Hoshizaki KMD860MRJ User Manual

Page 1
Service Manual
Modular Crescent Cuber
Model KMD-860MAJ, MWJ, MRJ
hoshizakiamerica.com
Number: 73221 Issued: 1-30-2018
Page 2
Only qualied service technicians should install and service the appliance. To obtain the name and phone number of your local Hoshizaki Certied Service Representative, visit www.hoshizaki.com. No service should be undertaken until the technician has thoroughly read this Service Manual. Failure to service and maintain the appliance in accordance with this manual will adversely affect safety, performance, component life, and warranty coverage and may result in costly water damage. Proper installation is the responsibility of the installer. Product failure or property damage due to improper installation is not covered under warranty.
Should the reader have any questions or concerns which have not been satisfactorily addressed, please call, send an e-mail message, or write to the Hoshizaki Technical Support Department for assistance.
Phone: 1-800-233-1940; (770) 487-2331 Fax: 1-800-843-1056; (770) 487-3360
E-mail: techsupport@hoshizaki.com
618 Highway 74 South Peachtree City, GA 30269 Attn: Hoshizaki Technical Support Department
Web Site: www.hoshizaki.com
NOTE: To expedite assistance, all correspondence/communication MUST include the
following information:
• Model Number
• Serial Number
• Complete and detailed explanation of the problem.
2
Page 3
IMPORTANT
This manual should be read carefully before the appliance is serviced. Read the warnings and guidelines contained in this manual carefully as they provide essential information for the continued safe use, service, and maintenance of the appliance. Retain this manual for any further reference that may be necessary.
CONTENTS
Important Safety Information ................................................................................................. 5
I. Construction and Water/Refrigeration Circuit Diagram ....................................................... 7
A. Construction .................................................................................................................. 7
1. Air-Cooled (MAJ) ...................................................................................................... 7
2. Water-Cooled (MWJ) ............................................................................................... 8
3. Remote Air-Cooled (MRJ) ........................................................................................ 9
B. Water/Refrigeration Circuit Diagram ............................................................................ 10
1. Air-Cooled Models (MAJ) ....................................................................................... 10
2. Water-Cooled Models (MWJ) ..................................................................................11
3. Remote Models (MRJ) ........................................................................................... 12
II. Sequence of Operation and Service Diagnosis ............................................................... 13
A. Sequence of Operation Flow Chart ............................................................................. 13
1. Operation Flow Chart ............................................................................................ 13
2. Shutdown Flow Chart ............................................................................................ 14
3. Freeze-Time Correction Chart ............................................................................... 15
B. Service Diagnosis ....................................................................................................... 16
C. Freeze-Time Correction Cycle (90 min.) ..................................................................... 24
D. Control Board Check ................................................................................................... 26
E. Bin Control Check ....................................................................................................... 27
F. Float Switch Check and Cleaning ................................................................................ 29
1. Float Switch Check ................................................................................................ 29
2. Float Switch Cleaning ............................................................................................ 30
G. Thermistor Check ........................................................................................................ 31
H. Control Switch ............................................................................................................. 31
I. Diagnostic Tables .......................................................................................................... 32
J. Freeze-Up Check List .................................................................................................. 36
III. Controls and Adjustments ............................................................................................... 37
A. Control Board Layout ................................................................................................. 38
B. LED Lights and Audible Alarm Safeties ....................................................................... 39
C. Settings and Adjustments ............................................................................................ 40
1. Default Dip Switch Settings .................................................................................... 40
2. Harvest Time (S4 dip switch 1 & 2)........................................................................ 41
3. Pump-Out Time/Harvest Time During Pump-Out (S4 dip switch 3 & 4) ................. 41
4. Pump-Out Frequency Control (S4 dip switch 5) ..................................................... 42
5. Harvest Pump Time (Harvest Assist) (S4 dip switch 6) ......................................... 42
6. Harvest Pump Time (Harvest Assist)/Freeze-Time Correction (S4 dip switch 7) .. 43
7. Factory Use (S4 dip switch 8)................................................................................. 43
8. Freeze Timer (S4 dip switch 9 & 10) ...................................................................... 44
9. Float Switch Selector (S5 dip switch 1) ................................................................. 44
10. Rell Counter (S5 dip switch 2 and 3) ................................................................... 44
11. Minimum Harvest Time (S5 dip switch 4) ............................................................... 45
12. Anti-Slush (S5 dip switch 5) ................................................................................... 45
3
Page 4
IV. Refrigeration Circuit and Component Service Information.............................................. 46
A. Refrigeration Circuit Service Information .................................................................... 46
B. Component Service Information .................................................................................. 49
C. Water Regulating Valve Adjustment (water-cooled model) .......................................... 49
V. Maintenance .................................................................................................................... 50
VI. Preparing the Icemaker for Periods of Non-Use ............................................................. 51
VII. Disposal ......................................................................................................................... 53
VIII. Technical Information .................................................................................................... 54
A. Specication and Performance Data Sheets ............................................................... 54
1. KMD-860MAJ ......................................................................................................... 54
2. KMD-860MWJ ....................................................................................................... 55
3. KMD-860MRJ ........................................................................................................ 56
B. Wiring Diagram ........................................................................................................... 57
4
Page 5

Important Safety Information

Throughout this manual, notices appear to bring your attention to situations which could result in death, serious injury, damage to the appliance, or damage to property.
WARNING Indicates a hazardous situation which could result in death or
serious injury.
NOTICE Indicates a situation which could result in damage to the
appliance or property.
IMPORTANT Indicates important information about the use and care of the
appliance.
The appliance should be destined only to the use for which it has been expressly conceived. Any other use should be considered improper and therefore dangerous. The manufacturer cannot be held responsible for injury or damage resulting from improper, incorrect, and unreasonable use. Failure to service and maintain the appliance in accordance with this manual will adversely affect safety, performance, component life, and warranty coverage and may result in costly water damage.
To reduce the risk of death, electric shock, serious injury, or re, follow basic precautions including the following:
• Only qualied service technicians should install and service this appliance.
• The appliance must be installed in accordance with applicable national, state, and local codes and regulations.
• Electrical connection must be hard-wired and must meet national, state, and local electrical code requirements. Failure to meet these code requirements could result in death, electric shock, serious injury, re, or damage.
• The icemaker requires an independent power supply of proper capacity. See the nameplate for electrical specications. Failure to use an independent power supply of proper capacity can result in a tripped breaker, blown fuses, damage to existing wiring, or component failure. This could lead to heat generation or re.
THE ICEMAKER MUST BE GROUNDED. Failure to properly ground the icemaker could result in death or serious injury.
• Move the control switch to the "OFF" position and turn off the power supply before servicing. Lockout/Tagout to prevent the power supply from being turned back on inadvertently.
• To reduce the risk of electric shock, do not touch the control switch or service switch with damp hands.
• Do not make any alterations to the unit. Alterations could result in electric shock, injury, re, or damage to the unit.
• The appliance is not intended for use by persons (including children) with reduced physical, sensory, or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
5
Page 6
WARNING, continued
• Children should be properly supervised around this appliance.
• Do not climb, stand, or hang on the appliance or allow children or animals to do so. Serious injury could occur or the appliance could be damaged.
• Do not use combustible spray or place volatile or ammable substances near the appliance. They might catch re.
• Keep the area around the appliance clean. Dirt, dust, or insects in the appliance could cause harm to individuals or damage to the appliance.
Additional Warning for Remote Models
THE REMOTE CONDENSER UNIT MUST BE GROUNDED. The power supply and ground connection to the remote condenser unit are supplied from the icemaker. Failure to properly ground the remote condenser unit could result in death or serious injury.
• Move the icemaker control switch to the "OFF" position and turn off the power supply to the icemaker before servicing the remote condenser unit. Lockout/Tagout to prevent the power supply from being turned back on inadvertently.
NOTICE
• Follow the instructions in this manual carefully to reduce the risk of costly water damage.
• In areas where water damage is a concern, install in a contained area with a oor drain.
• Install the appliance in a location that stays above freezing. Normal operating ambient temperature must be within 45°F to 100°F (7°C to 38°C).
• Do not leave the icemaker on during extended periods of non-use, extended absences, or in sub-freezing temperatures. To properly prepare the icemaker for these occasions, follow the instructions in "VI. Preparing the Appliance for Periods of Non-Use."
• Do not place objects on top of the appliance.
• The dispenser unit/ice storage bin is for ice use only. Do not store anything else in the dispenser unit/ice storage bin.
6
Page 7

I. Construction and Water/Refrigeration Circuit Diagram

A. Construction

1. Air-Cooled (MAJ)

Spray Tubes
Inlet Water Valve
Thermostatic Expansion Valves
Water Supply Inlet
Hot Gas Valve
Junction Box
Condenser
Control Box
Float Switch
Drain Valve
Cleaning Valve
Condenser Fan Motor
Main Transformer
Drier
Control Switch
Water Pump
Compressor
Bin Control
7
Page 8

2. Water-Cooled (MWJ)

Spray Tubes
Thermostatic Expansion Valves
Inlet Water Valve
Water Supply Inlet
Hot Gas Valve
Junction Box
Water Regulator
Condenser
Control Box
Float Switch
Drain Valve
Water Pump
Cleaning Valve
Control Switch
Bin Control
Main Transformer
Drier
Compressor
8
Page 9

3. Remote Air-Cooled (MRJ)

Spray Tubes
Inlet Water Valve
Water Supply Inlet
Hot Gas Valve
Main Transformer
Junction Boxes
Control Box
Receiver Tank
Float Switch
Drain Valve
Water Pump
Cleaning Valve
Thermostatic Expansion Valves
Bin Control
Control Switch
Drier
Liquid Line Valve
Compressor
Crankcase Heater
9
Page 10

B. Water/Refrigeration Circuit Diagram

1. Air-Cooled Models (MAJ)

10
Page 11

2. Water-Cooled Models (MWJ)

11
Page 12

3. Remote Models (MRJ)

12
Page 13

II. Sequence of Operation and Service Diagnosis

A. Sequence of Operation Flow Chart

1. Operation Flow Chart

10th cycle
(S4 dip switch 5)
2 sec., then reverses for
10/20 sec.
• Pump motor stops for
(S4 dip switch 3 & 4)
FS in control
Comp energized
FMR energized
HGV energized
LLV de-energized
PM de-energizes for 2 sec.,
then reverses for 10/20 sec.
FS opens or freeze
timer terminates
Anti-Slush
Thermistor temperature
reaches 36°F (2.2°C)
(5.8 kΩ).
PM de-energized for
10 sec.
• Factory set for every
4. Pump-Out Cycle
CB: 2A7664-02
When freeze time differential exceeded,
freeze-time correction cycle starts.
See "II.A.3. Freeze-Time Correction Chart."
FS closed
50 sec.
Comp energized
FM energized
FMR energized
LLV energized
PM energized
HGV de-energized
FS check
FS open
3. Freeze Cycle
• Min. freeze time: 5 min.
• Max. freeze time: freeze timer setting
(S4 dip switch 9 & 10).
5-min.
minimum
freeze timer in
Harvest Pump
control
Time
Operation Flow Chart
PM energized
1 to 3-min. harvest timer in
control (S4 dip switch 1 & 2)
Thermistor
in control
HPT setting (S4 dip switch 6), whichever is shorter.
• WV time: 6 min. or the length of harvest minus
• Max. harvest time: 20 min.
2. Harvest Cycle
WV de-energized
FS closed
Thermistor temperature reaches
Comp energized
FMR energized
48°F (9°C) (3.9 kΩ or less).
Harvest timer starts.
HGV energized
WV energized
Components Energized when the Control Switch is in the "WASH" Position
The "WASH" position on the control switch is used when cleaning and sanitizing the unit. When in the "WASH" position, power is supplied
to the pump motor. With the cleaning valve closed, the cleaner and sanitizer ow over the outside of the evaporator plate assembly. With the
cleaning valve open, the cleaner and sanitizer ow over both the outside and the inside of the evaporator plate assembly.
Note: Close the cleaning valve after cleaning and sanitizing are complete, otherwise the unit will not restart when the control
switch is placed in the "ICE" position.
WV energized
13
FS open
If FS is open, Comp stops and cycle
returns to 1-Min. ll.
Legend:
BC–bin control
CB–control board
Comp–compressor
FM–fan motor
FMR–fan motor-remote
FS–oat switch
HGV–hot gas valve
HPT–harvest pump time
LLV –liquid line valve
PM–pump motor
WV–inlet water valve
Fill Cycle
1. 1-Minute
Cycle
Steps
FS check
Startup
Page 14

