Only qualied service technicians should attempt to install, service, or maintain
this icemaker. No service or maintenance should be undertaken until the
technician has thoroughly read this Service Manual. Failure to service and
maintain the equipment in accordance with this manual may adversely affect
safety, performance, and warranty coverage.
HOSHIZAKI provides this manual primarily to assist qualied service technicians in the
service and maintenance of the icemaker.
Should the reader have any questions or concerns which have not been satisfactorily
addressed, please call, write, or send an e-mail message to the HOSHIZAKI Technical
Support Department for assistance.
HOSHIZAKI AMERICA, INC.
618 Highway 74 South
Peachtree City, GA 3069
NOTE: To expedite assistance, all correspondence/communication MUST include the
following information:
• Model Number ________________________
• Serial Number ________________________
• Complete and detailed explanation of the problem.
Page 3
IMPORTANT
This manual should be read carefully before the icemaker is serviced or
maintenance operations are performed. Only qualied service technicians
should install, service, and maintain the icemaker. Read the warnings
contained in this booklet carefully as they give important information regarding
safety. Please retain this booklet for any further reference that may be
necessary.
CONTENTS
I. Specications ..................................................................................................................... 6
A. Icemaker ....................................................................................................................... 6
. Sanitizing Procedure - Following Cleaning Procedure .......................................... 54
B. Maintenance ............................................................................................................... 54
C. Preparing the Icemaker for Long Storage .................................................................. 55
5
Page 6
I. Specications
SPECIFICATION DATA NO. 08A001ISSUED: January 22,2008
REVISED:
ITEM: HOSHIZAKI MODULAR CRESCENT CUBER WITH REMOTE COMPRESSOR/CONDENSER UNITMODEL: KMS-1400MLH with SRK-14H
AC SUPPLY VOLTAGE208-230/60/1 ( 3 wire with neutral for 115V )
AMPERAGE15 A ( 5 Min. Freeze AT 104°F / WT 80°F )
MINIMUM CIRCUIT AMPACITY20 A
MAXIMUM FUSE SIZE20 A
APPROXIMATE ICE PRODUCTIONAmbientWATER TEMP. (°F)
PER 24 HR.Temp.(°F)507090
lbs./day ( kg/day ) 70 * 1284 (582) 1242 (564) 1164 (528)
Reference without *marks 80 1252 (568) 1188 (539) 1097 (497)
90 1242 (564) * 1142 (518) 1054 (478)
1001170 (531) 1121 (509) 974 (442)
SHAPE OF ICECrescent Cube
ICE PRODUCTION PER CYCLE24 lbs. ( 10.9 kg ) 1248 pcs.
APPROXIMATE STORAGE CAPACITYN/A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)2522 ( 5.3 )2354 ( 4.4 )
WATER gal./24HR (gal./100 lbs.) 270 ( 23.6 ) 560 ( 43.6 )
EXTERIOR DIMENSIONS (WxDxH)KMS-1400MLH : 30" x 24" x 28" ( 762 x 610 x 711 mm )
- CONDENSATE DRAIN5/8" OD Pipe
CUBE CONTROL SYSTEMFloat Switch
HARVESTING CONTROL SYSTEMHot Gas and Water, Thermistor and Timer
ICE MAKING WATER CONTROLTimer Controlled, Overflow Pipe
COOLING WATER CONTROLN/A
BIN CONTROL SYSTEMMechanical Level Switch and Timer
COMPRESSORHermetic, Model CS18K6E-PFV
CONDENSERAir cooled, Fin and Tube type
EVAPORATORVertical type, Stainless Steel and Copper
REFRIGERANT CONTROLThermostatic Expansion Valve
Condensing Pressure Regulator
REFRIGERANT CHARGER-404A, 16 lb. 5 oz. ( 7400 g )
( Icemaker 7 oz.; Comp/Cond unit 15 lbs. 14 oz. )
DESIGN PRESSUREHigh 467 PSIG, Low 230 PSIG
P.C. BOARD CIRCUIT PROTECTIONHigh Voltage Cut-out ( Internal )
COMPRESSOR PROTECTIONAuto-reset Overload Protector ( Internal )
REFRIGERANT CIRCUIT PROTECTIONAuto-reset High Pressure Control Switch
LOW WATER PROTECTIONFloat Switch
ACCESSORIES -SUPPLIEDN/A
-REQUIREDIce Storage Bin or Dispenser
OPERATING CONDITIONSVOLTAGE RANGE187 - 253 V
AMBIENT TEMP.
KMS-1400MLH 45 - 100° F
SRK-14H( Outdoor use ) -20 - 122° F
WATER SUPPLY TEMP. 45 - 90° F
WATER SUPPLY PRESSURE 10 - 113 PSIG
A. Icemaker
1. KMS-1400MLH – SRK-14H
Note: We reserve the right to make changes in specications and design without prior
notice.
6
Page 7
2. KMS-1400MLH – SRK-14H3
Intentionally Left Blank
Note: We reserve the right to make changes in specications and design without prior
notice.
7
Page 8
B. Condensing Unit
AC SUPPLY VOLTAGE208-230/60/1 ( 3 wire with neutral for 115V )
( Connection to icemaker )
AMPERAGE15 A ( 5 Min. Freeze AT 104°F / WT 80°F )
MINIMUM CIRCUIT AMPACITY20 A
MAXIMUM FUSE SIZE20 A
EXTERIOR DIMENSIONS ( WxDxH )50" x 17" x 28" ( 1270 x 432 x 711 mm )
DIMENSIONS INCLUDING LEGS ( WxDxH )52-3/8" x 19-1/2" x 43" ( 1330 x 495 x 1092 mm )
EXTERIOR FINISHGalvanized steel
WEIGHTNet 230 lbs. ( 104 kg )Shipping 273 lbs. ( 124 kg )
REFRIGERANT CIRCUIT PROTECTIONAuto-reset High Pressure Control Switch
REFRIGERANT CONTROLCondensing Pressure Regulator
REFRIGERANT CHARGE15 lbs. 14 oz.( 7200 g )
DESIGN PRESSUREHigh 467 PSIG, Low 230 PSIG
OPERATING CONDITIONSVOLTAGE RANGE187 - 253 V
AMBIENT TEMP. ( Outdoor use ) -20 - 122° F
ACCESSORIES -SUPPLIEDLeg2 pcs
Hex. Head Bolt w/WasherM8 x 1616 pcs
Hex. NutM816 pcs
1. SRK-14H
Note: We reserve the right to make changes in specications and design without prior
notice.
8
Page 9
2. SRK-14H3
Intentionally Left Blank
Note: We reserve the right to make changes in specications and design without prior
notice.
9
Page 10
II. General Information
A. Construction
1. Icemaker
Spray Tubes
Hot Gas Valve
Liquid Line Valve
Service
Valve
(High Side)
Bin Control Switch
Control Switch
Service Switch
Drier
Wash Valve
Thermistor
Service
Valve
(Low Side)
Harvest Water Valve
Fill Water Valve
Control Box
Control Board
Pump Motor
Float Switch
Drain Water Valve
10
Page 11
2. Condensing Unit
Headmaster
(C.P. Regulator)
Shut-off Valve
(Low Side)
Condenser
Liquid Line Valve
Hot Gas Valve
Control Box
Junction Box
Receiver Tank
Accumulator
Fan Motor and Fan Blade
Shut-off Valve (High Side)
Compressor
Thermostat (Discharge Pipe)
11
Page 12
B. Sequence of Operation
The steps in the sequence are as outlined below. When power is supplied, the red
POWER OK LED and the green BC CLOSED LED on the control board come on (If the
yellow BC OPEN LED is on, the unit will not start. In this case clear ice away from the
bin control actuator in the bin area). A 5-second delay occurs at startup. Note that the
order of the green sequence LEDs from the outer edge of the board is 1, 4, 3, .
1. One Minute Fill Cycle
LED 4 is on. FWV opens and the ll period begins. After 1 minute, the board checks
for a closed LF/S. If LF/S is closed, the harvest cycle begins. If not, FWV will remain
energized through additional 1 minute cycles until water enters the sump and LF/S
closes. This serves as a low water safety to protect the water pump.
2. Initial Harvest Cycle
LEDs 1, 4 and are on. Comp, FMR, HGVs, HWV and X1 relay energize, FWV closes.
The control board monitors the warming of the evaporator via the thermistor located
on the suction line. When the thermistor reaches 48°F (9°C), the control board reads a
3.9 kΩ signal from the thermistor and turns harvest termination over to the adjustable
harvest timer which is factory set for normal conditions. The timer has settings of 60,
90, 10, and 180 seconds (S4 dip switch 1 & ). When the harvest timer completes its
count down, the harvest cycle is complete and the freeze cycle starts. The minimum
total time allowed by the board for a complete harvest cycle is minutes. HWV is open
during harvest for a maximum of 6 minutes or the length of harvest minus 50 seconds,
whichever is shorter. LED 4 goes off when HWV closes. PM energizes and runs for the
last 50 seconds of harvest. LED 3 comes on when PM energizes. At the end of harvest,
the control board checks the position of LF/S and proceeds to the freeze cycle if it is
closed or calls for a 1-minute ll if it is open.
3. Freeze Cycle
LED 1 is on. Comp, FMR and PM continue to run, LLVs open, HGVs close. For the rst
5 minutes, the control board will not terminate the freeze cycle. As ice builds and LF/S
opens, FWV opens (LED 4 is on when FWV is open). The rell will last until U/FS closes
or for 60 seconds, whichever is shorter. After UF/S closes, FWV closes 3 seconds later.
The KMS-1400MLH rells 1 time. After the rell, the freeze continues until LF/S opens
again. The freeze cycle is then terminated, provided the 5 minute freeze timer has
expired.
4. Pump-Out Cycle
The 1st pump out occurs after the 11th freeze cycle and every 10th cycle thereafter.
