Only qualified service technicians should attempt to service or maintain this icemaker.
No service or maintenance should be undertaken until the technician has thoroughly
read this Service Manual.
HOSHIZAKI provides this manual primarily to assist qualified service technicians in the
service and maintenance of the icemaker.
Should the reader have any questions or concerns which have not been satisfactorily
addressed, please call or write to the HOSHIZAKI Technical Support Department for
assistance.
HOSHIZAKI AMERICA, INC.
618 Highway 74 South
Peachtree City, GA 30269
Attn: HOSHIZAKI Technical Support Department
Phone: 1-800-233-1940 Technical Service
(770) 487-2331
Fax:(770) 487-3360
NOTE: To expedite assistance, all correspondence/communication MUST include the
following information:
•Model Number
•Serial Number
•Complete and detailed explanation of the problem
2
Please review this manual. It should be read carefully before the icemaker is serviced
or maintenance operations are performed. Only qualified service technicians should
service and maintain the icemaker. This manual should be made available to the
technician prior to service or maintenance.
CONTENTS
PAGE
I. SPECIFICATIONS .................................................................................................... 5
AC SUPPLY VOLTAGE208/230/60/1 ( 3 wire with neutral for 115V )
AMPERAGE11 A ( 5 Min. Freeze AT 104°F / WT 80°F)
MINIMUM CI RCUIT AMPACITY20 A
MAXIMUM FUSE SIZE20 A
APPROXIMATE ICE PRODUCTIONAmbientW ATER TEMP. (°F)
PER 24 HR.Temp.(°F)507090
lbs./ day ( kg/day )70*838 (380)804 (365)759 (344)
Reference without *marks80812 (368)759 (344)715 (324)
90804 (365)*721 (327)676 (306)
100795 (361)710 (322)634 (288)
SHAPE OF ICECresc ent Cube
ICE P RODUCTION PER CYCLE14.3 lbs. ( 6.5 kg ) 720 pcs.
APPROXIMATE STORAGE CAPACITYN/A
ELECTRIC & WATER CONSUMPTION90/70° F70/50° F
ELECTRIC W (kWH/100 lbs.)1965 (6.6)1783 (5.1)
WATER gal./24HR (gal./100 lbs.)244 (31.5)472 (56.3)
EXTERIOR DIMENSIONS (WxDxH)30" x 27-3/8" x 37-7/16" (762 x 695 x 950 mm)
EXTERIOR FINISHStainless Steel, Galvanized Steel (Rear)
WEIGHTNet 216 lbs. ( 98 kg ), S hipping 282 lbs. (128 kg)
CONNECTIONS - ELECTRICPermanent - Connection
- WATER SUPPLYInlet 1/2" FPT
- DRAINOutlet 3/4" FPT
3/8" OD Pipe
CUBE CONTROL SYSTEMFloat Switch
HARVESTING CONTROL SYSTEMHot Gas and W ater, Thermistor and Timer
ICE MAKI NG WATER CONTROLTimer Controlled. Overflow Pipe
COOLING WATER CONTROLN/A
BIN CONTROL SYSTEMProximity Switch with Delay
COMPRESSORHermetic, Model CS14K6E-PFV
CONDENSERAir-cooled, Fin and tube ty pe
EVAPORATORVertical type, Stainless Steel and Copper
REFRIGERANT CONTROLThermostatic Expansion Valve
REFRIGERANT CHARGER-404A,3 lb. 7 oz. ( 1550 g )
DESI GN PRESSUREHigh 467 PSIG, Low 230 PSIG
P.C. BOARD CI RCUIT PROTECTIONHigh Voltage Cut-out ( Internal )
COMPRESSOR PROTECTIONAuto-r eset Overload Protector ( Internal )
REFRIGERANT CIRCUIT PROTECTIONAuto-reset High Pressure Control Switch
LOW WATER PROTECTIONFloat Switch
ACCESSORIES -SUPPLIEDN/A
-REQUIREDIce Storage Bi n
OPERATING CONDITIONSVOLTAGE RANGE187 - 253 V
AMBIENT TEMP.45 -100° F
W ATER SUPPLY TEMP.45 - 90° F
WATER SUPPLY PRESSURE10 - 113 PSIG
We reserve the right to make changes in specifications and design without prior notice.