2. Shutdown Flow Chart

2. Icemaker Off
3. Ice Level Lowered
Icemaker starts at
All components
"1. 1-Minute Fill Cycle."
de-energized.
To 1. 1-Minute Fill Cycle
BC closed
(BC actuator paddle disengaged)
Green "BC CLOSED" LED on
Yellow "BC OPEN" LED off
Yellow "BC OPEN" LED continues. All
components de-energized.
Shutdown Flow Chart
Control board 2A7664-02 retains freeze-time correction
count data between bin control restarts.
to 15 sec. into the freeze cycle if
activated at the end of the harvest cycle.
15 sec. before the 5-min. short cycle
protection timer terminates.
Otherwise, at the end of the next harvest
cycle.
BC open (BC actuator paddle engaged)
Green "BC CLOSED" LED off
Yellow "BC OPEN" LED on
BC Operation
Legend:
BC–bin control
1. Bin Full
Shutdown
Shutdown Delay:
and Restart
Fill Cycle–15 sec. after activation.
Harvest Cycle–At the end of the harvest cycle, or up
Freeze Cycle– 15 sec. after activation if activated at least
14
Page 15

3. Freeze-Time Correction Chart

2. 10-Minute Fill/Overow
WV energized
Comp de-energized
FMR de-energized
HGV de-energized
PM de-energized
After 5th 10-Minute Harvest Pump Cycle with WV
Freeze-Time Correction Cycle Complete.
Go to Step "3. Freeze Cycle" in Operation Flow Chart.
step 1 for 5th and nal time.
• Do not adjust S4 dip switch 7 out of the factory position.
• After step 2 completes 4th sequence (80 min. completed), repeat
1. 10-Minute Harvest Cycle with WV
Comp energized
FMR energized
HGV energized
PM energized
WV energized
2A7664-02 Freeze-Time Correction Flow Chart
Cycle Steps
Steps 1 and 2 repeat
4 times (total 80 min.),
then step 1 repeats for
a 5th time to complete
Freeze-Time Correction
Start
Legend:
Comp–compressor
FM–fan motor
FMR–fan motor-remote
HGV–hot gas valve
PM–pump motor
WV–inlet water valve
Appliance Cycle Reset and Alarm Reset:
Cycle Reset: Power Supply or Control Switch Turned Off and On again:
Appliance turns off, then re-starts at 1.Fill Cycle.
Alarm Reset: CB "ALARM RESET" pressed during or after a freeze-time
correction cycle with power supply on:
Appliance continues cycle with no interruption or reset.
CB red "POWER OK" LED blinking:
CB red "POWER OK" LED resets to solid.
CB yellow "EXT HARVEST" LED blinking:
Cycle.
Differential
Value in Sec.
3 254
4 309
5 349
6 380
7 406
8 427
9 446
10 462
CB yellow "EXT HARVEST: LED turns off.
Number of
Freeze Time Differential Exceeded.
Minimum and Maximum Freeze times have
exceeded differential parameters.
Freeze-Time Correction function is enabled
when S4 Dip Switch 7 is in the "ON" position.
CB monitors freeze time. After 3freeze cycles,
CB compares the minimum and maximum
differential of the 3 freeze cycle times. Every
freeze cycle time after the third freeze cycle
time is added to the minimum/maximum
calculation.
Example: After 8 cycles, if the differential
between the shortest cycle (minimum) and the
longest cycle (maximum) is equal to or greater
than 427 sec. a freeze-time correction cycle is
initiated:
Freeze Cycles
Note: When 1st freeze-time correction cycle
is initiated, CB "POWER OK" LED starts
blinking. On 2nd freeze-time correction cycle,
if CB "POWER OK" LED has been reset,
CB "POWER OK" LED starts blinking. If CB
"POWER OK" had not been reset after 1st
freeze-time correction cycle CB "POWER OK"
LED continues to blink.
After 3rd freeze-time correction cycle in
36hours, CB yellow "EXT HARVEST" LED
starts blinking.
Appliance continues to operate and LEDs
continue to blink until ALARM RESET button is
pressed with power on.
15
Page 16