LEDs 1, 3, and are on. Comp and FMR continue to run, DWV opens, HGVs open,
LLVs close. PM stops for seconds. PM restarts, pumping water from the water tank
through the DWV and down the drain. At the same time, water ows through the vent
tube to power ush the F/S. After 10 seconds, the pump out is complete. The pump-out
frequency control is factory-adjusted to drain the water tank every 10 cycles, and no
adjustment is required. However, where water quality is bad and the icemaker needs a
pump out more often, the pump-out frequency can be adjusted. See "II.C.3.d) Pump-Out
Frequency Control."
1
Page 13
5. Normal Harvest Cycle
LEDs 1, 4 and are on. Comp, FMR and HGVs remain energized. HWV and X1 relay
energize, PM stops. As the evaporator warms, the thermistor reaches 48°F (9°C). The
control board then receives the thermistor's 3.9 kΩ signal and starts the harvest timer.
When the harvest timer completes its count down, the harvest cycle is complete. The
minimum total time allowed by the board for a complete harvest cycle is minutes. HWV
is energized during harvest for a maximum of 6 minutes or the length of harvest minus
50 seconds, whichever is shorter. LED 4 goes off when HWV closes. PM energizes and
runs for the last 50 seconds of harvest. LED 3 comes on when PM energizes. At the
end of harvest, the control board checks the position of LF/S and proceeds to the freeze
cycle if it is closed or calls for a 1-minute ll if it is open.
The unit continues to cycle through freeze and harvest cycles until the bin control
activates (opens) and shuts the unit down.
Note: To prevent incomplete batches of ice from forming on the evaporator, the control
board will only shut down the machine within the rst 5 minutes of the freeze
cycle. If ice pushes the bin control actuator in (open) after the rst ve minutes of
the freeze cycle, the control board will allow the machine to complete the freeze
cycle and the following harvest cycle before shutting down the machine.
Legend: Comp–compressor; DWV–drain water valve; FMR –remote fan motor; F/S–oat
switch; FWV–ll water valve; HGV–hot gas valve; HWV–harvest water valve;
LF/S–lower oat switch contacts; LLV–liquid line valve; PM–pump motor;
UF/S–upper oat switch contacts
13
Page 14
Pump motor stops
for sec. and then
4. Pump-Out Cycle
Factory set for every
10th cycle
runs for 10 sec.
Lower oat
switch in
3. Freeze Cycle
5 minute timer
• Minimum freeze time: 5 minutes
• Maximum freeze time: freeze timer setting
• Lower oat switch used to initiate water
tank rell (1 rell for KMS-1400MLH)
• Upper oat switch used to terminate
water tank rell (1 minute maximum ll time)
control
in control
LF/S closed
PM de-energizes sec. ,
energizes for 10 sec.
Comp continues
FMR continues
DWV energized
HGV energized
LLV de-energized
Freeze cycle
operation turned
over to LF/S
Comp continues
FMR continues
PM continues
LLV energizes
FWV energized/
for rell only
HGV de-energized
de-energized
50 sec.
LF/S check
PM energized
1 to 3 minute timer
in control
HWV de-energized
Thermistor temp
2. Harvest Cycle
Thermistor in
(HWV time is 6 minutes or the length of
harvest minus 50 sec., whichever is shorter.
PM energizes and runs for the last 50 sec. of
• Maximum harvest water valve time: 6 minutes
KMS-1400MLH Sequence Flow Chart and Component Operation
Fill Cycle
harvest.)
• Maximum harvest time: 0 minutes
1. One Minute
control
LF/S closed
LF/S check
Comp energized
FMR energized
HGV energized
LF/S open
FWV energized
LF/S open
reaches 48°F (9°C)
(3.9 kΩ or less)
Harvest timer starts
HWV energized
FWV de-energized
DWV de-energized
If LF/S is open, compressor stops and cycle returns to 1 minute ll
Power is supplied to the pump and drain valve. This drains the water tank.
Power is supplied to the pump only. This operation can be used to circulate cleaner and
sanitizer for extended periods of time over the outside surface of the evaporator.
DRAIN
Components Energized when the Control Switch is in the SERVICE Position
When in the "SERVICE" position, the control switch supplies power to the service switch and the machine is
in service mode. The service switch has three positions: "DRAIN," "CIRC." and "WASH." See the information
CIRC.
below for details of each function.
Power is supplied to the pump and wash valve. This operation is used to circulate cleaner
and sanitizer over both the inside and outside surfaces of the evaporator.
WASH
Cycle Steps
"G" board will have
Initial startup always
5 second delay
begins here
14
Legend:
Comp - compressor
DWV - drain water valve
FMR - remote fan motor
FWV - ll water valve
HGV - hot gas valve
HWV - harvest water valve
LF/S - lower oat switch contacts
LLV - liquid line valve
PM - pump motor
UF/S - upper oat switch contacts
Page 15
C. Control Board
• A HOSHIZAKI exclusive solid-state control is employed in the KMS-1400MLH Modular
Crescent Cuber.
• All models are pretested and factory-adjusted.
CAUTION
1. Fragile, handle very carefully.
. A control board contains integrated circuits, which are susceptible to failure
due to static discharge. It is especially important to touch the metal part of
the unit when handling or replacing the board.
3. Do not touch the electronic devices on the board or the back of the board to
prevent damage to the board.
4. Do not change wiring and connections. Do not misconnect K3, K4 and K5,
because the same connector is used for the thermistor, mechanical bin
control and oat switch.
5. Always replace the whole board assembly if it goes bad.
6. Do not short out power supply to test for voltage.
15
Page 16
1. Control Board Layout
Control Products "G" Control Board
Bin Control Switch
Closed LED (green)
Bin Control Switch
Open LED (yellow)
Part Number
Alarm Buzzer
LED (green)
Hot Gas Valves (HGV)
Power LED (red)
(lights when power
is supplied to the
board)
LED 3 (green)
Pump Motor (PM)
(PM on, but LED off,
at freeze cycle)
LED 4 (green)
Fill Water Valve
(FWV) (when LED
is off)
Harvest Water Valve
(HWV) (when LED
is on)
LED 1 (green)
Compressor (Comp)
Alarm Reset Button
S4 Dip
Switch
Output Test Button
(used to test relays on board)
Connector K3
Harvest Control
(thermistor)
Connector K4
Mechanical Bin
Control
S5 Dip Switch
(factory set do not adjust)
Connector K5
Float Switch
Label
(board revision level
indicated on label
on side of relay)
Connector K1
Pins #1 through #10
#1, 9 Magnetic Contactor
# Hot Gas Valves (HGV)
Water Valve Relay
#3 Liquid Line Valves (LLV)
#4 Pump Motor (icemaking)
#5 Pump Motor (harvest)
#6 Fill Water Valve (FWV)
#7 10 Supply Voltage
#8 Open
Switch for "C" board
and "ALPINE" board
(service boards only)
Connector K
Transformer
Control Board
Part Number A379-01 (factory); 2A3792-02 (service)
16
Page 17
2. Features
a) Maximum Water Supply Period – 6 minutes
The harvest water valve will be open during harvest for 6 minutes or the length of
harvest minus 50 seconds, whichever is shorter.
b) Harvest Backup Timer and Freeze Timer
The harvest backup timer shuts down the icemaker if, for two cycles in a row, the harvest
cycle takes more than 0 minutes to complete. The control board will signal this problem
using beeps every 3 seconds.
The freeze timer shuts down the icemaker if, for two cycles in a row, the freeze cycle
takes longer than the time specied to complete. The control board will signal this
problem using 3 beeps every 3 seconds. The time is factory set using S4 dip switch 9 &
10.
The alarm reset button on the control board must be pressed with power on to reset
either of these safeties.
c) High Temperature Safety
The temperature of the suction line in the refrigeration circuit is limited by the high
temperature safety. This protects the unit from excessively high temperatures. If the
evaporator temperature rises above 17 ± 7°F (53 ± 4°C), the control board reads a
.804 k
and the icemaker automatically stops.
The control board will signal this problem using 1 beep every 3 seconds. The alarm reset
button on the control board must be pressed with power on to reset the safety.
Ω signal from the thermistor and operates the safety. This shuts down the circuit
d) Low Water Safety
The control board checks the position of the lower oat switch at the end of the initial one
minute water ll cycle and at the end of each harvest cycle. If the lower oat switch is
closed, the control board proceeds to the next cycle. If the lower oat switch is open, the
control board calls for a one minute water ll cycle. After one minute, the control board
checks the position of the oat and either proceeds to the next cycle if the lower oat
switch is closed or calls for an additional one minute ll if the switch is open. This serves
as a low water safety to protect the water pump.
e) High Voltage and Low Voltage Cut-outs
High voltage and low voltage cut-outs help protect the icemaker from supply voltages
outside of the accepted range.
If miswiring causes excessive voltage (147Vac ±5% or more for 3 seconds) on
the control board, the high voltage cut-out shuts down the circuit and the icemaker
automatically stops. The control board will signal this problem using 7 beeps every 3
seconds.
The icemaker also automatically stops in cases of insufcient voltage (9Vac ±5% or
less). The control board will signal this problem using 6 beeps every 3 seconds.
When the proper supply voltage is resumed, the icemaker automatically starts running
again.
17
Page 18
f) LED Lights and Audible Alarm Safeties
The control board includes LED indicator lights, audible alarm safeties, and an output
test. The red LED indicates control voltage and will remain on unless a control voltage
problem occurs. At startup a 5-second delay occurs while the board conducts an internal
timer check. A beep occurs when the control switch is moved to the "ICE" position.
The green LEDs 1 through 4 energize and sequence from initial startup as listed in the
table below. Note that the order of the LEDs from the outer edge of the board is 1, 4, 3,
. For more information, see "II.B. Sequence of Operation."
Sequence StepLED
1 Minute Fill Cycle 4FWV60 seconds
Harvest Cycle1, 4 and Comp, FMR
Last 50 seconds of harvest, HWV de-energizes and PM energizes.
LEDs 1, 3 and are on.
Freeze Cycle1 (and 4 at
rells)
Pump-Out Cycle1, 4*, 3, and Comp, FMR,
The built in safeties shut down the unit and have alarms as listed below.
No. of Beeps
(every 3 sec.)
1High Evaporator Temp.
