.

A. Refrigeration Circuit Service Information

WARNING
• Repairs requiring the refrigeration circuit to be opened must be performed by properly trained and EPA-certied service personnel.
• Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of refrigerant to the system (if using an electronic leak detector), and then raise the pressure using nitrogen gas (140 PSIG). Do not use R-404A as a mixture with pressurized air for leak testing.
NOTICE
• Always recover the refrigerant and store it in an approved container. Do not discharge the refrigerant into the atmosphere.
• Do not leave the system open for longer than 15 min. when replacing or servicing parts. The Polyol Ester (POE) oils used in R-404A applications can absorb moisture quickly. Therefore it is important to prevent moisture from entering the system when replacing or servicing parts.
• Always install a new drier every time the sealed refrigeration system is opened. Do not replace the drier until after all other repair or replacement has been made. Install the new drier with the arrow on the drier in the direction of the refrigerant ow.
• When brazing, protect the drier by using a wet cloth to prevent the drier from overheating. Do not allow the drier to exceed 250°F (121°C).
1. Refrigerant Recovery
The condensing unit and icemaker are provided with refrigerant shutoff valves. Using proper refrigerant practices, recover the refrigerant. Recovery via the condensing unit's refrigerant shutoff valves is recommended. Store the refrigerant in an approved container. Do not discharge the refrigerant into the atmosphere.
46
Page 47
2. Brazing
WARNING
• R-404A itself is not ammable at atmospheric pressure and temperatures up to 176°F (80°C).
• R-404A itself is not explosive or poisonous. However, when exposed to high temperatures (open ames), R-404A can be decomposed to form hydrouoric acid and carbonyl uoride both of which are hazardous.
• Do not use silver alloy or copper alloy containing arsenic.
1) Braze all ttings while purging with nitrogen gas owing at a pressure of 3 to 4 PSIG. Note: Because the pipes in the evaporator case are specially coated to resist corrosion,
it is important to make connections outside the evaporator case when possible. Ifit is necessary to braze inside the evaporator case, use sandpaper to remove the coating from the brazing connections before unbrazing the components.
NOTICE
• Always install a new drier every time the sealed refrigeration system is opened.
• Do not replace the drier until after all other repair or replacement has been made. Install the new drier with the arrow on the drier in the direction of the refrigerant ow.
• When brazing, protect the drier by using a wet cloth to prevent the drier from overheating. Do not allow the drier to exceed 250°F (121°C).
2) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of refrigerant to the system (if using an electronic leak detector), and then raise the pressure using nitrogen gas (140 PSIG). Do not use R-404A as a mixture with pressurized air for leak testing.
3. Evacuation and Recharge (R-404A)
The condensing unit and icemaker are provided with refrigerant shutoff valves. Evacuation and recharge via the condensing unit's refrigerant shutoff valves is recommended.
1) Attach a vacuum pump to the system. Be sure to connect the charging hoses to both high and low-side refrigerant access valves.
IMPORTANT
The vacuum level and vacuum pump may be the same as those for current refrigerants. However, the rubber hose and gauge manifold to be used for evacuation and refrigerant charge should be exclusively for POE oils.
2) Turn on the vacuum pump. Open the gauge manifold valves. Never allow the oil in the vacuum pump to ow backwards.
3) Allow the vacuum pump to pull down to a 29.9" Hg vacuum. Evacuating period depends on pump capacity.
47
Page 48
4) Close the low-side valve and high-side valve on the gauge manifold.
5) Disconnect the gauge manifold hose from the vacuum pump and attach it to a refrigerant service cylinder. Remember to loosen the connection and purge the air from the hose. For the required refrigerant charge, see the rating label inside the icemaker. Hoshizaki recommends only virgin refrigerant or reclaimed refrigerant which meets ARI Standard 700 (latest edition) be used.
6) A liquid charge is required when charging an R-404A system (to prevent fractionation). Place the service cylinder on the scales; if the service cylinder is not equipped with a dip tube, invert the service cylinder, then place it on the scales. Open the high-side valve on the gauge manifold.
7) Allow the system to charge with liquid until the proper charge weight is met.
8) If necessary, add any remaining charge to the system through the low-side.
NOTICE!To prevent compressor damage, use a throttling valve or liquid dispensing device to add the remaining liquid charge through the low-side refrigerant access valve with the icemaker running.
9) Close the high and low-side gauge manifold valves, then disconnect the gauge manifold hoses.
10) Cap the refrigerant access valves to prevent a possible leak.
48
Page 49