B. Service Diagnosis

• The appliance should be diagnosed and repaired only by qualied service personnel to reduce the risk of death, electric shock, serious injury, or re.
• Risk of electric shock. Control switch in "OFF" position does not de-energize all loads. Use extreme caution and exercise safe electrical practices.
• Moving parts (e.g., fan blade) can crush and cut. Keep hands clear.
• Before servicing the appliance, move the control switch to the "OFF" position and turn off the power supply.
CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews are securely in place after the appliance is serviced. Make sure that none have fallen into the dispenser unit/ice storage bin.
• Make sure all food zones in the appliance and dispenser unit/ice storage bin are clean after service.
The diagnostic procedure is a sequence check that allows you to diagnose the electrical system and components. Before proceeding, check for correct installation, proper voltage per nameplate, and adequate water supply. Check CB using the steps in "II.D. Control Board Check." Check dip switch settings to assure that S4 dip switch 3, 4, 7, 8, 9, 10 and S5 dip switch 1 through 5 are in the factory default position. S4 dip switch 1, 2, 5, 6 are cleaning adjustments and the settings are exible. For factory default settings, see "III.C.1. Default Dip Switch Settings."
Note: • When checking high voltage (115VAC), always choose a white (W) neutral wire to
establish a good neutral connection.
• The neutral (W) is provided through MT. To conrm a good neutral, check for 60VAC from white (W) neutral to ground (GND). If 60VAC is present, neutral is good. If 60VAC is not present, check 208-230VAC main power supply to MT. If208-230VAC is present, check MT continuity.
• When checking voltage from the CB K1 connector (10 pin connector), pull CB K1connector out slightly to allow room for multimeter test leads contact.
1) Turn off the power supply, then access the control box. Move the control switch to the "OFF" position. Clear any ice from BC.
2) Check that BC is closed and the 115VAC 10A fuse is good.
16
Page 17
1. Operation Diagnosis
3) Power On: Turn on the power supply, then move the control switch to the "ICE" position. A 5-sec. delay occurs. CB red "POWER OK" LED and green "BC CLOSED" LED turn on. If yellow "BC OPEN" LED is on (indicating a full bin), check BC. Move ice away from BC actuator paddle. If yellow "BC OPEN" LED stays on, see "II.E. Bin Control Check.".
Note: • CB red "POWER OK" LED remains on unless the 10.5VAC power supply is
interrupted (K2 connector).
• Check CB using the steps in "II.D.Control Board Check."
• Conrm CB green "BC CLOSED" LED is on. If CB yellow "BC OPEN" LED is on, remove ice from BC. If no ice is around BC and yellow "BC OPEN" LED is on, see "II.E. Bin Control Check."
a) Power On Diagnosis: If CB red "POWER OK" LED is off, conrm 10A fuse is good.
Check for 115VAC at control switch #1 (BR) to neutral (W) then at control switch #2(P) to neutral (W). If 115VAC is present on #1 (BR) and not on #2(P), replace control switch. If 115VAC is present on control switch #2 (P), check for 115VAC at HPS (P) to neutral (W) then HPS (BK) to neutral (W). If115VAC is present at HPS (P) and not at HPS (BK), HPS is open. See HPS Diagnosis below. If115VAC is present at HPS (BK), check for 10.5VAC at CB K2#1 red wire to CB K2 #2 red wire. If10.5VAC is not present, check that the cleaning valve interlock switch is closed. Next, check CT continuity. If open, replace CT.
b) HPS Diagnosis: Conrm condenser coil is not clogged or restricted. Let refrigeration
circuit pressures equalize. If HPS does not reset and pressures are equalized, replace HPS. Ifpressures are not equalized, reclaim refrigerant and diagnose refrigeration circuit restriction. Check that there are no restrictions in the refrigeration circuit. Harvest Cycle: HGV, strainer, or check valve. Freeze Cycle: FM, FMR, TXV, HM, LLV, WRV, strainer, check valve, drier, damaged line set or tting, and fan blade for binding.
Conrm that the location meets installation requirements. See the appliance's
instruction manual for details.
4) 1-Min. Fill Cycle – LED 4 is on. WV and X11 relay energize. After 1 min., CB checks for a closed FS. If FS is closed, the harvest cycle begins. If harvest cycle begins (Comp, HGV, FMR energized), continue to step 5a. If FS is open, WV remains energized until FS closes (low water safety protection during initial start up and at the end of each harvest). Diagnosis: Check that water enters the water tank. If not, check that the water supply line shut-off valve is open and screens or external lters are clear. Check for 115VAC at CB K1 #6 (O) to neutral (W). If 115VAC is not present, replace CB. If 115VAC is present, and WV does not energize, check for 115VAC at WV. If 115VAC is present, check coil continuity. Ifopen, replace WV. If the water tank lls, but the appliance fails to start harvest (Comp energized), check for open FS. See "II.F. Float Switch Check and Cleaning." If FS is closed and CB fails to start the harvest cycle after 1 min., replace CB.
17
Page 18
5a) Initial Harvest Cycle – LEDs 1, 4, and 2 are on. WV and X11 relay continue. Comp,
FMR, HGV, and X10 relay energize. CBmonitors the warming of the evaporator via the thermistor located on the suction line. When the thermistor reaches 48°F (9°C), CB reads 3.9 kΩ from the thermistor and turns harvest termination over to the harvest timer (S4 dip switch 1 & 2 and S5dip switch 4). WV and X11 relay are energized during harvest for a maximum of 6 min. or the length of harvest minus HPT setting (S4dip switch 6), whichever is shorter. See step 5b below.
a) Comp Diagnosis: Check that evaporator is warming. Ifnot, conrm that Comp
energizes. If not, check for 115VAC at CB K1 #1 (V) or #9 (V) to neutral (W). If115VAC is not present, check for 115VAC at CB K1 #7 (BR) or #10 (BR) to neutral (W). If115VAC is present at #7 (BR) or #10 (BR) and not at #1 (V) or #9 (V), replace CB. If 115VAC is present, check for 115VAC at CR solenoid. If 115VAC is present, conrm contacts are closed. If not, replace CR. If CR contacts are closed, check Comp external overload, Comp start and run capacitors, Comp start relay, and Comp motor winding.
b) HGV Diagnosis: If Comp is energized and evaporator is not warming, check that
HGV energizes and opens. Check for 115VAC at CB K1 #2 (P) to neutral (W). If115VAC is not present and LED 2 is on, replace CB. If 115VAC is present, check for 115VAC at HGV coil and check HGV coil continuity. Replace as needed.
c) LLV Diagnosis: Conrm that LLV is de-energized and closed (not bypassing).
Ifenergized, replace CB. If de-energized and bypassing, replace LLV.
d) WRV Diagnosis: Conrm WRV is not leaking by. If WRV is leaking by, conrm HGV
is open and LLV is closed. Next, check for proper refrigerant pressures. If refrigerant pressures are correct, adjust or replace WRV. See "IV.C. Water Regulating Valve Adjustment (water-cooled model)."
18
Page 19
5b) Harvest Pump Time (Harvest Assist) – LEDs 1, 3, and 2 are on. When the
thermistor reaches 48°F (9°C), CB reads 3.9 kΩ from the thermistor and turns harvest termination over to the harvest timer (S4 dip switch 1 & 2 and S5 dip switch4). WhenWV de-energizes, LED 4 turns off, X11 relay de-energizes and LED 3turns on. PM energizes. Comp, FMR, HGV, and X10relay continue. Diagnosis: Place a thermometer on the suction line next to the thermistor. Has it warmed to 48°F (9°C) or warmer? Conrm thermistor status. See "II.G. Thermistor Check." If the thermistor reading is in proper range, dip switch 7 is on, and PM does not energize before harvest terminates, replace CB. If WV continues, check for 115VAC at CB K1 #6 (O). If115VAC is present, and LED 4 is off, replace CB. If LED 3is on and PM is not energized, check for 115VAC at CB K1 #5(DBU). If115VAC is not present, replace CB. If 115VAC is present and PM is not energized, check for 115VAC at X10relay terminal #8 (Y) to neutral (W). If 115VAC is not present, check for 115VAC at X10 relay terminal #4 (P) to neutral (W) and X10 relay terminal #6 (Y) to neutral (W). If 115VAC is present on terminal #4(P) and not on terminal #6 (Y), replace X10 relay. If 115VAC is present on X10 relay terminal #8 (Y) and PM is not energized, check for 115VAC at X10 relay terminal #3 (R) to neutral (W) and terminal #5 (DBU) to neutral (W). If 115VAC is present on terminal #5(DBU) and not on terminal #3 (R), replace X10relay. If 115VAC is present on X10relay terminal #3 (R), check control switch contact continuity between terminals #4(R) and #5(Y). Ifcontacts are open, replace control switch. If contacts are closed and 115VAC is present between control switch terminal #5(Y) and neutral (W), check PM capacitor and motor winding continuity.
5c) Initial Harvest Cycle Termination Diagnosis: When the thermistor reaches 48°F
(9°C), CB reads 3.9 kΩ from the thermistor and turns harvest termination over to the harvest timer (S4 dip switch 1 & 2 and S5 dip switch 4). Check discharge line temperature. For a thermistor check, see "II.G.Thermistor Check." If 1-min. ll cycle starts after harvest timer terminates, check that FS is clean and operating properly, see "II.F. Float Switch Check and Cleaning." If FS is closed, CB proceeds to the next cycle. Ifnot, replace CB. Note: The minimum total time allowed by CB for a complete harvest cycle is based on
S5 dip switch 4. Maximum harvest time allowed is 20min.
NOTICE! S4 dip switch 7 must remain on. Otherwise, PM will not energize during the last seconds of harvest.
19
Page 20
6) Freeze Cycle – LED 1 is on. Comp, FMR, and PM continue. FM and LLV energize. HGV and X10 relay de-energize. Appliance is held in freeze by a 5-min. short cycle protection timer. After 5-min. short cycle protection timer terminates and FS opens, freeze cycle terminates. Note: PM power supply switches from CBK1 #5(DBU) in harvest to K1 #4 (R) in freeze. Anti-Slush: When anti-slush is enabled (S5 dip switch 5 "ON"), PM de-energizes when thermistor reaches 36°F (2.2°C) (5.8kΩ) for 10 sec. then, energizes for the remainder of the freeze cycle.
a) Freeze Cycle Diagnosis: Conrm Comp, FMR, and PM continue. Conrm that
FM and LLV energize. Conrm WRV opens. Next, conrm HGV and X10 relay de-energize. During the rst 5 min. of freeze, conrm evaporator is cooling. If not, conrm WV de-energized (not leaking by), HGV de-energized (not bypassing), LLV and FM (if not connected to CB K1 connector pin #9) energize, TXV and HM operate correctly, WRV opens, Comp is efficient, and refrigerant charge is correct. See"VIII.A. Specication and Performance Data."
b) Comp, FM, and FMR Diagnosis: If Comp, FM, and FMR de-energize once freeze
begins, check that appliance has not shut off on HPS ("POWER OK" LED off). If so, check "3)b) HPS Diagnosis" above. If"POWER OK" LED is on, check for 115VAC at CB K1 #1 (V) or #9 (V) to neutral (W). If 115VAC is not present and LED 1 is on, replace CB. Comp: If 115VAC is present, check for 115VAC at CR coil. If 115VAC is present, check CR coil and contact continuity. Replace as needed. If CR is okay, check Comp start relay and start and run capacitors. Next, check Comp motor winding continuity. If Comp is energized but evaporator is not cooling, check for an inefficient Comp. See"VIII.A. Specication and Performance Data." FM: If Comp is energized but FM is not, check capacitor, motor winding, and fan blade for binding. FMR: If Comp is energized but FMR is not, check for 115VAC at the FMR junction box. If 115VAC is not present, check icemaker wiring connections. If 115VAC is present, check for voltage at condenser unit. If115VAC is not present, check eld wiring connections. If 115VAC is present, check FMR capacitor, motor winding, and fan blade for binding.
c) WV and HGV Diagnosis: If WV is energized, check for 115VAC at CB K1 #6 (O) to
neutral (W). If 115VAC is present after PM energizes in harvest cycle, replace CB. If115VAC is not present, replace WV (bypassing). If HGV did not close at the end of harvest, check for 115VAC at CB K1 #2 (P) to neutral (W). If 115VAC is present and LED 3 is off, replace CB. If 115VAC is not present, replace HGV (bypassing).
d) PM Diagnosis: Conrm water is owing over evaporator from PM and not WV. If PM
de-energizes once freeze begins, check for 115VAC at CB K1 #4 (R) to neutral (W). If 115VAC is not present, replace CB. If 115VAC is present and PM is de-energized, check for 115VAC at control switch #5 (Y) to neutral (W). If 115VAC is present at CB K1 #4 (R) and not at control switch #5 (Y), check control switch continuity between #5 (Y) and #4 (R). Replace as needed. If 115VAC is present at control switch #5 (Y) to neutral (W), check PM capacitor and motor winding continuity.
20
Page 21
e) FM and LLV Diagnosis: If FM or LLV does not energize, check for 115VAC at CB
K1#3 (BK) to neutral (W). If 115VAC is not present, replace CB. If 115VAC is present: For FM, check capacitor, motor winding, and blade for binding. For LLV, check coil voltage and continuity.
f) Refrigerant Pressures, HM, and TXV Diagnosis: If evaporator is still not cooling,
check refrigerant pressures. See "VIII.A. Specication and Performance Data Sheets." Next, check HM operation. If refrigeration pressures are above HM setpoint and HMis bypassing, replace HM. Check TXV for proper operation. Remove TXV bulb and hold it in your hand, refrigerant low-side pressure should rise, place TXV bulb in ice water, refrigerant low-side pressure should drop. A 10 to 15 pound pressure swing between warm and cold conditions indicate a good TXV. If a 10 to 15 pound swing is not present, replace TXV.
g) WRV Diagnosis: WRV is factory set and generally no adjustment is required.
IfWRV fails to open in freeze, check for proper refrigerant pressures. See "VIII.A. Specication and Performance Data Sheets." If refrigerant pressures are correct and WRV does not open, adjust or replace as needed. See "IV.C. Water Regulating Valve Adjustment (water-cooled model)."
h) Freeze Termination Diagnosis: After 5 min. in freeze, disconnect CB K5 FS
connector. 15 sec. later appliance should switch out of the freeze cycle (15 second delay after FS opens before terminating the freeze cycle). If appliance remains in freeze longer than 15 sec. after FS removed, replace CB. If appliance switches with FS removed but would previously not switch out of freeze with FS connected (long freeze - 3 beep alarm), see "II.F. Float Switch Check and Cleaning."
Note: Normal freeze cycle will last 20 to 40 min. depending on model and conditions.
Cycle times and pressures should follow performance data provided in this manual. See "VIII.A. Specication and Performance Data Sheets."
i) Short Freeze Cycle Diagnosis: Conrm water tank lls and overows during ll and
harvest cycles. If not, check water supply lters, shut-off valve, WV screen. Ifwater tank empties before 5 min. timer terminates and freeze cycle is short, check that CV is not leaking by (water owing down the potable drain). If CV is leaking by, remove and clean CV, replace rubber seat and spring if necessary. If water tank is full, see "II.F. Float Switch Check and Cleaning." for erratic FS.
21
Page 22
7) Pump-Out Cycle – LEDs 1, 3, and 2 are on (10/20 second pump-out). Timing of the rst pump-out is determined by S4 dip switch 5. See the table below.
Control Board Settings
S4 Dip Switch
Setting
No. 5
OFF Every 10 cycles After 11th freeze cycle
ON Every cycle After 2nd freeze cycle
Pump-Out Frequency
1st Pump-Out
Comp and FMR continue, HGV energizes. If S4dip switch 3 & 4 are set to 3off Comp continues, HGV energizes, FM and LLV (if applicable) de-energizes. NOTICE!S4dip
switch 3 & 4 must not be set to 3 off and 4 on. Otherwise, LED 4 turns on energizing WV, X11, and X10 relay. Once X10 relay energizes, X12 relay, PM, and DV cannot energize. PM stops for 2 sec., then X12 relay, PM, and DV energize for
10/20 sec. depending on pump-out timer (S4 dip switch 3 & 4) setting. When pump-out timer terminates, pump-out is complete. The pump-out frequency control (S4 dip switch
5) is factory set, and generally no adjustment is required. However, the pump-out frequency control can be set to have a pump-out occur every 10 cycles or every cycle. For details, see "III.C.4. Pump-Out Frequency Control (S4 dip switch 5)."
a) Pump-Out Diagnosis: In the freeze cycle before pump-out (see table above), after
5min. of freeze disconnect CB black K5 connector (FS connector). Check that CB LEDs 1, 3, and 2are on, PM stops, then re-starts, DV energizes, and water is owing down the drain through DV.
b) CB Diagnosis: Conrm FM and LLV (if applicable) de-energize. If FM or LLV
(ifapplicable) is energized with LEDs 1, 3, and 2 on, replace CB. If PM does not stop and re-start and DV does not energize, check that CB LEDs 1, 3, and 2 are on. Ifnot, replace CB. IfLEDs 1, 3, and 2 are on and X12 relay is not energized, check for 115VAC at CB K1 #5 (DBU) to neutral (W). If 115VAC is not present, replace CB. If115VAC is present at CB K1 #5 (DBU) and X12 relay is not energized, continue to "c) X12 Relay, PM, and DV Diagnosis:" below. If X12 relay is energized and PM and DV are not energized, check for 115VAC at CB K1 #2 (P) to neutral (W). If LED 2 is on and 115VAC is not present at CB K1 #2 (P), replace CB.
c) X12 Relay Diagnosis: If 115VAC is present at CB K1 #5 (DBU) and CB K1 #2
(P) and X12 relay, PM, and DV are not energized, check for 115VAC at X12 relay #8 (DBU) to neutral (W). If115VAC is not present, check wiring connections from CB K1 #5 (DBU) to X10 relay #5 (DBU), then at X10 relay #1 (DBU). If 115VAC is present at X10 relay #5 (DBU) and not at X10 relay #1 (DBU), conrm X10 relay is de-energized, if X10 relay is de-energized, replace X10 relay (sticking contacts). If 115VAC is present at X12 relay #8 (DBU) to neutral (W), and X12 is de-enrgized, check relay coil continuity. Replace as needed.
22
Page 23
d) PM Diagnosis: Check for 115VAC at X12 relay #6 (P) to neutral(W). If 115VAC is not
present, see "b) CB Diagnosis" above. Next, check for 115VAC at X12 relay #4(Y) to neutral (W). If 115VAC is not present, conrm X12 relay is energized. If X12 relay is de-energized, see "c) X12 Relay Diagnosis:" above. If X12 relay is energized and 115VAC is present at X12 relay #6 (P) and not at X12 relay #4 (Y), replace X12 relay. If 115VAC is present at X12 relay #4 (Y) and PM is de-energized, check PM capacitor, motor winding, wiring connections, and impeller for binding.
e) DV Diagnosis: Check for 115VAC at X12 relay #5 (P) to neutral (W) and at X12relay
#3 (GY) to neutral (W). If 115VAC is not present at X12 relay #5 (P), see "b) CB Diagnosis:" above. If 115VAC is present at X12 relay #5 (P) and not at X12 relay #3(GY), conrm X12 relay is energized. If X12 relay is de-energized, see "c) X12 Relay Diagnosis:" above. If X12 relay is energized and 115VAC is present at X12 relay #5 (P) and not at X12 relay #3 (GY), replace X12 relay. If115VAC is present at X12 #3 (GY) and DV is de-energized, check DV coil continuity, make sure the drain line is not clogged and that DV is clean and operating properly.
8) Normal Harvest Cycle – Same as the initial harvest cycle. Return to step 5a) above. Note: Appliance continues to cycle until BC is satised or power is switched off. The
appliance always restarts at the 1-min. ll cycle.
2. Shutdown Diagnosis
1) See "II.E. Bin Control Check."
3. Freeze-Time Correction Cycle Diagnosis
1) See "II.C. Freeze-Time Correction Cycle (90 min.)."
Legend: BC–bin control; CB–control board; Comp–compressor; CR–compressor relay;
CT–control transformer; CV–check valve; FM–fan motor; FMR–fan motor remote; FS–oat switch; HGV–hot gas valve; HM–headmaster (C.P.R.); HPS–high-pressure switch; L LV–liquid line valve; PM–pump motor; TXV–thermostatic expansion valve; WRV–water regulating valve; WV–inlet water valve
23
Page 24

