Hoshizaki KMD850MRH Service Manual

Hoshizaki America, Inc.
Hoshizaki
Modular Crescent Cuber
Models KMD-850MAH
“A Superior Degree
of Reliability”
www.hoshizaki.com
KMD-850MWH KMD-850MRH
SERVICE MANUAL
Number: 73163 Issued: 9-3-2008 Revised: 1-9-2014
IMPORTANT
Only qualied service technicians should attempt to install, service, or maintain this icemaker. No service or maintenance should be undertaken until the technician has thoroughly read this Service Manual. Failure to service and maintain the equipment in accordance with this manual may adversely affect safety, performance, and warranty coverage.
Hoshizaki provides this manual primarily to assist qualied service technicians in the service and maintenance of the icemaker.
Should the reader have any questions or concerns which have not been satisfactorily addressed, please call, write, or send an e-mail message to the Hoshizaki Technical Support Department for assistance.
HOSHIZAKI AMERICA, INC. 618 Highway 74 South Peachtree City, GA 30269
Attn: Hoshizaki Technical Support Department
Phone: 1-800-233-1940 Technical Service (770) 487-2331 Fax: 1-800-843-1056 (770) 487-3360 E-mail: techsupport@hoshizaki.com
Web Site: www.hoshizaki.com
NOTE: To expedite assistance, all correspondence/communication MUST include the
following information:
  •ModelNumber
  •SerialNumber
  •Completeanddetailedexplanationoftheproblem.
IMPORTANT
This manual should be read carefully before the icemaker is serviced or maintenance operations are performed. Only qualied service technicians should install, service, and maintain the icemaker. Read the warnings contained in this booklet carefully as they give important information regarding safety. Please retain this booklet for any further reference that may be necessary.
CONTENTS
I. Specications ...................................................................................................................... 5
A. Icemaker ....................................................................................................................... 5
1. KMD-850MAH (air-cooled) ....................................................................................... 5
2. KMD-850MWH (water-cooled) ................................................................................. 6
3. KMD-850MRH (remote air-cooled) .......................................................................... 7
B. Condenser Unit ............................................................................................................. 8
1. URC-9F .................................................................................................................... 8
II. General Information ......................................................................................................... 10
A. Construction ................................................................................................................ 10
1a. Air-Cooled Auxiliary Code C-0 and Earlier ........................................................... 10
1b. Air-Cooled Auxiliary Code C-1 and Later .............................................................11
2a. Water-Cooled Auxiliary Code C-0 and Earlier ...................................................... 12
2b. Water-Cooled Auxiliary Code C-1 and Later ........................................................ 13
3a. Remote Air-Cooled Auxiliary Code C-0 and Earlier ............................................. 14
3b. Remote Air-Cooled Auxiliary Code C-1 and Later ................................................ 15
B. Sequence of Operation ............................................................................................... 16
1. One Minute Fill Cycle ............................................................................................. 16
2. Initial Harvest Cycle .............................................................................................. 16
3. Freeze Cycle ......................................................................................................... 16
4. Pump-Out Cycle ................................................................................................... 16
5. Normal Harvest Cycle ........................................................................................... 17
C. Control Board .............................................................................................................. 19
1. Control Board Layout ............................................................................................. 20
2. Features ................................................................................................................. 21
a) Maximum Water Supply Period – 6 minutes .................................................... 21
b) Harvest Backup Timer and Freeze Timer ......................................................... 21
c) High Temperature Safety .................................................................................. 21
d) Low Water Safety ............................................................................................. 21
e) High Voltage and Low Voltage Cut-outs ........................................................... 21
f) LED Lights and Audible Alarm Safeties ............................................................ 22
3. Controls and Adjustments ...................................................................................... 23
a) Default Dip Switch Settings .............................................................................. 23
b) Harvest Timer (S4 dip switch 1 & 2) ................................................................. 23