B. Component Service Information

NOTICE
When replacing a component listed below, see the notes to help ensure proper operation.
Component Notes
Compressor 1 Phase SRK: Install a new start capacitor, run capacitor, and start relay.
3 Phase SRK: Install a new magnetic contactor.
Thermostatic Expansion Valves
Hot Gas Valves Liquid Line Valves
Fan Motors Install a new capacitor.
Pump Motor Install a new capacitor.
Thermistor • Attach the new thermistor to the suction line in the same location as the previous
• Attach the thermostatic expansion valve bulb to the suction line in the same location as the previous bulb.
• The bulb should be between the 10 and 2 o'clock positions on the tube.
• Secure the bulb with the clamp and holder, then insulate it.
• Replace the strainer if applicable.
• Use copper tube of the same diameter and length when replacing valve lines.
thermistor.
• The thermistor should be at the 12 o'clock position on the tube.
• Smoothly ll the recessed area of the thermistor holder with high thermal conductive type sealant. Hoshizaki America part number 4A0683-01 (Silicone Heat Sink Compound 10-8108 manufactured by GC Electronics), KE-4560 RTV (manufactured by ShinEtsu Silicones), or equivalent are recommended.
• Secure the thermistor with the holder, then insulate it.
• Be very careful to prevent damage to the leads.
49
Page 50

V. Maintenance

The maintenance schedule below is a guideline. More frequent maintenance may be required depending on water quality, the appliance's environment, and local sanitation regulations.
WARNING
• Only qualied service technicians should service the appliance.
• To reduce the risk of electric shock, do not touch the control switch or service switch with damp hands
• Before servicing: Move the control switch to the "OFF" position and turn off the power supply. Place the disconnect in the "OFF" position. Lockout/Tagout to prevent the power supply from being turned back on inadvertently.
CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews are securely in place after any maintenance is done to the icemaker. Make sure that none have fallen into the dispenser unit/ice storage bin.
Maintenance Schedule
Frequency Area Task
Daily Scoop Clean the ice scoop using a neutral cleaner. Rinse thoroughly after
cleaning. Bi-Weekly Air Filters Inspect. Wash with warm water and neutral cleaner if dirty. Monthly External Water
Filters Icemaker Exterior Wipe down with a clean, soft cloth. Use a damp cloth containing a
Underside of Icemaker and Top Kits; Bin Door and Snout
Yearly Icemaker and
Dispenser Unit/Ice Storage Bin Liner
Water Supply Inlet Close the icemaker water supply line shut-off valve and drain the water
Condenser Inspect. Clean if necessary by using a brush or vacuum cleaner. More
Water Hoses Inspect the water hoses and clean/replace if necessary.
Check for proper pressure and change if necessary.
neutral cleaner to wipe off oil or dirt build up. Clean any chlorine staining
(rust colored spots) using a non-abrasive cleanser.
Wipe down with a clean cloth and warm water.
Clean and sanitize per the cleaning and sanitizing instructions provided
in the instruction manual or maintenance label on the icemaker.
system. Clean the water supply inlet screen.
frequent cleaning may be required depending on location.
50
Page 51