C. Freeze-Time Correction Cycle (90 min.)

Freeze-Time Correction function is enabled when S4 Dip Switch 7 is in the "ON" position and initiates when the minimum and maximum freeze times have exceeded differential parameters. Freeze-time correction timer and count starts at the beginning of the 2nd freeze cycle after startup from power off condition. Freeze-time correction timer and count continues and retains its freeze-time correction timer and count during a BC off cycle and resumes its freeze-time correction timer and count on the 2nd freeze cycle after BC restart. If freeze-time differential is exceeded (see table below), freeze-time correction cycle starts and CB red "POWER OK" LED blinks. When freeze-time correction cycle occurs 3 or more times within a 36 hour period, CB yellow "EXT HARVEST" LED blinks with CB red "POWER OK" LED. Appliance starts in freeze cycle after a freeze-time correction cycle. Toreset CB LEDs, press ALARM RESET button on CB with power on. CB resets LEDs and appliance continues cycle without interruption.
1) Freeze Time Differential Initiation: CB starts monitoring freeze times on the second freeze time. After 3freeze cycles (4th total), CBbegins to compare minimum and maximum freeze time cycles. Every freeze cycle time after the rst freeze cycle time is added to the freeze time list. Minimum and maximum freeze time differential comparisons begin on the third cycle and are monitored up to 10cycles. On the 11th cycle the rst freeze cycle time is dropped to maintain the 10 maximum number of cycles. Example: After 8 cycles (excluding rst cycle), if the differential between the shortestcycle (minimum) and the longest cycle (maximum) is equal to or greater than 427 sec. a freeze-time correction cycle is initiated:
Number of Freeze Cycles
3 254 4 309 5 349 6 380 7 406 8 427 9 446
10 462
Differential Value in Sec.
24
Page 25
2) Freeze-Time Correction Sequence: First occurrence within 36 hr., minimum and maximum freeze times have exceeded differential parameters. CB "POWER OK" LED starts blinking. Freeze-Time Correction Cycle starts. Second occurrence within 36 hr., minimum and maximum freeze times have exceeded differential parameters. If not reset, CB "POWER OK" LED continues blinking. If reset from rst occurrence, CB "POWER OK" LED starts blinking. Freeze-Time Correction Cycle starts. Third occurrence within 36 hr. minimum and maximum freeze times have exceeded differential parameters. CB yellow "EXT HARVEST" LED starts blinking. Also, If not reset, CB "POWER OK" LED continues blinking. If reset, CB "POWER OK" LED starts blinking. Freeze-time Correction Cycle starts. Total freeze-time correction cycle last for 90min. At the end of 80min., the nal step initiates and nal Harvest Pump Time (Harvest Assist) with WV (10-min.) starts. Once the nal Harvest Pump Time (Harvest Assist) with WV (10-min.) terminates (90 min. complete), normal freeze cycle begins.
2a) 10-Min. Harvest Pump Time (Harvest Assist) with WV: CB "POWER OK" LED
blinking. CB LEDs 1, 4, 3, and 2 are on and Comp, FMR, HGV, PM, and WV energize. 10-min. timer starts. Once 10-min. timer terminates, CB LEDs 1, 3, and 2 turn off and Comp, FMR, HGV, and PM de-energize. WV continues.
2b) 10-Min. Fill: CB LED 4 on and WV energized. 10-min. timer starts.
2c) Final 10-Min. Harvest Pump Time (Harvest Assist) with WV: CB "POWER OK" LED
blinking. Once 10-min. timer terminates, CB LEDs 1, 4, 3, and 2 are on and Comp, FMR, HGV, and PM energizes. WV continues. 10-min. timer starts. Once 10-min. timer terminates, normal freeze cycle begins. CB LED 1 on and Comp, FMR, and PM continue. HGV and WV de-energize.
Note: After 3rd Freeze-Time Correction Cycle in 36 hours, CB signals with blinking CB
yellow "EXT HARVEST" LED. Appliance continues normal operation. CB "POWER OK" LED and CB yellow "EXT HARVEST" LED continue blinking in normal operation sequence.
3) Appliance Cycle Reset and CB Alarm Reset: Cycle Reset: Power supply or control switch turned off and on again: Appliance turns off, then re-starts at 1. Fill Cycle. Alarm Reset: CB "ALARM RESET" pressed during or after a freeze-time correction cycle with power supply on: Appliance continues cycle with no interruption or reset. CB red "POWER OK" LED blinking: CB red "POWER OK" LED resets to solid. CB yellow "EXT HARVEST" LED blinking: CB yellow "EXT HARVEST: LED turns off.
Legend: BC–bin control; CB–control board; Comp–compressor; CR–compressor relay;
CT–control transformer; CV–check valve; FM–fan motor; FMR–fan motor remote; FS–oat switch; HGV–hot gas valve; HM–headmaster (C.P.R.); HPS–high-pressure switch; L LV–liquid line valve; PM–pump motor; TXV–thermostatic expansion valve; WRV–water regulating valve; WV–inlet water valve
25
Page 26

D. Control Board Check

Before replacing CB that does not show a visible defect and that you suspect is bad, always conduct the following check procedure. This procedure will help you verify your diagnosis.
Alarm Reset: If CB is in alarm (beeping), press the "ALARM RESET" button on CB
while CB is beeping. WARNING!Risk of electric shock. Care should be taken not to touch live terminals. Once reset, the icemaker starts at the 1-minute ll cycle. For audible alarm information, see "III.B. LED Lights and Audible Alarm Safeties."
1) Check the dip switch settings to assure that S4 dip switch 3, 4, 7, 8, 9, 10 and S5 dip switch 1 through 5 are in the factory default position. S4 dip switch 1, 2, 5,are cleaning adjustments and the settings are exible. For factory default settings, see "III.C.1. Default Dip Switch Settings."
2) Move the control switch to the "ICE" position. If the red "POWER OK" LED is on, control voltage is good, continue to step 3. If the "POWER OK" LED is off, check CT secondary circuit. CT output is 10.5VAC at 115VAC primary input. If the secondary circuit has proper voltage and the red LED is off, replace CB.
If the secondary circuit does not have proper voltage (10.5VAC), check CT primary
circuit. Check for 115VAC at control switch terminal #1 (BR) and control switch terminal #3 (P) to neutral (W). If 115VAC is present at control switch terminal #1 (BR) and not at control switch terminal #3 (P), replace control switch. If 115VAC is present at control switch terminal #3 (P), check for 115VAC at HPS (BK) to neutral (W). If 115VAC is not present, see "B.1. or 2. 3)b) HPS Diagnosis." If 115VAC is present check CT coil continuity. Replace as needed. For additional checks, see "II.I.1. No Ice Production."
3) The "OUTPUT TEST" button provides a relay sequence test. Make sure the control switch is in the "ICE" position, then press the "OUTPUT TEST" button. For the correct lighting sequence, see the table below. Note that the order of the LEDs from the outer edge of the control board is 1, 4, 3, 2. Components (e.g., compressor) cycle during the test.
Following the test, the icemaker begins operation at the 1-minute ll cycle. If the LEDs do not light as described above, replace CB.
4) To verify voltage output from CB to the components, slide the CB K1 connector out far enough to allow multimeter lead contact. With the icemaker in the cycle to be tested, check output voltage from the corresponding pin on CB K1 connector to a neutral (Wwire). If output voltage is not found and the appropriate LED is on, replace CB.
5) Conrm BC communication and shutdown sequence: Move the control switch to the "ICE" position. Once the ll cycle starts press and hold the BC actuator paddle. CB shuts down the appliance after 15 sec.. If not, conrm BC status. See "II.E. Bin Control Check." If BC checks ok, replace CB.
Legend: BC–bin control; CB–control board; CT–control transformer
26
Page 27

E. Bin Control Check

a) Bin Control Check
A lever-actuated proximity switch is used to control the ice level in the storage bin. No adjustment is required.
To check BC, follow the steps below.
1) Turn off the power supply.
2) Remove the front panel, then move the control switch to the "OFF" position.
3) Remove the control box cover, then clear any ice away from BC.
4) Check BC wire harness connections. See Fig. 1.
BC Connector (to control board K4 (red) connector)
5) Disconnect BC connector from CB K4 connector.
6) Check for continuity across the wires of BC connector. When the actuator paddle is not engaged, BC switch is closed. If open, check that the wire harness connector is
BC
BC Wire Harness (white) Connector
properly connected and that the actuator paddle is not sticking. Clean if necessary. See "II.E.b) Bin Control Cleaning." If BC switch still reads open, replace BC.
Actuator Paddle
Fig. 1
7) Press and hold the actuator paddle; check for continuity across the wires of BC connector. When the actuator paddle is engaged, BC switch is open. If closed, check that the actuator paddle is not restricted. Clean if necessary. See "II.E.b) Bin Control Cleaning." If BC switch still reads closed, replace BC.
8) Reconnect BC connector to CB K4 connector, then move the control switch to the "ICE" position. Turn on the power supply.
9) Check that CB green "BC CLOSED" LED is on.
10) Allow the icemaker to cycle on. Press and hold the actuator paddle. CB yellow "BCOPEN" LED should turn on and the icemaker should shut down according to the chart below. If it does not, replace CB.
Cycle at Bin Control Activation
Fill Cycle 15 sec. after activation.
Harvest Cycle At the end of the harvest cycle, or up to 15 sec. into the freeze cycle if activated at the
Freeze Cycle 15 sec. after activation if activated at least 15 sec. before the 5-min. short cycle
Shutdown
end of the harvest cycle.
protection timer terminates. Otherwise, at the end of the next harvest cycle.
Legend: BC–bin control; CB–control board
27
Page 28
b) Bin Control Cleaning
Scale may build up on BC. Scale can cause the actuator paddle and magnet to stick. In this case, BC should be cleaned.
CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews are
securely in place after the icemaker is serviced. Make sure that none have fallen into the dispense unit/ice storage bin.
1) Turn off the power supply.
2) Remove the front panel, then move the control switch to the "OFF" position.
3) Clear any ice away from BC.
4) Disconnect BC connector from CB K4 connector, then remove BC from the icemaker.
5) Remove the actuator paddle from the switch mount. See Fig. 2.
6) Wipe down BC with a mixture of 1 part of Hoshizaki "Scale Away" and 25 parts of warm water. Rinse the parts thoroughly with clean water.
7) Reassemble BC and replace it in its correct position. Note: If the magnet was removed for cleaning, be sure to replace it in its correct
position.
8) Reconnect BC connector to CB K4 connector, then move the control switch to the "ICE" position.
9) Replace the control box cover in its correct position.
10) Turn on the power supply to start the automatic icemaking process.
11) Replace the front panel in its correct position.
Legend: BC–bin control; CB–control board
BC Wire Harness (white) Connector
BC Bracket
Switch Mount
Actuator Paddle
BC Connector (to control board K4 (red) connector)
Bin Control Proximity Switch Closed (calling for ice)
Bin Control Proximity Switch Open (bin full, icemaker off or shutting down)
Fig. 2
Magnet
Model Shown: KMD-530M_H
28
Page 29

F. Float Switch Check and Cleaning

FS is used to determine that there is sufficient water in the water tank after the 1-min. ll cycle and after each harvest cycle. FS is also used to determine that the appropriate volume of water has been converted into ice before switching out of the freeze cycle. No adjustment is required.

