MODULAR CRESCENT CUBER
KM-900MAF
KM-900MWF
KM-900MRF
KM-900MRF3
SERVICE MANUAL
IMPORTANT
Only qualified service technicians should attempt to service or maintain this icemaker. No service or maintenance should be undertaken until the technician has thoroughly read this Service Manual.
HOSHIZAKI provides this manual primarily to assist qualified service technicians in the service and maintenance of the icemaker.
Should the reader have any questions or concerns which have not been satisfactorily addressed, please call or write to the HOSHIZAKI Technical Support Department for assistance.
HOSHIZAKI AMERICA, INC. 618 Highway 74 South Peachtree City , GA 30269
Attn: HOSHIZAKI T echnical Support Department
Phone: 1-800-233-1940 T echnical Service
(770) 487-2331
Fax: (770) 487-3360
NOTE: T o expedite assistance, all correspondence/communication MUST include the following
information:
• Model Number
• Serial Number
• Complete and detailed explanation of the problem
2
Please review this manual. It should be read carefully before the icemaker is serviced or maintenance operations are performed. Only qualified service technicians should service and maintain the icemaker. This manual should be made available to the technician prior to service or maintenance.
CONTENTS
PAGE
I. SPECIFICATIONS .................................................................................................... 5
1. KM-900MAF (Air-cooled) .................................................................................... 5
2. KM-900MWF (Water-cooled) .............................................................................. 6
3. KM-900MRF (Remote air-cooled) ....................................................................... 7
4. KM-900MRE3 (Remote air-cooled 3 phase) ....................................................... 8
5. CONDENSING UNIT, URC-12F ......................................................................... 9
II. GENERAL INFORMATION .................................................................................... 11
1. CONSTRUCTION ............................................................................................. 11
[a] KM-900MAF (Air-cooled) ............................................................................ 1 1
[b] KM-900MWF (Water-cooled) ...................................................................... 12
[c] KM-900MRF (Remote air-cooled) ............................................................... 13
[d] KM-900MRF3 (Remote air-cooled 3 phase) ............................................... 14
2. CONTROLLER BOARD.................................................................................... 15
[a] SOLID-STATE CONTROL .......................................................................... 15
[b] CONTROLLER BOARD.............................................................................. 15
[c] SEQUENCE ................................................................................................ 19
[d] CONTROLS AND ADJUSTMENTS ............................................................ 22
[e] CHECKING CONTROLLER BOARD.......................................................... 25
III. TECHNICAL INFORMATION............................................................................... 27
1. WATER CIRCUIT AND REFRIGERANT CIRCUIT........................................... 27
[a] KM-900MAF (Air-cooled) ............................................................................ 2 7
[b] KM-900MWF (Water-cooled) ...................................................................... 28
[c] KM-900MRF (Remote air-cooled) ...................................................................
and KM-900MRF3 (Remote air-cooled 3 phase) ........................................ 29
2. WIRING DIAGRAMS......................................................................................... 30
[a] KM-900MAF (Air-cooled) ............................................................................ 3 0
[b] KM-900MWF (Water-cooled) ...................................................................... 31
[c] KM-900MRF (Remote air-cooled) ............................................................... 32
[d] KM-900MRF3 (Remote air-cooled 3 phase) ............................................... 33
3. TIMING CHART ................................................................................................ 34
4. PERFORMANCE DATA.................................................................................... 36
[a] KM-900MAF (Air-cooled) ............................................................................ 3 6
[b] KM-900MWF (Water-cooled) ...................................................................... 37
[c] KM-900MRF (Remote air-cooled) ............................................................... 38
[d] KM-900MRF3 (Remote air-cooled 3 phase) ............................................... 39
3
IV. SERVICE DIAGNOSIS ...........................................................................................40
1. NO ICE PRODUCTION........................................................................................40
2. EVAPORATOR IS FROZEN UP.......................................................................... 43
3. LOW ICE PRODUCTION.....................................................................................43
4. ABNORMAL ICE..................................................................................................4 4
5. OTHERS ..............................................................................................................44
V. REMOVAL AND REPLACEMENT OF COMPONENTS ..........................................45
1. SERVICE FOR REFRIGERANT LINES...............................................................45
[a] REFRIGERANT RECOVERY ........................................................................ 45
[b] EVACUATION AND RECHARGE [R-404A]...................................................45
2. BRAZING .............................................................................................................46