(temperature > 17°F)
(53°C)
Type of AlarmNotes
Energized
Components
HWV, HGV
Comp, FMR,
PM, LLV
(FWV at rell)
HWV*, PM,
HGV, DWV,
Check for harvest problem (stuck HGV or
relay), hot water entering unit, stuck HM or
shorted thermistor.
Min.Max.Avg.
minutes0 minutes3 to 5 minutes
5 minutesfreeze timer
10 seconds 0 seconds*pump-out
Time LEDs are On
30 to 35
setting
minutes
timer setting
Harvest Backup Timer
(harvest > 0 min. for two
cycles in a row)
3Freeze Timer
(freeze > specied setting
for two cycles in a row)
Timer is factory set using
S4 dip switch 9 & 10
To reset the above safeties, press the "ALARM RESET" button with the power supply on.
6Low Voltage
(9Vac ±5% or less)
7High Voltage
(147Vac ±5% or more)
Legend: Comp–compressor; DWV–drain water valve; FMR–remote fan motor; FWV–ll
water valve; HGV–hot gas valve; HM–headmaster; HWV–harvest water valve;
LLV–liquid line valve; PM–pump motor; TXV–thermostatic expansion valve
Check for open thermistor, HGV not opening,
TXV leaking by, low charge or inefcient Comp.
Check for a oat switch stuck closed (up),
HWV or FWV leaking by, HGV leaking by,
PM not pumping, TXV not feeding properly,
low charge, HM not bypassing or inefcient
compressor.
Red LED will turn off if voltage protection
operates.
The control voltage safeties automatically reset
when voltage is corrected.
18
Page 19
3. Controls and Adjustments
a) Default Dip Switch Settings
The dip switches are factory-adjusted to the following positions:
S4 Dip Switch
Dip Switch No.1345678910
KMS-1400MLHOFF OFF OFF ONONONON OFF OFF ON
S5 Dip Switch (Do Not Adjust)
Dip Switch No.
KMS-1400MLHOFF ON OFF OFF OFF
1345
Freeze Timer (9 & 10)
S4 Dip Switch
Normally off (8)
Do not adjust (7)
Pump-Out Frequency Control (5 & 6)
Pump-Out Timer (3 & 4)
Harvest Timer (1 & )
b) Harvest Timer (S4 dip switch 1 & 2)
The harvest timer starts counting when the thermistor reads 48°F (9°C) at the evaporator
outlet. No adjustment is required under normal use, as the harvest timer is adjusted to
the suitable position. Before changing this setting, contact Hoshizaki Technical Support
at 1-800-33-1940 for recommendations. Keep in mind that setting the harvest timer to a
longer setting will decrease 4 hour production.
Dip Switch Setting
No. 1
OFF
ON
OFF
ON
No.
OFF60
OFF90
ON10
ON180
Time (seconds)
19
Page 20
c) Pump-Out Timer (S4 dip switch 3 & 4)
During cycles when a pump out is called for, the pump motor drains the water tank for
the time determined by the pump-out timer (T1). The pump-out timer's harvest timer (T)
acts in place of the harvest timer (S4 dip switch 1 & ) during cycles with a pump out.
The pump-out timer is factory-adjusted, and no adjustment is required.
Dip Switch SettingTime (seconds)
T1
OFFOFF10150Closed
ONOFF10180Closed
OFFON1010Open
ONON0180Closed
T
Harvest Water
ValveNo. 3No. 4
T1: Time to drain the water tank
T: Harvest timer at pump out
Depending on the pump-out frequency control setting (dip switch 5 & 6), pump out
occurs every cycle, or every nd, 5th or 10th cycle.
d) Pump-Out Frequency Control (S4 dip switch 5 & 6)
The pump motor drains the water tank at the frequency set by the pump-out frequency
control.
The pump-out frequency control is factory-adjusted to drain the water tank every 10
cycles, and no adjustment is required. However, where water quality is bad and the
icemaker needs a pump out more often, the pump-out frequency can be adjusted as
shown in the table below.
Dip Switch Setting
No. 5No. 6
OFFOFFevery cycle
ONOFFevery cycles
OFFONevery 5 cycles
ONONevery 10 cycles
e) Factory Use (S4 Dip Switch 7 & 8)
Factory set for optimum performance. Do not adjust.
Frequency
0
Page 21
f) Freeze Timer (S4 dip switch 9 & 10)
CAUTION
Adjust to proper specication, or the unit may not operate correctly.
The freeze timer setting determines the maximum allowed freeze time to prevent
possible freeze-up issues. Upon termination of freeze timer, the control board initiates
the harvest cycle. After consecutive timer terminations, the control board shuts the
machine down. In this case, see "IV.B.3. Low Ice Production" for possible solutions.
The freeze timer is factory adjusted and no adjustment is required.
Dip Switch Setting
No. 9No. 10
OFFOFF60
OFFON50
ONOFF70
ONON60
Time
(minutes)
g) Float Switch Control and Refill Counter (S5 dip switch 1 through 5)
Do not adjust. These must be left in the factory default position or the unit will not
operate properly. The KMS-1400MLH rells 1 time.
4. Control Board Check Procedure
Before replacing a control board that does not show a visible defect and that you suspect
is bad, always conduct the following check procedure. This procedure will help you verify
your diagnosis.
1) Check the S4 and S5 dip switch settings to assure that they are in the factory default
positions.
) Turn the control switch to "ICE" and check for proper control voltage. If the red LED
is on, the control voltage is good. If the red LED is off, check the control transformer
circuit.
3) Check the 115 volt input at the wire harness terminals and the 10-pin connector. Check
the brown and white wire at pin #10 to a white neutral wire for 115 volts. (Always
choose a white neutral wire to establish a good neutral connection when checking
voltages.) On the 10 pin connector, a jumper also feeds 115 volts into pin #7. If no
voltage is present, check the 115 volt supply circuit.
4) The output test button provides a relay sequence test. Make sure the control switch is
in the "ICE" position, then press the output test button. The correct lighting sequence
should be 1, 4, 3, . Some components (e.g., the compressor) will cycle during the test.
Note that the order of the relays from the outer edge of the board is 1, 4, 3, . After
checking the sequence, the unit automatically starts at the 1 minute ll cycle. If the
LEDs light in a different sequence, the control board is bad and should be replaced.
1
Page 22
5. Control Board Replacement
The dip switches should be adjusted to the factory default settings as outlined in this
manual. S4 dip switch #8 must remain off.
D. Harvest Control – Thermistor
A thermistor (semiconductor) is used for a harvest control sensor. The resistance varies
depending on the suction line temperatures. The thermistor detects the temperature of
the evaporator outlet to start the harvest timer. No adjustment is required. If necessary,
check for resistance between thermistor leads, and visually check the thermistor
mounting, located on the suction line next to the evaporator outlet.
Temperature (°F) Temperature (°C) Resistance (kΩ)
0-1814.401
10-110.614
306.000
50103.871
701.474
9031.633
Check a thermistor for resistance by using the following procedure:
1) Disconnect the connector K3 on the board.
) Remove the thermistor. See "V.C.6. Removal and Replacement of Thermistor."
3) Immerse the thermistor sensor portion in a glass containing ice and water for or 3
minutes.
4) Check for a resistance between thermistor leads. Normal reading is within 3.5 to 7 kΩ.
Replace the thermistor if it exceeds the normal reading.
Page 23
E. Float Switch
1. Explanation of Operation
The oat operates switches within the oat switch. The lower switch (black and
blue wires) is used for low water safety protection, initiating the freeze cycle rell and
terminating the freeze cycle. The upper switch (black and red wires) is used to terminate
the freeze cycle rell only. Rell will last until the upper oat switch closes or the 1
minute countdown timer ends, whichever comes rst.
2. Cleaning
Depending on local water conditions, scale may build up on the oat, oat switch shaft
and inside the housing. Scale on the oat or shaft can cause the oat to stick causing
erratic operation. The oat switch should be cleaned and checked before replacing.
First, disconnect the black K5 oat switch connector from the control board and remove
the oat switch and rubber boot from the icemaker. Remove the rubber boot from the
oat switch. Twist the mechanical lock at the top of the oat housing and lower out the
oat and oat shaft. Remove the retainer clip from the shaft and slide the oat off the
shaft. Soak the switch assembly in ice machine cleaner. Wipe down the shaft, oat,
housing, and rubber boot with cleaning solution. See "VI. Cleaning and Maintenance
Instructions."
3. Float Switch Check Procedure
Before replacing a oat switch that you suspect is bad, make sure the oat switch has
been cleaned. This procedure will help you verify your diagnosis. The oat switch has
three wires. The black wire is common. The blue wire is for the lower oat switch contact
and the red wire is for the upper oat switch contact.
1) Disconnect the black K5 oat switch connector from the control board.
) Drain the reservoir water.
3) Turn the control switch to "ICE".
4) As water lls the reservoir, the oat switch contacts should close. Check continuity of
the lower oat switch contacts using the black and blue wires and the upper oat switch
contacts using the black and red wires. With the oat positioned all the way up, both
oat switch contacts should be closed. If either oat switch contact fails, the assembly
should be replaced.
5) Turn the control switch to "OFF".
6) Drain the reservoir water.
7) As water drains, the oat switch contacts should open. Check continuity of the upper
oat switch contacts using the black and red wires and the lower oat switch contacts
using the black and blue wires. With the oat positioned all the way down, both oat
switch contacts should be open. If either oat switch contact fails, the assembly should
be replaced.
8) Reconnect the black K5 connector to the control board when nished.
3
Page 24
Blue - Lower Switch
Housing
Lower Switch
Black - Common
Red - Upper Switch
Mechanical Lock
Upper Switch
Retainer Clip
Float
Fig. 1
Float Switch
4
Page 25
F. Bin Control
This machine uses a lever-actuated proximity switch (mechanical bin control) to control
the ice level in the storage bin. No adjustment is required.
