Hoshizaki KM660MRJ, KM520MRJ, KM520MAJ, KM350MWJ User Manual

Page 1
Service Manual
Modular Crescent Cuber
Models KM-350MAJ, MWJ KM-520MAJ, MWJ, MRJ KM-660MAJ, MWJ, MRJ
hoshizakiamerica.com
Number: 73230 Issued: 8-3-2018
Page 2
WARNING
Only qualied service technicians should install and service the appliance. To obtain the name and phone number of your local Hoshizaki Certied Service Representative, visit www.hoshizaki.com. No service should be undertaken until the technician has thoroughly read this Service Manual. Failure to service and maintain the appliance in accordance with this manual will adversely affect safety, performance, component life, and warranty coverage. Proper installation is the responsibility of the installer. Product failure or property damage due to improper installation is not covered under warranty.
Hoshizaki provides this manual primarily to assist qualied service technicians in the service of the appliance.
Should the reader have any questions or concerns which have not been satisfactorily addressed, please call, send an e-mail message, or write to the Hoshizaki Technical Support Department for assistance.
Phone: 1-800-233-1940; (770) 487-2331 Fax: 1-800-843-1056; (770) 487-3360
E-mail: techsupport@hoshizaki.com
618 Highway 74 South Peachtree City, GA 30269 Attn: Hoshizaki Technical Support Department
Web Site: www.hoshizaki.com
NOTE: To expedite assistance, all correspondence/communication MUST include the
following information:
• Model Number
• Serial Number
• Complete and detailed explanation of the problem.
Page 3
IMPORTANT
This manual should be read carefully before the appliance is serviced. Read the warnings and guidelines contained in this manual carefully as they provide essential information for the continued safe use, service, and maintenance of the appliance. Retain this manual for any further reference that may be necessary.
CONTENTS
Important Safety Information ................................................................................................. 5
I. Construction and Water/Refrigeration Circuit Diagram ....................................................... 7
A. Construction .................................................................................................................. 7
1. Air-Cooled Models (MAJ) ......................................................................................... 7
2. Water-Cooled Models (MWJ) ................................................................................... 8
3. Remote Models (MRJ) ............................................................................................. 9
B. Water/Refrigeration Circuit Diagram ............................................................................ 10
1. Air-Cooled Models (MAJ) ....................................................................................... 10
2. Water-Cooled Models (MWJ) ..................................................................................11
3. Remote Models (MRJ) ........................................................................................... 12
II. Sequence of Operation and Service Diagnosis ............................................................... 13
A. Sequence of Operation Flow Chart ............................................................................. 13
1. Operation Flow Chart ............................................................................................ 13
2. Shutdown Flow Chart ............................................................................................ 14
3. Freeze-Time Correction Chart ............................................................................... 15
B. Service Diagnosis ....................................................................................................... 16
C. Freeze-Time Correction Cycle (90 min.) ..................................................................... 22
D. Control Board Check ................................................................................................... 24
E. Bin Control Check and Adjustment .............................................................................. 25
F. Float Switch Check and Cleaning ................................................................................ 28
G. Thermistor Check ........................................................................................................ 30
H. Control Switch ............................................................................................................. 30
I. Mode Switch ................................................................................................................. 30
J. Diagnostic Tables ......................................................................................................... 31
K. Freeze-Up Check List .................................................................................................. 35
III. Controls and Adjustments ............................................................................................... 36
A. Control Board Layout .................................................................................................. 37
B. LED Lights and Audible Alarm Safeties ....................................................................... 38
C. Settings and Adjustments ............................................................................................ 39
1. Default Dip Switch Settings .................................................................................... 39
2. Harvest Time (S4 dip switch 1 & 2)........................................................................ 40
3. Pump-Out Time/Harvest Time During Pump-Out (S4 dip switch 3 & 4) ................. 40
4. Pump-Out Frequency Control (S4 dip switch 5) ..................................................... 41
5. Harvest Pump Time (Harvest Assist) (S4 dip switch 6) ......................................... 41
6. Harvest Pump Time (Harvest Assist)/Freeze-Time Correction (S4 dip switch 7) .. 42
7. Factory Use (S4 dip switch 8)................................................................................. 42
8. Freeze Timer (S4 dip switch 9 & 10) ...................................................................... 43
9. Pump-Out Pump Motor Direction (S5 dip switch 1) ............................................... 43
10. Rell Counter (S5 dip switch 2 and 3) .................................................................. 44
11. Minimum Harvest Time (S5 dip switch 4) ............................................................. 44
12. Anti-Slush (S5 dip switch 5) ................................................................................. 44
Page 4
IV. Refrigeration Circuit and Component Service Information.............................................. 45
A. Refrigeration Circuit Service Information .................................................................... 45
B. Component Service Information .................................................................................. 48
C. Water Regulating Valve Adjustment (water-cooled model) .......................................... 49
V. Maintenance .................................................................................................................... 50
VI. Preparing the Appliance for Periods of Non-Use ............................................................ 51
VII. Disposal ......................................................................................................................... 53
VIII. Technical Information .................................................................................................... 54
A. Specication and Performance Data Sheets ............................................................... 54
1. KM-350MAJ ........................................................................................................... 54
2. KM-350MWJ .......................................................................................................... 55
3. KM-520MAJ ........................................................................................................... 56
4. KM-520MWJ .......................................................................................................... 57
5. KM-520MRJ with URC-5F ..................................................................................... 58
6. KM-660MAJ ........................................................................................................... 59
7. KM-660MWJ .......................................................................................................... 60
8. KM-660MRJ with URC-5F ..................................................................................... 61
B. Wiring Diagrams ......................................................................................................... 62
1. KM-350M_J, KM-520M_J, KM-660M_J ................................................................. 62
Page 5