3. REMOVAL AND REPLACEMENT OF COMPRESSOR ......................................47
4. REMOVAL AND REPLACEMENT OF DRIER.....................................................49
5. REMOVAL AND REPLACEMENT OF EXPANSION VALVE ..............................49
6. REMOVAL AND REPLACEMENT OF HOT GAS VALVE AND...............................
LINE VALVE .......................................................................................................50
7. REMOVAL AND REPLACEMENT OF EVAPORATOR .......................................52
8. REMOVAL AND REPLACEMENT OF WATER-REGULATING VALVE..................
- WATER COOLED MODEL ONLY .................................................................... 53
9. ADJUSTMENT OF WATER-REGULATING VALVE................................................
- WATER COOLED MODEL ONLY .................................................................... 54
10. REMOVAL AND REPLACEMENT OF CONDENSING PRESSURE .......................
REGULATOR (C.P.R.) - REMOTE AIR-COOLED MODEL ONLY .................. 55
11. REMOVAL AND REPLACEMENT OF THERMISTOR.........................................5 6
12. REMOVAL AND REPLACEMENT OF FAN MOTOR ...........................................57
13. REMOVAL AND REPLACEMENT OF WATER VALVE.......................................58
14. REMOVAL AND REPLACEMENT OF PUMP MOTOR........................................5 8
15. REMOVAL AND REPLACEMENT OF SPRAY TUBES .......................................59
VI. MAINTENANCE AND CLEANING INSTRUCTIONS..............................................60
1. PREPARING THE ICEMAKER FOR LONG STORAGE......................................60
2. CLEANING...........................................................................................................62
[a] CLEANING PROCEDURE.............................................................................63
[b] SANITIZING PROCEDURE ...........................................................................64
3. MAINTENANCE...................................................................................................65
4
I. SPECIFICATIONS
1. KM-900MAF
* We reserve the right to make changes in specifications and design without prior notice.
5
2. KM-900MWF
* We reserve the right to make changes in specifications and design without prior notice.
6
3. KM-900MRF
* We reserve the right to make changes in specifications and design without prior notice.
7
4. KM-900MRF3
* We reserve the right to make changes in specifications and design without prior notice.
8
5. CONDENSING UNIT
URC-12F
9
MODEL: URC-12F
SPECIFICATIONS
EXTERIOR
DIMENSIONS (W x D x H)
REFRIGERANT CHARGE
URC-12F
WEIGHT
CONNECTIONS
REFRIGERANT ELECTRICAL
CONDENSER
HEAD PRESSURE CONTROL
AMBIENT CONDITION
Galvanized Steel
35 - 11/16” x 15-11/16” x 21-15/16” (907.2 x 398 x 557.8 mm)
R404A 4 lbs. 7 oz. (2000 g)
Net 80 lbs. (36 kg) Shipping 87 lbs. (39 kg)
One Shot Couplings (Aeroquip) Permanent Connection
Air-cooled
Condensing Pressure Regulator
Min. -20°F - Max. +122°F (-29°C to +50°C) Outdoor use
10
II. GENERAL INFORMATION
1. CONSTRUCTION
[a] KM-900MAF
11
[b] KM-900MWF
12
[c] KM-900MRF
13
[d] KM-900MRF3
14
2. CONTROLLER BOARD
[a] SOLID-STATE CONTROL
1) A HOSHIZAKI exclusive solid-state control is employed in KM-900MAF, KM-900MWF, KM-900MRF and KM-900MRF3 Modular Crescent Cubers.