1. Explanation of Operation
The bin control is connected to the red K4 connector on the control board. When the
bin control is calling for ice (proximity switch closed; green LED, BC CLOSED, on), the
control board continues icemaking operations. When the bin control is activated in the
bin full position (proximity switch open; yellow LED, BC OPEN, on), the control board
shuts down the unit. However, to prevent incomplete batches of ice from forming on the
evaporator, the control board will only shut down the machine within the rst 5 minutes of
the freeze cycle. If ice pushes the lever in after the rst ve minutes of the freeze cycle,
the control board will allow the machine to complete the freeze cycle and the following
harvest cycle before shutting down the machine.
2. Bin Control Check Procedure
1) Clear any ice away from the bin control.
) Turn the control switch to "ICE".
3) Check that the green "BC CLOSED" LED on the control board is on.
4) Activate the bin control actuator (press the actuator in). Check that the yellow "BC
OPEN" LED on the control board is on.
5) Disconnect the red K4 bin control connector from the control board.
6) Check for continuity across the bin control leads. When calling for ice, the bin control
proximity switch should be closed. If open, replace the bin control. Activate the bin
control actuator (press the actuator in), check for continuity across the bin control leads.
The bin control proximity switch should be open. If closed, replace the bin control.
7) Reconnect the red K4 connector. Allow the machine to cycle into the freeze cycle.
In the rst 5 minutes of the freeze cycle, activate the bin control actuator (press the
actuator in). The yellow "BC OPEN" LED should come on and the machine should turn
off. If not, replace the control board.
Bin Control
Switch Closed
(calling for ice)
Bin Control
Switch Open
(bin full)
5
Fig. 2
Bin Control
Page 26
G. Switches
Two control switches are used to control operation in KMS Series Modular Crescent
Cubers. These switches are referred to as the "control switch" and the "service switch"
and are located on the control box.
1. Control Switch
The control switch has three positions: "OFF" for power off; "ICE" for icemaking, and
"SERVICE" to activate the service switch.
2. Service Switch
When the control switch is in the "SERVICE" position, the control switch supplies power
to the service switch and the machine is in service mode. The service switch has three
positions: "DRAIN," "CIRC." and "WASH." See the information below for details of
each function.
Note:
1. When the service switch is activated, power is supplied to the water pump in all
three positions.
. When the control switch is in the "OFF" position or in the "ICE" position, the
service switch has no power and can be left in any position.
a) DRAIN
The KMS series utilizes a pump-out drain system. When the service switch is active and
placed in the "DRAIN" position, power is supplied to the pump and drain valve.
b) CIRC.
When the service switch is active and placed in the "CIRC." position, power is
supplied to the pump only. This operation can be used to circulate cleaner for extended
periods of time over the outside surface of the evaporator.
c) WASH
The KMS series utilizes a solenoid operated wash (bypass) valve. When the service
switch is active and placed in the "WASH" position, power is supplied to the pump and
wash valve. This operation is used to circulate cleaner and sanitizer over both the inside
and outside of the evaporator.
6
Page 27
III. Technical Information
A. Water Circuit and Refrigeration Circuit
SRK-14H/3
Strainer
Service Valve
Drier
Line Valve
Condenser
Fan
Line Valve
Headmaster
(C.P. Regulator)
Check Valve
Shutoff
Valve
Hot Gas
Valve
Access Valve
Strainer
Fusible Plug
High
Suction Line
OS Quick
Thermistor
Pressure
Switch
Strainer
Discharge
Line
Hot Gas
Valve
Thermostat
Compressor
Receiver Tank
Accumulator
Check Valve
Expansion Valve
Wash Valve
Water Supply
Harvest
Water Valve
KMS-1400MLH
Spray Tube
Evaporator
Fill
Water Valve
7
Float Switch
Drain
Water Valve
Drain
Pump Motor
Water Tank
Page 28
B. Wiring Diagrams
1. KMS-1400MLH – SRK-14H
Thermostat Switch
**
Cut-out66°F±9°F
Cut-in 39°F±9°F
PSIG
0
1
Transformer Output
10.5V at 115V
* Pressure Switch
Cut-out41±
Cut-in 37±1 PSIG
**
*
8
Page 29
2. KMS-1400MLH – SRK-14H3
Thermostat Switch
**
Cut-out66°F±9°F
Cut-in 39°F±9°F
PSIG
0
1
Transformer Output
10.5V at 115V
* Pressure Switch
Cut-out41±
Cut-in 37±1 PSIG
**
*
9
Page 30
3. Wire Harness Connections
W
PBK
V
BR
W
BK
VP
Neutral
LLV
HGV
CB
GN
KMS Icemaker Unit
(factory connected)
Wire Harness Connections
BR
Fuse 10A
GND
GND
GN
W
SRK Condensing Unit
BK
P
V
BR
30
GN
BKW
P
BRV
LLV
HGV
L2
or
Neutral
Contactor
L3
Legend:
GND-ground
HGV-hot gas valve
CB-control board
LLV-liquid line valve
L2-single phase power supply
Wire Color Code:
BK-black
BR-brown
GN-green
P-pink
V-violet
L3-three phase power supply
W-white
Page 31
C. Performance Data
PERFORMANCE DATA NO. 08A001ISSUED: January 22,2008
REVISED:
ITEM: HOSHIZAKI MODULAR CRESCENT CUBER WITH REMOTE COMPRESSOR/CONDENSER UNITMODEL: KMS-1400MLH with SRK-14H
70/21
1284
582
12425641164528
80/27125256811885391097497
90/321242564
1142
518
1054478
lbs./day kg./day
100/3811705311121509974442
70/21
80/27
90/32
watts
100/38
70/21
560
2.12
4751.804131.56
80/274951.873631.373311.25
90/324751.80
270
1.02
2230.85
gal./day m3/day
100/383701.402590.981810.69
70/21
80/27
90/32
min.
100/38
70/21
80/27
90/32
min.
100/38
70/21
186
13.1
20414.322415.7
80/2720014.022816.024517.2
90/3220414.3
247
17.4
26618.7
PSIG kg/cm2G
100/3820614.525217.728319.9
70/21
39
2.7402.8412.9
80/27392.8412.9423.0
90/32402.8
42
2.9
433.0
PSIG kg/cm2G
100/38402.8423.0453.1
CONDENSER VOLUME (SRK-14H UNIT)226 CU. IN
25
26
28
246825312597
APPROXIMATE ICE
PRODUCTION PER 24 HR.
AMBIENT TEMP.
(ºF/ºC)
WATER TEMP. (ºF/ºC)
50/1070/2190/32
APPROXIMATE ELECTRIC
CONSUMPTION
2354
24032449
239124682501
2403
2522
2561
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
FREEZING CYCLE TIME
22
24
2326
24
27
262729
HARVEST CYCLE TIME
6
55
544
5
3
2
432
TOTAL HEAT OF REJECTION (SRK-14H UNIT)25270 BTU/h [ AT 90ºF (32ºC) / WT 70ºF (21ºC) ]
HEAD PRESSURE
SUCTION PRESSURE
1. KMS-1400MLH – SRK-14H
Note:
1. Pressure data is recorded at 5 minutes into freezing cycle. The data not in bold
. We reserve the right to make changes in specications and design without prior
should be used for reference only.
notice.
31
Page 32
2. KMS-1400MLH – SRK-14H3
Intentionally Left Blank
Note:
1. Pressure data is recorded at 5 minutes into freezing cycle. The data not in bold
should be used for reference only.
. We reserve the right to make changes in specications and design without prior
notice.
3
Page 33
IV. Service Diagnosis
A. 10-Minute Diagnostic Procedure
The 10-minute check out procedure is basically a sequence check which can be used
at unit start-up or for system diagnosis. Using this check out procedure will allow you
to diagnose electrical system and component failures in approximately 10 minutes
under normal operating conditions of 70°F (1°C) or warmer air and 50°F (10°C) or
warmer water temperatures. Before conducting a 10 minute checkout, check for correct
installation, proper voltage per unit nameplate and adequate water supply. As you go
through the procedure, check to assure the components energize and de-energize
correctly. If not, those components and controls are suspect.
1) Turn power off and access the icemaker's control box. Clear any ice from the bin
control actuator located in the bin.
) Turn power on and place the control switch in the "ICE" position. A 5 second delay
occurs. The red "POWER OK" LED and the green "BC CLOSED" LED on the control
board come on.
3) One Minute Fill Cycle – LED 4 is on. The ll water valve is energized. After 1 minute,
the control board checks for a closed lower oat switch. If the lower oat switch is
closed, the harvest cycle begins. If closed, continue to step 4. If the lower oat switch
is open, the ll water valve will remain energized through additional 1 minute ll
cycles until water enters the sump and the lower oat switch closes (low water safety
protection during initial start up and at the end of each harvest). Diagnosis: If the ll
water valve does not open, check for no supply voltage at water valve terminals, bad
coil, or plugged screen or external lter (no water ow). If the reservoir lls, but the unit
fails to start harvest, check for open lower oat switch (see "II.F.3. Float Switch Check
Procedure") or bad 1 minute timer in control board. See "II.C.4. Control Board Check
Procedure."
4) Initial Harvest Cycle – LEDs 1, 4 and are on. The contactor coil energizes to start
the compressor and fan motors, the hot gas valves energize (also energizing the
X1 relay), the harvest water valve energizes and the ll water valve de-energizes. The
harvest water valve is open during harvest for a maximum of 6 minutes or the length of
harvest minus 50 seconds, whichever is shorter. The pump motor energizes and runs
for the last 50 seconds of harvest.
The evaporator warms and the thermistor senses 48°F (9°C). The control board then
receives the thermistor's 3.9 kΩ signal and turns operation of harvest over to the
harvest countdown timer. The last 50 seconds of the harvest countdown timer, the
harvest water valve de-energizes and the water pump energizes, (LED 4 goes off and
LED 3 comes on). When the harvest countdown timer completes, the freeze cycle
starts. Diagnosis: Check if evaporator is warming up, compressor and fan motors are
on, hot gas valves are open, harvest water valve open. If these are okay, next check
for at least 48°F (9°C) on the suction line. If the evaporator is cool, check for inlet
water too cold or liquid line valves stuck open. If the suction line is at least 48°F (9°C),
disconnect the thermistor at the white K3 connector on the control board and check for
resistance of 3.9 kΩ or less. If different, see "II.D. Harvest Control – Thermistor," for
check procedure. Replace if necessary. If resistance is 3.9 kΩ or less, reconnect the
thermistor to the white K3 connector on the control board. If harvest does not terminate
within 3 minutes, replace the control board.