Important Safety Information

Throughout this manual, notices appear to bring your attention to situations which could result in death, serious injury, damage to the appliance, or damage to property.
WARNING Indicates a hazardous situation which could result in death or
serious injury.
NOTICE Indicates a situation which could result in damage to the
appliance or property.
IMPORTANT Indicates important information about the use and care of the
appliance.
WARNING
The appliance should be destined only to the use for which it has been expressly conceived. Any other use should be considered improper and therefore dangerous. The manufacturer cannot be held responsible for injury or damage resulting from improper, incorrect, and unreasonable use. Failure to service and maintain the appliance in accordance with this manual will adversely affect safety, performance, component life, and warranty coverage and may result in costly water damage.
To reduce the risk of death, electric shock, serious injury, or re, follow basic precautions including the following:
• Only qualied service technicians should install and service this appliance.
• The appliance must be installed in accordance with applicable national, state, and local codes and regulations.
• Electrical connection must be hard-wired and must meet national, state, and local electrical code requirements. Failure to meet these code requirements could result in death, electric shock, serious injury, re, or severe damage to equipment.
• The icemaker requires an independent power supply of proper capacity. See the nameplate for electrical specications. Failure to use an independent power supply of proper capacity can result in a tripped breaker, blown fuses, damage to existing wiring, or component failure. This could lead to heat generation or re.
THE ICEMAKER MUST BE GROUNDED. Failure to properly ground the icemaker could result in death or serious injury.
• Move the control switch to the "OFF" position and turn off the power supply before servicing. Lockout/Tagout to prevent the power supply from being turned back on inadvertently.
• To reduce the risk of electric shock, do not touch the control switch with damp hands.
• Do not make any alterations to the unit. Alterations could result in electric shock, injury, re, or damage to the unit.
• The appliance is not intended for use by persons (including children) with reduced physical, sensory, or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
Page 6
WARNING, continued
• Children should be properly supervised around this appliance.
• Do not climb, stand, or hang on the appliance or allow children or animals to do so. Serious injury could occur or the appliance could be damaged.
• Do not use combustible spray or place volatile or ammable substances near the appliance. They might catch re.
• Keep the area around the appliance clean. Dirt, dust, or insects in the appliance could cause harm to individuals or damage to the appliance.
Additional Warning for Remote Models
THE REMOTE CONDENSER UNIT MUST BE GROUNDED. The power supply and ground connection to the remote condenser unit are supplied from the icemaker. Failure to properly ground the remote condenser unit could result in death or serious injury.
• Move the icemaker control switch to the "OFF" position and turn off the power supply to the icemaker before servicing the remote condenser unit. Lockout/Tagout to prevent the power supply from being turned back on inadvertently.
NOTICE
• Follow the instructions in this manual carefully to reduce the risk of costly water damage.
• In areas where water damage is a concern, install in a contained area with a oor drain.
• Install the appliance in a location that stays above freezing. Normal operating ambient temperature must be within 45°F to 100°F (7°C to 38°C).
• Do not leave the icemaker on during extended periods of non-use, extended absences, or in sub-freezing temperatures. To properly prepare the icemaker for these occasions, follow the instructions in "VI. Preparing the Appliance for Periods of Non-Use."
• Do not place objects on top of the appliance.
• The dispenser unit/ice storage bin is for ice use only. Do not store anything else in the dispenser unit/ice storage bin.
Page 7

I. Construction and Water/Refrigeration Circuit Diagram

A. Construction

1. Air-Cooled Models (MAJ)

Drain Valve
Cleaning Valve
Water Supply Inlet
Spray Tubes
Evaporator
Inlet Water Valve
Thermostatic Expansion Valve
Float Switch
Compressor
Water Pump
Control Switch
Stainer
Hot Gas Valve
Condenser
High-Pressure Switch
Fan Motor
Liquid Line Valve
Drier
Bin Control
Control Box
Mode Switch
Model Shown: KM-350MAJ
Page 8

2. Water-Cooled Models (MWJ)

Cleaning Valve
Spray Tubes
Inlet Water Valve
Drain Valve
Water Supply Inlet
Stainer
Evaporator
Thermostatic Expansion Valve
Float Switch
Water Pump
Compressor
Control Switch
Mode Switch
Hot Gas Valve
Water Regulating Valve
High-Pressure Switch
Condenser
Drier
Liquid Line Valve
Bin Control
Control Box
Model Shown: KM-520MWJ
Page 9