c) Pump-Out Timer (S4 dip switch 3 & 4) ............................................................. 24
d) Pump-Out Frequency Control (S4 dip switch 5 & 6)......................................... 24
e) S4 Dip Switch 7 & 8 ........................................................................................ 25
f) Freeze Timer (S4 dip switch 9 & 10) ................................................................. 25
g) Float Switch Control (S5 dip switch 1 through 5) ............................................. 25
4. Control Board Check Procedure ............................................................................ 25
5. Control Board Replacement ................................................................................ 26
D. Harvest Control – Thermistor ...................................................................................... 26
1. Thermistor Check Procedure .................................................................................. 26
E. Float Switch ................................................................................................................. 26
1. Float Switch Check Procedure ............................................................................... 26
2. Float Switch Cleaning ............................................................................................ 28
F. Bin Control ................................................................................................................... 29
1. Explanation of Operation ........................................................................................ 29
2. Bin Control Check Procedure................................................................................. 29
III. Technical Information ...................................................................................................... 30
A. Water Circuit and Refrigeration Circuit ........................................................................ 30
1. Air-Cooled Model .................................................................................................... 30
2. Water-Cooled Model .............................................................................................. 31
3. Remote Air-Cooled Model ...................................................................................... 32
B. Wiring Diagrams .......................................................................................................... 33
1a. KMD-850MAH Auxiliary Code C-0 and Earlier ................................................... 33
KMD-850MWH Auxiliary Code C-1 and Earlier .................................................... 33
1b. KMD-850MRH Auxiliary Code C-0 and Earlier .................................................... 34
2. KMD-850MAH and KMD-850MRH Auxiliary Code C-1 and Later ......................... 35
KMD-850MWH Auxiliary Code C-2 and Later ....................................................... 35
C. Performance Data ....................................................................................................... 36
1. KMD-850MAH (air-cooled) ..................................................................................... 36
2. KMD-850MWH (water-cooled) ............................................................................... 37
3. KMD-850MRH (remote air-cooled) ........................................................................ 38
IV. Service Diagnosis ........................................................................................................... 39
A. 10-Minute Diagnostic Procedure ................................................................................ 39
B. Diagnostic Charts ........................................................................................................ 41
1. No Ice Production ................................................................................................... 41
2. Evaporator is Frozen Up ........................................................................................ 44
3. Low Ice Production ................................................................................................ 45
4. Abnormal Ice ......................................................................................................... 46
5. Other ...................................................................................................................... 46
V. Refrigeration Circuit and Component Service Information............................................... 47
A. Refrigeration Circuit Service Information .................................................................... 47
1. Refrigerant Recovery ............................................................................................. 47
2. Brazing .................................................................................................................. 48
3. Evacuation and Recharge (R-404A) ...................................................................... 48
B. Component Service Information .................................................................................. 50
C. Adjustment of Water Regulating Valve - Water-Cooled Model Only ............................. 50
VI. Maintenance ................................................................................................................... 51
VII. Preparing the Icemaker for Long Storage ...................................................................... 52
VIII. Disposal ........................................................................................................................ 54
I. Specications