33
Page 34
5) Freeze Cycle – LED 1 is on. The compressor, fan motors and pump motor remain
energized. The liquid line valves energize and the hot gas valves de-energize (also
de-energizing the X1 relay). The lower oat switch activates (open) times during
the course of a freeze cycle; the rst is for rell, the second is for freeze termination.
After the second lower oat switch activation, the control board terminates freeze and
initiates harvest. Every 10th cycle, the control board initiates a 10 second pump-out
cycle between the freeze and harvest cycles. See "II.C.3.d) Pump-Out Frequency
Control."
a. Lower Float Switch 1st Activation: Rell – LEDs 1 and 4 are on. The rell can occur
at any time during the freeze cycle (1 rell per cycle). As ice builds the water level
drops in the reservoir and the lower oat switch activates (opens). LED 4 comes on and
the control board energizes the ll water valve. The ll water valve remains energized
until the upper oat switch closes or the 1 minute ll timer terminates, whichever comes
rst.
b. Lower Float Switch 2nd Activation: LED 1 is on. The unit is held in freeze by a
5 minute short cycle protection timer. After the 1st lower oat switch activation and
rell, ice continues to form and the water level drops in the reservoir. When the lower
oat switch activates (opens) a second time, the freeze cycle terminates (freeze
can only be terminated on the second activation of the lower oat switch and after
5 minutes of freeze). Diagnosis: Minimum freeze time is 5 minutes. During the rst
5 minutes of freeze, conrm that the evaporator temperature drops, compressor, fan
motors, pump motor, and liquid line valves are energized and that the hot gas valves,
harvest water valve and ll water valve (except during rell) are de-energized and
not bypassing. Make sure the expansion valves are operating properly and, in cold
conditions, make sure the headmaster (C.P. Regulator) is operating correctly. Make
sure that the drain water valve is not leaking by (water owing down the potable drain).
Check for proper unit pressures (see "III.C. Performance Data"), or an inoperative
compressor. Disconnect the black K5 oat switch connector from the control board.
15 seconds after disconnecting the black K5 oat switch connector, LED 4 comes
on and rell begins. Connect the black K5 oat switch connector back on the control
board. When the rell is nished (LED 4 goes off), disconnect the black K5 oat switch
connector again. If 5 or more minutes have elapsed in the freeze cycle, the unit should
switch out of the freeze cycle. After the unit switches out of freeze, reconnect the black
K5 oat switch connector to the control board. If the unit remains in freeze with the oat
switch disconnected, replace the board. To check the oat switch, see "II.F.3. Float
Switch Check Procedure."
Note: Normal freeze cycle will last 30 to 35 minutes depending on model and
conditions. Cycle times and pressures should follow performance data provided
in this manual.
34
Page 35
6) Pump-Out Cycle – The 1st pump out occurs after the 11th freeze cycle and every
10th cycle thereafter. LEDs 1, 3, are on. The compressor and fan motors remain
energized. The drain water valve, hot gas valves and X1 relay energize, the liquid line
valves de-energize. The pump motor stops for seconds then restarts for 10 seconds
(pump out frequency can be adjusted on S4 dip switches 5 and 6). This pump out
removes contaminants from the water reservoir through the drain water valve and
allows for a power ush of the oat switch. Diagnosis: If the pump motor does not
come on, check the circuit and capacitor. If water does not pump out, remove the drain
water valve housing and check/clean the valve assembly, check for voltage on the
drain valve coil with LED 3 on, make sure that the drain line is not clogged.
7) Normal Harvest Cycle – Same as the initial harvest cycle. Return to step 4.
Note: Unit continues to cycle until bin control is satised or power is switched off. The
unit always restarts at the 1 minute ll cycle.
35
Page 36
B. Diagnostic Charts
1. No Ice Production
ProblemPossible CauseRemedy
[1] The icemaker will not
start.
Power Supply
a)
(Condensing Unit)
Water Supply1. Water supply off or
b)
High Pressure Control1. Open contacts.1. Check for continuity, let
c)
Thermostat
d)
(Condensing Unit High
Temperature Safety)
Wire Harness Terminal
e)
Block: Condensing Unit
and Icemaker
Fuse (Icemaker fused
f)
disconnect, if any)
Fuse (10A fuse in
g)
icemaker)
Control Switch1. "OFF" position.1. Move to "ICE" position.
h)
Transformer1. Open windings.1. Replace.
i)
1. Off, blown fuse, or
tripped breaker.
Loose connections.. Tighten.
.
3. Bad contacts.3. Check for continuity and
4. Not within
specications.
pressure too low.
.
Dirty condenser coil.. Clean.
3. Refrigerant
overcharged.
4. Fan not operating.4. See chart 1.[6]
5. Refrigerant line or
components plugged.
1. Open contacts. 1. Let cool and reset. Check
1. Loose connection.1. Tighten.
1. Blown.1. Check for short circuit and
1. Blown.1. Check for short circuit and
.
Bad contacts.. Check for continuity and
3. Loose connection.3. Tighten.
1. Turn on, replace, or reset.
replace.
4. Refer to nameplate and
correct.
1. Check and get
recommended pressure.
reset or replace.
3. Recharge.
5. Clean and replace drier.
for continuity and replace
if open.
correct. Reset or replace.
replace.
replace.
Bin Control1. Tripped with bin lled
j)
with ice.
.
Proximity switch stuck
open.
Wiring to Control Board 1. Loose connections or
k)
open.
36
1. Remove ice.
. Replace bin control.
1. Check for continuity and
replace.
Page 37
ProblemPossible CauseRemedy
[1] The icemaker will not
start. (continuted)
Water continues to
[]
be supplied, and the
icemaker will not
start.
[3] Compressor will
not start or stops
operating.
Fill Water Valve1. Mesh lter or orice
l)
clogged.
Coil winding opened.. Replace.
.
3. Wiring to water valve. 3. Check for loose
Control Board1. Defective.1. See "II.C.4. Control Board
m)
Control Board in Alarm 1. Audible alarm.1. See "II.C..f) LED Lights
n)
Float Switch1. Connector
a)
disconnected.
Leads opened or
.
defective switch.
3. Float does not move
freely.
Control Board1. Defective.1. Replace. See "II.C.4.
b)
Control Switch1. "SERVICE" position.1. Move to "ICE" position.
a)
Bad contacts.. Check and replace.
.
Control Board1. Defective.1. See "II.C.4. Control Board
b)
Wire Harness Terminal
c)
Block: Condensing Unit
and Icemaker
Magnetic Contactor1. Bad contacts.1. Check for continuity and
d)
Starter1. Bad contacts.1. Check and replace.
e)
Start Capacitor or Run
f)
Capacitor
Overload Protector1. Bad contacts.1. Check for continuity and
g)
Compressor1. Wiring to compressor. 1. Check for loose
h)
1. Loose connection.1. Tighten.
Coil winding opened.. Replace.
.
.
Coil winding opened.. Replace.
1. Defective.1. Replace.
Voltage too low.. Increase voltage.
.
3. Refrigerant
overcharged or
undercharged.
4. Line valve continues
to close in freeze
cycle and overload
protector operates.
. Defective.. Replace.
1. Clean.
connection or open, and
replace.
Check Procedure".
and Audible Alarm
Safeties".
1. Reconnect.
. Check and replace.
3. Clean or replace.
Control Board Check
Procedure."
Check Procedure."
replace.
replace.
3. Recharge.
4. Check line valves
operation in freeze cycle
and replace.
connection or open, and
replace.
37
Page 38
ProblemPossible CauseRemedy
[4] Water continues to
be supplied in freeze
cycle (outside of
rell).
[5] No water comes from
spray tubes. Water
pump will not start, or
freeze cycle time is
too short.
[6] Fan motor will
not start, or is not
operating.
[7] All components
run, but no ice is
produced.
Fill or Harvest Water
a)
Valve
Control Board1. Defective.1. See "II.C.4. Control Board
b)
Water Supply Line1. Water pressure too
a)
Fill or Harvest Water
b)
Valve
Water System1. Water leaks.1. Check connections for
c)
d)
Pump Motor1. Motor winding
e)
Control Board1. Defective.1.
a)
Fan Motor1. Motor winding
Magnetic Contactor1. Bad contacts.1. Check for continuity and
b)
a)
Refrigerant1. Undercharged.1. Check for leaks and
b)
Compressor1. Defective valve.1. Replace.
1. Diaphragm does not
close.
low and water level in
water tank too low.
1. Dirty mesh lter or
orice and water level
in water tank too low.
Clogged.. Clean.
.
3. Drain valve leaking by. 3. Check assembly and
opened.
Bearing worn out.. Replace.
.
3. Wiring to pump motor. 3. Check for loose
4. Defective capacitor.4. Replace.
5. Defective or bound
impeller.
6. Mechanical seal worn
out.
opened.
Bearing worn out.. Replace.
.
3. Wiring to fan motor.3. Check for loose
4. Defective capacitor.4. Replace.
5. Fan blade bound.5. Check and replace.
Air or moisture
.
trapped.
1. Check for water leaks with
icemaker off.
Check Procedure".
1. Check and get
recommended pressure.
1. Clean.
water leaks, and replace.
clean.
1. Replace.
connection or open, and
replace.
5. Replace or clean.
6. Check and replace.
See "II.C.4. Control Board
Check Procedure".
1. Replace.
connection or open, and
replace.
replace.
recharge.
. Replace drier and
recharge.
c)
Hot Gas Valve1. Continues to open in
freeze cycle.
d)
Liquid Line Valve1. Continues to close in
freeze cycle.
e)
Fill or Harvest Water
Valve
1. Water valve is wide
open during freeze
(outside of rell).
38
1. Check and replace.
1. Check and replace.
1. Check for water leaks.
Page 39
2. Evaporator is Frozen Up
ProblemPossible CauseRemedy
[1]Freeze cycle time is
too long.