5
2a. KM-900MWH
AC SUPPLY VOLTAGE208-230/60/1 (3 wire with neutral for 115 V)
AMPERAGE10.2 A
MI NIMUM CIRCUIT AMPACITY15 A
MAXIMUM FUSE SIZE15 A
APPROXIMATE ICE PRODUCTIONAmbientW ATER TEMP. (°F)
PER 24 HR.Temp. (°F )5 07090
lbs./day ( kg/ day )70*853 (387)836 (379)787 (357)
Reference without *marks80840 (381)813 (369)750 (340)
90836 (379)794 (360)736 (334)
100818 (371)780 (354)683 (310)
SHAPE OF ICECresc ent Cube
ICE P RODUCTION PER CYCLE14.3 lbs. ( 6.5 kg ) 720 pcs.
APPROXIMATE STORAGE CAPACITYN/A
ELECTRIC & WATER CONSUMPTION90/70° F70/50° F
ELECTRIC W (kWH/100 lbs.)1775 (5. 3)1768 (5. 0)
WA TER gal./24HR (gal. /100 lbs.)256 (32.2)409 (47. 9)
WA TER COOLED CONDENSER1024 (129)580 (68)
gal./24HR (gal./100 lbs. )
EXTERIOR DIMENSIONS (WxDxH)30" x 27- 3/8" x 37 7/16" ( 762 x 695 x 950 mm)
EXTERIOR FINISHStainless Steel, Galvanized Steel (Rear)
W E IGHTNet 211 lbs. ( 96 kg ), Shipping 277 lbs. ( 126 kg )
CONNECTIONS - ELECTRICPermanent - Connec ti on
- WATER SUPPLYInlet 1/ 2" FPTCondenser Inlet 1/2" FPT
- DRAINOutlet 3/ 4" FPTCondenser Outlet 3/8" FPT
3/8" OD Pi pe
CUBE CONTROL SYSTEMFloat Switch
HARVESTING CONTROL SYSTEMHot Gas and Water, Thermistor and Timer
ICE MAKI NG WATER CONTROLTimer Controlled. Overflow Pipe
COOLING WATER CONTROLPressure Regulator
BIN CONTROL SYSTEMPr oximity Switch with Delay
COMPRESSORHermetic, Model CS14K6E-PFV
CONDENSERW ater-c ooled, Tube in tube type
EVAPORATORVerti cal type, Stainless Steel and Copper
REFRIGERANT CONTROLThermostatic Expansion Valve
REFRIGERANT CHARGER-404A,1 lb 7 oz. ( 650 g )
DESIGN PRESSUREHigh 427 PSIG, Low 230 PSIG
P.C. BOARD CIRCUIT PROTECTIONHigh Voltage Cut-out ( Internal )
COMPRESSOR PROTECTIONAuto-r eset Overload Protector ( Internal )
REFRIGERANT CIRCUIT PROTECTIONAuto-reset High Pressure Control Switch
LOW WATER PROTECTIONFloat Switch
ACCESSORIES -S UPPLIEDN/A
-REQUIREDIce Storage Bin
OPERATING CONDITIONSVOLTAGE RANGE187 - 253 V
AMBIENT TEMP.45 -100° F
W A TER SUPPLY TEMP.45 - 90° F
W A TER SUPPLY PRESSURE10 - 113 PSIG
Beginni ng S erial No. L00001D
Ending Serial No. M20500D
We reserve the right to make changes in specifications and design without prior notice.