A. Icemaker

1. KMD-850MAH (air-cooled)

AC SUPPLY VOLTAGE 208-230/60/1 (3 wire with netrual for 115V) AMPERAGE 9.8 A ( 5 Min. Freeze AT 104°F / WT 80°F) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A APPROXIMATE ICE PRODUCTION Ambient WATER TEMP. (°F) PER 24 HR. Temp.(°F) 50 70 90 lbs./day ( kg/day ) 70 *786 (357) 743 (337) 685 (311) Reference without *marks 80 753 (342) 686 (311) 629 (285)
90 743 (337) *639 (290) 580 (263)
100 732 (332) 625 (284) 526 (239) SHAPE OF ICE Crescent Cube ICE PRODUCTION PER CYCLE 11.8 lbs. (5.4 kg) 624pcs. APPROXIMATE STORAGE CAPACITY N/A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 1570(5.9) 1510(4.6) WATER gal./24HR (gal./100 lbs.) 125(19.5) 291(37.0) CEC/CEE TIER LEVEL 1 ENERGY STAR NO EXTERIOR DIMENSIONS (WxDxH) 30" x 24-5/8" x 28" (762 x 625 x 713 mm) EXTERIOR FINISH Stainless Steel, Galvanized Steel (Rear) WEIGHT Net 217 lbs. (98 kg), Shipping 249 lbs. (113 kg) CONNECTIONS - ELECTRIC Permanent - Connection
- WATER SUPPLY Inlet 1/2" FPT
- DRAIN Outlet 3/4" FPT
5/8" OD Tube CUBE CONTROL SYSTEM Float Switch HARVESTING CONTROL SYSTEM Hot Gas and Water, Thermistor and Timer ICE MAKING WATER CONTROL Timer Controlled. Overflow Pipe COOLING WATER CONTROL N/A BIN CONTROL SYSTEM Mechanical Lever Switch and Timer COMPRESSOR Hermetic, Model CS08KQE-PFV-255 CONDENSER Air-Cooled , Fin and tube type EVAPORATOR Vertical type, Stainless Steel and Copper REFRIGERANT CONTROL Thermostatic Expansion Valve REFRIGERANT CHARGE R404A, 2 lb. 8.2 oz. (1140g) DESIGN PRESSURE High 467PSIG, Low 230PSIG P.C. BOARD CIRCUIT PROTECTION High Voltage Cut-out ( Internal ) COMPRESSOR PROTECTION Auto-reset Overload Protector ( Internal ) REFRIGERANT CIRCUIT PROTECTION Auto-reset High Pressure Control Switch LOW WATER PROTECTION Float Switch ACCESSORIES -SUPPLIED N/A
-REQUIRED Ice Dispenser or Ice Storage Bin OPERATING CONDITIONS VOLTAGE RANGE 187 - 253 V
AMBIENT TEMP. 45 -100° F WATER SUPPLY TEMP. 45 - 90° F
WATER SUPPLY PRESSURE 10 - 113 PSIG
Note: We reserve the right to make changes in specications and design without prior
notice.

2. KMD-850MWH (water-cooled)

AC SUPPLY VOLTAGE 208-230/60/1 (3 wire with netrual for 115V) AMPERAGE 8.3A ( 5 Min. Freeze AT 104°F / WT 80°F) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A APPROXIMATE ICE PRODUCTION Ambient WATER TEMP. (°F) PER 24 HR. Temp.(°F) 50 70 90 lbs./day ( kg/day ) 70 *836 (379) 830 (376) 786 (357) Reference without *marks 80 831 (377) 822 (373) 759 (344)
90 830 (376) *815 (370) 759 (344)
100 809 (367) 802 (364) 708 (321) SHAPE OF ICE Crescent Cube ICE PRODUCTION PER CYCLE 12.1 lbs. (5.5 kg) 624pcs. APPROXIMATE STORAGE CAPACITY N/A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 1390(4.1) 1390(4.0) WATER gal./24HR (gal./100 lbs.) 165(20.2) 298(35.7) WATER COOLED CONDENSER 1035(127) 565(68)
gal./24HR (gal./100 lbs.) CEC/CEE TIER LEVEL 2 ENERGY STAR N/A EXTERIOR DIMENSIONS (WxDxH) 30" x 24-5/8" x 28" (762 x 625 x 713 mm) EXTERIOR FINISH Stainless Steel, Galvanized Steel (Rear) WEIGHT Net 217 lbs. (98 kg), Shipping 249 lbs. (113 kg) CONNECTIONS - ELECTRIC Permanent - Connection
- WATER SUPPLY Inlet 1/2" FPT Cond. Inlet 1/2" FPT
- DRAIN Outlet 3/4" FPT Cond. Outlet 3/8" FPT
5/8" OD Tube CUBE CONTROL SYSTEM Float Switch HARVESTING CONTROL SYSTEM Hot Gas and Water, Thermistor and Timer ICE MAKING WATER CONTROL Timer Controlled. Overflow Pipe COOLING WATER CONTROL Pressure Regulator BIN CONTROL SYSTEM Mechanical Lever Switch and Timer COMPRESSOR Hermetic, Model CS08KQE-PFV-255 CONDENSER Water-cooled, Tube in tube type EVAPORATOR Vertical type, Stainless Steel and Copper REFRIGERANT CONTROL Thermostatic Expansion Valve REFRIGERANT CHARGE R404A, 1 lb. 12.6 oz. (810g) DESIGN PRESSURE High 427PSIG, Low 230PSIG P.C. BOARD CIRCUIT PROTECTION High Voltage Cut-out ( Internal ) COMPRESSOR PROTECTION Auto-reset Overload Protector ( Internal ) REFRIGERANT CIRCUIT PROTECTION Auto-reset High Pressure Control Switch LOW WATER PROTECTION Float Switch ACCESSORIES -SUPPLIED N/A
-REQUIRED Ice Dispenser or Ice Storage Bin OPERATING CONDITIONS VOLTAGE RANGE 187 - 253 V
AMBIENT TEMP. 45 -100° F WATER SUPPLY TEMP. 45 - 90° F WATER SUPPLY PRESSURE 10 - 113 PSIG
Note: We reserve the right to make changes in specications and design without prior
notice.