VI. Preparing the Appliance for Periods of Non-Use

NOTICE
• When storing the appliance for an extended time or in sub-freezing temperatures, follow the instructions below to prevent damage.
• To prevent damage to the water pump, do not operate the appliance with the control switch in the "SERVICE" position when the water tank is empty.
When the appliance is not used for two or three days under normal conditions, it is sufficient to move the control switch to the "OFF" position. When storing the appliance for an extended time or in sub-freezing temperatures, follow the instructions below.
1) Turn off the power supply, then remove the front panel.
2) Move the control switch to the "OFF" position. Conrm that the service switch is in the "CIRC." position.
3) Remove the front insulation, front frame, right side panel, and control box cover.
4) Disconnect the thermistor connector from the control board K3 (white) connector, then unplug the water pump connector at the water pump.
5) Wait 3 minutes, then move the control switch to the "ICE" position. Conrm that the bin control switch is closed and calling for ice. The green "BC CLOSED" LED on the control board should be on.
6) Once LED 1 and 2 on the control board energize (the order of the LEDs from the outer edge of the control board is 1, 4, 3, 2), close the inlet water supply line shut-off valve and open the inlet water supply line drain valve. Allow the line to drain by gravity.
7) Disconnect the harvest water valve (WV2) hose in the evaporator section and blow out the water line to the harvest water valve (WV2) using compressed air or carbon dioxide. See Fig.5. This will clear water from the harvest water valve (WV2).
8) Move the control switch to the "OFF" position.
9) Move the service switch to the "WASH" position and the control switch to the "SERVICE" position.
10) Using the same hose as with the harvest water valve (WV2), blow out the wash valve using compressed air or carbon dioxide.
11) Move the service switch to the "CIRC." position and the control switch to the "OFF" position.
12) Remove the 4 hoses connected to the water tank. Allow the water tank and hoses to completely drain.
13) Move the control switch to the "ICE" position.
14) Using the ll/rell water valve (WV1) hose, blow out the water line using compressed air or carbon dioxide. This will clear water from the ll/rell water valve (WV1).
15) Move the control switch to the "OFF" position.
16) Disconnect the oat switch ush tube from the drain hose tee. Move the service switch to the "DRAIN" position and the control switch to the "SERVICE" position.
51
Page 52
17) From the tee on the drain hose, blow out the drain valve using compressed air or carbon dioxide.
18) Move the service switch to the "CIRC." position and the control switch to the "OFF" position.
19) Turn off the power supply.
20) Reconnect the thermistor connector to the control board K3 (white) connector. Reconnect the water pump connector.
21) Close the inlet water supply line drain valve.
22) Remove all ice from the dispenser unit/storage bin and clean the dispenser unit/storage bin liner using a neutral cleaner. Rinse thoroughly after cleaning.
23) Replace all removed parts and panels in their correct positions.
Harvest Water Valve Hose
Harvest Water Valve (WV2)
Drain Hose Tee
Suction Hose
Wash Valve
Fill/Rell Water Valve Hose
Fill/Rell Water Valve (WV1)
Float Switch Flush Tube
Drain Valve
Fig. 5
52
Page 53

VII. Disposal

This appliance contains refrigerant and must be disposed of in accordance with applicable national, state, and local codes and regulations. Refrigerant must be recovered by properly certied service personnel.
53
Page 54

VIII. Technical Information

We reserve the right to make changes in specications and design without prior notice.
A. Specication and Performance Data Sheets
Pressure data is recorded at 5 min. into freezing cycle. The data not in bold should be used for reference only.