2) A Printed Circuit Board (hereafter called “Controller Board”) includes a stable and
high quality control system.
3) All models are pretested and factory-adjusted.
[b] CONTROLLER BOARD
CAUTION
1. Fragile, handle very carefully.
2. A controller board contains integrated circuits, which are susceptible to failure due to static discharge. It is especially important to touch the metal part of the unit when handling or replacing the board.
3. Do not touch the electronic devices on the board or the back of the board to prevent damage to the board.
4. Do not change wiring and connections. Do not misconnect K3, K4 and K5, because the same connector is used for the Thermistor and Float Switch. K4 is not connected.
5. Always replace the whole board assembly when it goes bad.
6. Do not short out power supply to test for voltage.
PART NUMBER TYPE
2A1410-01 HOS-001A (Control Products)
Features of Control Products “E” Controller Board
1) Maximum Water Supply Period - 6 minutes Water Solenoid Valve opening, in the Defrost (Harvest) Cycle, is limited by the de-
frost timer. The Water Valve cannot remain open longer than the maximum period. The Water Valve can close in less than six minutes if the defrost cycle is completed.
15
2) Defrost Timer The defrost cycle starts when the Float Switch opens and completes the freeze cycle.
But the Defrost Timer does not start counting until the Thermistor senses 48°F at the Evaporator outlet. The period from the end of the freeze cycle up to the point of the Thermistor's sensing varies depending on the ambient and water temperatures.
3) High Temperature Safety - 127 ± 7°F The temperature of the suction line in the refrigerant circuit is limited by the High Tem-
perature Safety. During the defrost cycle the Evaporator temperature rises. The Thermistor senses 48°F and starts the Defrost Timer. After the Defrost Timer counts down to zero, the normal freeze cycle begins. If the Evaporator temperature continues to rise, the Thermistor will sense the rise in temperature and at 127 ± 7°F the Thermistor operates the High Tem­perature Safety. This High Temperature Safety shuts down the circuit and the icemaker automatically stops. To reset the safety, turn the power off and back on again. This High Temperature Safety protects the unit from excessive temperature. The Control Board will Beep every 3 seconds. The white Reset Button on the Control Board must be pressed with power on to reset the Safety.
4) Low Water Safety If the Pump Motor is operated without water, the mechanical seal can fail. To prevent this
type of failure, the Controller Board checks the position of the Float Switch at the end of the initial one minute water fill cycle and at the end of each defrost cycle. If the Float Switch is in the up position (electrical circuit closed), the Controller Board changes to the ice making cycle. If the Float Switch is in the down position (electrical circuit open), the Controller Board changes to a one minute water fill cycle before starting the ice making cycle. This method allows for a Low Water Safety shut down to protect the Water Pump from mechanical seal failure. For water-cooled model, if the water is shut off, the unit is protected by the High Pressure Switch.
5) High Voltage Cut-out The maximum allowable supply voltage of this icemaker is limited by the High Voltage
Cut-out. If miswiring (especially on single phase 3 wire models) causes excessive voltage on the Controller Board, the High Voltage Cut-out shuts down the circuit in 3 seconds and the icemaker automatically stops. When the proper supply voltage is resumed, the icemaker automatically starts running again. The Control Board will signal this problem using 7 Beeps every 3 seconds.
6) LED Lights and Audible Alarm Safeties The red LED indicates proper control voltage and will remain on unless a control voltage
16
problem occurs. At startup a 5 second delay occurs while the board conducts an internal timer check. A short beep occurs when the power switch is turned ON or OFF.
The green LED’s 1-4 represent the corresponding relays and energize and sequence 5 seconds from initial startup as follows:
Sequence Step LED’s on Length: Min. Max. Avg.