3. KMD-850MRH (remote air-cooled)

AC SUPPLY VOLTAGE 208-230/60/1 (3 wire with netrual for 115V) AMPERAGE 9.8A ( 5 Min. Freeze AT 104°F / WT 80°F) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A APPROXIMATE ICE PRODUCTION Ambient WATER TEMP. (°F) PER 24 HR. Temp.(°F) 50 70 90 lbs./day ( kg/day ) 70 *833 (378) 793 (360) 738 (335) Reference without *marks 80 803 (364) 741 (336) 686 (311)
90 793 (360) *698 (317) 641 (291)
100 782 (355) 685 (311) 589 (267) SHAPE OF ICE Crescent Cube ICE PRODUCTION PER CYCLE 11.6 lbs. (5.3 kg) 624pcs. APPROXIMATE STORAGE CAPACITY N/A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 1570(5.4) 1490(4.3) WATER gal./24HR (gal./100 lbs.) 136(19.5) 280(33.6) CEC/CEE TIER LEVEL 2 ENERGY STAR YES EXTERIOR DIMENSIONS (WxDxH) 30" x 24-5/8" x 28" (762 x 625 x 713 mm) EXTERIOR FINISH Stainless Steel, Galvanized Steel (Rear) WEIGHT Net 203 lbs. (92 kg), Shipping 235 lbs. (107 kg) CONNECTIONS - ELECTRIC Permanent - Connection
- WATER SUPPLY Inlet 1/2" FPT
- DRAIN Outlet 3/4" FPT
5/8" OD Tube CUBE CONTROL SYSTEM Float Switch HARVESTING CONTROL SYSTEM Hot Gas and Water, Thermistor and Timer ICE MAKING WATER CONTROL Timer Controlled. Overflow Pipe COOLING WATER CONTROL N/A BIN CONTROL SYSTEM Mechanical Lever Switch and Timer COMPRESSOR Hermetic, Model CS08KQE-PFV-255 CONDENSER Air-Cooled Remote, Condenser Unit URC-9F EVAPORATOR Vertical type, Stainless Steel and Copper REFRIGERANT CONTROL Thermostatic Expansion Valve
Condensing Pressure Regulator on URC-9F
REFRIGERANT CHARGE R404A, 9 lbs. 4.2 oz. (4200g)
(Icemaker 5 lbs. 5.4 oz. Cond. Unit 3 lbs. 14.8 oz.) DESIGN PRESSURE High 467PSIG, Low 230PSIG P.C. BOARD CIRCUIT PROTECTION High Voltage Cut-out ( Internal ) COMPRESSOR PROTECTION Auto-reset Overload Protector ( Internal ) REFRIGERANT CIRCUIT PROTECTION Auto-reset High Pressure Control Switch LOW WATER PROTECTION Float Switch ACCESSORIES -SUPPLIED N/A
-REQUIRED Ice Dispenser or Ice Storage Bin, Remote Condenser Unit OPERATING CONDITIONS VOLTAGE RANGE 187 - 253 V
AMBIENT TEMP. 45 -100° F
WATER SUPPLY TEMP. 45 - 90° F
WATER SUPPLY PRESSURE 10 - 113 PSIG
Note: We reserve the right to make changes in specications and design without prior
notice.