[]
All ice formed on
evaporator does not
fall into bin in harvest
cycle.
a)Float Switch1. Leads short-circuit or
defective switch.
. Float does not move
freely.
b)Fill or Harvest Water
Valve
Control Board
c)
a)Evaporator1. Scaled up.1. Clean.
b)Water Supply Line1. Water pressure too
c) Water Filter System1. Dirty/restricted.1. Replace lter.
d)Harvest Water Valve1. Dirty mesh lter or
e) Ambient and/or Water
Temperature
f) Liquid Line Valve1. Continues to open in
1. Diaphragm does not
close.
1. Defective.1.
low.
orice.
. Diaphragm does not
close.
1. Too cool.1. Increase temperature.
harvest cycle.
1. Check and replace.
. Clean or replace.
1. Check for water leaks.
See "II.C.4. Control Board
Check Procedure".
1. Check and get
recommended pressure.
1. Clean.
. Check for water leaks.
1. Check operation in harvest
cycle and replace.
g)Thermistor1. Out of position or
loose attachment.
h)Control Board1. Defective.1.
[3]Othera) Spray Tubes1. Clogged.1. Clean.
Out of position.. Place in position.
.
b)Water System1. Dirty.1. Clean.
c) Refrigerant1. Undercharged.1. Check for leaks and
d)Expansion Valve1. Bulb out of position or
loose attachment.
Defective.. Replace.
.
e)Hot Gas Valve1. Coil winding opened.1. Replace.
Plunger does not
.
move.
3. Wiring to hot gas
valve.
f) Water Supply Line1. Too small; requires
1/" OD line dedicated
per machine.
g)Water Filter 1. Flow rate too small.1. Replace with lter that has
1. See "V.C.6. Removal
and Replacement of
Thermistor."
See "II.C.4. Control Board
Check Procedure".
recharge.
1. Place in position.
. Replace.
3. Check for loose
connection or open, and
replace.
1. Increase water line size.
larger ow rate.
39
Page 40
3. Low Ice Production
ProblemPossible CauseRemedy
[1] Freeze cycle time is
long.
[]
Harvest cycle time is
long.
a) See chart 1.[3]. Also check dirty condenser coil, ambient temperature and
refrigerant charge.
b) See chart .[1] and check oat switch, water valves and control board.
a) See chart .[] and check evaporator, water supply line, harvest water valve,
ambient and/or water temperature, liquid line valve, thermistor, and control
board.
4. Abnormal Ice
ProblemPossible CauseRemedy
[1] Small cubes.a) Ice Cube Guide or Ice
Separator
b) See chart 1.[5] and check water supply line, water valves, water system, pump
motor, and control board.
c) Drain Water Valve1. Leaking.1. Check and replace.
1. Out of position.
Circulated water falls
into bin.
1. Place in position.
Cloudy or irregular
[]
cubes.
a) See chart .[1] and .[3], and check oat switch, water valves, control board,
spray tubes, water system, refrigerant charge, and expansion valve.
1.Ensure all components, fasteners, and thumbscrews are securely in place
after the equipment is serviced.
. The Polyol Ester (POE) oils used in R-404A units can absorb moisture
quickly. Therefore it is important to prevent moisture from entering the
system when replacing or servicing parts.
3. Always install a new drier every time the sealed refrigeration system is
opened. Do not replace the drier until after all other repair or replacement
has been made.
4. Do not leave the system open for longer than 15 minutes when replacing or
servicing parts.
A. Service for Refrigerant Lines
WARNING
Use an electronic leak detector or soap bubbles to check for leaks. Add a trace
of refrigerant to the system (if using an electronic leak detector), and then raise
the pressure using nitrogen gas (140 PSIG). DO NOT use R-404A as a mixture
with pressurized air for leak testing.
IMPORTANT
1. The condensing unit is provided with two shutoff valves, one on the low-side,
one on the high-side and also with an access valve on the receiver tank. The
icemaker unit is provided with two service valves, one on the low-side and
one on the high-side.
. For refrigerant recovery, evacuation and recharge of the system, always use
the access valve on the receiver tank for the high-side and either the shutoff
valve of the condensing unit or the service valve of the icemaker unit for the
low-side line.
1. Refrigerant Recovery
Using proper refrigerant practices, recover the refrigerant and store it in an approved
container. Do not discharge the refrigerant into the atmosphere.
41
Page 42
2. Brazing.
WARNING
1. Refrigerant R-404A itself is not ammable at atmospheric pressure and
temperatures up to 176°F (80°C).
. Refrigerant R-404A itself is not explosive or poisonous. However, when
exposed to high temperatures (open ames), R-404A can be decomposed to
form hydrouoric acid and carbonyl uoride both of which are hazardous.
3. Always recover the refrigerant and store it in an approved container. Do not
discharge the refrigerant into the atmosphere.
4. Do not use silver alloy or copper alloy containing arsenic.
5. Use an electronic leak detector or soap bubbles to check for leaks. Add a
trace of refrigerant to the system (if using an electronic leak detector), and
then raise the pressure using nitrogen gas (140 PSIG). DO NOT use R-404A
as a mixture with pressurized air for leak testing.
1) Always install a new drier every time the sealed refrigeration system is opened. Do not
replace the drier until after all other repair or replacement has been made. Install the
new drier with the arrow on the drier in the direction of the refrigerant ow.
) Braze all ttings while purging with nitrogen gas owing at a pressure of 3 to 4 PSIG.
Note: Because the pipes in the evaporator case are specially coated to resist corrosion,
it is important to make connections outside the evaporator case when possible. If
it is necessary to braze inside the evaporator case, use sandpaper to remove the
coating from the brazing connections before unbrazing the components.
3) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of
refrigerant to the system (if using an electronic leak detector), and then raise the
pressure using nitrogen gas (140 PSIG). DO NOT use R-404A as a mixture with
pressurized air for leak testing.
3. Evacuation and Recharge (R-404A)
1) Attach a vacuum pump to the system. Be sure to connect the charging hoses to both
high and low-side lines.
IMPORTANT
The vacuum level and vacuum pump may be the same as those for current
refrigerants. However, the rubber hose and gauge manifold to be used for
evacuation and refrigerant charge should be exclusively for POE oils.
) Turn on the vacuum pump. Open the system service valves and service manifold
valves. Never allow the oil in the vacuum pump to ow backwards.
3) Allow the vacuum pump to pull down to a 9.9" Hg vacuum. Evacuating period depends
on pump capacity.
4) Close the low-side valve and high-side valve on the service manifold.
4
Page 43
5) Disconnect the vacuum pump and attach a refrigerant service cylinder to the high-side
line. Remember to loosen the connection and purge the air from the hose. For the
required refrigerant charge, see the rating label inside the front panel on the icemaker
or on the nameplate on the condensing unit. Hoshizaki recommends only virgin
refrigerant or reclaimed refrigerant which meets ARI Standard No. 700-88 be used.
6) A liquid charge is recommended for charging an R-404A system. Invert the service
cylinder and place it on scales. Open the high-side valve on the service manifold.
7) Allow the system to charge with liquid until the proper charge weight is met.
8) If necessary, add any remaining charge to the system through the low-side. Use a
throttling valve or liquid dispensing device to add the remaining liquid charge through
the low-side access port with the unit running.
9) Close the service manifold valves, the two refrigerant access valves and disconnect the
service manifold hoses.
10) Cap the access valves to prevent a possible leak.
B. Condensing Unit
1. Removal and Replacement of Compressor
IMPORTANT
Always install a new drier every time the sealed refrigeration system is
opened. Do not replace the drier until after all other repair or replacement has
been made. Install the new drier with the arrow on the drier in the direction of
the refrigerant ow.
Note: When replacing a compressor with a defective winding, be sure to install the
new start capacitor and start relay supplied with the replacement compressor.
Due to the ability of the POE oil in the compressor to absorb moisture quickly,
the compressor must not be opened more than 15 minutes for replacement or
service. Do not mix lubricants of different compressors even if both are charged
with R-404A, except when they use the same lubricant.
1) Turn off the power supply.
) Remove the panels.
3) Recover the refrigerant and store it in an approved container.
4) Remove the terminal cover on the compressor and disconnect the compressor wiring.
5) Remove the hold-down bolts, washers, and rubber grommets.
6) Remove the discharge and suction pipes.
7) Remove the compressor. Unpack the new compressor package.
8) Attach the rubber grommets of the prior compressor.
9) Place the compressor in position and secure it using the bolts and washers.
10) Remove the drier, then place the new drier in position, (located in the icemaker). Install
the new drier with the arrow on the drier in the direction of the refrigerant ow.
43
Page 44
11) Remove the plugs from the suction, discharge, and process pipes.
1) Braze all ttings while purging with nitrogen gas owing at a pressure of 3 to 4 PSIG.
13) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of
refrigerant to the system (if using an electronic leak detector), and then raise the
pressure using nitrogen gas (140 PSIG). DO NOT use R-404A as a mixture with
pressurized air for leak testing.
14) Evacuate the system and charge it with refrigerant. See the nameplate on the
condensing unit for the required refrigerant charge.
15) Connect the terminals and replace the terminal cover in its correct position.
16) Replace the panels in their correct positions.
17) Turn on the power supply.
2. Removal and Replacement of Condenser
IMPORTANT
Always install a new drier every time the sealed refrigeration system is
opened. Do not replace the drier until after all other repair or replacement has
been made. Install the new drier with the arrow on the drier in the direction of
the refrigerant ow.
1) Turn off the power supply.
) Remove the panels.
3) Recover the refrigerant and store it in an approved container.
4) Disconnect the condenser refrigerant tubing.
5) Remove the condenser.
6) Place the new condenser in position and secure with the mounting screws.
7) Remove the drier, then place the new drier in position, (located in the icemaker). Install
the new drier with the arrow on the drier in the direction of the refrigerant ow.
8) Braze all ttings while purging with nitrogen gas owing at a pressure of 3 to 4 PSIG.
9) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of
refrigerant to the system (if using an electronic leak detector), and then raise the
pressure using nitrogen gas (140 PSIG). DO NOT use R-404A as a mixture with
pressurized air for leak testing.