1. Float Switch Check

To check FS, follow the steps below.
1) Turn off the power supply.
2) Remove the front panel and move the control switch to the "OFF" position.
3) Remove the front insulation panel, then remove splash guard, cube guide B, and cube guide A. Next, remove the overow cap, overow pipe, and water shield. See Fig. 3.
4) Remove the drain plug and drain the water tank. Replace the drain plug in its correct position. Be careful not to cross thread it.
5) Replace the water shield, overow pipe, overow cap, cube guide A, cube guide B, splash guard, and front insulation panel in their correct positions.
NOTICE! Be careful not to cross thread the overow pipe.
Overow Cap
Overow Pipe
Splash Guard
6) Remove the control box cover.
7) Disconnect the black oat switch connector from the K5 connector on the control board.
8) Check for continuity across the oat switch leads. With the water tank empty, the oat switch should be open. If open, continue to step 9. If closed, follow the steps in "II.F.2.
Cube Guide A
Cube Guide B
Fig. 3
Drain Plug
Water Shield
Float Switch Cleaning." After cleaning the oat switch, check it again. Replace ifnecessary.
9) Reconnect the black oat switch connector, then replace the control box cover.
10) Move the control switch to the "ICE" position. Replace the front panel in its correct position, then turn the power supply on. After 1 minute, the 1 minute ll cycle should end and the initial harvest cycle should begin. If the initial harvest cycle begins, the oat switch is good and the check is complete. If the initial harvest cycle does not begin, continue to step 11.
11) Turn off the power supply.
12) Remove the front panel.
13) Move the control switch to the "OFF" position.
14) Remove the control box cover.
29
Page 30
15) Disconnect the black oat switch connector from the K5 connector on the control board.
16) Check for continuity across the oat switch leads. With the water tank full, the oat switch should be closed. If the oat switch is closed and the icemaker will not switch from the 1 minute ll cycle to the initial harvest cycle, replace the control board.
If FS is open, conrm that the water tank is full. If the water tank is not full, check the water supply, water lters, and inlet water valve. If the water tank is full, follow the steps in "II.F.2. Float Switch Cleaning." After cleaning FS, check it again. Replace if needed.
Legend: CB–control board; FS–oat switch

2. Float Switch Cleaning

Depending on local water conditions, scale may build up on FS. Scale on the switch can cause the oat to stick. In this case, FS should be cleaned.
1) Turn off the power supply.
2) Remove the front panel and move the control switch to the "OFF" position.
3) Remove the front insulation panel, then remove splash guard, cube guide B, and cube guide A. Next, remove the overow cap, overow pipe, and water shield. See Fig. 3.
4) Remove the drain plug and drain the water tank. Replace the drain plug in its correct position. Be careful not to cross thread it.
5) Replace the water shield, overow pipe, overow cap, cube guide A, cube guide B, splash guard, and front insulation in their correct positions. NOTICE! Be careful not to
cross thread the overow pipe.
6) Disconnect the vent tube and ush tube from the top of the oat switch, then remove the oat switch and rubber boot.
7) Remove the retainer rod from the bottom of the oat switch assembly, then remove the oat. Be careful not to bend the retainer rod excessively when removing it. See Fig. 4.
8) Wipe down the oat switch assembly's housing, shaft, oat, and retainer rod and clean the inside of the rubber boot and hose with a mixture of 1 part of Hoshizaki "Scale Away" 25 parts of warm water. Rinse the parts thoroughly with clean water.
9) Reassemble the oat switch assembly and replace it and the rubber boot in their correct positions. Reconnect the vent tube and the ush tube.
10) Move the control switch to the "ICE" position.
Vent
11) Replace the front panel in its correct position.
12) Turn on the power supply to start the automatic icemaking process.
Legend: CB–control board; FS–oat switch; PM–pump motor
Shaft
Float Switch Housing
30
Float
Retainer Rod
Fig. 4
Page 31

G. Thermistor Check

To check thermistor resistance, follow the steps below.
1) Turn off the power supply.
2) Remove the front panel. Move the control switch to the "OFF" position.
3) Remove the control box cover.
4) Remove the thermistor from the refrigerant tubing.
5) Immerse the thermistor sensor portion in a glass containing ice and water for 2 or 3 min.
6) Disconnect the thermistor connector from CB K3 connector and check the resistance between thermistor leads. Normal range is 4.7 to 6.2 kΩ. If outside the normal range, replace the thermistor. See "IV.B. Component Service Information." If within the normal range, continue to the next step.
7) Replace the thermistor in its correct position. See "IV.B. Component Service Information."
8) Reconnect the thermistor connector to CB K3 connector.
9) Replace the control box cover in its correct position.
10) Move the control switch to the "ICE" position.
11) Replace the front panel in its correct position.
12) Turn on the power supply.
13) Once the harvest cycle starts (Comp energizes), begin timing the harvest cycle.
14) The harvest timer and harvest cycle should terminate within 2 to 5 min. If the harvest cycle does not terminate within 2 to 5 min., replace CB.
Legend: CB–control board; Comp–compressor

H. Control Switch

The control switch has three positions: "OFF" for power off, "ICE" for icemaking, and "WASH" to energize the pump motor when cleaning and sanitizing. WARNING! Control
switch in "OFF" position does not de-energize all loads. Risk of electric shock. Use extreme caution and exercise safe electrical practices.
31
Page 32

I. Diagnostic Tables

1. No Ice Production
No Ice Production - Possible Cause
1. Power Supply a) Off, blown fuse, or tripped breaker.
b) Not within specications.
2. Main Transformer a) Voltage tap switch not set to proper voltage.
b) Coil winding open or shorted, defective.
3. Fuse (control box) a) Blown.
4. Control Switch a) In "OFF" or "WASH" position.
b) Bad contacts.
5. High-Pressure Switch a) Dirty condenser.
b) Fan motor not operating.
c) Refrigerant overcharged.
d) Bad contacts.
e) Refrigerant lines or components plugged.
6. Control Transformer (115VAC/10.5VAC)
7. Control Board See "II.D. Control Board Check"
8. Bin Control See "II.E. Bin Control Check "
9. Water Supply a) Water supply off or improper water pressure.
10. Inlet Water Valve a) Screen or orice clogged.
11. Float Switch See "II.F. Float Switch Check and Cleaning"
12. Compressor a) Compressor relay contacts bad or coil winding open.
13. Hot Gas Valve a) Closed in harvest cycle.
14. Thermistor See "II.G. Thermistor Check"
15. Pump Motor a) Motor winding open.
a) Coil winding open or shorted.
a) In alarm.
b) Yellow "BC OPEN" LED on: Bin full.
c) Defective.
a) Tripped with bin lled with ice.
b) Actuator does not move freely.
c) Defective.
b) External water lters clogged.
b) Coil winding open.
c) Water valve open in freeze cycle.
a) Float does not move freely.
b) Defective.
b) Start capacitor or run capacitor defective.
c) Internal protector open.
d) Start relay contacts bad or coil winding open (single phase).
e) Compressor defective.
b) Open in freeze cycle.
a) Loose, disconnected, or defective.
b) Bearing worn out or locked rotor.
c) Defective capacitor.
32
Page 33
No Ice Production - Possible Cause
16. Thermostatic Expansion Valve a) Bulb loose.
b) Operating erratically.
1 7. Liquid Line Valve a) Closed in freeze cycle.
b) Open in harvest cycle.
18. Fan Motor a) Motor winding open.
b) Bearing worn out or locked rotor.
c) Defective capacitor.
19. Water System a) Water leaks causing short freeze time.
2. Freeze-Up
Defrost and clean the icemaker prior to diagnosing freeze-up. Fill out a freeze-up checklist. See "II.J. Freeze Up Check List," the Hoshizaki America Technician's Pocket Guide, or contact your local distributor for a copy of the freeze-up checklist.
Freeze-Up - Possible Cause
Harvest Cycle
1. Evaporator a) Scaled up.
b) Damaged.
2. Cube Guides a) Out of position.
b) Damaged.
3. Spray Tubes and/or Spray Guides
4. Water Supply a) Low water pressure.
5. Inlet Water Valve a) Screen or orice clogged.
6. Float Switch See "II.F. Float Switch Check and Cleaning"
7. Refrigerant Charge a) Low.
8. Control Board See "III.C. Settings and Adjustments" and "II.D. Control Board Check"
9. Bin Control See "II.E. Bin Control Check"
10. Thermistor See "II.G. Thermistor Check"
11. Thermostatic Expansion Valve a) Defective.
12. Hot Gas Valve a) Closed or restricted.
13. Liquid Line Valve a) Open.
a) Dirty.
b) Out of position.
b) External water lters clogged.
c) Insufficient water line size.
Minimum 1/4" Nominal ID (6 mm Nominal OD in the EU) copper water tubing or equivalent.
b) Defective.
a) Dirty, sticking.
b) Defective.
a) Harvest timer (S4 dip switch 1 & 2) set too short.
b) Harvest pump timer (S4 dip switch 7) not in factory default position.
c) Defective.
a) Actuator does not move freely, sticking.
b) Defective.
a) Loose, disconnected, or defective.
33
Page 34
Freeze-Up - Possible Cause
Freeze Cycle
1. Evaporator a) Scaled up.
b) Damaged.
2. Spray Tubes and/or Spray Guides and Splash Guard
3. Refrigerant Charge a) Low.
4. Control Board See "II.D. Control Board Check"
5. Inlet Water Valve a) Leaking by.
6. Float Switch See "II.F. Float Switch Check and Cleaning"
7. Pump Motor a) RPM too slow.
8. Thermostatic Expansion Valve a) Bulb loose or defective.
9. Liquid Line Valve a) Restricted.
10. Headmaster (C.P.R.) (remote models)
a) Dirty.
b) Out of position.
a) Freeze timer (S4 dip switch 9 & 10) set incorrectly.
b) Defective.
a) Float does not move freely.
b) Defective.
b) Impeller damaged.
a) Not bypassing.
3. Low Ice Production
Low Ice Production - Possible Cause
Long Harvest Cycle
1. Evaporator a) Scaled up.
2. Spray Tubes and/or Spray Guides
3. Refrigerant Charge a) Low.
4. Water Supply a) Low water pressure.
5. Control Board See "II.D. Control Board Check"
6. Thermistor See "II.G. Thermistor Check"
7. Hot Gas Valve a) Erratic or closed.
8. Inlet Water Valve a) Screen or orice clogged.
9. Compressor a) Inefficient or off.
10. Liquid Line Valve a) Erratic or open.
11. Thermostatic Expansion Valve a) Defective.
a) Dirty.
b) Out of position.
b) External water lters clogged.
c) Insufficient water line size.
Minimum 1/4" Nominal ID (6 mm Nominal OD in the EU) water tubing or equivalent.
d) Too cold.
a) Thermistor connection loose (K3).
b) Defective.
a) Loose, disconnected, or defective.
34
Page 35
Low Ice Production - Possible Cause
Long Freeze Cycle
1. Evaporator a) Scaled up, dirty.
2. Float Switch See "II.F. Float Switch Check and Cleaning"
3. Inlet Water Valve a) Leaking by.
4. Hot Gas Valve a) Erratic or open.
5. Condenser a) Clogged.
6. Control Board See "II.D. Control Board Check"
7. Refrigerant Charge a) Low.
8. Thermostatic Expansion Valve a) Bulb loose.
9. Compressor a) Inefficient or off.
10. Pump Motor a) RPM too slow.
11. Liquid Line Valve a) Erratic or restricted.
12. Headmaster (C.P.R.) (remote models)
a) Scaled up, dirty.
b) Float sticking.
c) Defective switch.
a) Float switch connection loose (K5).
b) Defective.
b) Defective.
a) Not bypassing.
35
Page 36