1. KMS-1402MLJ with SRK-15J

Specification Sheet
AC SUPPLY VOLTAGE 115VAC Supplied by SRK-15J via Factory Supplied
Wire Harness
ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F
ELECTRIC W (kWH/100 lbs.) 2510 (4.30) 2310 (3.70)
WATER gal./24HR (gal./100 lbs.) 294 (21.0) 642 (42.8)
ICE PRODUCTION PER CYCLE 26.4 lbs. (12 kg) 1248pcs.
BIN CONTROL SYSTEM Mechanical Lever Switch
REFRIGERANT CHARGE TOTAL R404A, 16 lb. 5 oz. (7400g)
ICEMAKER, 0 lb. 7.1 oz. (200g)
CONDENSER, 15 lb. 14 oz. (7200g)
Performance Sheet
APPROXIMATE ICE PRODUCTION PER 24 HR.
lbs./day kg./day APPROXIMATE ELECTRIC CONSUMPTION
watts 100/38 APPROXIMATE WATER CONSUMPTION PER 24 HR.
gal./day m3/day FREEZING CYCLE TIME
min. 100/38 HARVEST CYCLE TIME
min. 100/38 HEAD PRESSURE
PSIG kg/cm2G SUCTION PRESSURE
PSIG kg/cm2G
AMBIENT
TEMP. (ºF/ºC)
70/21 1501 681
80/27 1478 671 1432 650 1269 576
90/32 1471 667 1400 635 1253 568
100/38 1421 644 1365 619 1117 507
70/21
80/27
90/32
70/21 642 2.43
80/27 565 2.14 406 1.54 1471 5.57
90/32 540 2.05 294 1.11 1190 4.51
100/38 716 2.71 504 1.91 2014 7.62
70/21
80/27
90/32
70/21
80/27
90/32
70/21 183 12.9
80/27 196 13.8 222 15.6 233 16.4
90/32 200 14.0 240 16.9 254 17.8
100/38 200 14.1 243 17.1 266 18.7
70/21 45 3.2 46 3.2 48 3.4
80/27 46 3.2 47 3.3 49 3.5
90/32 46 3.2 48 3.4 50 3.5
100/38 46 3.3 48 3.4 52 3.7
50/10 70/21 90/32
2310
2355 2446 2461
2369
2362 2516 2560
22
23 24 27
23
24 26 30
4.4
3.9 3.1 3.0
3.8
3.1 2.4
WATER TEMP. (ºF/ºC)
1471 667 1352 613
2369 2407
2510
540 2.05 1175 4.45
23 25
26
3.8 3.5
2.4
200 14.0 215 15.1
2536
28
2.2
2.0
TOTAL HEAT OF REJECTION FROM CONDENSER
TOTAL HEAT OF REJECTION FROM COMPRESSOR 3,500 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
CONDENSER VOLUME 226 CU. IN (SRK-15J)
28,400 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
54
Page 55

2. KMS-1402MLJ with SRK-15J3

Specification Sheet AC SUPPLY VOLTAGE 115VAC Supplied by SRK-15J3 via Factory Supplied
Wire Harness ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 2510 (4.55) 2340 (3.81) WATER gal./24HR (gal./100 lbs.) 292 (22.0) 725 (49.2) ICE PRODUCTION PER CYCLE 26.4 lbs. (12 kg) 1248pcs. BIN CONTROL SYSTEM Mechanical Lever Switch REFRIGERANT CHARGE TOTAL R404A, 16 lb. 5 oz. (7400g)
ICEMAKER, 0 lb. 7.1 oz. (200g)
CONDENSER, 15 lb. 14 oz. (7200g)
Performance Sheet APPROXIMATE ICE PRODUCTION PER 24 HR.
lbs./day kg./day APPROXIMATE ELECTRIC CONSUMPTION
watts 100/38 APPROXIMATE WATER CONSUMPTION PER 24 HR.
gal./day m3/day FREEZING CYCLE TIME
min. 100/38 HARVEST CYCLE TIME
min. 100/38 HEAD PRESSURE
PSIG kg/cm2G SUCTION PRESSURE
PSIG kg/cm2G
AMBIENT
TEMP. (ºF/ºC)
70/21 1474 669 80/27 1441 654 1373 623 1258 571 90/32 1430 649 1325 601 1217 552
100/38 1399 635 1300 589 1117 507
70/21 80/27 90/32
70/21 725 2.75 80/27 628 2.38 431 1.63 410 1.55 90/32 598 2.26 292 1.10 246 0.93
100/38 449 1.70 281 1.06 204 0.77
70/21 80/27 90/32
70/21 80/27 90/32
70/21 186 13.1 80/27 199 14.0 225 15.8 234 16.5 90/32 203 14.3 244 17.2 255 18.0
100/38 203 14.3 247 17.3 266 18.7
70/21 45 3.2 46 3.3 48 3.4 80/27 46 3.2 48 3.4 49 3.5 90/32 46 3.3 50 3.5 51 3.6
100/38 46 3.3 50 3.5 52 3.7
50/10 70/21 90/32
2340 2390 2429 2378 2455 2479 2390 2510 2541 2388 2517 2570
22 23 25 23 25 27 23 26 28 24 27 30
4.8 4.0 3.7
4.2 3.1 3.1
4.0 2.3 2.1
3.2 2.2 2.0
WATER TEMP. (ºF/ºC)
1430 649 1335 606
598 2.26 523 1.98
203 14.3 217 15.3
TOTAL HEAT OF REJECTION FROM CONDENSER TOTAL HEAT OF REJECTION FROM COMPRESSOR 3,500 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)] CONDENSER VOLUME 226 CU. IN (SRK-15J3)
28,000 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
55
Page 56

