Only qualied service technicians should install and service the appliance. To
obtain the name and phone number of your local Hoshizaki Certied Service
Representative, visit www.hoshizaki.com. No installation or service should be
undertaken until the technician has thoroughly read this Service Manual. Likewise,
the owner/manager should not proceed to operate the appliance until the installer
has instructed them on its proper operation. Failure to install, operate, and
maintain the appliance in accordance with this manual will adversely affect safety,
performance, component life, and warranty coverage and may result in costly water
damage. Proper installation is the responsibility of the installer. Product failure or
property damage due to improper installation is not covered under warranty.
Hoshizaki provides this manual primarily to assist qualied service technicians in the
installation, maintenance, and service of the appliance.
Should the reader have any questions or concerns which have not been satisfactorily
addressed, please call, send an e-mail message, or write to the Hoshizaki Technical
Support Department for assistance.
618 Highway 74 South
Peachtree City, GA 30269
Attn: Hoshizaki Technical Support Department
NOTE: To expedite assistance, all correspondence/communication MUST include the
following information:
• Model Number
• Serial Number
• Complete and detailed explanation of the problem.
2
IMPORTANT
This manual should be read carefully before the appliance is serviced. Read
the warnings and guidelines contained in this manual carefully as they provide
essential information for the continued safe use, service, and maintenance of the
appliance. Retain this manual for any further reference that may be necessary.
CONTENTS
Important Safety Information ................................................................................................. 5
I. Construction and Water/Refrigeration Circuit Diagram ....................................................... 7
A. KMH Construction ......................................................................................................... 7
B. Wiring Diagrams .......................................................................................................... 56
1. Single Phase Models ............................................................................................. 56
2. Three Phase Models .............................................................................................. 57
4
Important Safety Information
Throughout this manual, notices appear to bring your attention to situations which could
result in death, serious injury, damage to the appliance, or damage to property.
WARNING Indicates a hazardous situation which could result in death or
serious injury.
NOTICE Indicates a situation which could result in damage to the
appliance or property.
IMPORTANT Indicates important information about the use and care of the
appliance.
WARNING
The appliance should be destined only to the use for which it has been expressly
conceived. Any other use should be considered improper and therefore dangerous.
The manufacturer cannot be held responsible for injury or damage resulting from
improper, incorrect, and unreasonable use. Failure to service and maintain the
appliance in accordance with this manual will adversely affect safety, performance,
component life, and warranty coverage and may result in costly water damage.
To reduce the risk of death, electric shock, serious injury, or re, follow basic
precautions including the following:
• Only qualied service technicians should install and service this appliance.
• The appliance must be installed in accordance with applicable national, state, and
local codes and regulations. Failure to meet these code requirements could result in
death, electric shock, serious injury, re, or damage to the appliance.
• Electrical connection must be hard-wired and must meet national, state, and local
electrical code requirements. Failure to meet these code requirements could result
in death, electric shock, serious injury, re, or damage.
• The icemaker requires an independent power supply of proper capacity. See the
nameplate for electrical specications. Failure to use an independent power supply
of proper capacity can result in a tripped breaker, blown fuse, damage to existing
wiring, or component failure. This could lead to heat generation or re.
• THE ICEMAKER MUST BE GROUNDED. Failure to properly ground the icemaker
could result in death or serious injury.
• To reduce the risk of electric shock, do not touch the control switch with damp
hands.
• Move the control switch to the "OFF" position and turn off the power supply before
servicing. Lockout/Tagout to prevent the power supply from being turned back on
inadvertently.
• Do not make any alterations to the appliance. Alterations could result in electric
shock, serious injury, re, or damage.
5
WARNING, continued
• The appliance is not intended for use by persons (including children) with reduced
physical, sensory, or mental capabilities, or lack of experience and knowledge,
unless they have been given supervision or instruction concerning use of the
appliance by a person responsible for their safety.
• Children should be properly supervised around the appliance.
• Do not climb, stand, or hang on the appliance or allow children or animals to do so.
Serious injury could occur or the appliance could be damaged.