3. Remote Models (MRJ)

Inlet Water Valve
Evaporator
Float Switch
Drain Valve
Spray Tubes
Cleaning Valve
Thermostatic Expansion Valve
Water Supply Inlet
Stainer
Hot Gas Valve
Receiver Tank
High-Pressure Switch
Drier
Water Pump
Crankcase Heater
Compressor
Liquid Line Valve
Bin Control
Control Switch
Control Box
Mode Switch
Model Shown: KM-660MRJ
Page 10

B. Water/Refrigeration Circuit Diagram

1. Air-Cooled Models (MAJ)

Hot Gas
Val ve
Condenser
High-Pressure
Switch
Drier
Fan
Liquid Line Valve
Heat
Exchanger
Thermistor
Water Supply
Strainer
Suction Line
Discharge Line
Compressor
Thermostatic Expansion Valve
Spray Tubes
Inlet Water Valve
Water Pump
Drain
Refrigeration Circuit
Water Circuit
Evaporator
Cleaning Valve
Drain Valve
Float Switch
Water Tank
10
Page 11

2. Water-Cooled Models (MWJ)

High-Pressure
Switch
Strainer
Hot Gas
Val ve
Discharge Line
Water Regulating Valve
Condenser
Inlet Water Valve
Drier
Thermostatic Expansion Valve
Suction Line
Heat
Exchanger
Liquid Line Valve
Thermistor
Water Supply
Cleaning Valve
Drain Valve
Float Switch
Compressor
Water Pump
Refrigeration Circuit
Water Circuit
Spray Tubes
Water Tank
Evaporator
Drain
11
Page 12

3. Remote Models (MRJ)

High-Pressure
Switch
Strainer
Hot Gas
Val ve
Headmaster
(C.P.R.)
Fan
Remote Condenser
Receiver
Drier
Suction Line
Liquid Line
Val ve
Heat
Exchanger
Water Supply
Cleaning Valve
Inlet Water Valve
Thermistor
Drain Valve
Float Switch
Discharge Line
Compressor
Thermostatic Expansion
Val ve
Water Pump
Spray Tubes
Evaporator
12
Water Tank
Drain
Refrigeration Circuit
Water Circuit
Page 13

II. Sequence of Operation and Service Diagnosis

A. Sequence of Operation Flow Chart

1. Operation Flow Chart

cycle
(S4 dip switch 5)
2 sec., then reverses for
10/20 sec.
• Pump motor stops for
(S4 dip switch 3 & 4)
FS in control
Comp energized
DV energized
FMR energized
HGV energized
PM de-energizes for 2 sec.,
then energizes for 10/20 sec.
FM de-energized
LLV de-energized
FS opens or freeze
timer terminates
Anti-Slush
Thermistor temperature
reaches 36°F (2.2°C)
(5.8 kΩ).
PM de-energized for
10 sec.
Freeze Time Differential Exceeded.
• Factory set for every 10th
4. Pump-Out Cycle
Initiate Freeze-Time Correction Cycle.
See "II.A.3. Freeze-Time Correction Cycle.
• Min. freeze time: 5 min.
3. Freeze Cycle
switch 9 & 10)
Correction starts at 2nd freeze cycle.
• Max. freeze time: freeze timer setting (S4 dip
• Freeze-Time monitoring for Freeze-Time
5-min.
minimum
freeze timer in
Harvest Pump
control
Timer
FS closed
50 sec.
Comp energized
FM energized
FMR energized
PM energized
LLV energized
HGV de-energized
FS check
FS open
Operation Flow Chart
PM energized
WV de-energized
FS closed
Thermistor temperature reaches
Comp energized
FMR energized
48°F (9°C) (3.9 kΩ or less).
Harvest timer starts.
HGV energized
WV energized
Components Energized when the Control Switch is in the "PUMP" Position
When the control switch is in the "PUMP" position power is supplied to the pump motor. Water tank contents then ows over the outside of the
evaporator plate assembly. Note: Water tank contents does not ow inbetween the evaporator plates.
(S4 dip switch 7), whichever is shorter. Do not adjust S4
dip switch 7 out of the factory position.
• WV time: 6 min. or the length of harvest minus 50 sec.
2. Harvest Cycle
1 to 3-min. harvest timer in
control (S4 dip switch 1 & 2)
Thermistor
in control
• Max. harvest time: 20 min.
WV energized
FS open
1-Min. ll.
then initiates a clean/sanitze program. See the maintenance label on the top cover or the instruction manual for details.
over outside of evaporator plate assembly as the control board power supply has been disconnected. The Clean/Sanitize program cannot initiate in this scenario.
Legend:
BC–bin control
Comp–compressor
DV–drain valve
FM–fan motor
FMR–fan motor-remote
FS–oat switch
HGV–hot gas valve
LLV –liquid line valve
Components Energized when the Control Switch is in the "ON" or "PUMP" position and the Mode Switch
PM–pump motor
WV–inlet water valve
• When the control switch is in the "PUMP" position and the mode switch is in the "CLEAN" position, only the pump motor energizes and circulates water tank contents
is in the "CLEAN" Position
Fill Cycle
FS check
1. 1-Minute
Cycle
Steps
Startup
13
Page 14