J. Freeze-Up Check List

[ ] 29) Is ice still dropping when next freeze cycle starts?
(Freeze pressure should be taken 5 minutes into
(Freeze pressure should be taken 5 minutes into
shutdown within 15seconds in the rst 5minutes
Freeze-Up Check List
Please Complete When Diagnosing a Freeze-Up, Refrigerant Leak, or Low Charge
Technical Support Fax #: 770-487-3360
Make Copies And Use As Needed
Model #___________________________ Serial # ____________________Install Date____________Freeze-Up Date___________
List model and manufacture of bin or dispenser__________________________.
Date appliance was last cleaned:__________.
Freeze-Up Defrost
YES NO [ ] [ ] 1) After defrosting, was the appliance leak
checked?
[ ] [ ] 2) Were any leaks found?
If so where?_____________________.
[ ] [ ] 3) Was any refrigerant added to the unit?
If so, how much?_________________.
Set Up
[ ] [ ] 4) Is the appliance stand alone? [ ] [ ] 5) Is water line independent? [ ] [ ] 6) Is water line correct size? If not________”.
3/8" Nominal ID Copper Water Tubing or Equivalent.
7) What is water pressure?___________. Water Temperature_________.
[ ] [ ] 8) Does appliance have any water ltration?
If yes please list the following: Filter brand___________________. Model________________. Filter pressure gauge reading during the ll cycle___________. Date lter was last replaced?__________________________. GPM or LPM ow rate of lter system?__________________.
9) Ambient temperature at appliance? ______________.
At remote condenser (if applicable)?________.
Appliance Status
[ ] [ ] 10) Is the appliance and/or oat switch dirty?
11) List the S4 (1-10) and S5 (1-5) DIP switch settings.
S4: 1___2___3___4___5___6___7___8___9___10____ S5: 1_____2_____3_____4_____5______ [ ] [ ] 12) Is DIP switch number 7 ON (harvest pump
time (harvest assist) all models and freeze-time correction models with control board
2A7664-02? [ ] [ ] 13) Is the cube guide positioned correctly? [ ] [ ] 14) Are the evaporator separators positioned
properly? [ ] [ ] 15) Is the thermistor properly mounted, tight, and
insulated? [ ] [ ] 16) Is the TXV bulb properly mounted, tight, and
insulated?
Appliance Operation
Fill YES NO [ ] [ ] 17) Does the water tank ll and overow?
[ ] [ ] 18) If NO in step 17, is water ow 5GPM for larger? [ ] [ ] 19) Does the appliance utilize re-ll (S5 dip switch
Harvest [ ] [ ] 20) Is the hot gas valve opening? [ ] [ ] 21) Is harvest pump time (harvest assist) utilized
[ ] [ ] 22) Is hot gas valve opening in harvest? [ ] [ ] 23) Does water valve close completely when
Freeze [ ] [ ] 25) Is pump motor energized in freeze cycle except
[ ] [ ] 28) Is the cube size consistent from inlet to outlet of
[ ]
[ ] [ ] 33) When activating bin control, did appliance
Freeze-Time Correction Operation
[ ] [ ] 34) Has Freeze-Time Correction been activated?
[ ] [ ] 35) Has moer than 1 Freeze-Time Correction been
60-90 sec. Note: Larger models may take up to 120 seconds to overow when empty.
2and 3)?
(S4dip switch 7)?
de energized?
24) What was length of harvest?___________.
during 10-sec. anti-slush. If activated (S5 dip switch 5 on)?
26) Water-cooled condenser outlet temperature 5-min. into freeze? ______________°F.
27) What was length of freeze?____________.
evaporator?
30) What is the ice drop weight?___________.
31) What is head pressure? Freeze_________Harvest_______.
the cycle).
32) What is suction pressure? Freeze______Harvest_______.
the cycle).
of freeze cycle?
("POWER OK" LED blinking).
activated? (POWER OK" LED and "EXT HARVEST" LED blinking).
Note: Make copies of this form and use it when diagnosing a freeze up condition. Submit a completed copy of the checklist
along with the freeze-up labor claim form.
36
Page 37

III. Controls and Adjustments

• A Hoshizaki exclusive control board is employed in KMD series appliances.
• All models are pretested and factory adjusted.
• For a control board check procedure, see "II.D. Control Board Check."
NOTICE
• Fragile, handle very carefully.
• The control board contains integrated circuits, which are susceptible to failure due to static discharge. It is especially important to touch the metal part of the icemaker when handling or replacing the control board.
• Do not touch the electronic devices on the control board or the back of the control board.
• Do not change wiring and connections. Do not misconnect K3 WHITE, K4RED, and K5 BLACK, because the same connector is used for the thermistor, mechanical bin control, K4 jumper, and oat switch.
• Do not short out power supply to test for voltage.
• Always replace the whole control board assembly if it goes bad.
37
Page 38

A. Control Board Layout

• Bin Control Switch Closed LED (green)
• "ALARM RESET" Button
"J" Control Board
• S4 Dip Switch
• "OUTPUT TEST" Button
(used to test relays on control board)
• Bin Control Switch Open LED (yellow)
• Alarm Buzzer
• Ext. Harvest LED (yellow) (lights
when water line thermistor initiates extended harvest) Not used this model
• POWER OK LED (red) (lights when
10.5VAC is supplied to K2 connector)
• Relay LEDs
(4) (indicate which relays are energized and which K1 connector pins are energized
• LED 2 (X2 Relay)
LED 2 on: K1 Connector Pin #2 LED 2 off: K1 Connector Pin #3
• LED 3 (X3 Relay)
LED 3 on: K1 Connector Pin #5 LED 3 off: K1 Connector Pin #4 (energized in freeze)
• LED 4 (X4 Relay) K1 Connector Pin #6
• LED 1 (X1 Relay)
K1 Connector Pin #1, #9
• K3 (white) Connector
Thermistor (harvest control and high temperature safety)
• K4 (red) Connector
Bin Control
• S5 Dip Switch
• K5 (black) Connector
Float Switch (water level)
• Part Number
• K1 Connector
Pins #1 through #10 #1, 9 Compressor Relay #2 Hot Gas Valve #3 Fan Motor Liquid Line Valve #4 Pump Motor (icemaking) #5 Pump Motor (harvest pump timer and pump-out) #6 Inlet Water Valve, X11 Relay #7, 10 Component Power Supply #8 Open
• K2 Connector
Control Transformer (10.5VAC)
"J" Control Board
Part Number 2A7664-02
38
Page 39

B. LED Lights and Audible Alarm Safeties

Beep occurs and red "POWER OK" LED turns on when control switch is moved to "ICE" position.
Sequence
Green LEDs 1 through 4 turn on and sequence from initial startup as listed in the table below. Order of green LEDs from the outer edge of control board is 1, 4, 3, 2.
Sequence Step LED
1-Minute Fill Cycle 4 WV Harvest Cycle 1, 4, 2 Comp, FM*, FMR, HGV, WV 1 minute 20 minutes Harvest Pump Time
(harvest assist) Freeze Cycle 1 Comp, FM/FMR, PM, LLV 5 minutes freeze timer
Anti-Slush Control 1, 3 Comp, FM/FMR, LLV If S5 dip switch 5 on,
Pump-Out Cycle 1, 4 *FM energized if on K1 Connector Pin #9;
1, 3, 2 Comp, FM*, FMR, HGV, PM 0 seconds 50 seconds
, 3, 2 Comp, FM*, FMR, HGV, PM, WV †, DV 10 seconds 20 seconds
pump-out timer setting
Energized
Components
Time LEDs are On
Min. Max.
setting
PM off 10 sec. when thermistor at 36°F (2.2°C)
Alarms
Type Alarm Notes
1
Beep
2
Beep
3
Beep
LED Blink Freeze-Time
To reset above safeties, press "ALARM RESET" button with power supply on.
6 Low Voltage
7 High Voltage
High Evaporator Temp. (temperature > 127°F) (53°C)
Harvest Backup Timer (harvest > 20 min. for two cycles in a row)
Freeze Timer (freeze > freeze timer setting for two cycles in a row)
Correction (CB-2A7664-02) (maximum freeze time differential exceeded)
(92Vac±5% or less)
(147Vac±5% or more)
Check for harvest problem (stuck HGV or relay), hot wa­ter entering unit, stuck HM, or shorted thermistor.
Check thermistor (open), HGV not opening, TXV or LLV leaking by, low charge, inefficient Comp, or WRV leaking by.
Check FS stuck closed (up), WV leaking by, HGV leaking by, PM not pumping, TXV defective, LLV not opening, low charge, HMnot bypassing, or inefficient Comp.
Red POWER OK LED blinks. After 3freeze-time correction cycles in 36hours, yellow EXT HARVEST LED also blinks. Fill out freeze-up checklist. See "II.J. Freeze-Up Check List."
Red LED turns off if voltage protection operates. Control voltage safeties automatically reset when voltage is corrected.
Legend: CB–control board; Comp–compressor; FM–fan motor; FMR–fan motor remote;
FS–oat switch; HGV–hot gas valve; HM–headmaster (C.P.R.); LLV –liquid line valve; PM–pump motor; TXV–thermostatic expansion valve; WRV–water regulating valve; WV–inlet water valve
39
Page 40

C. Settings and Adjustments

NOTICE
Dip switches are factory set. Failure to maintain factory settings may adversely affect performance and warranty coverage. For more information, contact your Hoshizaki Service Center.

1. Default Dip Switch Settings

The dip switches are factory-adjusted to the following positions for both the 2A7664-01 and 2A7664-02 control boards:
S4 Dip Switch
Model 1 2 3 4 5 6 7 8 9 10
KMD-860MAJ OFF OFF OFF OFF OFF OFF ON OFF OFF OFF
KMD-860MWJ OFF OFF OFF OFF OFF OFF ON OFF OFF OFF
KMD-860MRJ OFF OFF OFF OFF OFF OFF ON OFF OFF OFF
S5 Dip Switch (Do Not Adjust)
Model
All Models OFF OFF OFF OFF ON
1 2 3 4 5
ON
Freeze Timer (9 & 10)
Factory Use (8) Harvest Pump Time (Harvest Assist) and Freeze-Time Correction (7) (Do Not Adjust)
Harvest Pump Time Timer (Harvest Assist) (6)
Pump-Out Frequency Control (5)
Pump-Out Time (3 & 4)
1 2 3 4 5 6 7 8 9 10
Harvest Timer (1 & 2)
S4 Dip Switch "J" Control Board
S5 Dip Switch (Do Not Adjust) "J" Control Board
Anti-Slush (5)
Minimum Harvest Time (4)
Rell Counter (2 and 3)
1 2 3 4 5
ON
Float Switch Selector (1)
40
Page 41

2. Harvest Time (S4 dip switch 1 & 2)

The harvest timer starts counting when the thermistor reaches 48°F (9°C) at the evaporator outlet and the control board reads 3.9 kΩ from the thermistor. The harvest timer is factory set, and generally no adjustment is required. However, a setting longer than the factory setting may be advised in cases where the drain provided at harvest needs to be prolonged for extra cleaning. Note that the pump-out timer (S4 dip switch 3 & 4) acts in place of the harvest timer during cycles with a pump out. For details, see "III.C.3. Pump-Out Timer (S4 dip switch 3& 4)."
Note: On models with a pump-out every cycle, the harvest timer is only relevant during
the initial harvest cycle since a pump out occurs every cycle thereafter.
Time
S4 Dip Switch Setting
No. 1 No. 2 S5-4 OFF S5-4 ON
OFF OFF 60 30
ON OFF 90 45
OFF ON 120 60
ON ON 180 75
(sec.)

3. Pump-Out Time/Harvest Time During Pump-Out (S4 dip switch 3 & 4)

NOTICE
Do not adjust 3 off and 4 on. Pump motor does not run in pump-out rotation in this setting.
When a pump-out is called for, the pump motor stops for 2 sec., then energizes in the reverse direction, taking water from the bottom of the water tank and forcing pressure against the check valve seat allowing water to go through the check valve and down the drain. At the same time, water ows through the small tube to power ush the oat switch. The pump motor drains the water tank for the time determined by the pump-out timer. The pump-out timer also acts in place of the harvest timer during cycles with a pump-out. The pump-out timer is factory set, and generally no adjustment is required. However, where water quality is bad and the icemaker needs a longer pump-out time, the pump-out timer can be adjusted. The pump-out time can be set to pump-out for 10or 20 sec. During pump-out cycles minimum harvest time is based on times given in the table below.
S4 Dip Switch Setting Time (sec.)
T1 T2
No. 3 No. 4
OFF OFF 10 150 100 Closed Closed
ON OFF 10 180 130 Closed Closed
OFF ON 10 120 70 Open Closed
ON ON 20 180 180 Closed Closed
S5-4 OFF S5-4 ON S5-4 OFF S5-4 ON
Inlet Water
Valve
T1: Time to drain the water tank T2: Harvest timer at pump out
41
Page 42

4. Pump-Out Frequency Control (S4 dip switch 5)

The pump-out frequency control is factory set to drain the water tank every 10 cycles. Generally no adjustment is required. However, where water quality is bad and the icemaker needs a pump-out more often, the pump-out frequency can be adjusted. The pump-out frequency control can be set to have a pump-out occur every cycle, or every 10 cycles.
The rst pump-out is dependent on S4 dip switch 5. See the table below.
S4 Dip Switch Setting
No. 5
OFF Every 10 cycles After 11th freeze cycle
ON Every cycle After 2nd freeze cycle
Pump-Out Frequency 1st Pump-Out