3. SRK-15J

Specification Sheet
AC SUPPLY VOLTAGE 208-230/60/1 ( 3 wire with neutral for 115V )
(115VAC Supplied to KMS via Factory Wire Harness) AMPERAGE 11.3 A ( 5 Min. Freeze AT 104°F / WT 80°F ) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A EXTERIOR DIMENSIONS (WxDxH) 50-1/4" x 17" x 28" (1274 x 432 x 712 mm) DIMENSIONS INCLUDING LEGS (WxDxH) 50-1/4" x 17" x 43" (1274 x 432 x 1092 mm) EXTERIOR FINISH Galvanized steel WEIGHT CONNECTIONS - ELECTRIC Main Power Supply: Permanent Connection
- REFRIGERATION Suction line - 5/8" Brazed Connections CIRCUIT Liquid line - 1/2" Brazed Connections COMPRESSOR Hermetic, Model CS16K6E-PFV CONDENSER Air Cooled, Fin and Tube Type COMPRESSOR PROTECTION Auto-Reset Overload Protector (Internal) FAN MOTOR PROTECTION Thermal Protection REFRIGERANT CIRCUIT PROTECTION Auto-Reset High-Pressure Switch REFRIGERANT CONTROL Condensing Pressure Regulator REFRIGERANT CHARGE
DESIGN PRESSURE High 467 PSIG, Low 230 PSIG OPERATING CONDITIONS VOLTAGE RANGE 187-253VAC
ACCESSORIES -SUPPLIED Legs and hardware
-REQUIRED
TOTAL HEAT OF REJECTION FROM CONDENSER 28,400 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)] TOTAL HEAT OF REJECTION FROM COMPRESSOR 3,500 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)] CONDENSER VOLUME 226 CU. IN.
Net 230 lbs. (104 kg), Shipping 275 lbs. (125 kg)
SRK to KMS: Wire Harness Connection
TOTAL R404A, 16 lb. 5 oz. (7400g)
ICEMAKER, 0 lb. 7.1 oz. (200g)
CONDENSER, 15 lb. 14 oz. (7200g)
AMBIENT TEMP. (Outdoor use) -20-122°F
Compatible KMS icemaker, Water Filter (2) cartridge, Ice Dispenser or Ice Storage Bin
Line set HS-0250, HS-0244, HS-0245
56
Page 57