2. Shutdown Flow Chart

3. Ice Level Lowered
2. Icemaker Off
Icemaker starts at
All components
"1. 1-Minute Fill Cycle."
de-energized.
BC closed
(BC sensor disengaged)
Green UBC LED on
Yellow "BC OPEN" LED off
Yellow "BC OPEN" LED continues. All
components de-energized.
Shutdown Flow Chart
Control board retains freeze-time correction count data
between bin control restarts.
to 15 sec. into the freeze cycle if
activated at the end of the harvest cycle.
15 sec. before the 5-min. short cycle
protection timer terminates.
Otherwise, at the end of the next harvest
cycle.
BC open (BC sensor engaged)
Green UBC LED off
Yellow "BC OPEN" LED on
BC Operation
Legend:
BC–bin control
1. Bin Full
Shutdown
Shutdown Delay:
and Restart
Fill Cycle–15 sec. after activation.
Harvest Cycle–At the end of the harvest cycle, or up
Freeze Cycle– 15 sec. after activation if activated at least
14
Page 15

3. Freeze-Time Correction Chart

Overow
2. 10-Minute Fill/
WV energized
Comp de-energized
FMR de-energized
HGV de-energized
PM de-energized
After 5th 10-Minute Harvest Pump Cycle with WV
Freeze-Time Correction Cycle Complete.
Go to Step "3. Freeze Cycle" in Operation Flow Chart.
step 1 for 5th and nal time.
• Do not adjust S4 dip switch 7 out of the factory position.
• After step 2 completes 4th sequence (80 min. completed), repeat
1. 10-Minute Harvest Cycle with WV
Comp energized
FMR energized
HGV energized
PM energized
2A8242-01 Freeze-Time Correction Flow Chart
Cycle Steps
Steps 1 and 2 repeat
4 times (total 80 min.),
then step 1 repeats for
a 5th time to complete
Freeze-Time Correction
Start
Cycle.
WV energized
Legend:
Comp–compressor
FM–fan motor
FMR–fan motor-remote
HGV–hot gas valve
PM–pump motor
WV–inlet water valve
Appliance Cycle Reset and Alarm Reset:
Cycle Reset: Power Supply or Control Switch Turned Off and On again:
Appliance turns off, then re-starts at 1.Fill Cycle.
Alarm Reset: CB "ALARM RESET" pressed during or after a freeze-time
correction cycle with power supply on:
Appliance continues cycle with no interruption or reset.
CB red "POWER OK" LED blinking:
CB red "POWER OK" LED resets to solid.
CB yellow "EXT HARVEST" LED blinking:
CB yellow "EXT HARVEST: LED turns off.
Freeze Time Differential Exceeded.
times have exceeded 600 sec. (10 min.)
Freeze-Time Correction function is enabled
when S4 Dip Switch 7 is in the "ON" position
and initiates when the difference between
times is equal to or greater than 600 sec.
(10min.).
Freeze time is recorded and freeze cycles
are counted starting at the 2nd freeze cycle
after startup from a power off condition.
After 6recorded freeze cycles, CB starts
comparing the minimum and maximum
differential ofrecorded freeze cycle times.
Up to 10 freeze cycles are recorded and
maintained in memory. At the 11th recorded
freeze cycle, the rst recorded freeze
cycle time is dropped to maintain the
cycles.
Note: When 1st freeze-time correction cycle
is initiated, CB "POWER OK" LED starts
blinking. On 2nd freeze-time correction cycle,
if CB "POWER OK" LED has been reset,
CB "POWER OK" LED starts blinking. If CB
"POWER OK" had not been reset after 1st
freeze-time correction cycle CB "POWER
OK" LED continues to blink.
After 3rd freeze-time correction cycle in
36hours, CB yellow "EXT HARVEST" LED
starts blinking.
Appliance continues to operate and LEDs
continue to blink until ALARM RESET button
is pressed with power on.
15
Page 16