• Do not use combustible spray or place volatile or ammable substances near the
appliance. They might catch re.
• Keep the area around the appliance clean. Dirt, dust, or insects in the appliance
could cause harm to individuals or damage to the appliance.
Additional Warning for Remote Models
• THE REMOTE CONDENSER UNIT MUST BE GROUNDED. The power supply and
ground connection to the remote condenser unit are supplied from the icemaker.
Failure to properly ground the remote condenser unit could result in death or
serious injury.
• Wire routing (conduit) and disconnect (if required) must meet national, state, and
local electrical code requirements. Failure to meet these code requirements could
result in death, electric shock, serious injury, re, or damage.
• Move the icemaker control switch to the "OFF" position and turn off the power
supply to the icemaker before servicing the remote condenser unit.
Lockout/Tagout to prevent the power supply from being turned back on
inadvertently.
NOTICE
• Follow the instructions in this manual carefully to reduce the risk of costly water
damage.
• In areas where water damage is a concern, install in a contained area with a oor
drain.
• Install the appliance in a location that stays above freezing. Normal operating
ambient temperature must be within 45°F to 100°F (7°C to 38°C).
• Do not leave the appliance on during extended periods of non-use, extended
absences, or in sub-freezing temperatures. To properly prepare the appliance for
these occasions, follow the instructions in "VI. Preparing the Appliance for Periods
of Non-Use."
• Do not place objects on top of the appliance.
• The dispenser unit/ice storage bin is for ice use only. Do not store anything else in
the dispenser unit/ice storage bin.
6
I. Construction and Water/Refrigeration Circuit Diagram
A. KMH Construction
1. Water-Cooled Models (SWJ3)
Spray Tubes
Evaporator Assembly
Cleaning Valve
Inlet Water Valve
Junction Boxes
Water Supply Inlet
Check Valve
(water)
Water Pump
Float Switch
Low-Side Service Valve
Thermostatic
Expansion Valves
Check Valves
High-Side Service Valve
Bin Control Thermostat
Hot Gas
Valve
Control Box
Control Switch
Main Transformer Box
(3 phase models)
Water Regulating
Valve
High-Pressure Switch
Condenser
Liquid Line
Valve
Strainer
Drier
Compressor
7
2. Remote Models (SRJ/3)
Evaporator Assembly
Compressor
Cleaning Valve
Spray Tubes
Inlet Water Valve
Junction Boxes
Water Supply Inlet
Check Valve
(water)
Water Pump
Float Switch
Low-Side Service Valve
Thermostatic
Expansion Valves
Check Valves
Discharge Service Valve
Bin Control Thermostat
Hot Gas
Valve
Control Switch
High-Side Service Valve
Control Box
Main Transformer Box
(3 phase models)
Liquid-Line
Service Valve
High-Pressure Switch
Strainer
Receiver
Drier
Liquid Line
Valve
Crankcase
Compressor
Heater
8
B. Bin Control
1a. Single Thermostatic Bin Control
Bin Control Bulb Holder F
Bin Control Bulb Holder E
Spacer
Bin Control Bulb Holder C
Bin Control
Extension Bracket
Z Bracket Used for Hoshizaki
B-1300, B-1500, B-1650, and
Non-Hoshizaki Ice Stoarage
Bin
1b. Stacked Thermostatic Bin Control
Bin Control Bulb Holder G
Silicone Hose
Bin Control Bulb Holder
Upper Bin Control Bulb Holder
Lower Bin Control Bulb Holder
Bin Control Bulb Holder E
Bin Control Bulb Holder C
Bin Control
Extension Bracket
Z Bracket Used for Hoshizaki
B-1300, B-1500, B-1650, and
Non-Hoshizaki Ice Stoarage
Bin
Bin Control Bulb Holder F
Bin Control Bulb Holder G
Spacer
Silicone Hose
Upper Bin Control Bulb Holder
Lower Bin Control Bulb Holder
9
C. Water/Refrigeration Circuit Diagram
1. Water-Cooled Models (SWJ3)
Check
Valves
Water Regulating Valve
Drain/Return
Condenser
Water Supply
Drier
Liquid Line
Val ve
Thermistor
Cleaning Valve
High-Pressure
Switch
Heat Exchanger
Hot Gas
Val ve
Suction Line
Service
Strainer
Service
Val ve
Val ve
Discharge Line
Compressor
Thermostatic Expansion Valves
Float Switch
Water Supply
Inlet Water Valve
Spray Tubes
Evaporator
Spray Tubes
Check Valve
Water
Tank
Drain
Water Pump
Pump-Out
Freeze/Harvest
Pump Timer
Refrigeration Circuit
Water Circuit
10
2. Remote Models (SRJ/3)
Service
Val ve
Fusible Plug
High Pressure
Hot Gas
Switch
Check
Valves
Val ve
Strainer
KM-2500SRH3: Headmaster
located in icemaker
Condenser
Water
Service
Val ve
Discharge Line
Suction Line
Receiver
Drier
Headmaster
(C.P.R.)