4. SRK-15J3

Specification Sheet
AC SUPPLY VOLTAGE 208-230/60/3
(115VAC Supplied to KMS via Factory Wire Harness) AMPERAGE 9.2 A ( 5 Min. Freeze AT 104°F / WT 80°F ) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A EXTERIOR DIMENSIONS (WxDxH) 50-1/4" x 17" x 28" (1274 x 432 x 712 mm) DIMENSIONS INCLUDING LEGS (WxDxH) 50-1/4" x 17" x 43" (1274 x 432 x 1092 mm) EXTERIOR FINISH Galvanized steel WEIGHT CONNECTIONS - ELECTRIC Main Power Supply: Permanent Connection
- REFRIGERATION Suction line - 5/8" Brazed Connections CIRCUIT Liquid line - 1/2" Brazed Connections COMPRESSOR Hermetic, Model CS16K6E-TF5 CONDENSER Air Cooled, Fin and Tube Type COMPRESSOR PROTECTION Auto-Reset Overload Protector (Internal) FAN MOTOR PROTECTION Thermal Protection REFRIGERANT CIRCUIT PROTECTION Auto-Reset High-Pressure Switch REFRIGERANT CONTROL Condensing Pressure Regulator REFRIGERANT CHARGE
DESIGN PRESSURE High 467 PSIG, Low 230 PSIG OPERATING CONDITIONS VOLTAGE RANGE 187-253VAC
ACCESSORIES -SUPPLIED Legs and hardware
-REQUIRED
TOTAL HEAT OF REJECTION FROM CONDENSER 28,000 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)] TOTAL HEAT OF REJECTION FROM COMPRESSOR 3,500 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)] CONDENSER VOLUME 226 CU. IN.
Net 230 lbs. (104 kg), Shipping 275 lbs. (125 kg)
SRK to KMS: Wire Harness Connection
TOTAL R404A, 16 lb. 5 oz. (7400g)
ICEMAKER, 0 lb. 7.1 oz. (200g)
CONDENSER, 15 lb. 14 oz. (7200g)
AMBIENT TEMP. (Outdoor use) -20-122°F
Compatible KMS icemaker, Water Filter (2) cartridge, Ice Dispenser or Ice Storage Bin
Line set HS-0250, HS-0244, HS-0245
57
Page 58

B. Wiring Diagrams

1. Wire Harness Connections

W
W
BK
Neutral
LLV
KMS Icemaker Unit
(factory connected)
Wire Harness Connections
P BK
V
BR
GR
P
V
BR
HGV
CB
Fuse 10A
GND
GR
W
SRK Condensing Unit
(eld connected)
BK
P
V
BR
58
GR
W
BK
P
BR V
GND
LLV
HGV
Fuse 10A
Neutral
Contactor
Legend:
GND-ground
HGV-hot gas valve
Wire Color Code:
BK-black
BR-brown
CB-control board
GR-green
LLV-liquid line valve
L2-single phase power supply
P-pink
V-violet
L3-three phase power supply
W-white
Page 59
WIRE COLOR CODE
BK -BLACK
BR -BROWN
DBU -DARK BLUE
GR -GREEN
GY -GRAY
O -ORANGE
P -PINK
R -RED
V -VIOLET
W -WHITE
Y -YELLOW
W/BR -WHITE/BROWN
W/R -WHITE/RED
W/BK -WHITE/BLACK
W/O -WHITE/ORANGE
W/BU -WHITE/BLUE
2A8704-012
208-230/60/3