5. Harvest Pump Time (Harvest Assist) (S4 dip switch 6)

NOTICE
Factory set for proper operation. Do not adjust. Adjustment outside of the factory default setting may result in damage to the appliance.
Harvest pump time (harvest assist) is only active when S4 dip switch 7 is in the "ON" position. In the factory default position, the harvest pump time (harvest assist) starts with 50sec. left to go in harvest cycle (S4 dip switch 6) and after the thermistor reaches 48°F (9°C) at the evaporator outlet and the control board reads 3.9kΩ from the thermistor. The harvest pump time (harvest assist) is factory set, and no adjustment is required.
Harvest Pump Time
S4 Dip Switch Setting
No. 6 S5-4 OFF S5-4 ON
OFF 50 sec. 25 sec.
ON 25 sec. 15 sec.
(Harvest Assist)
42
Page 43

6. Harvest Pump Time (Harvest Assist)/Freeze-Time Correction (S4 dip switch 7)

NOTICE
Factory set for proper operation. Do not adjust. Adjustment outside of the factory default setting may result in damage to the appliance.
a) Harvest Pump Time (Harvest Assist)
Depending on S4 dip switch 7 setting, the pump motor either stays off or is energized during the last seconds of the harvest cycle. When the pump motor is energized (S4 dip switch 7 on), water circulates over the evaporator. The harvest water valve is open during harvest for a maximum of 6 minutes or the length of harvest minus the harvest pump time value (S4 dip switch 6), whichever is shorter.
When S4 dip switch 7 is in the on position and harvest begins, X11 and X10 relays energize. A latching circuit is created through the X11 and X10 relays. For further details, see "VIII.B. Wiring Diagram." In the factory default position, 50 sec. before harvest termination, LED 4 turns off, inlet water valve and X11 relay de-energize. X10 relay remains energized through the latching circuit. Next, LED 3 turns on and control board K1connector pin #5 (DBU wire) energizes, energizing the pump motor for the last seconds of harvest. Harvest pump time adjusted by S4 dip switch 1 & 2 and S5 dip switch 4settings. Contact Technical Support before adjusted these settings.
b) Freeze-Time Correction
When S4 dip switch 7 is in the on position, freeze-time correction enabled. See "II.C. Freeze-Time Correction Cycle (90 min.)."
S4 Dip Switch Setting
No. 7
OFF Disabled
ON Enabled
Harvest Pump Time
(Harvest Assist)
Freeze-Time Correction
(CB: 2A7664-02)

7. Factory Use (S4 dip switch 8)

Factory set for proper operation. Do not adjust. This must be left in the factory default position.
43
Page 44

8. Freeze Timer (S4 dip switch 9 & 10)

NOTICE
Adjust to proper specication, or the icemaker may not operate correctly.
The freeze timer setting determines the maximum allowed freeze time to prevent possible freeze-up issues. Upon termination of the freeze timer, the control board initiates the harvest cycle or pump-out cycle. After 2 consecutive freeze timer terminations, the control board shuts down the icemaker. In this case, see "II.I.3. Low Ice Production" for possible solutions. The freeze timer is factory set and no adjustment is required. Before changing this setting, contact Hoshizaki Technical Support at 1-800-233-1940 for recommendations.
S4 Dip Switch Setting Time
No. 9 No. 10
OFF OFF 60
OFF ON 50
ON OFF 70
ON ON 75

9. Float Switch Selector (S5 dip switch 1)

This dip switch setting allows use of this control board in single and dual oat switch models. This model uses a single oat switch style.
(min.)
NOTICE
Do not adjust. This must be left in the factory default position or the icemaker will not operate correctly.
S5 Dip Switch Setting
OFF Bottom Float Switch Enabled
ON Top Float Switch Enabled
Top or Bottom Float Switch
ControlNo. 1
10. Rell Counter (S5 dip switch 2 and 3)
NOTICE
Do not adjust. These must be left in the factory default position or the icemaker will not operate correctly.
S5 Dip Switch Setting Rell
No. 2 No. 3
OFF OFF 0
OFF ON 1 rell
ON OFF 9 rells
ON ON 10 rells
Counter
44
Page 45

11. Minimum Harvest Time (S5 dip switch 4)

NOTICE
Factory set for proper operation. Do not adjust. Adjustment outside the factory default setting may result in damage to the appliance.
S5 Dip Switch Setting Minimum
No. 4
OFF 120 sec.
ON 70 sec.
Harvest Timer

12. Anti-Slush (S5 dip switch 5)

This dip switch setting provides anti-slush control during the freeze cycle. When the evaporator temperature reaches 36°F (2.2°C) the control board reads a 5.8kΩ signal from the thermistor and de-energizes the water pump for 10 sec. to melt ice slush and prevent ice slush from blocking the water supply tubing, causing irregular freeze patterns.
NOTICE
Factory set for proper operation. Do not adjust. Adjustment outside the factory default setting may result in damage to the appliance.
S5 Dip Switch Setting
OFF Disabled
ON Enabled
Anti-SlushNo. 5
45
Page 46

IV. Refrigeration Circuit and Component Service Information

• This appliance should be diagnosed and repaired only by qualied service personnel to reduce the risk of death, electric shock, serious injury, or re.
• Move the control switch to the "OFF" position and turn off the power supply. Place the disconnect in the "OFF" position. Lockout/Tagout to prevent the power supply from being turned back on inadvertently.
CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews are securely in place after the icemaker is serviced. Make sure that none have fallen into the dispenser unit/ice storage bin.
• Make sure all food zones in the icemaker and dispenser unit/ice storage bin are clean after service.

A. Refrigeration Circuit Service Information

• Repairs requiring the refrigeration circuit to be opened must be performed by properly trained and EPA-certied service personnel.
• Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of refrigerant to the system (if using an electronic leak detector), and then raise the pressure using nitrogen gas (140 PSIG). Do not use R-404A as a mixture with pressurized air for leak testing.
NOTICE
• Always recover the refrigerant and store it in an approved container. Do not discharge the refrigerant into the atmosphere.
• Do not leave the system open for longer than 15 min. when replacing or servicing parts. The Polyol Ester (POE) oils used in R-404A applications can absorb moisture quickly. Therefore it is important to prevent moisture from entering the system when replacing or servicing parts.
• Always install a new drier every time the sealed refrigeration system is opened. Do not replace the drier until after all other repair or replacement has been made. Install the new drier with the arrow on the drier in the direction of the refrigerant ow.
• When brazing, protect the drier by using a wet cloth to prevent the drier from overheating. Do not allow the drier to exceed 250°F (121°C).
1. Refrigerant Recovery
The icemaker is provided with refrigerant access valves. Using proper refrigerant practices, recover the refrigerant. Store the refrigerant in an approved container. Do not discharge the refrigerant into the atmosphere.
46
Page 47
2. Brazing
• R-404A itself is not ammable at atmospheric pressure and temperatures up to 176°F (80°C).
• R-404A itself is not explosive or poisonous. However, when exposed to high temperatures (open ames), R-404A can be decomposed to form hydrouoric acid and carbonyl uoride both of which are hazardous.
• Do not use silver alloy or copper alloy containing arsenic.
1) Braze all ttings while purging with nitrogen gas owing at a pressure of 3 to 4 PSIG. Note: Because the pipes in the evaporator case are specially coated to resist corrosion,
it is important to make connections outside the evaporator case when possible. If it is necessary to braze inside the evaporator case, use sandpaper to remove the coating from the brazing connections before unbrazing the components.
NOTICE
• Always install a new drier every time the sealed refrigeration system is opened.
• Do not replace the drier until after all other repair or replacement has been made. Install the new drier with the arrow on the drier in the direction of the refrigerant ow.
• When brazing, protect the drier by using a wet cloth to prevent the drier from overheating. Do not allow the drier to exceed 250°F (121°C).
2) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of refrigerant to the system (if using an electronic leak detector), and then raise the pressure using nitrogen gas (140 PSIG). Do not use R-404A as a mixture with pressurized air for leak testing.
3. Evacuation and Recharge (R-404A)
1) Attach a vacuum pump to the system. Be sure to connect the charging hoses to both high and low-side refrigerant access valves.
IMPORTANT
The vacuum level and vacuum pump may be the same as those for current refrigerants. However, the rubber hose and gauge manifold to be used for evacuation and refrigerant charge should be exclusively for POE oils.
2) Turn on the vacuum pump. Open the gauge manifold valves. Never allow the oil in the vacuum pump to ow backwards.
3) Allow the vacuum pump to pull down to a 29.9" Hg vacuum. Evacuating period depends on pump capacity.
47
Page 48
4) Close the low-side valve and high-side valve on the gauge manifold.
5) Disconnect the gauge manifold hose from the vacuum pump and attach it to a refrigerant service cylinder. Remember to loosen the connection and purge the air from the hose. For the required refrigerant charge, see the rating label inside the icemaker. Hoshizaki recommends only virgin refrigerant or reclaimed refrigerant which meets AHRI Standard 700 (latest edition) be used.
6) A liquid charge is required when charging an R-404A system (to prevent fractionation). Place the service cylinder on the scales; if the service cylinder is not equipped with a dip tube, invert the service cylinder, then place it on the scales. Open the high-side valve on the gauge manifold.
7) Allow the system to charge with liquid until the proper charge weight is met.
8) If necessary, add any remaining charge to the system through the low-side.
NOTICE!To prevent compressor damage, use a throttling valve or liquid dispensing device to add the remaining liquid charge through the low-side refrigerant access valve with the icemaker running.
9) Close the high and low-side gauge manifold valves, then disconnect the gauge manifold hoses.
10) Cap the refrigerant access valves to prevent a possible leak.
48
Page 49

B. Component Service Information

NOTICE
When replacing a component listed below, see the notes to help ensure proper operation.
Component Notes
Compressor 1 phase: Install a new start capacitor, run capacitor, and start relay.
3 phase: Install a new magnetic contactor.
Thermostatic Expansion Valves
Hot Gas Valves Liquid Line Valves
Fan Motors Install a new capacitor.
Pump Motor Install a new capacitor.
Thermistor • Attach the new thermistor to the suction line in the same location as the previous
• Attach the thermostatic expansion valve bulb to the suction line in the same location as the previous bulb.
• The bulb should be between the 10 and 2 o'clock positions on the tube.
• Secure the bulb with the clamp and holder, then insulate it.
• Replace the strainer if applicable.
• Use copper tube of the same diameter and length when replacing valve lines.
thermistor.
• The thermistor should be at the 12 o'clock position on the tube.
• Smoothly ll the recessed area of the thermistor holder with high thermal conductive type sealant. Hoshizaki America part number 4A0683-01 (Silicone Heat Sink Compound 10-8108 manufactured by GC Electronics), KE-4560 RTV (manufactured by ShinEtsu Silicones), or equivalent are recommended.
• Secure the thermistor with the holder, then insulate it.
• Be very careful to prevent damage to the leads.