Service
Liquid Line
Val ve
Fan
Heat Exchanger
Val ve
Compressor
Expansion Valves
Thermistor
Cleaning Valve
Supply
Inlet Water Valve
Float Switch
Check Valve
Drain
Water Pump
Spray Tubes
Spray Tubes
Evaporator
11
Water
Tank
Pump-Out
Freeze/Harvest
Pump Timer
Refrigeration Circuit
Water Circuit
II. Sequence of Operation and Service Diagnosis
A. Sequence of Operation Flow Chart
1. Operation Flow Chart
10th cycle
(S4 dip switch 5)
2 sec., then reverses
for 10/20 sec.
• Factory set for every
4. Pump-Out Cycle
• Pump motor stops for
(S4 dip switch 3 & 4)
FS in control
FS opens or freeze
timer terminates
Comp energized
FMR energized
HGV energized
PM de-energizes for 2 sec.,
then reverses for 10/20 sec.
Anti-Slush
Thermistor temperature
reaches 36°F (2.2°C)
(5.8 kΩ).
PM de-energized for
LLV de-energized
10 sec.
When freeze time differential exceeded,
freeze-time correction cycle starts.
See "II.A.3. Freeze-Time Correction
Chart."
Time
FS closed
50 sec.
Comp energized
FMR energized
PM energized
LLV energized
HGV de-energized
FS check
FS open
3. Freeze Cycle
• Min. freeze time: 5 min.
• Max. freeze time: freeze timer setting
(S4 dip switch 9 & 10).
5-min.
minimum
freeze timer
in control
Harvest Pump
Operation Flow Chart
PM energized
1 to 3-min. harvest timer in
control (S4 dip switch 1 & 2)
Thermistor
in control
HPT setting (S4 dip switch 6), whichever is
shorter.
• WV time: 6 min. or the length of harvest minus
2. Harvest Cycle
• Max. harvest time: 20 min.
WV de-energized
FS closed
Comp energized
Thermistor temperature reaches
48°F (9°C) (3.9 kΩ or less).
Harvest timer starts.
FMR energized
HGV energized
WV energized
Components Energized when the Control Switch is in the "WASH" Position
The "WASH" position on the control switch is used when cleaning and sanitizing the unit. When in the "WASH" position,
power is supplied to the pump motor. With the cleaning valve closed, the cleaner and sanitizer ow over the outside of the
evaporator plate assembly. With the cleaning valve open, the cleaner and sanitizer ow over both the outside and the inside
of the evaporator plate assembly.
Note: Close the cleaning valve after cleaning and sanitizing are complete, otherwise the icemaker will not restart when the
control switch is placed in the "ICE" position.
WV energized
12
FS open
If FS is open, Comp stops and cycle
returns to 1-Min. ll.
Legend:
BC–bin control
CB–control board
Comp–compressor
FMR–fan motor-remote
FS–oat switch
HGV–hot gas valve
HPT–harvest pump time
LLV –liquid line valve
PM–pump motor
WV–inlet water valve
Fill Cycle
1. 1-Minute
Cycle
Steps
FS check
Startup
2. Shutdown Flow Chart
3. Ice Level Lowered
No ice touching BC bulb.