B. Service Diagnosis

WARNING
• The appliance should be diagnosed and repaired only by qualied service personnel to reduce the risk of death, electric shock, serious injury, or re.
• Risk of electric shock. Control switch in "OFF" position does not de-energize all loads Use extreme caution and exercise safe electrical practices.
• Moving parts (e.g., fan blade) can crush and cut. Keep hands clear.
• Before servicing the appliance, move the control switch to the "OFF" position and turn off the power supply.
CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews are securely in place after the appliance is serviced. Make sure that none have fallen into the dispenser unit/ice storage bin.
• Make sure all food zones in the appliance and dispenser unit/ice storage bin are clean after service.
The diagnostic procedure is a sequence check that allows you to diagnose the electrical system and components. Before proceeding, check for correct installation, proper voltage per nameplate, and adequate water supply. Check CB using the steps in "II.D. Control Board Check." Check dip switch settings to assure that S4 dip switches and S5 dip switches 1 through 5 are in the factory default position. S4 dip switch 1, 2, 3, 4, and 5 are cleaning adjustments and the settings are exible. For factory default settings, see "III.C.1. Default Dip Switch Settings."
Note: • When checking high voltage (115VAC), always choose a white (W) neutral wire to
establish a good neutral connection.
• When checking voltage from the CB K1 connector (10 pin connector), pull CBK1connector out slightly to allow room for multimeter test leads contact.
1) Turn off the power supply, then access the control box. Move the control switch to the "OFF" position. Clear ice from BC sensing area.
2) Check that the 115VAC 10A fuse is good.
16
Page 17
1. Sequence and Component Diagnosis
3) Power On: Turn on the power supply, then move the control switch to the "ON" position and the mode switch to the "ICE" position. A 5-sec. delay occurs. CB red "POWER OK" LED turns on. If CB yellow "BC OPEN" LED is on (indicating a full bin), move ice away from BC sensing area.
Note: • CB red "POWER OK" LED remains on unless the 10.5VAC power supply is
interrupted (K2 connector).
• Check CB using the steps in "II.D. Control Board Check" or BC using steps in "II.E. Bin Control Check and Adjustment."
a) Power On Diagnosis: If CB red "POWER OK" LED is off, conrm 10A fuse is good.
Check for 115VAC at control switch #2 (BK) to neutral (W) then at control switch #1(P) to neutral (W). If 115VAC is present on #2 (BK) and not on #1(P), replace control switch. If 115VAC is present on control switch #1 (P), check for 115VAC at HPS (P) to neutral (W) then HPS (BK) to neutral (W). If115VAC is present at HPS (P) and not at HPS (BK), HPS is open. See HPS Diagnosis below. If 115VAC is present at HPS (BK), check for 10.5VAC at CB K2#1 red wire to CB K2 #2 red wire. If 10.5VAC is not present, check that the cleaning valve is closed and the interlock switch is closed. Next, check CT continuity. If open, replace CT.
b) HPS Diagnosis: Check that the condenser coil is not clogged or restricted. Let
refrigeration circuit pressures equalize. If HPS does not reset and pressures are equalized, replace HPS. If pressures are not equalized, reclaim refrigerant and diagnose refrigeration circuit restriction. Check that there are no restrictions in the refrigeration circuit. Harvest Cycle: HGV, strainer, or check valve. Freeze Cycle: FM, FMR, TXV, WRV, HM, LLV, strainer, check valve, drier, and damaged line set or tting.
Conrm that the location meets installation requirements:
• The appliance is not intended for outdoor use. Normal operating ambient temperature should be within 45°F to 100°F (7°C to 38°C).
• Allow 6" (15 cm) clearance at rear, sides, and top for proper air circulation and ease of maintenance and/or service should they be required.
• The appliance should not be located in a corrosive environment.
4) 1-Min. Fill Cycle – LED 4 is on. WV energizes. After 1 min., CB checks for a closed FS. If FS is closed, the harvest cycle begins. If harvest cycle begins (Comp, HGV, FMR energized), continue to step 5a. If FS is open, WV remains energized until FS closes (low water safety protection during initial start up and at the end of each harvest). Diagnosis: Check that water enters the water tank. If not, check that the water supply line shut-off valve is open and screens or external lters are clear. Check for 115VAC at CB K1 #6 (O) to neutral (W). If 115VAC is not present, replace CB. If 115VAC is present, and WV does not energize, check for 115VAC at WV. If 115VAC is present, check coil continuity. Ifopen, replace WV. If the water tank lls, but the appliance fails to start harvest (Comp energized), check for open FS. See "II.F. Float Switch Check and Cleaning." If FS is closed and CB fails to start the harvest cycle after 1 min., replace CB.
17
Page 18
5a) Initial Harvest Cycle – LEDs 1, 4, and 2 are on. WV continues. Comp, FMR, and
HGV energize. CB monitors the warming of the evaporator via the thermistor located on the suction line. When the thermistor reaches 48°F (9°C), CB reads 3.9 kΩ from the thermistor and turns harvest termination over to the harvest timer (S4 dip switch 1 & 2 and S5 dip switch 4). WV are energized during harvest for a maximum of 6 min. or the length of harvest minus HPT setting (S4 dip switch 6), whichever is shorter. See step 5b below.
a) Comp Diagnosis: Check that evaporator is warming. Ifnot, conrm that Comp