6
2b. KM-900MWH
Beginning Seri al No. M30501D
AC SUPPLY VOLTAGE208-230/60/ 1 (3 wire with neutral for 115V)
AMPERAGE10.2 A ( 5 Min. Fr eeze AT 104°F / WT 80°F)
MI NIMUM CIRCUIT AMP ACITY15 A
MAXIMUM FUSE SIZE15 A
APPROXIMATE ICE PRODUCTIONAmbientW ATER TEMP. (°F)
PER 24 HR.Temp. (°F )50709 0
lbs./day ( kg/day )70*846 (384)830 (376)787 (357)
Reference without *marks80833 (378)808 (367)754 (342)
90830 (376)*790 (358)740 (336)
100814 (369)778 (353)694 (315)
SHAPE OF ICECresc ent Cube
ICE PRODUCTION PER CYCLE14.3 lbs. ( 6.5 kg ) 720 pcs.
APPROXIMATE STORAGE C APACITYN/A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W ( kWH/100 lbs.)1700 (5.2)1692 (4.8)
W A TER gal./24HR (gal./100 lbs.)269 ( 34.0)418 (49.4)
W A TER COOLED CONDENSER916 (116)491 (58)
gal./24HR (gal./ 100 lbs. )
EXTERIOR DIMENSI ONS (WxDxH)30" x 27-3/8" x 37 7/16" (762 x 695 x 950 mm)
EXTERIOR FINISHStainless Steel, Galvanized Steel (Rear)
WEIGHTNet 211 lbs. ( 96 kg ), S hipping 277 lbs. ( 126 kg )
CONNECTIONS - ELECTRICPermanent - Connection
- WATER SUPPLYInlet 1/2" FPTCondenser Inlet 1/2" FPT
- DRAINOutlet 3/4" FPTCondenser Outlet 3/8" FPT
3/8" OD Pi pe
CUBE CONTROL SYSTEMFloat Switch
HARVESTING C ONTROL SYSTEMHot Gas and W ater , Thermistor and Timer
ICE MAKI NG WATER CONTROLTimer Controlled. Overflow Pipe
COOLING WATER CONTROLPressure Regulator
BIN CONTROL SYSTEMProximity Switch with Delay
COMPRESSORHermetic , Model CS14K6E-PFV-237
CONDENSERW ater-cooled, Tube in tube type
EVAPORATORVerti cal type, Stai nless Steel and Copper
REFRIGERANT CONTROLThermostatic Expansion Valve
REFRIGERANT CHARGER-404A,1 lb. 14 oz. ( 850 g )
DESI GN PRESSUREHigh 427 PSIG, Low 230 PSIG
P.C. BOARD CIRCUIT PROTECTIONHigh Voltage Cut-out ( I nternal )
COMPRESSOR PROTECTIONAuto-reset Overload Protector ( Internal )
REFRIGERANT CIRCUIT PROTECTIONAuto-reset High Pressure Control Switch
LOW WATER PROTECTIONFloat Switch
ACCESSORIES - SUPPLIEDN/A
-REQUIREDIce Storage Bin
OPERATING CONDITIONSVOLTAGE RANGE187- 253 V
AMBIENT TEMP.45 -100° F
W ATER SUPPLY TEMP.45 - 90° F
W A TER SUPPLY PRESSURE10 - 113 PSIG
We reserve the right to make changes in specifications and design without prior notice.
7
3. KM-900MRH
AC SUP PLY V OLTAGE208-230/60/ 1 (3 wire wi t h neutral for 115V)
AMPERAGE12.5 A ( 5 Mi n. Freeze A T 104°F / WT 80°F)
MINIMUM CIRCUIT AM PACITY20 A
MAXIMUM FUSE SIZE20 A
APPROXIMATE ICE PRODUCTIONAmbientWATER TEMP. (°F)
PER 24 HR.Tem p.(°F )507090
lbs ./day ( kg/ day )70*835 (379)817 (370)786 (356)
Reference without *mark s80821 (372)792 (359)758 (344)
90817 (370)*772 (350)739 (335)
100808 (367)764 (347)708 (321)
SHAPE OF ICECrescent Cube
ICE P RO DUCTION P ER CYCLE14. 3 l b s. ( 6.5 kg ) 720 pcs.