10) Evacuate the system, and charge it with refrigerant. See the nameplate on the
condensing unit for the required refrigerant charge.
11) Replace the panels in their correct positions.
1) Turn on the power supply.
44
Page 45
3. Removal and Replacement of Hot Gas Valve and Liquid Line Valve
CAUTION
1. The condensing unit has 1 hot gas valve and 1 liquid line valve. Both valves
have a strainer prior to the valve body. It is advisable to change the strainer
when replacing the hot gas or liquid line valve.
. Always use a copper tube of the same diameter and length when replacing
the hot gas and liquid lines; otherwise performance may be reduced.
3. Always install a new drier every time the sealed refrigeration system is
opened. Do not replace the drier until after all other repair or replacement
has been made. Install the new drier with the arrow on the drier in the
direction of the refrigerant ow.
1) Turn off the power supply.
) Remove the panels.
3) Recover the refrigerant and store it in an approved container.
4) Remove the screw and the solenoid.
5) Disconnect the valve body. Remove the strainer and check valve.
6) Place the new valve and strainer in position.
7) Remove the drier, then place the new drier in position (located in the icemaker). Install
the new drier with the arrow on the drier in the direction of the refrigerant ow.
8) Braze all ttings while purging with nitrogen gas owing at a pressure of 3 to 4 PSIG.
CAUTION
Always protect the valve body by using a damp cloth to prevent the valve from
overheating. Do not braze with the valve body exceeding 50°F (11°C).
9) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of
refrigerant to the system (if using an electronic leak detector), and then raise the
pressure using nitrogen gas (140 PSIG). DO NOT use R-404A as a mixture with
pressurized air for leak testing.
10) Evacuate the system, and charge it with refrigerant. See the nameplate on the
condensing unit for the required refrigerant charge.
11) Cut the leads of the solenoid allowing enough lead length to reconnect using closed
end connectors.
1) Connect the new solenoid leads.
13) Attach the solenoid to the valve body and secure it with a screw.
14) Replace the panels in their correct positions.
15) Turn on the power supply.
45
Page 46
4. Removal and Replacement of Headmaster
(Condensing Pressure Regulator - C.P. Regulator)
IMPORTANT
Always install a new drier every time the sealed refrigeration system is opened.
Do not replace the drier until after all other repair or replacement has been
made. Install the new drier with the arrow on the drier in the direction of the
refrigerant ow.
1) Turn off the power supply.
) Remove the panels.
3) Recover the refrigerant and store it in an approved container.
4) Before heating, break off the stub on the dome to release the dome charge.
5) Disconnect the headmaster.
6) Place the new headmaster in position.
7) Remove the drier, then place the new drier in position (located in the icemaker). Install
the new drier with the arrow on the drier in the direction of the refrigerant ow.
8) Braze all ttings with nitrogen gas owing at a pressure of 3 to 4 PSIG.
CAUTION
Always protect the headmaster body by using a damp cloth to prevent it from
overheating. Do not braze with the headmaster body exceeding 50°F (11°C).
9) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of
refrigerant to the system (if using an electronic leak detector), and then raise the
pressure using nitrogen gas (140 PSIG). DO NOT use R-404A as a mixture with
pressurized air for leak testing.
10) Evacuate the system and charge it with refrigerant. See the nameplate on the
condensing unit for the required refrigerant charge.
11) Replace the panels in their correct positions.
1) Turn on the power supply.
5. Removal and Replacement of Fan Motor
Note: When replacing a fan motor with defective winding, it is recommended that a new
capacitor be installed.
1) Turn off the power supply.
) Remove the panels.
3) Remove the closed end connectors from the fan motor leads.
4) Remove the fan motor bracket and fan motor.
46
Page 47
5) Install the new fan motor and replace the removed parts in the reverse order of which
they were removed.
6) Replace the panels in their correct positions.
7) Turn on the power supply.
C. Icemaker
IMPORTANT
Always install a new drier every time the sealed refrigeration system is
opened. Do not replace the drier until after all other repair or replacement has
been made. Install the new drier with the arrow on the drier in the direction of
the refrigerant ow.
Note: Because the pipes in the evaporator case are specially coated to resist corrosion,
it is important to make connections outside the evaporator case when possible. If
it is necessary to braze inside the evaporator case, use sandpaper to remove the
coating from the brazing connections before unbrazing the components.
1. Removal and Replacement of Evaporator
1) Turn off the power supply.
) Remove the panels and insulation pieces.
3) Recover the refrigerant and store it in an approved container.
4) Remove the spray tubes and the insulation at the "U" shaped notch where the
refrigeration tubing passes through the molded chassis.
5) Disconnect the evaporator tubing.
6) Remove the pop rivets securing the evaporator, then lift out the evaporator.
7) Install the new evaporator.
8) Remove the drier, then place the new drier in position. Install the new drier with the
arrow on the drier in the direction of the refrigerant ow.
9) Braze all ttings while purging with nitrogen gas owing at a pressure of 3 to 4 PSIG.
10) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of
refrigerant to the system (if using an electronic leak detector), and then raise the
pressure using nitrogen gas (140 PSIG). DO NOT use R-404A as a mixture with
pressurized air for leak testing.
11) Evacuate the system, and charge it with refrigerant. See the nameplate on the
condensing unit for the required refrigerant charge.
1) Replace the removed parts in the reverse order of which they were removed.
13) Replace the insulation pieces and the panels in their correct positions.
14) Turn on the power supply.
47
Page 48
2. Removal and Replacement of Expansion Valve
IMPORTANT
1. Sometimes moisture in the refrigerant circuit exceeds the drier capacity and
freezes up at the expansion valve. Always install a new drier every time the
sealed refrigeration system is opened. Install the new drier with the arrow on
the drier in the direction of the refrigerant ow.
. It is advisable to change out both expansion valves when replacing an
expansion valve.
3. Connect the expansion valve bulb to the corresponding refrigeration circuit
suction line.
1) Turn off the power supply.
) Remove the panels.
3) Recover the refrigerant and store it in an approved container.
4) Remove the insulation and the expansion valve bulb on the suction line.
5) Remove the expansion valve cover and disconnect the expansion valve. Place the new
expansion valve in position.
6) Remove the drier, then place the new drier in position. Install the new drier with the
arrow on the drier in the direction of the refrigerant ow.
7) Braze all ttings while purging with nitrogen gas owing at a pressure of 3 to 4 PSIG.
WARNING
1. Do not heat the wall of the machine. Place a steel barrier for protection.
. Always protect the valve body by using a damp cloth to prevent the valve
from overheating. Do not braze with the valve body exceeding 50°F
(11°C).
8) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of
refrigerant to the system (if using an electronic leak detector), and then raise the
pressure using nitrogen gas (140 PSIG). DO NOT use R-404A as a mixture with
pressurized air for leak testing.
9) Evacuate the system and charge it with refrigerant. See the nameplate on the
condensing unit for the required refrigerant charge.
10) Attach the expansion valve bulb to the suction line in the same location as the previous
bulb. The bulb should be at the 1 o’clock position on the tube. Be sure to secure the
bulb with the clamp and holder and to insulate it.
11) Place the new expansion valve cover in position.
1) Replace the panels in their correct positions.
13) Turn on the power supply.
48
Page 49
3. Removal and Replacement of Hot Gas Valve and Liquid Line Valve
CAUTION
1. The icemaker unit has 1 hot gas valve and 1 liquid line valve. The hot gas
valve has a strainer prior to the valve body. It is advisable to change the
strainer and check valves when replacing the hot gas valve.
. Always use a copper tube of the same diameter and length when replacing
the hot gas and liquid lines; otherwise performance may be reduced.
3. Always install a new drier every time the sealed refrigeration system is
opened. Do not replace the drier until after all other repair or replacement
has been made. Install the new drier with the arrow on the drier in the
direction of the refrigerant ow.
1) Turn off the power supply.
) Remove the panels.
3) Recover the refrigerant and store it in an approved container.
4) Remove the screw and the solenoid.
5) Disconnect the valve body. Remove the strainer and check valve (if applicable).
6) Place the new valve, strainer and check valve in position.
7) Remove the drier, then place the new drier in position. Install the new drier with the
arrow on the drier in the direction of the refrigerant ow.
8) Braze all ttings while purging with nitrogen gas owing at a pressure of 3 to 4 PSIG.
CAUTION
Always protect the valve body by using a damp cloth to prevent the valve from
overheating. Do not braze with the valve body exceeding 50°F (11°C).
9) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of
refrigerant to the system (if using an electronic leak detector), and then raise the
pressure using nitrogen gas (140 PSIG). DO NOT use R-404A as a mixture with
pressurized air for leak testing.
10) Evacuate the system, and charge it with refrigerant. See the nameplate on the
condensing unit for the required refrigerant charge.
11) Cut the leads of the solenoid allowing enough lead length to reconnect using closed
end connectors.
1) Connect the new solenoid leads.
13) Attach the solenoid to the valve body and secure it with a screw.
14) Replace the panels in their correct positions.
15) Turn on the power supply.
49
Page 50
4. Removal and Replacement of Pump Motor
1) Turn off the power supply.
) Remove the panels.
3) Drain the water tank by removing the
insulation panel, front frame and suction
hose. (See Fig. 3.)
4) Disconnect the pump suction and
discharge hoses.
5) Unplug the water pump connector.
6) Remove the screws and pump motor
bracket.
7) Remove the pump housing and check the impeller.
8) If the impeller is defective, install a new impeller.
9) Install the new motor or new parts, and replace the removed parts in the reverse order
of which they were removed.
10) Turn on the power supply and check for leaks.
11) Replace the panels in their correct positions.
Thumbscrew
Fig. 3
Suction Hose
Front Frame
5. Removal and Replacement of Fill and Harvest Water Valve
1) Turn off the power supply.
) Close the water supply line shut-off valve.
3) Open the water supply line drain valve and let the water supply line drain.
4) Remove the panels.
5) Remove the valve outlet tubing and tting nut.
6) Disconnect the terminals from the water valve.
7) Remove the bracket and water valve from the unit.
8) Install the new water valve and replace the removed parts in the reverse order of which
they were removed.