energizes. If not, check for 115VAC at CB K1 #9 (Y) to neutral (W). If 115VAC is not present, check for 115VAC at CB K1 #10 (BK) to neutral (W). If115VAC is present at #10 (BK) and not at #9 (Y), replace CB. If 115VAC is present, check for 115VAC at mode switch #2 (Y) to neutral and mode switch #1 (V) to neutral. If 115VAC is present at #2 (Y) and not at #1 (V), conrm mode switch is in "ICE" position. If in "ICE" position, check mode switch continuity. If open, replace mode switch. If 115VAC is present at mode switch #1 (V), check for 115VAC at CR solenoid. If 115V AC is present, conrm contacts are closed. If not, replace CR. If CR contacts are closed, check Comp external overload, Comp start and run capacitors, Comp start relay, and Comp motor winding.
b) HGV Diagnosis: If Comp is energized and evaporator is not warming, check that
HGV energizes and opens. Check for 115VAC at CB K1 #2 (P) to neutral (W). If115VAC is not present, check for 115VAC at CB K1 #1 (V). If 115VAC is not present, check wiring for loose connection from CB 10 pin connector pin #1 (V) to mode switch. If 115VAC is present on #1 (V) and not at #2 (Y), replace CB. If 115VAC is present at #2 (Y), check for 115VAC at HGV coil and check HGV coil continuity. Replace as needed. Note: LED is off when HGV is energized and on when LLV/FM are energized.
c) LLV Diagnosis: Conrm that LLV is de-energized and closed (not bypassing).
Ifenergized, replace CB. If de-energized and bypassing, replace LLV.
d) WRV Diagnosis: Conrm WRV is not leaking by. If WRV is leaking by, conrm HGV
is open and LLV is closed. Next, check for proper refrigerant pressures. If refrigerant pressures are correct, adjust or replace WRV. See "IV.C. Water Regulating Valve Adjustment (water-cooled models).".
5b) Harvest Pump Time (Harvest Assist) – LEDs 1 and 3 are on. When the thermistor
reaches 48°F (9°C), CB reads 3.9 kΩ from the thermistor and turns harvest termination over to the harvest timer (S4 dip switch 1 & 2 and S5 dip switch 4). When WV de-energizes, LED 4 turns off and LED 3 turns on. PM energizes. Comp, FMR, and HGV continue. Diagnosis: Place a thermometer on the suction line next to the thermistor. Has it warmed to 48°F (9°C) or warmer? Conrm thermistor status. See "II.G Thermistor Check." If the thermistor reading is in proper range, dip switch 7 is on, and PM does not energize before harvest terminates, replace CB. If WV continues, check for 115VAC at CB K1 #6 (O). If115VAC is present, and LED 4 is off, replace CB. If LED 3is on and PM is not energized, check for 115VAC at CB K1 #4(R). If115VAC is not present, replace CB. If 115VAC is present and PM is not energized, check PM capacitor and motor winding continuity.
18
Page 19
5c) Initial Harvest Cycle Termination Diagnosis: When the thermistor reaches 48°F
(9°C), CB reads 3.9 kΩ from the thermistor and turns harvest termination over to the harvest timer (S4 dip switch 1 & 2 and S5 dip switch 4). Check discharge line temperature. For a thermistor check, see "II.G.Thermistor Check." If 1-min. ll cycle starts after harvest timer terminates, check that FS is clean and operating properly, see "II.F. Float Switch Check and Cleaning." If FS is closed, CB proceeds to the next cycle. Ifnot, replace CB. Note: The minimum total time allowed by CB for a complete harvest cycle is based on S5 dip switch 4. Maximum harvest time allowed is 20 min.
NOTICE! S4 dip switch 7 must remain on. Otherwise, PM will not energize during the last seconds of harvest.
6) Freeze Cycle – LED 1, 2, and 3 are on. Comp, FMR, and PM continue. FM and LLV energize. HGV de-energizes. Appliance is held in freeze by a 5-min. short cycle protection timer. After 5-min. short cycle protection timer terminates and FS opens, freeze cycle terminates. Note: PM power supply continues from CB K1 #4 (R) in harvest and in freeze. Anti-Slush: When anti-slush is enabled (S5 dip switch 5 "ON"), PM de-energizes when thermistor reaches 36°F (2.2°C) (5.8 kΩ) for 10 sec. then, energizes for the remainder of the freeze cycle.
a) Freeze Cycle Diagnosis: Conrm Comp, FMR, and PM continue. Conrm that FM
and LLV energize. Conrm WRV opens. Next, conrm HGV de-energizes. During the rst 5 min. of freeze, conrm evaporator is cooling. If not, conrm WV de-energized (not leaking by), HGV de-energized (not bypassing), LLV and FM energize, TXV and HM operate correctly, WRV opens, Comp is efficient, and refrigerant charge is correct. See "VIII.A. Specication and Performance Data Sheets."
b) Comp and FMR Diagnosis: If Comp and FMR de-energize once freeze begins,
check that appliance has not shut off on HPS (CB "POWER OK" LED off). If so, check "3)b) HPS Diagnosis" above. If CB "POWER OK" LED is on, check for 115VAC at CB K1 #9 (Y) to neutral (W). If 115VAC is not present and LED 1 is on, replace CB. If 115VAC is present, check for 115VAC at CR coil. If 115VAC is present, check CR coil and contact continuity. Replace as needed. If CR is okay, check Comp start relay and start and run capacitors. Next, check Comp motor winding continuity. If Comp is energized but evaporator is not cooling, check for an inefficient Comp. See "VIII.A. Specication and Performance Data Sheets." If Comp is energized but FMR is not, check for 115VAC at the FMR junction box. If 115VAC is not present, check icemaker wiring connections. If 115VAC is present, check for voltage at condenser unit. If115VAC is not present, check eld wiring connections. If 115VAC is present, check FMR capacitor, motor winding, and fan blade for binding.
c) WV and HGV Diagnosis: If WV is energized, check for 115VAC at CB K1 #6 (O)
to neutral (W). If 115VAC is present after PM energizes in harvest cycle, replace CB. If 115VAC is not present, replace WV (bypassing). If HGV did not de-energize at the end of harvest, check for 115VAC at CB K1 #2 (P) to neutral (W). If 115VAC is present and LED 2 is on, replace CB. If 115VAC is not present, replace HGV (bypassing).