B. Condenser Unit

1. URC-9F

Unit: mm [inches]
Specications
MODEL: URC-9F
AC SUPPLY VOLTAGE 115/60/1 (Connection to Icemaker)
FAN MOTOR 115 V Total 1.3FLA 65W
EXTERIOR DIMENSIONS (WxDxH) 32-3/16" x 15-11/16" x 21-15/16" (817 x 398 x 558 mm)
DIMENSIONS INCLUDING LEGS (WxDxH) 34-5/16" x 18-1/8" x 36-15/16" (871 x 460 x 938 mm)
EXTERIOR FINISH Galvanized Steel
WEIGHT Net 81 lbs. ( 37 kg ) Shipping 92 lbs. ( 42 kg )
CONNECTIONS - ELECTRIC Permanent - Connection
- REFRIGERANT Discharge Line 1-1/16"-12 UNF Fitting (#10 AEROQUIP)
Liquid Line 5/8"-18 UNF Fitting (#6 AEROQUIP)
CONDENSER Air-cooled, Fin and tube type
FAN MOTOR PROTECTION Thermal Protection
REFRIGERANT CONTROL Condensing Pressure Regulator
REFRIGERANT CHARGE R-404A 3 lbs. 14.8 oz. (1780g)
DESIGN PRESSURE High 467 PSIG
OPERATING CONDITIONS VOLTAGE RANGE 104 ~ 127 V
AMBIENT TEMP. -20 ~ 122 °F
ACCESSORIES -SUPPLIED Leg 2 pcs
Hex. Head Bolt w/Washer 8 x 16 8 pcs
Hex. Nut 8 8 pcs
Note: We reserve the right to make changes in specications and design without prior
notice.

II. General Information

A. Construction

1a. Air-Cooled Auxiliary Code C-0 and Earlier

Spray Tubes
Inlet Water Valve
Water Supply Inlet
Hot Gas Valve
Junction Box
Condenser
Control Box
Float Switch
Drain Valve
Thermostatic Expansion Valves
Water Pump
Cleaning Valve
Bin Control
Condenser Fan Motor
Control Switch
Drier
Compressor
10

1b. Air-Cooled Auxiliary Code C-1 and Later

Spray Tubes
Thermostatic Expansion Valves
Inlet Water Valve
Water Supply Inlet
Hot Gas Valve
Junction Box
Condenser
Control Box
Float Switch
Drain Valve
Cleaning Valve
Condenser Fan Motor
Main Transformer
Drier
Control Switch
Water Pump
Compressor
Bin Control
11
2a. Water-Cooled Auxiliary Code C-1 and Earlier
Spray Tubes
Inlet Water Valve
Water Supply Inlet
Hot Gas Valve
Junction Box
Condenser
Control Box
Water Regulator
Float Switch
Drain Valve
Control Switch
Drier
Compressor
Water Pump
Cleaning Valve
Thermostatic Expansion Valves
Bin Control
12
2b. Water-Cooled Auxiliary Code C-2 and Later
Spray Tubes
Thermostatic Expansion Valves
Inlet Water Valve
Water Supply Inlet
Hot Gas Valve
Junction Box
Water Regulator
Condenser
Control Box
Float Switch
Drain Valve
Water Pump
Cleaning Valve
Control Switch
Bin Control
Main Transformer
Drier
Compressor
13

3a. Remote Air-Cooled Auxiliary Code C-0 and Earlier

Spray Tubes
Inlet Water Valve
Water Supply Inlet
Hot Gas Valve
Junction Boxes
Control Box
Receiver Tank
Control Switch
Float Switch
Drain Valve
Water Pump
Drier
Liquid Line Valve
Compressor
Cleaning Valve
Thermostatic Expansion Valves
Bin Control
14

3b. Remote Air-Cooled Auxiliary Code C-1 and Later

Spray Tubes
Inlet Water Valve
Water Supply Inlet
Hot Gas Valve
Main Transformer
Junction Boxes
Control Box
Receiver Tank
Float Switch
Drain Valve
Water Pump
Cleaning Valve
Thermostatic Expansion Valves
Bin Control
Control Switch
Drier
Liquid Line Valve
Compressor
15

B. Sequence of Operation

The steps in the sequence are as outlined below. When power is supplied, the red "POWER OK" LED and the green "BC CLOSED" LED on the control board come on (If the yellow "BC OPEN" LED is on, the unit will not start. In this case clear ice away from the bin control actuator). A 5-second delay occurs at startup. Note that the order of the green sequence LEDs from the outer edge of the board is 1, 4, 3, 2.