APPROXIMATE STORAGE CAPACITYN/A
ELE CTRIC & WATER CONSUMPTION90/70°F70/50°F
ELE CTRIC W (kW H/ 100 l bs.)2060 (6.4)2005 (6.0)
W A TER gal./24HR (gal. /100 lbs.)255 (33.0)450 (53.9)
EXTERIOR DIMENS IONS (Wx Dx H)30" x 27-3/8" x 37-7/16" (762 x 695 x 950 mm)
EXTERIOR FINISHSt ai nl ess Steel, Galvanized St eel (Rear)
W E IGHTNet 216 lbs. ( 98 kg ), S hi pping 282 l bs. ( 128 kg )
CONNECTIONS - ELECTRICP erm anent - Connecti on
- WATER SUPPLYInlet 1/2" FPT
- DRAINOutlet 3/4" FPT
3/8" OD Pipe
CUBE CONTROL SYSTEMFloat Switch
HARVESTING CONTROL SYSTEMHot Gas and Water, Thermistor and Timer
ICE MAKING WA TER CONTROLTimer Controlled. Overflow Pipe
COOLING WA TER CO NTROLN/A
BIN CONTROL SYSTEMProximity Switch with Delay
COMPRESSORHermetic, Model CS14K6E-PFV
CONDENSERA i r-cooled Remot e, Condenser Unit URC 12F
EVAPORATORVertical type, Stainless Steel and Copper
REFRIGERA NT CONTROLThermos t atic E xpansi on V al ve
Condensin g Pressu re Re gu l a tor on URC-12 F
REFRIGERA NT CHARGER-404A,9 lbs. 14 oz. ( 4500 g )
( Icemaker 5 lbs. 8 oz. Cond. Unit 4 l b. 6 oz. )
DESIGN PRE SSUREHigh 467 PSIG, Low 230 P S IG
P.C. BOARD CIRCUIT PROTE CTIONHi gh Voltage Cut-out ( Inte rna l )
COMPRESSOR PROTECTIONAuto-reset Overload Protector ( Internal )
REF RIGERANT CIRCUIT PROTECTIONA uto-reset High P ressure Control Switch
LOW WATER PROTECTIONFloat Switch
ACCESSORIES -SUPPLIEDN/A
-REQUIREDIc e Storage B i n, Rem ote Condenser Unit
OPE RA TING CONDITIONSVOLTAGE RA NGE187 - 253 V
AM B IE NT TEM P .45 -100° F
W A TER SUPPLY TEMP .45 - 90° F
WATER SUPPLY PRESSURE10 - 113 PSIG
We reserve the right to make changes in specifications and design without prior notice.
8
4. KM-900MRH3
AC SUPPLY VOLTAGE208-230/60/3
AMPERAGE6.5 A ( 5 Min. Fr eeze AT 104°F / WT 80°F)
MINIMUM CI RCUIT AMPACITY20 A
MAXIMUM FUSE SIZE20 A
APPROX IMATE ICE PRODUCTIONAmbientWATER TEMP. (° F)
PER 24 HR.Temp.(°F)507090
lbs./ day ( kg/day )70*842 (382)826 (375)784 (356)
Reference without *marks80830 (377)806 (366)753 (341)
90826 (375)*789 (358)739 (335)
100811 (368)777 ( 353)694 (315)
SHAPE OF ICECresc ent Cube
ICE P RODUCTION PER CYCLE14.3 lbs. (6.5 kg ) 720 pcs.