9) Close the water supply line drain valve.
10) Open the water supply line shut-off valve.
11) Turn on the power supply and check for leaks.
1) Replace the panels in their correct positions.
50
Page 51
6. Removal and Replacement of Thermistor
CAUTION
1. Fragile, handle very carefully.
. Always use a recommended sealant (high thermal conductive type),
Model KE4560RTV manufactured by SHINETSU SILICONE, Part Code
60Y000-11, or Part Code 4A0683-01 equivalent.
3. Always use a recommended foam insulation (Non-absorbent Type) or
equivalent.
4. Do not shorten or cut the thermistor leads when installing.
1) Turn off the power supply.
) Remove the panels.
3) Remove the control box cover.
4) Disconnect the thermistor leads from the
K3 connector on the control board.
5) Remove the plastic cable ties, foam
insulation, thermistor holder and
thermistor.
6) Scrape away the old sealant on the
thermistor holder and the suction pipe.
7) Wipe off moisture or condensation on the
suction pipe.
8) Smoothly apply recommended sealant (KE4560RTV, Part Code 60Y000-11 or
4A0683-01) to the thermistor holder concave.
9) Attach the new thermistor to the suction pipe in the same position as the previous
thermistor. Be very careful to prevent damage to the leads. Secure it using the
thermistor holder and recommended foam insulation.
Thermistor Lead Cable Tie
Foam Insulation Thermistor Holder
Fig. 4
10) Secure the insulation using plastic cable ties.
11) Connect the thermistor leads through the bushing of the control box to the K3
connector on the control board.
Note: Do not shorten or cut the thermistor leads.
1) Replace the control box cover and the panels in their correct positions.
13) Turn on the power supply.
51
Page 52
VI. Cleaning and Maintenance
IMPORTANT
Ensure all components, fasteners, and thumbscrews are securely in place after
any cleaning or maintenance is done to the equipment.
A. Cleaning and Sanitizing Instructions
HOSHIZAKI recommends cleaning this unit at least once a year. More frequent cleaning,
however, may be required in some existing water conditions.
WARNING
1. To prevent injury to individuals and damage to the icemaker, do not use
ammonia type cleaners.
. Always wear liquid-proof gloves to prevent the cleaning and sanitizing
solutions from coming into contact with skin.
3. Carefully follow any instructions provided with the bottles of cleaning and
sanitizing solution.
4. Never run the icemaker when the water tank is empty.
1. Cleaning Procedure
1) Dilute . oz. (650 ml) of the recommended cleaner Hoshizaki "Scale Away" or
"LIME-A-WAY" (Economics Laboratory, Inc.) with 4 gal. (15 l) of warm water.
) Remove all ice from the evaporator and the dispenser unit/storage bin.
Note: To remove cubes on the evaporator, turn off the power supply and turn it on
after 3 minutes. The harvest cycle starts and the cubes will be removed from the
evaporator.
3) Turn off the power supply. Remove the front panel.
4) Place the control switch in the "SERVICE" position. Then place the service switch in the
"DRAIN" position.
5) Replace the front panel and turn on the power supply for minutes.
6) Turn off the power supply.
7) Remove the front panel.
8) In bad or severe water conditions, clean the oat switch as described below. Otherwise,
continue to step 9.
a. Remove the right-side panel.
b. Disconnect the vent tube from the top of the oat switch, then remove the oat switch
and rubber boot.
c. Twist the wire stem on top of the oat switch housing to release the oat assembly,
then lower it out of the housing.
d. Wipe down the oat switch housing, shaft, and oat with cleaning solution. Clean the
inside of the rubber boot and hose with cleaning solution. Rinse the parts thoroughly
with clean water.
5
Page 53
e. Reassemble the oat switch. Replace the rubber boot and the oat switch in their
correct positions. Reconnect the vent tube.
f. Replace the right-side panel in its correct position.
9) Remove the insulation panel by removing the thumbscrews, then pour the cleaning
solution into the water tank.
10) Move the service switch to the "WASH" position.
11) Replace the insulation panel and the front panel in their correct positions.
1) Turn on the power supply to start the washing process.
13) Turn off the power supply after 30 minutes. Remove the front panel.
14) Move the service switch to the "DRAIN" position.
15) Replace the front panel and turn on the power supply for minutes.
16) Turn off the power supply and remove the front panel.
17) Move the control switch to the "ICE" position.
18) Replace the front panel in its correct position.
19) Turn on the power supply to ll the water tank with water.
0) Turn off the power supply after 3 minutes.
1) Remove the front panel.
) Move the control switch to the "SERVICE" position, then move the service switch to the
"WASH" position.
3) Replace the front panel in its correct position.
4) Turn on the power supply to rinse off the cleaning solution.
5) Turn off the power supply after 5 minutes.
6) Remove the front panel.
7) Move the service switch to the "DRAIN" position.
8) Replace the front panel and turn on the power supply for minutes.
9) Turn off the power supply. Remove the front panel.
30) Repeat steps 17 through 9 three more times to rinse thoroughly.
Note: If you do not sanitize the icemaker, go to step 13 in ". Sanitizing Procedure."
53
Page 54
2. Sanitizing Procedure - Following Cleaning Procedure
1) Dilute . oz. (60 ml or 4 tbs) of a 5.5% sodium hypochlorite solution (chlorine bleach)
with 4 gal. (15 l) of warm water.
) Remove the insulation panel if it is in its normal position.
3) Pour the sanitizing solution into the water tank.
4) Move the service switch to the "WASH" position.
5) Replace the insulation panel and the front panel in their correct positions.
6) Turn on the power supply to start the sanitizing process.
7) Turn off the power supply after 15 minutes. Remove the front panel.
8) Move the service switch to the "DRAIN" position.
9) Replace the front panel and turn on the power supply for minutes.
10) Turn off the power supply. Remove the front panel.
11) Repeat steps 17 through 9 in "1. Cleaning Procedure" two times to rinse thoroughly.
1) Repeat steps 1 through 11 above one more time.
13) Move the control switch to the "ICE" position.
14) Replace the front panel in its correct position.
15) Clean the dispenser unit/storage bin liner using a neutral cleaner. Rinse thoroughly
after cleaning.
16) Turn on the power supply to start the automatic icemaking process.
B. Maintenance
IMPORTANT
This icemaker must be maintained individually, referring to the instruction
manual and labels provided with the icemaker.
1. Stainless Steel Exterior
To prevent corrosion, wipe the exterior occasionally with a clean and soft cloth. Use a
damp cloth containing a neutral cleaner to wipe off oil or dirt build up.
2. Dispenser Unit/Storage Bin and Scoop
• Wash your hands before removing ice. Use the plastic scoop provided (bin accessory).
• The dispenser unit/storage bin is for ice use only. Do not store anything else in the
dispenser unit/storage bin.
• Clean the scoop and the dispenser unit/storage bin liner using a neutral cleaner. Rinse
thoroughly after cleaning.
3. Condenser
Check the condenser once a year, and clean if required by using a brush or vacuum
cleaner. More frequent cleaning may be required depending on location.
54
Page 55
C. Preparing the Icemaker for Long Storage
CAUTION
When shutting off the icemaker for an extended time, drain out all water from
the water tank and remove the ice from the dispenser unit/storage bin. The
dispenser unit/storage bin should be cleaned and dried. Drain the icemaker to
prevent damage to the water supply line at sub-freezing temperatures, using air
or carbon dioxide. Shut off the icemaker until the proper ambient temperature
is resumed.
When the icemaker is not used for two or three days, it is sufcient to only move the control
switch to the "OFF" position, unless the icemaker will be at sub-freezing temperatures.
1. Remove the water from the inlet water supply line: See Fig. 11.
1) Remove the front panel.
) Move the control switch to the "OFF" position. Conrm that the service switch is in the
"CIRC" position.
3) Remove the front insulation, front frame, right side panel, and control box cover.
4) Disconnect the thermistor from the K3 connector on the control board, and unplug the
water pump connector at the water pump.
5) Wait 3 minutes, then move the control switch to the "ICE" position. Conrm that the bin
control switch is closed and calling for ice. The green BC CLOSED LED on the control
board should be on.
6) Once LED 1 and on the control board energize (the order of the LEDs from the outer
edge of the control board is 1,4,3,), close the inlet water supply line shut-off valve and
open the inlet water supply line drain valve. Allow the line to drain by gravity.
7) Disconnect the harvest water valve hose in the evaporator section and blow out the
water line to the harvest water valve using compressed air or carbon dioxide. This will
clear water from the harvest water valve.
8) Move the control switch to the "OFF" position.
9) Move the service switch to the "WASH" position and the control switch to the
"SERVICE" position.
10) Using the same hose as with the harvest water valve, blow out the wash valve using
compressed air or carbon dioxide.
11) Move the service switch to the "CIRC" position and the control switch to the "OFF"
position.
1) Remove the 4 hoses connected to the water tank. Allow the tank and hoses to
completely drain.
13) Move the control switch to the "ICE" position.
14) Using the ll water valve hose, blow the water line out using compressed air or carbon
dioxide. This will clear water from the ll water valve.
55
Page 56
15) Move the control switch to the "OFF" position.
16) Disconnect the oat switch vent hose from the drain hose tee. Move the service switch
to the "DRAIN" position and the control switch to the "SERVICE" position.
17) From the tee on the drain hose, blow the drain water valve out using compressed air or
carbon dioxide.
18) Move the service switch to the "CIRC" position and the control switch to the "OFF"
position.
19) Reconnect the thermistor to the K3 connector on the control board. Reconnect the
water pump connector.
0) Close the inlet water supply line drain valve.
1) Remove all ice from the dispenser unit/storage bin and clean the dispenser unit/storage
bin liner using a neutral cleaner. Rinse thoroughly after cleaning.
) Turn off the power supply.
3) Replace all removed parts and panels in their correct positions.
Harvest Water Valve Hose
Harvest Water Valve
Wash Valve
Fill Water Valve
Fill Water Valve Hose
Drain Water Valve
Suction Hose
Fig. 5
56
Float Switch Vent Hose
Drain Hose Tee
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.