19
Page 20
d) PM Diagnosis: Conrm water is owing over evaporator from PM and not WV. If PM
de-energizes once freeze begins, check for 115VAC at CB K1 #4 (R) to neutral (W). If 115VAC is not present, replace CB. If 115VAC is present and PM is de-energized, check PM capacitor and motor winding continuity.
e) FM and LLV Diagnosis: If FM or LLV does not energize, check for 115VAC at CB
K1#3 (BK) to neutral (W). If 115VAC is not present and LED 2 is on, check for 115VAC at CB K1 #1(V). If 115VAC is present at #1 (V) and not at #3 (BK), replace CB. If 115VAC is present and LED 2 is on: For FM, check capacitor, motor winding, and blade for binding. For LLV, check coil voltage and continuity. Note: LED 2 is on for LLV/FM and off for HGV.
f) Refrigerant Pressures, HM, and TXV Diagnosis: If evaporator is still not cooling,
check refrigerant pressures. See "VIII.A. Specication and Performance Data Sheets." Next, check HM operation. If refrigeration pressures are above HM setpoint and HMis bypassing, replace HM. Check TXV for proper operation. Remove TXV bulb and hold it in your hand, refrigerant low-side pressure should rise, place TXV bulb in ice water, refrigerant low-side pressure should drop. A 10 to 15 pound pressure swing between warm and cold conditions indicate a good TXV. If a 10 to 15 pound swing is not present, replace TXV.
g) WRV Diagnosis: WRV is factory set and generally no adjustment is required.
IfWRV fails to open in freeze, check for proper refrigerant pressures. See "VIII.A. Specication and Performance Data Sheets." If refrigerant pressures are correct and WRV does not open, adjust or replace as needed. See "IV.C. Water Regulating Valve Adjustment (water-cooled models)."
h) Freeze Termination Diagnosis: After 5 min. in freeze, disconnect CB K5 FS
connector. 15 sec. later appliance should switch out of the freeze cycle (15 second delay after FS opens before terminating the freeze cycle). If appliance remains in freeze longer than 15 sec. after FS removed, replace CB. If appliance switches with FS removed but would previously not switch out of freeze with FS connected (long freeze - 3 beep alarm), see "II.F. Float Switch Check and Cleaning."
Note: Normal freeze cycle will last 20 to 40 min. depending on model and conditions.
Cycle times and pressures should follow performance data provided in this manual. See "VIII.A. Specication and Performance Data Sheets."
i) Short Freeze Cycle Diagnosis: Conrm water tank lls and overows during 1 min.
ll and harvest cycles. If not, check water supply lters, shut-off valve, WV screen. Ifwater tank empties before 5 min. timer terminates and freeze cycle is short, check that DV is not leaking by (water owing down the drain). If DV is leaking by, remove and clean DV, replace if necessary. If water tank is full, see "II.F. Float Switch Check and Cleaning." for erratic operating FS.
20
Page 21
7) Pump-Out Cycle – LEDs 1, 3, and 5 are on (10/20 second pump-out). Timing of the rst pump-out is determined by S4 dip switch 5. See the table below.
Control Board Settings
S4 Dip Switch Setting
No. 5
OFF Every 10 cycles After 11th freeze cycle
ON Every cycle After 2nd freeze cycle
Pump-Out Frequency Control Board
Comp and FMR continue, HGV energizes. Note: If S4dip switch 3 & 4 are set to 3 off and 4 on, LED 4 turns on and WV energizes.
NOTICE!S5 dip switch 1 must not be adjusted. This is the pump-out circulation selection and allows DV to energize in pump-out.
FM and LLV de-energize. PM stops for 2 sec., then PM and DV energize for 10/20 sec. depending on pump-out timer (S4dip switch 3 & 4) setting. When the pump-out timer terminates, pump-out is complete. The pump-out frequency control (S4 dip switch 5) is factory set, and generally no adjustment is required. However, the pump-out frequency control can be set to have a pump-out occur every 10 cycles or every cycle. For details, see "III.C.4. Pump-Out Frequency Control (S4 dip switch 5)."
Pump-Out Diagnosis: In the freeze cycle before pump-out (see table above), after 5min. of freeze disconnect CB black K5 connector (FS connector). Check that PM stops and re-starts. Next, check that PM and DV energized (water owing down the drain through DV). If PM does not stop and re-start, check that CB LEDs 1, 3, and 5are on. If not, replace CB. IfLEDs1,3, and 5 are on and PM does not energize, check for 115VAC at CB K1 #4 (R) to neutral (W). If 115VAC is not present, replace CB. If not, check PM motor windings and impeller for binding. If energized, make sure DV energized. If not, check for 115VAC at CB K1 #5 (W/BU). If 115VAC is not present and LED 5 is on, replace CB. If 115VAC is present, check DV solenoid continuity. Replace as needed. If DV is energized and open, check that the drain line is not clogged.
Conrm FM and LLV de-energize. If FM or LLV are energized with LEDs 1, 3, and 5 on, replace CB.
8) Normal Harvest Cycle – Same as the initial harvest cycle. Return to step 5a) above. Note: Appliance continues to cycle until BC is satised or power is switched off.
Theappliance always restarts at the 1-min. ll cycle.
2. Shutdown Diagnosis
1) See "II.E.1. Bin Control Check."
3. Freeze-Time Correction Cycle Diagnosis
1) See "II.C. Freeze-Time Correction Cycle."
Legend: BC–bin control; CB–control board; Comp–compressor; CT–control transformer;
DV–drain valve; FM–fan motor; FMR–fan motor remote; FS–oat switch; HGV–hot gas valve; HM–headmaster (C.P.R.); HPS–high-pressure switch; L LV–liquid line valve; PM–pump motor; TXV–thermostatic expansion valve; WRV–water regulating Valve; WV–inlet water valve
21
Page 22