1. One Minute Fill Cycle

LED 4 is on. WV opens and the ll period begins. After 1 minute, the board checks for a closed F/S. If F/S is closed, the harvest cycle begins. If not, WV will remain energized through additional 1 minute cycles until water enters the sump and F/S closes. This serves as a low water safety to protect the water pump.

2. Initial Harvest Cycle

LEDs 1, 4, and 2 are on. WV remains open, Comp, FMR, HGV energize. The control board monitors the warming of the evaporator via the thermistor located on the suction line. When the thermistor reaches 48°F (9°C), the control board reads a 3.9 kΩ signal from the thermistor and turns harvest termination over to the adjustable harvest timer which is factory set for normal conditions. The timer has settings of 60, 90, 120, and 180 seconds (S4 dip switch 1 & 2). For details, see "II.C.3.b) Harvest Timer." When the harvest timer completes its countdown, the harvest cycle is complete and the freeze cycle starts. The minimum total time allowed by the board for a complete harvest cycle is 2 minutes. WV is open during harvest for a maximum of 6 minutes or the length of harvest minus 50 seconds, whichever is shorter. LED 4 goes off when WV closes. PM energizes and runs for the last 50 seconds of harvest. LED 3 comes on when PM energizes. At the end of harvest, the control board checks the position of F/S and proceeds to the freeze cycle if it is closed or calls for a 1-minute ll if it is open.

3. Freeze Cycle

LED 1 is on. Comp, FMR, and PM continue to run, FMS energizes, LLV opens, HGV closes and the freeze cycle starts. For the rst 5 minutes the control board will not accept a signal from F/S. This 5 minute minimum freeze acts as a short cycle protection. At the end of 5 minutes, F/S assumes control. As ice builds on the evaporator the water level in the sump lowers. The freeze continues until F/S opens and terminates ice production.

4. Pump-Out Cycle

LEDs 1, 4, 3, and 2 are on. With S4 dip switch 5 and 6 in the factory default position, the 1st pump out occurs after the 11th freeze cycle and every 10th cycle thereafter. Comp and FMR continue to run, DV and WV open, HGV opens, LLV closes, and FMS de­energizes. PM stops for 2 seconds. SR energizes, restarting PM and taking water from the sump and forcing it to go through DV and down the drain. At the same time, water ows through the vent tube to power ush the F/S. After 10 seconds, the pump out is complete. The pump-out frequency control is factory-adjusted to drain the water tank every 10 cycles, and no adjustment is required. However, where water quality is bad and the icemaker needs a pump out more often, the pump-out frequency can be adjusted. The pump-out frequency control can be set to have a pump out occur every cycle, or every 2, 5, or 10 cycles (S4 dip switch 5 & 6). For details, see "II.C.3.d) Pump-Out Frequency Control."
16

5. Normal Harvest Cycle

LEDs 1, 4, and 2 are on. Comp, FMR, and HGV remain energized and WV opens. PM stops. As the evaporator warms, the thermistor reaches 48°F (9°C). The control board then receives the thermistor's 3.9 kΩ signal and starts the harvest timer. When the harvest timer completes its countdown, the harvest cycle is complete. The minimum total time allowed by the board for a complete harvest cycle is 2 minutes. WV is energized during harvest for a maximum of 6 minutes or the length of harvest minus 50 seconds, whichever is shorter. LED 4 goes off when WV closes. PM energizes and runs for the last 50 seconds of harvest. LED 3 comes on when PM energizes. At the end of harvest, the control board checks the position of F/S and proceeds to the freeze cycle if it is closed or calls for a 1-minute ll if it is open. The unit continues to cycle through freeze and harvest cycles until the bin control activates (opens) and shuts the unit down.
Note: To prevent incomplete batches of ice from forming on the evaporator, the control
board will only shut down the machine within the rst 5 minutes of the freeze cycle. If ice pushes the bin control actuator in (open) after the rst ve minutes of the freeze cycle, the control board will allow the machine to complete the freeze cycle and the following harvest cycle before shutting down the machine.
Legend: Comp–compressor; DV–Drain Valve; FMR–remote fan motor; FMS–self-contained fan motor; F/S–oat switch; HGV–hot gas valve; LLV–liquid line valve; PM–pump motor; SR–service relay; WV–inlet water valve
17