C. Water Regulating Valve Adjustment (water-cooled model)

The water regulating valve is factory set, and generally no adjustment is required. However, when necessary, adjust the water regulator using the following procedure.
1) Prepare a thermometer to check the condenser drain temperature. Attach a pressure gauge to the high-side line of the system.
2) 5 min. after a freeze cycle starts, conrm that the thermometer reads 104°F to 115°F (40°C to 46°C). If it does not, rotate the adjustment screw by using a at blade screwdriver until the temperature is in the proper range. See Fig. 5. Next, check that the reference pressure is in the range indicated in the Head Pressure table in the Performance Data section. If it is not in the proper range, verify the refrigerant charge.
Top View
Adjustment Screw
CW – Higher CCW – Lower
Fig. 5
3) Check that the condenser drain temperature is stable.
49
Page 50

V. Maintenance

The maintenance schedule below is a guideline. More frequent maintenance may be required depending on water quality, the appliance's environment, and local sanitation regulations
• Only qualied service technicians should service the appliance.
• To reduce the risk of electric shock, do not touch the control switch or service switch with damp hands
• Before servicing: Move the control switch to the "OFF" position and turn off the power supply. Place the disconnect in the "OFF" position. Lockout/Tagout to prevent the power supply from being turned back on inadvertently.
CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews are securely in place after any maintenance is done to the icemaker. Make sure that none have fallen into the dispenser unit/ice storage bin.
Maintenance Schedule
Frequency Area Task
Daily Scoop Clean the ice scoop using a neutral cleaner. Rinse thoroughly after
cleaning. Bi-Weekly Air Filters Inspect. Wash with warm water and neutral cleaner if dirty. Monthly External Water
Filters Icemaker Exterior Wipe down with a clean, soft cloth. Use a damp cloth containing a
Underside of Icemaker and Top Kits; Bin Door and Snout
Yearly Icemaker and
Dispenser Unit/Ice Storage Bin Liner
Water Supply Inlet Close the icemaker water supply line shut-off valve and drain the water
Condenser Inspect. Clean if necessary by using a brush or vacuum cleaner. More
Water Hoses Inspect the water hoses and clean/replace if necessary.
Check for proper pressure and change if necessary.
neutral cleaner to wipe off oil or dirt build up. Clean any chlorine staining
(rust colored spots) using a non-abrasive cleanser.
Wipe down with a clean cloth and warm water.
Clean and sanitize per the cleaning and sanitizing instructions provided
in the instruction manual or maintenance label on the icemaker.
system. Clean the water supply inlet screen.
frequent cleaning may be required depending on location.
50
Page 51

VI. Preparing the Icemaker for Periods of Non-Use

NOTICE
• When storing the icemaker for an extended time or in sub-freezing temperatures, follow the instructions below to prevent damage.
• To prevent damage to the water pump seal, do not leave the control switch in the "WASH" position for extended periods when the water tank is empty.
When the icemaker is not used for two or three days under normal conditions, it is sufficient to move the control switch to the "OFF" position. When storing the icemaker for an extended time or in sub-freezing temperatures, follow the instructions below.
1. Remove the water from the icemaker water supply line:
1) Turn off the power supply, then remove the front panel.
2) Move the control switch to the "OFF" position.
3) Close the icemaker water supply line shut-off valve, then open the icemaker water supply line drain valve.
4) Allow the line to drain by gravity.
5) Attach a compressed air or carbon dioxide supply to the icemaker water supply line drain valve.
6) Move the control switch to the "ICE" position.
7) Replace the front panel in its correct position, then turn on the power supply.
8) Blow the icemaker water supply line out using the compressed air or carbon dioxide supply.
9) Close the icemaker water supply line drain valve.
2. Drain the water tank:
1) Turn off the power supply, then remove the front panel.
2) Move the control switch to the "OFF" position.
3) Remove the front insulation panel. Remove splash guard, cube guide B, then remove cube guide A. Remove the overow cap, overow pipe, and water shield. See Fig. 3.
4) Remove the drain plug.
5) Remove all ice from the dispenser unit/ice storage bin. Clean the dispenser unit/ice storage bin using a neutral cleaner. Rinse thoroughly after cleaning.
6) Replace the drain plug, water shield, overow pipe, overow cap, cube guide A, cube guide B, splash guard, and front insulation panel in their correct positions. Be careful not to cross thread the drain plug or overow pipe.
7) Replace the front panel in its correct position.
51
Page 52
3. On water-cooled models, remove the water from the water-cooled condenser:
1) Make sure the power supply is off, then remove the front panel and right side panel.
2) Close the condenser water supply line shut-off valve. If connected to a closed loop system, also close the condenser return line shut-off valve.
3) Open the condenser water supply line drain valve. If connected to a closed loop system, also open the condenser return line drain valve.
4) Attach a compressed air or carbon dioxide supply to the condenser water supply line drain valve.
5) Open the water regulating valve by using a screwdriver to pry up on the spring retainer underneath the spring. While holding the valve open, blow out the condenser using the compressed air or carbon dioxide supply until water stops coming out.
6) Close the drain valve(s).
7) Replace the right side panel and front panel in their correct positions.
52
Page 53

VII. Disposal

The appliance contains refrigerant and must be disposed of in accordance with applicable national, state, and local codes and regulations. Refrigerant must be recovered by properly certied service personnel.
53
Page 54

VIII. Technical Information

We reserve the right to make changes in specications and design without prior notice.
A. Specication and Performance Data Sheets
Pressure data is recorded at 5 min. into freezing cycle. The data not in bold should be used for reference only.

1. KMD-860MAJ

Specification Sheet
AC SUPPLY VOLTAGE 208-230/60/1 AMPERAGE 10 A MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kW H/100 lbs.) 1430 (5.16) 1330 (3.74) WATER gal./24HR (gal./100 lbs.) 200 (30.0) 291 (34.0) ICE PRODUCTION PER CYCLE 12.7 lbs. (5.8 kg) 720pcs. BIN CONTROL SYSTEM Mechanical Lever Switch REFRIGERANT CHARGE TOTAL R404A, 2 lb. 6.8 oz. (1100g)
ICEMAKER, 2 lb. 6.8 oz. (1100g)
Performance Data Sheet
APPROXIMATE ICE PRODUCTION PER 24 HR.
lbs./day kg./day APPROXIMATE ELECTRIC CONSUMPTION
watts 100/38 APPROXIMATE WATER CONSUMPTION PER 24 HR.
gal./day m3/day FREEZING CYCLE TIME
min. 100/38 HARVEST CYCLE TIME
min. 100/38 HEAD PRESSURE
PSIG kg/cm2G SUCTION PRESSURE
PSIG kg/cm2G
AMBIENT TEMP.
(ºF/ºC)
70/21 855 388 80/27 813 369 726 329 679 308 90/32 799 363 665 302 612 278
100/38 794 360 653 296 564 256
70/21 80/27 90/32
70/21 291 1.10 80/27 271 1.02 229 0.87 211 0.80 90/32 264 1.00 200 0.76 178 0.67
100/38 229 0.87 194 0.74 158 0.60
70/21 80/27 90/32
70/21 80/27 90/32
70/21 227 16.0 80/27 226 15.9 224 15.8 307 21.6 90/32 226 15.9 223 15.7 294 20.7
100/38 255 17.9 240 16.9 360 25.3
70/21 46 3.2 51 3.6 56 3.9 80/27 50 3.5 58 4.0 61 4.3 90/32 51 3.6 63 4.4 67 4.7
100/38 51 3.6 64 4.5 71 5.0
50/10 70/21 90/32
1330 1359 1381 1352 1398 1409 1359 1430 1446 1357 1434 1460
20 22 24 21 24 22 25 28 22 26 30
2.2 2.2 2.1
2.2 2.1 2.1
2.2 2.0 2.0
2.1 2.0 2.0
WATER TEMP. (ºF/ºC)
799 363 742 337
264 1.00 239 0.91
226 15.9 279 19.6
26
TOTAL HEAT OF REJECTION FROM CONDENSER TOTAL HEAT OF REJECTION FROM COMPRESSOR 1,500 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
13,100 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
54
Page 55

2. KMD-860MWJ

Specification Sheet
AC SUPPLY VOLTAGE 208-230/60/1 AMPERAGE 10 A MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kW H/100 lbs.) 1400 (3.90) 1410 (3.60) WATER gal./24HR (gal./100 lbs.) 176 (20.5) 254 (27.0) ICE PRODUCTION PER CYCLE 12.8 lbs. (5.8 kg) 720pcs. BIN CONTROL SYSTEM Mechanical Lever Switch REFRIGERANT CHARGE TOTAL R404A, 1 lb. 12.2 oz. (800g)
ICEMAKER, 1 lb. 12.2 oz. (800g)
Performance Data Sheet
APPROXIMATE ICE PRODUCTION PER 24 HR.
lbs./day kg./day APPROXIMATE ELECTRIC CONSUMPTION
watts 100/38 APPROXIMATE WATER CONSUMPTION PER 24 HR.
gal./day m3/day FREEZING CYCLE TIME
min. 100/38 HARVEST CYCLE TIME
min. 100/38 HEAD PRESSURE
PSIG kg/cm2G SUCTION PRESSURE
PSIG kg/cm2G
AMBIENT TEMP.
(ºF/ºC)
70/21 940 426 80/27 923 418 887 402 831 377 90/32 917 416 862 391 809 367
100/38 902 409 850 385 760 345
70/21 80/27 90/32
70/21 884 3.34 80/27 993 3.76 1217 4.61 1176 4.45 90/32 1027 3.89 1374 5.20 1371 5.19
100/38 1179 4.46 1374 5.20 1368 5.18
70/21 80/27 90/32
70/21 80/27 90/32
70/21 237 16.7 80/27 238 16.7 240 16.9 255 17.9 90/32 238 16.8 242 17.0 255 17.9
100/38 243 17.1 245 17.2 266 18.7
70/21 39 2.7 40 2.8 44 3.1 80/27 40 2.8 42 3.0 47 3.3 90/32 40 2.8 44 3.1 48 3.4
100/38 42 2.9 45 3.2 52 3.7
50/10 70/21 90/32
1410 1407 1367 1408 1403 1344 1407 1400 1348 1387 1388 1300
17 18 19 18 19 18 19 20 18 20 21
2.6 2.4 2.4
2.5 2.2 2.3
2.4 2.1 2.1
2.3 2.1 2.1
WATER TEMP. (ºF/ºC)
917 416 870 395
1027 3.89 1072 4.06
20
238 16.8 248 17.5
TOTAL HEAT OF REJECTION FROM CONDENSER TOTAL HEAT OF REJECTION FROM COMPRESSOR 1,600 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
11,000 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
55
Page 56

3. KMD-860MRJ

Specification Sheet
AC SUPPLY VOLTAGE 208-230/60/1 AMPERAGE 10 A MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kW H/100 lbs.) 1810 (5.10) 1690 (4.19) WATER gal./24HR (gal./100 lbs.) 155 (18.2) 329 (34.1) ICE PRODUCTION PER CYCLE 12.8 lbs. (5.8 kg) 720pcs. BIN CONTROL SYSTEM Mechanical Lever Switch REFRIGERANT CHARGE TOTAL R404A, 9 lb. 14.6 oz. (4497g)
ICEMAKER, 5 lb. 15.9 oz. (2718g) CONDENSER, 3 lb. 14.8 oz. (1779g)
Performance Data Sheet
APPROXIMATE ICE PRODUCTION PER 24 HR.
lbs./day kg./day APPROXIMATE ELECTRIC CONSUMPTION
watts 100/38 APPROXIMATE WATER CONSUMPTION PER 24 HR.
gal./day m3/day FREEZING CYCLE TIME
min. 100/38 HARVEST CYCLE TIME
min. 100/38 HEAD PRESSURE
PSIG kg/cm2G SUCTION PRESSURE
PSIG kg/cm2G
AMBIENT TEMP.
(ºF/ºC)
70/21 967 439 80/27 941 427 888 403 835 379 90/32 933 423 850 386 797 362
100/38 922 418 838 380 749 340
70/21 80/27 90/32
70/21 329 1.25 80/27 290 1.10 211 0.80 220 0.83 90/32 278 1.05 155 0.59 151 0.57
100/38 223 0.84 154 0.58 148 0.56
70/21 80/27 90/32
70/21 80/27 90/32
70/21 205 14.4 80/27 218 15.3 244 17.1 265 18.7 90/32 222 15.6 262 18.4 284 20.0
100/38 226 15.9 267 18.8 305 21.4
70/21 36 2.5 39 2.7 43 3.1 80/27 38 2.7 42 3.0 47 3.3 90/32 39 2.7 45 3.2 50 3.5
100/38 40 2.8 46 3.2 55 3.9
50/10 70/21 90/32
1690 1725 1896 1717 1771 2010 1725 1810 2024 1801 1860 2220
17 18 19 17 19 18 20 22 18 20 23
3.1 2.7 2.7
2.8 2.3 2.4
2.7 2.0 2.0
2.4 2.0 2.0
WATER TEMP. (ºF/ºC)
933 423 882 400
278 1.05 259 0.98
21
222 15.6 244 17.1
TOTAL HEAT OF REJECTION FROM CONDENSER TOTAL HEAT OF REJECTION FROM COMPRESSOR 2,000 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
13,000 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
56
Page 57

B. Wiring Diagram

*
Water-Cooled Model
* High-Pressure Switch
Air-Cooled and
Remote Air-Cooled Models
PSIG
21.3
PSIG 384±
0 0
21.3
Cut-out 412±
Cut-in 327±21.3 PSIG 284±21.3 PSIG
57
Loading...