Icemaker starts at
"1. 1-Minute Fill Cycle."
To 1. 1-Minute Fill Cycle
BC closed
2. Icemaker Off
All components
de-energized.
BC open
All components
de-energized
NOTE: Green "BC CLOSED" LED
on continuously when K4
jumper is in place.
Shutdown Flow Chart
1. Bin Full
Within 10 sec. after ice contacts
BC bulb, icemaker shuts down.
Ice contacts BC bulb
BC
Shutdown
and Restart
Operation
Legend:
BC–bin control
13
3. Freeze-Time Correction Chart
2. 10-Minute Fill/Overow
WV energized
Comp de-energized
FMR de-energized
HGV de-energized
PM de-energized
After 5th 10-Minute Harvest Pump Cycle with WV
Freeze-Time Correction Cycle Complete.
Go to Step "3. Freeze Cycle" in Operation Flow Chart.
repeat step 1 for 5th and nal time.
• Do not adjust S4 dip switch 7 out of the factory position.
• After step 2 completes 4th sequence (80 min. completed),
1. 10-Minute Harvest Cycle with WV
Comp energized
FMR energized
HGV energized
PM energized
WV energized
2A7664-02 Freeze-Time Correction Flow Chart
CycleSteps
Steps 1 and 2 repeat
4 times (total 80 min.),
then step 1 repeats for
a 5th time to complete
Freeze-Time Correction
Start
Legend:
Comp–compressor
FM–fan motor
FMR–fan motor-remote
HGV–hot gas valve
PM–pump motor
WV–inlet water valve
Appliance Cycle Reset and Alarm Reset:
Cycle Reset: Power Supply or Control Switch Turned Off and On
again: Appliance turns off, then re-starts at 1.Fill Cycle.
Alarm Reset: CB "ALARM RESET" pressed during or after a
freeze-time correction cycle with power supply on:
Appliance continues cycle with no interruption or reset.
CB red "POWER OK" LED blinking:
CB red "POWER OK" LED resets to solid.
CB yellow "EXT HARVEST" LED blinking:
Cycle.
Differential
Value in Sec.
3254
4309
5349
6380
7406
8427
9446
10462
CB yellow "EXT HARVEST: LED turns off.
Freeze Time Differential Exceeded.
Minimum and Maximum Freeze times
have exceeded differential parameters.
Freeze-Time Correction function is
enabled when S4 Dip Switch 7 is in the
"ON" position. CB monitors freeze time.
After 3freeze cycles, CB compares the
minimum and maximum differential of
the 3 freeze cycle times. Every freeze
cycle time after the third freeze cycle
time is added to the minimum/maximum
calculation.
Example: After 8 cycles, if the differential
between the shortest cycle (minimum)
and the longest cycle (maximum) is equal
to or greater than 427 sec. a freeze-time
correction cycle is initiated:
Number of
Freeze Cycles
14
Note: When 1st freeze-time correction
cycle is initiated, CB "POWER OK"
LED starts blinking. On 2nd freeze-time
correction cycle, if CB "POWER OK"
LED has been reset, CB "POWER OK"
LED starts blinking. If CB "POWER OK"
had not been reset after 1st freeze-time
correction cycle CB "POWER OK" LED
continues to blink.
After 3rd freeze-time correction cycle in
36hours, CB yellow "EXT HARVEST"
LED starts blinking.
Appliance continues to operate and LEDs
continue to blink until ALARM RESET
button is pressed with power on.
B. Service Diagnosis
WARNING
• The appliance should be diagnosed and repaired only by qualied service
personnel to reduce the risk of death, electric shock, serious injury, or re.
• Risk of electric shock. Control switch in "OFF" position does not de-energize all
loads Use extreme caution and exercise safe electrical practices.
• Moving parts (e.g., fan blade) can crush and cut. Keep hands clear.