APPROXIMATE STORAGE CAPACITYN/A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs. )2070 (6.3)2000 (5.7)
WATER gal./24HR (gal./100 lbs.)264 (33.4)454 (53.9)
EXTERIOR DIMENSIONS (WxDxH)30" x 27-3/8" x 37-7/16" (762 x 695 x 950 mm)
EXTERIOR FINISHStainless Steel, Galvanized Steel (Rear)
WEIGHTNet 216 lbs. ( 98 kg ), S hipping 282 lbs. ( 128 kg )
CONNECTIONS - ELECTRICPermanent - Connection
- WATER SUPPLYInlet 1/2" FPT
- DRAINOutlet 3/4" FPT
3/8" OD Pipe
CUBE CONTROL SYSTEMFloat Switch
HARVESTING CONTROL SYSTEMHot Gas and W ater , Thermistor and Timer
ICE MAKI NG WATER CONTROLTimer Controlled. Overflow Pipe
COOLING WATER CONTROLN/A
BIN CONTROL SYSTEMProximity Switch with Delay
COMPRESSORHermetic, Model CS14K6E-TF5
CONDENSERAir-cooled Remote, Condenser Unit URC 12F
EVAPORATORVertical type, Stainless Steel and Copper
REFRIGERANT CONTROLThermostatic Expansion Valve
Condensing Pressure Regulator on URC-12F
REFRIGERANT CHARGER-404A,9 lbs. 14 oz. ( 4500 g )
( Icemaker 5 lbs. 8 oz. Cond. Unit 4 lb. 6 oz. )
DESI GN PRESSUREHigh 467 PSIG, Low 230 PSIG
P.C. BOARD CI RCUIT PROTECTIONHigh Voltage Cut-out ( Internal )
COMPRESSOR PROTECTIONAuto-reset Overload Pr otector ( Internal )
REFRIGERANT CIRCUIT PROTECTIONAuto-reset High Pressure Control Switch
LOW WATER PROTECTIONFloat Switch
ACCESSORIES -SUPPLIEDN/A
-REQUIREDIce Storage Bi n, Remote Condenser Unit
OPERATING CONDITIONSVOLTAGE RANGE187 - 253 V
AMBIENT TEMP.45 -100° F
W ATER SUPPLY TEMP.45 - 90° F
WATER SUPPLY PRESSURE10 - 113 PSIG
We reserve the right to make changes in specifications and design without prior notice.
9
5. CONDENSING UNIT
URC-12F
10
MODEL: URC-12F
SPECIFICATIONS
EXTERIOR
DIMENSIONS (W x D x H)
REFRIGERANT CHARGE
URC-12F
WEIGHT
CONNECTIONS
REFRIGERANT
ELECTRICAL
CONDENSER
HEAD PRESSURE CONTROL
AMBIENT CONDITION
Galvanized Steel
35 - 11/16” x 15-11/16” x 21-15/16”
(907.2 x 398 x 557.8 mm)
R404A 4 lbs. 7 oz. (2000 g)
Net 80 lbs. (36 kg)
Shipping 87 lbs. (39 kg)
One Shot Couplings (Aeroquip)
Permanent Connection
Air-cooled
Condensing Pressure Regulator
Min. -20°F - Max. +122°F
(-29°C to +50°C)
Outdoor use
11
II. GENERAL INFORMATION
1. CONSTRUCTION
[a] KM-900MAH
Models with Thermostat
Models with Mechanical Bin Control
12
[b] KM-900MWH
Models with Thermostat
Models with Mechanical Bin Control
13
[c] KM-900MRH
Models with Thermostat
Models with Mechanical Bin Control
14
[d] KM-900MRH3
Models with Thermostat
Models with Mechanical Bin Control
15
2. CONTROLLER BOARD
[a] SOLID-STATE CONTROL
1) A HOSHIZAKI exclusive solid-state control is employed in KM-900MAH,
KM-900MWH, KM-900MRH and KM-900MRH3 Modular Crescent Cubers.
2) A Printed Circuit Board (hereafter called “Controller Board”) includes a stable and
high quality control system.
3) All models are pretested and factory-adjusted.
[b] CONTROLLER BOARD
CAUTION
1. Fragile, handle very carefully.
2. A controller board contains integrated circuits, which are susceptible to
failure due to static discharge. It is especially important to touch the
metal part of the unit when handling or replacing the board.
3. Do not touch the electronic devices on the board or the back of the
board to prevent damage to the board.
4. Do not change wiring and connections. Do not misconnect K3, K4 and
K5, because the same connector is used for the Thermistor (white),
Float Switch (black), and Mechanical Bin Control (red).
(For machines with thermostat, there is no connection on K4.)