2. KMS-1402MLJ with SRK-15J

CONTROL
BOARD
(O)
THERMISTOR
KMS-1402MLJ ON ON OFF OFF OFF
KMS-1402MLJ OFF OFF OFF ON ON ON ON OFF OFF OFF
S5 DIP SWITCH SETTING No.1 No.2 No.3 No.4 No.5
S4 DIP SWITCH SETTING No.1 No.2 No.3 No.4 No.5 No.6 No.7 No.8 No.9 No.10
X10 WV1 AND WV2 RELAY
X11 DRAIN VALVE/HARVEST PUMP TIMER RELAY
X12 DRAIN VALVE LOCKOUT RELAY 1
X13 DRAIN VALVE LOCKOUT RELAY 2
BR
BK
BR
BR
DISCHARGE
THERMOSTAT
BK
5
**
BR
HI-
PRESS.
*
BR
SRK (1 PHASE)
FUSE 10A
BR
K3
WHITE
2
3
1
(O)
BIN CONTROL
BK
BK
BK
C
COMP.
GY
35 MFD
CAP.
RUN
GY
R
2
START RELAY
1
R
O
R
START CAP.
189-227MFD
R
T3T1NO
T2
K4
RED
321
BK
BK
(BK)(BK)
FUSE 10A
BR
TERMINAL BLOCK
13579
BR
WIRING
HARNESS
BR
BK
R
BK
BK
BK
BK
BKGYV
BK
NC
K5
BLACK
321
(R)
(BK)
FLOAT SW.
P
BR
BR
P
P
531
P
P
P
BK
BK
7
BK
(R)
(BK)
(BK)
(BK)
V
BK
W
W
9
10
W
GR
9
10
W
LINE
(R)
HOT GAS
(R)
HOT GAS
(W)
FAN
(W)
FAN
BR
CRANKCASE
HEATER
V
V
BR
V
V
V
TERMINAL BLOCK
V
V
GY
C2
BK
W
VALVE
VALVE
VALVE
BR
P
P
P
P
W
(BK)
GND
(Y)
(Y)
(Y)
W
BR
W
BR
BR
P
GND
10
BR
BR
BR
W W
CAP.
10MFD
CAP.
10MFD
1
V
V
P
P
W/O
3
ICE
1
CONTROL
6
5
4
DBU
R
P
GY
Y
Y
Y
W/BU
1
3
V
R
R
OFF
SW.
W/R
CAP.
Y
R
(R)
10MFD
DBU
R P
(WV1)
GY
P
P
P
W/BK
W
K2
321
R
V
HOT GAS
VALVE
8
P
6
O
4
GY
2
W/O
VALVE
LINE
(R)
BK
(R)
W/R
PUMP
D/BU
(D/BU)
8 6
4 2
FILL/
RE-FILL
WATER VALVE
HARVEST
WATER VALVE
(WV2)
X12X13
88 6
GY Y
4
P
2
P
6
Y
4 2
Y
W/BU
DRAIN
VALVE
W/BU
V
WASH
VALVE
R
V
R
R
V
(BR)
(BK)
V
V
Y
BK
(BK)
W/BK
W
W/BK
W
W
W/BK
W
W/BK
W
W
W/BU
W/BU
W/BU
W/BU
W/BU
W
WW
Y
W
WWW
Y
Y
Y
W
W
Y
W
W
Y
W
W
Y
WW
W
Thermostat Switch
**
Cut-out 266°F±9°F (130°C± 5°C)
Cut-in 239°F±9°F (115°C±5°C)
BK
PSIG
0
22
* High-Pressure Switch
Cut-in 341±22 PSIG
Cut-out 426±
(Y)
7 5 3 1
X10
(Y)
X11
7 5 3 1
7 5 3 1
7 5 3 1
K1
2
3
4
5
6
7
8
9
V
O
BR
V
V
V
O
P
O
GY
V
W/O
W/O
BK
GY
BR
W/BR
W/O
GY
BR BR
GY
W/BR
W/O
GY
W/BR
W/O
W
GY
W
W
W/BR
W
W
W
W
W
W/BR
WWW
W
DBU
DBU
DBU
DBU
P
W/BR
P
BK
P
R
P
R
BK
R
BR
2
R
W/BR
R
SERVICE
ICE
R
OFF
R
BR
SERVICE
R
R
W/O
GY
CIRC
2
SERVICE
SWITCH WASH
O
BK
DRAIN
GND
L1 L2N
BR
W
BK
BR
MAGNETIC CONTACTOR
L3
L1
L2
COM
BK
BR
BR
W
BK
W/BK
BK
C1
W
W
W
59
Page 60
WIRE COLOR CODE
DBU-DARK BLUE
W/BR -WHITE/BROWN
W/R -WHITE/RED
W/BK -WHITE/BLACK
W/O -WHITE/ORANGE
W/BU -WHITE/BLUE
2A8704-012
208-230/60/3
MAIN TRANSFORMER