• Before servicing the appliance, move the control switch to the "OFF" position and
turn off the power supply.
• CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews are
securely in place after the appliance is serviced. Make sure that none have fallen
into the dispenser unit/ice storage bin.
• Make sure all food zones in the appliance and dispenser unit/ice storage bin are
clean after service.
The diagnostic procedure is a sequence check that allows you to diagnose the electrical
system and components. Before proceeding, check for correct installation, proper voltage
per nameplate, and adequate water supply. Check CB using the steps in "II.D. Control
Board Check." Check dip switch settings to assure that S4 dip switch 3, 4, 7, 8, 9, 10 and
S5 dip switch 1 through 5 are in the factory default position. S4 dip switch 1, 2, 5, 6 are
cleaning adjustments and the settings are exible. For factory default settings, see "III.C.1.
Default Dip Switch Settings."
Note: • When checking high voltage (115VAC), always choose a white (W) neutral wire to
establish a good neutral connection.
• On models with a main transformer, the neutral (W) is provided through MT.
To conrm a good neutral, check for 60VAC from white (W) neutral to ground
(GND). If 60VAC is present, neutral is good. If 60VAC is not present, check
208-230VAC main power supply to MT. If 208-230VAC is present, check MT
continuity.
• When checking voltage from the CB K1 connector (10 pin connector), pull CB
K1connector out slightly to allow room for multimeter test leads contact.
Conrm that the location meets installation requirements:
• The appliance is not intended for outdoor use. Normal operating ambient temperature
should be within 45°F to 100°F (7°C to 38°C).
• The icemaker should not be located next to ovens, grills, or other high heat producing
equipment.
• Allow 6" (15 cm) clearance at rear, sides, and top for proper air circulation and ease of
maintenance and/or service should they be required.
• The appliance should not be located in a corrosive environment.
15
1. Operation Diagnosis
1) Turn off the power supply, then access the control box. Move ice away from BC bulb.
2) Check that 115VAC 10A fuse is good.
3) Power On: Turn on the power supply, then move the control switch to the "ICE" position.
A 5-sec. delay occurs. CB red "POWER OK" LED and green "BC CLOSED" LED turn
on. If CB yellow "BC OPEN" LED is on (indicating a full bin), check CB K4 red jumper
connection.
Note: • CB red "POWER OK" LED remains on unless the 10.5VAC power supply is
interrupted (K2 connector).
• Check CB using the steps in "II.D. Control Board Check."
a) Power On Diagnosis: If CB red "POWER OK" LED is off, conrm 10A fuse is good.
Check for 115VAC at control switch #1 (BR) to neutral (W) then at control switch
#2(P) to neutral (W). If 115VAC is present on #1 (BR) and not on #2(P), replace
control switch. If 115VAC is present on control switch #2 (P), check for 115VAC at
HPS (P) to neutral (W) then HPS (BK) to neutral (W). If115VAC is present at HPS
(P) and not at HPS (BK), HPS is open. See HPS Diagnosis below. If115VAC is
present at HPS (BK), check for 10.5VAC at CB K2#1 red wire to CB K2 #2 red wire.
If10.5VAC is not present, check that the cleaning valve interlock switch is closed.
Next, check CT continuity. If open, replace CT.
b) HPS Diagnosis: Conrm condenser coil is not clogged or restricted. Let refrigeration
circuit pressures equalize. If HPS does not reset and pressures are equalized,
replace HPS. Ifpressures are not equalized, reclaim refrigerant and diagnose
refrigeration circuit restriction. Check that there are no restrictions in the refrigeration
circuit.
Harvest Cycle: HGV, strainer, or check valve.
Freeze Cycle: FMR, TXV, HM, LLV, strainer, check valve, drier, damaged line set or
tting, and fan blade for binding.