1 Minute Fill Cycle LED4 60 sec. Harvest Cycle LED1, 4, & 2 2 min. 20 min. 3-5 min. Freeze Cycle LED1 5 min. 60 min. 30-35 min. Reverse Pump Out LED1, 3, & 2 10 sec. 20 sec. Factory set.
{LED 1 – Comp; LED 2 - HGV/CFM; LED 3 – PM; LED 4 - WV} The built in safeties shut down the unit and have alarms as follows:
1 beep every 3 sec. = High Evaporator Temperature >127 ° F. Check for defrost problem (stuck HGV or relay), hot water entering unit, stuck headmas-
ter, or shorted thermistor. 2 beeps every 3 sec. = Defrost Back Up Timer. Defrost >20 minutes.
Orange LED marked 20 MIN energizes. Check for open thermistor, HGV not opening, TXV leaking by, low charge, or inefficient compressor.
3 beeps every 3 sec. = Freeze Back Up Timer. Freeze > 60 minutes. Yellow LED marked 60 MIN energizes. Check for F/S stuck closed (up), WV leaking by, HGV leaking by, TXV not feeding prop­erly, low charge, or inefficient compressor.
To manually reset the above safeties, depress white alarm reset button with the power supply ON.
6 beeps every 3 sec. = Low Voltage. Voltage is 92 Vac or less. 7 beeps every 3 sec. = High Voltage. Control voltage > 147Vac ±5%.
The red LED will de-energize if voltage protection operates. The voltage safety automatically resets when voltage is corrected.
The Output Test switch “S3” provides a relay sequence test. With power OFF, place S3 ON and switch power to ICE. The correct lighting sequence should be none, 2, 3, 4, 1, & 4, normal sequence every 5 seconds. S3 should remain in the “OFF” position for normal operation.
The application switch located between relay X3 & X4 must be set to match the original board application. Place this switch in the ALP position if there is no white wire supplied
17
to the K1 connector. If there is a white wire, place the switch in the C position. If this switch is placed in the wrong position either the compressor contactor will remain ener­gized with the control switch OFF or the unit will not start.
The dip switches should be adjusted per the adjustment chart published in the Tech Specs book. 7 & 8 must remain in the OFF position.
(Control Products HOS-001A Board)
18
[c] SEQUENCE
1st Cycle
1. Unit energized and Control Switch to “ICE” position. Water supply cycle starts.
2. After 1 minute, Defrost cycle starts.
3. Thermistor reads 48° F. Defrost Timer starts counting.
5. After the first 5 minutes in freeze cycle. Ready to complete freeze cycle when Float Switch circuit opens.
IMPORTANT
Board never accepts freeze completion signal within the first 5 minutes in freeze cycle.
IMPORTANT
Water Valve opening is limited to 6 minutes.
&
4. Defrost Timer stops counting. Defrost cycle is completed and freeze cycle starts.
IMPORTANT
1. Board never accepts defrost completion signal within the first 2 minutes in defrost cycle.
2. Defrost cycle time is limited to 20 minutes even if Defrost Timer does not stop counting.
19
2nd Cycle and after with pump drain
IMPORTANT
Freeze cycle time is limited to 60 minutes even if Float Switch does not open.
1. Float Switch opens and signals to complete freeze cycle. Drain timer starts counting.
&
2. Drain timer stops counting. Pump drain is completed
3. Thermistor reads 48° F. Defrost Timer starts counting.
IMPORTANT
Water Valve opening is limited to 6 minutes.
5. After the first 5 minutes in freeze cycle. Ready to complete freeze cycle when Float Switch circuit opens.
IMPORTANT
Board never accepts freeze completion signal within the first 5 minutes in freeze cycle.
4. Defrost Timer stops counting. Defrost cycle is completed and freeze cycle starts.
IMPORTANT
1. Board never accepts defrost completion signal within the first 2 minutes in defrost cycle.
2. Defrost cycle time is limited to 20 minutes even if Defrost Timer does not stop counting.
20