5. Always replace the whole board assembly when it goes bad.
6. Do not short out power supply to test for voltage.
PART NUMBERTYPE
2A1410-01 HOS-001A (Control Products)
Features of Control Products “E” Controller Board
1) Maximum Water Supply Period - 6 minutes
Water Solenoid Valve opening, in the Defrost (Harvest) Cycle, is limited by the defrost timer. The Water Valve cannot remain open longer than the maximum period.
The Water Valve can close in less than six minutes if the defrost cycle is completed.
16
2) Defrost Timer
The defrost cycle starts when the Float Switch opens and completes the freeze cycle.
But the Defrost Timer does not start counting until the Thermistor senses 48°F at the
Evaporator outlet. The period from the end of the freeze cycle up to the point of the
Thermistor's sensing varies depending on the ambient and water temperatures.
3) High Temperature Safety - 127 ± 7°F
The temperature of the suction line in the refrigerant circuit is limited by the High
Temperature Safety.
During the defrost cycle the Evaporator temperature rises. The Thermistor
senses 48°F and starts the Defrost Timer. After the Defrost Timer counts down
to zero, the normal freeze cycle begins. If the Evaporator temperature continues
to rise, the Thermistor will sense the rise in temperature and at 127 ± 7°F the
Thermistor operates the High Temperature Safety.
This High Temperature Safety shuts down the circuit and the icemaker automatically
stops.
This High Temperature Safety protects the unit from excessive temperature. The Control
Board will Beep every 3 seconds. The white Reset Button on the Control Board must be
pressed with power on to reset the Safety.
4) Low Water Safety
If the Pump Motor is operated without water, the mechanical seal can fail. To prevent
this type of failure, the Controller Board checks the position of the Float Switch at the end
of the initial one minute water fill cycle and at the end of each defrost cycle.
If the Float Switch is in the up position (electrical circuit closed), the Controller Board
changes to the ice making cycle. If the Float Switch is in the down position (electrical
circuit open), the Controller Board changes to a one minute water fill cycle before starting
the ice making cycle. This method allows for a Low Water Safety shut down to protect
the Water Pump from mechanical seal failure.
For water-cooled model, if the water is shut off, the unit is protected by the High Pressure
Switch.
5) High Voltage Cutout
The maximum allowable supply voltage of this icemaker is limited by the High Voltage Cutout.
If miswiring (especially on single phase 3 wire models) causes excessive voltage on the
Controller Board, the High Voltage Cutout shuts down the circuit in 3 seconds and the
icemaker automatically stops. When the proper supply voltage is resumed, the icemaker
automatically starts running again. The Control Board will signal this problem using 7 Beeps
every 3 seconds.
6) LED Lights and Audible Alarm Safeties
The red LED indicates proper control voltage and will remain on unless a control voltage
problem occurs. At startup a 5 second delay occurs while the board conducts an internal
timer check. A short beep occurs when the power switch is turned ON or OFF.
17
The green LED’s 1-4 represent the corresponding relays and energize and sequence 5
seconds from initial start-up as follows:
Sequence StepLED’s on Length:Min.Max.Avg.
1 Minute Fill CycleLED460 sec.
Harvest CycleLED1, 4, & 22 min.20 min.3-5 min.
Freeze CycleLED15 min.60 min.30-35 min.
Reverse Pump OutLED1, 3, & 210 sec.20 sec.Factory set.
{LED 1 – Comp; LED 2 - HGV/CFM; LED 3 – PM; LED 4 - WV}
The built in safeties shut down the unit and have alarms as follows:
1 beep every 3 sec. = High Evaporator Temperature >127 ° F.
Check for defrost problem (stuck HGV or relay), hot water entering unit, stuck
headmaster, or shorted thermistor.
2 beeps every 3 sec. = Defrost Back Up Timer. Defrost >20 minutes.
Orange LED marked 20 MIN energizes.
Check for open thermistor, HGV not opening, TXV leaking by, low charge, or inefficient
compressor.
3 beeps every 3 sec. = Freeze Back Up Timer. Freeze > 60 minutes.
Yellow LED marked 60 MIN energizes.
Check for F/S stuck closed (up), WV leaking by, HGV leaking by, TXV not feeding
properly, low charge, or inefficient compressor.