4) 1-Min. Fill Cycle – LED 4 is on. WV and X11 relay energize. After 1 min., CB checks for
a closed FS. If FS is closed, the harvest cycle begins. If harvest cycle begins (Comp,
HGV, FMR energized), continue to step 5a. If FS is open, WV remains energized until
FS closes (low water safety protection during initial start up and at the end of each
harvest). Diagnosis: Check that water enters the water tank. If not, check that the water
supply line shut-off valve is open and screens or external lters are clear. Check for
115VAC at CB K1 #6 (O) to neutral (W). If 115VAC is not present, replace CB. If 115VAC
is present, and WV does not energize, check for 115VAC at WV. If 115VAC is present,
check coil continuity. Ifopen, replace WV. If the water tank lls, but the appliance fails to
start harvest (Comp energized), check for open FS. See "II.F. Float Switch Check and
Cleaning." If FS is closed and CB fails to start the harvest cycle after 1 min., replace CB.
16
5a) Initial Harvest Cycle – LEDs 1, 4, and 2 are on. WV and X11 relay continue. Comp,
FMR, HGV, X10, and X12 relays energize. CBmonitors the warming of the evaporator
via the thermistor located on the suction line. When the thermistor reaches 48°F (9°C),
CB reads 3.9 kΩ from the thermistor and turns harvest termination over to the harvest
timer (S4 dip switch 1 & 2 and S5dip switch 4). WV and X11 relay are energized during
harvest for a maximum of 6 min. or the length of harvest minus HPT setting (S4 dip
switch 6), whichever is shorter. See step 5b below.
a) Comp Diagnosis: Check that evaporator is warming. Ifnot, conrm that Comp
energizes. If not, check for 115VAC at CB K1 #1 (V) or #9 (V) to neutral (W).
If115VAC is not present, check for 115VAC at CB K1 #7 (BR) or #10 (BR) to neutral
(W). If115VAC is present at #7 (BR) or #10 (BR) and not at #1 (V) or #9(V),
replaceCB. If 115VAC is present, check for 115VAC MC solenoid. If 115VAC is
present, conrm contacts are closed. If not, replace MC. If MC contacts are closed,
check Comp start and run capacitors, start relay (single phase), and Comp motor
winding.
b) HGV Diagnosis: If Comp is energized and evaporator is not warming, check that
HGV energizes and opens. Check for 115VAC at CB K1 #2 (P) to neutral (W).
If115VAC is not present and LED 2 is on, replace CB. If 115VAC is present, check for
115VAC at HGV coil and check HGV coil continuity. Replace as needed.
c) LLV Diagnosis: Conrm that LLV is de-energized and closed (not bypassing).
Ifenergized, replace CB. If de-energized and bypassing, replace LLV.
5b) Harvest Pump Time (Harvest Assist) – LEDs 1, 3, and 2 are on. When the thermistor
reaches 48°F (9°C), CB reads 3.9 kΩ from the thermistor and turns harvest termination
over to the harvest timer (S4 dip switch 1 & 2 and S5 dip switch4). WhenWV
de-energizes, LED 4 turns off, X11 relay de-energizes and LED 3turns on. PM
energizes. Comp, FMR, HGV, X10 and X12 relays continue.
Diagnosis: Place a thermometer on the suction line next to the thermistor. Has it
warmed to 48°F (9°C) or warmer? Conrm thermistor status. See "II.G. Thermistor
Check." If the thermistor reading is in proper range, dip switch 7 is on, and PM does
not energize before harvest terminates, replace CB. If WV continues, check for 115VAC
at CB K1 #6 (O). If115VAC is present, and LED 4 is off, replace CB. If LED 3is on and
PM is not energized, check for 115VAC at CB K1 #5(DBU). If115VAC is not present,
replace CB. If 115VAC is present and PM is not energized, check for 115VAC at X10relay
terminal #7 (Y) to neutral (W). If 115VAC is not present, check for 115VAC at X10 relay
terminal #3 (P) to neutral (W) and X10 relay terminal #5 (Y) to neutral (W). If 115VAC is
present on terminal #3(P) and not on terminal #5 (Y), replace X10 relay. If 115VAC is
present on X10 relay terminal #7 (Y) and PM is not energized, check for 115VAC at X10
relay terminal #4 (R) to neutral (W) and terminal #6 (DBU) to neutral (W). If 115VAC is
present on terminal #6(DBU) and not on terminal #4 (R), replace X10relay. If 115VAC
is present on X10relay terminal #4 (R), check control switch contact continuity between
terminals #4(R) and #5(W/R). Ifcontacts are open, replace control switch. If contacts
are closed and 115VAC is present between control switch terminal #5(W/R) and
neutral(W), check PM capacitor and motor winding continuity.