3. KMS-1402MLJ with SRK-15J3

CONTROL
BOARD
(O)
THERMISTOR
KMS-1402MLJ ON ON OFF OFF OFF
KMS-1402MLJ OFF OFF OFF ON ON ON ON OFF OFF OFF
S5 DIP SWITCH SETTING No.1 No.2 No.3 No.4 No.5
S4 DIP SWITCH SETTING No.1 No.2 No.3 No.4 No.5 No.6 No.7 No.8 No.9 No.10
X10 WV1 AND WV2 RELAY
X11 DRAIN VALVE/HARVEST PUMP TIMER RELAY
X12 DRAIN VALVE LOCKOUT RELAY 1
X13 DRAIN VALVE LOCKOUT RELAY 2
BR
BR
DISCHARGE
THERMOSTAT
**
BR
HI-
PRESS.
BR
*
SRK (3 PHASE)
FUSE 10A
BR
K3
2
1
(O)
BR
WHITE
3
BK
(BK)(BK)
BIN CONTROL
C
BR
R
R
BR
T3T1NO
T2
K4
RED
321
321
BK
(BK)
FLOAT SW.
BR
V
V
BR
FUSE 10A
V
BR
TERMINAL BLOCK
13579
V
BR
WIRING
HARNESS
BR
V
TERMINAL BLOCK
R
V
COMP.
S
BK
BK
BK
V
BK
V
GY
BKGYV
BK
C2
NC
K5
(R)
BLACK
P
P
P
P
P
P
(BK)
(BK)
(BK)
BR
V
BK
W
BK
W
9
10
BK
GR
W
97531
10
W
BK
LINE
(R)
HOT GAS
(R)
HOT GAS
(R)
FAN
FAN
CRANKCASE
HEATER
BK
W
VALVE
VALVE
VALVE
(W)
BR
(W)
BR
123
V
V
P
P
W/O
3
ICE
1
CONTROL
6
5
4
DBU
R P
GY
Y
Y
Y
W/BU
1
3
V
R
R
OFF
SW.
W/R
CAP.
Y
W
(R)
10MFD
K2
R
P O
GY
W/O
R DBU P
(WV1)
FILL/
(WV2)
HARVEST
GY
P
P
P
W/BK
V
321
V
HOT GAS
VALVE
X10
8 6
4 2
VALVE
LINE
(R)
BK
(R)
W/R
PUMP
D/BU
(D/BU)
8 6
4 2
X11
RE-FILL
WATER VALVE
WATER VALVE
X12
88
GY
6
Y
4
P
2
X13
P
6
Y
4
P
2
Y
W/BU
DRAIN
VALVE
W/BU
WASH
VALVE
R
V
R
V
W
(Y)
V
7 5
V
3
Y
1
(Y)
BK
(BK)
7
W
5 3
W/BU
1
W/BK
W
W/BU
W/BK
W
7
W
5 3 1
W/BU
W/BK
7
W
5 3
W/BU
1
W/BK
W/BU
W
W
(BK)
(BR)
W W
Y
W
W
BK
Thermostat Switch
**
W
Y
W
W
Y
Y
W W
W
Y
W
W
Y
W
W
Y
W
W
W
Cut-out 266°F±9°F (130°C± 5°C)
PSIG
0
22
* High-Pressure Switch
Cut-out 426±
Cut-in 239°F±9°F (115°C±5°C)
Cut-in 341±22 PSIG
K1
456
789
10
V
V
V
BR BR
W W
WWW
W
W
10MFD
W
10MFD
WW
W/O
W/O
W/O
W/O
W W
BR
V
P
BK
W/BR
W/BR
W/BR
W/BR
W/BR
W/O
BR
O
O
O
GY
GY
GY
GY
GY
GY
DBU
DBU
DBU
DBU
P
W/BR
BK
R
R
BK
R
BR
R
W/BR
R
R
OFF
R
BR
R
R
W/O
GY
CIRC
2
SERVICE
SWITCH
P
P
P
O
BK
2
SERVICE
ICE
SERVICE
DRAIN
WASH
BR
BR
P
BR
P
BR
P
P
GND
GND
(Y)
(Y)
(Y)
W
BR
CAP.
W
BR
CAP.
(BK)
GND
L1 L3L2
MAGNETIC CONTACTOR
L3
L1
L2
BR
BK BR R
COM
R
BK
W/BK
BR
W/BK
R
VOLTAGE
TAP SW.
BR
BK
W
C1
0V
BR
W
208V
BK
115V
BK
230V
BK -BLACK
BR -BROWN
60
GR -GREEN
GY -GRAY
O -ORANGE
P -PINK
R -RED
V -VIOLET
W -WHITE
Y -YELLOW
Loading...