Machines
with
mechanical
bin control
ONLY
4 beeps every 3 sec. = Short Circuit between the K4 connection on
the control board and the bin control relay. Check connections and
replace wire harness if necessary.
5 beeps every 3 sec. = Open Circuit between the K4 connection
on the control board and the bin control relay. Check connections and
replace wire harness if necessary.
To manually reset the above safeties, depress white alarm reset button with the power
supply ON.
6 beeps every 3 sec. = Low Voltage. Voltage is 92 Vac or less.
7 beeps every 3 sec. = High Voltage. Control voltage > 147 Vac ±5%.
The red LED will de-energize if voltage protection operates.
The voltage safety automatically resets when voltage is corrected.
The Output Test switch “S3” provides a relay sequence test. With power OFF, place S3
ON and switch power to ICE. The correct lighting sequence should be none, 2, 3, 4, 1, &
4, normal sequence every 5 seconds. S3 should remain in the “OFF” position for normal
operation.
18
The application switch located between relay X3 & X4 must be set to match the original
board application. Place this switch in the ALP position if there is no white wire supplied
to the K1 connector. If there is a white wire, place the switch in the C position. If this
switch is placed in the wrong position, either the compressor contactor will remain energized with the control switch OFF, or the unit will not start.
The dip switches should be adjusted per the adjustment chart published in the Tech
Specs book. Number 8 must remain in the OFF position.
(Control Products HOS-001A Board)
19
[c] SEQUENCE
1st Cycle
1. Unit energized and Control Switch to “ICE”
position. Water supply cycle starts.
2. After 1 minute,
Defrost cycle starts.
3. Thermistor reads 48° F.
Defrost Timer starts counting.
5. After the first 5 minutes in freeze cycle.
Ready to complete freeze cycle when Float
Switch circuit opens.
IMPORTANT
Board never accepts freeze completion signal
within the first 5 minutes in freeze cycle.
IMPORTANT
Water Valve
opening is limited
to 6 minutes.
&
4. Defrost Timer stops counting.
Defrost cycle is completed and freeze cycle
starts.
IMPORTANT
1. Board never accepts defrost completion
signal within the first 2 minutes in defrost
cycle.
2. Defrost cycle time is limited to 20 minutes
even if Defrost Timer does not stop counting.
20
2nd Cycle and after with pump drain
IMPORTANT
Freeze cycle time is limited to 60 minutes even
if Float Switch does not open.
1. Float Switch opens and signals to complete
freeze cycle.
Drain timer starts counting.
&
2. Drain timer stops counting.
Pump drain is completed
3. Thermistor reads 48° F.
Defrost Timer starts
counting.
IMPORTANT
Water Valve
opening is limited to 6
minutes.
5. After the first 5 minutes in freeze cycle.
Ready to complete freeze cycle when Float
Switch circuit opens.
IMPORTANT
Board never accepts freeze completion signal
within the first 5 minutes in freeze cycle.
4. Defrost Timer stops counting.
Defrost cycle is completed and freeze cycle
starts.
IMPORTANT
1. Board never accepts defrost completion
signal within the first 2 minutes in defrost
cycle.
2. Defrost cycle time is limited to 20 minutes
even if Defrost Timer does not stop counting.
21
2nd Cycle and after with no pump drain
IMPORTANT
Freeze cycle time is limited to 60 minutes even
if Float Switch does not open.
1. Float Switch opens and signals to complete
freeze cycle.
&
2. Thermistor reads 48° F.
Defrost Timer starts counting.
IMPORTANT
Water Valve
opening is limited to 6
minutes.
4. After the first 5 minutes in freeze cycle.
Ready to complete freeze cycle when Float
Switch circuit opens.
IMPORTANT
Board never accepts freeze completion signal
within the first 5 minutes in freeze cycle.
3. Defrost Timer stops counting.
Defrost cycle is completed and freeze cycle
starts.
IMPORTANT
1. Board never accepts defrost completion
signal within the first 2 minutes in defrost
cycle.
2. Defrost cycle time is limited to 20 minutes
even if Defrost Timer does not stop counting.
22