17
5c) Initial Harvest Cycle Termination Diagnosis: When the thermistor reaches 48°F
(9°C), CB reads 3.9 kΩ from the thermistor and turns harvest termination over to
the harvest timer (S4 dip switch 1 & 2 and S5 dip switch 4). Check discharge line
temperature. For a thermistor check, see "II.G.Thermistor Check." If 1-min. ll cycle
starts after harvest timer terminates, check that FS is clean and operating properly, see
"II.F. Float Switch Check and Cleaning." If FS is closed, CB proceeds to the next cycle.
Ifnot, replace CB.
Note: The minimum total time allowed by CB for a complete harvest cycle is based on
S5 dip switch 4. Maximum harvest time allowed is 20min.
NOTICE! S4 dip switch 7 must remain on. Otherwise, PM will not energize during
the last seconds of harvest.
6) Freeze Cycle – LED 1 is on. Comp, FMR, and PM continue. LLV energizes. HGV and
X10 and X12 relays de-energize. Appliance is held in freeze by a 5-min. short cycle
protection timer. After 5-min. short cycle protection timer terminates and FS opens,
freeze cycle terminates.
Note: PM power supply switches from CBK1 #5(DBU) in harvest to K1 #4 (R) in freeze.
Anti-Slush: When anti-slush is enabled (S5 dip switch 5 "ON"), PM de-energizes when
thermistor reaches 36°F (2.2°C) (5.8kΩ) for 10 sec. then, energizes for the remainder of
the freeze cycle.
a) Freeze Cycle Diagnosis: Conrm Comp, FMR, and PM continue. Conrm that
LLV energizes. Next, conrm HGV, X10 and X12 relays de-energize. During the
rst 5 min. of freeze, conrm evaporator is cooling. If not, conrm WV de-energized
(not leaking by), HGV de-energized (not bypassing), LLV energizes, TXV and HM
operate correctly, Comp is efficient, and refrigerant charge is correct. See "VIII.A.
Specication and Performance Data."
b) Comp and FMR Diagnosis: If Comp. and FMR de-energize once freeze begins,
check that appliance has not shut off on HPS ("POWER OK" LED off). If so, check
"3)b) HPS Diagnosis" above. If"POWER OK" LED is on, check for 115VAC at CB K1
#1 (V) or #9 (V) to neutral (W). If 115VAC is not present and LED 1 is on, replace CB.
Comp: If 115VAC is present, check for 115VAC at MC coil. If 115VAC is present,
check MC coil and contact continuity. Replace as needed. If MC is okay, check
Comp start relay, start and run capacitors (single phase), and Comp motor winding
continuity. If Comp is energized but evaporator is not cooling, check for an inefficient
Comp. See "VIII.A. Specication and Performance Data."
FMR: If Comp is energized but FMR is not, check for 115VAC at the FMR junction
box. If 115VAC is not present, check icemaker wiring connections. If 115VAC is
present, check for voltage at condenser unit. If115VAC is not present, check eld
wiring connections. If 115VAC is present, check FMR capacitor, motor winding, and
fan blade for binding.
c) WV and HGV Diagnosis: If WV is energized, check for 115VAC at CB K1 #6 (O) to
neutral (W). If 115VAC is present after PM energizes in harvest cycle, replace CB.
If115VAC is not present, replace WV (bypassing). If HGV did not close at the end of
harvest, check for 115VAC at CB K1 #2 (P) to neutral (W). If 115VAC is present and
LED 3 is off, replace CB. If 115VAC is not present, replace HGV (bypassing).
18
Loading...
+ 39 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.