C. Freeze-Time Correction Cycle (90 min.)

Freeze-Time Correction function is enabled when S4 Dip Switch 7 is in the "ON" position and initiates when the difference between the minimum and maximum recorded freeze times is equal to or greater than 600sec. (10min. ). Freeze time is recorded and freeze cycles are counted starting at the 2nd freeze cycle after startup from a power off condition. After 6 recorded freeze cycles, CB starts comparing the minimum and maximum differential of recorded freeze cycle times. Up to 10freeze cycles are recorded and maintained in memory. At the 11th recorded freeze cycle, the rst recorded freeze cycle time is dropped to maintain the maximum number of 10 recorded freeze cycles. Freeze time recordings and freeze cycle counts are retained in memory during a BC off cycle and resume on the 2nd freeze cycle after BC restart.
1) Initiation and CB Operation: When the differential between minimum and maximum recorded freeze times exceeds 600 sec. (10min.), freeze-time correction cycle starts. CB red "POWER OK" LED blinks. When freeze-time correction cycle occurs 3 or more times within a 36 hour period, CB yellow "EXT HARVEST" LED blinks with CB red "POWER OK" LED. Appliance starts in freeze cycle after a freeze-time correction cycle. Toreset CB LEDs, press ALARM RESET button on CB with power on. CB resets LEDs and appliance continues cycle without interruption.
2) Freeze-Time Correction Sequence: First occurrence within 36 hr., minimum and maximum freeze times have exceeded differential parameters. CB "POWER OK" LED starts blinking. Freeze-Time Correction Cycle starts. Second occurrence within 36 hr., minimum and maximum freeze times have exceeded differential parameters. If not reset, CB "POWER OK" LED continues blinking. If reset from rst occurrence, CB "POWER OK" LED starts blinking. Freeze-Time Correction Cycle starts. Third occurrence within 36 hr. minimum and maximum freeze times have exceeded differential parameters. CB yellow "EXT HARVEST" LED starts blinking. Also, If not reset, CB "POWER OK" LED continues blinking. If reset, CB "POWER OK" LED starts blinking. Freeze-Time Correction Cycle starts. Total freeze-time correction cycle last for 90min. At the end of 80min., the nal step initiates and nal Harvest Pump Time (Harvest Assist) with WV (10-min.) starts. Once the nal Harvest Pump Time (Harvest Assist) with WV (10-min.) terminates (90 min. complete), normal freeze cycle begins.
22
Page 23
2a) 10-Min. Harvest Pump Time (Harvest Assist) with WV: CB "POWER OK" LED
blinking. CB LEDs 1, 4, and 3 are on and Comp, FMR, HGV, PM, and WV energize. 10-min. timer starts. Once 10-min. timer terminates, CB LEDs 1, 3, and 2 turn off and Comp, FMR, HGV, and PM de-energize. WV continues.
2b) 10-Min. Fill: CB LED 4 on and WV energized. 10-min. timer starts.
2c) Final 10-Min. Harvest Pump Time (Harvest Assist) with WV: CB "POWER OK"
LED blinking. Once 10-min. timer terminates, CB LEDs 1, 4, and 3 are on and Comp, FMR, HGV, and PM energizes. WV continues. 10-min. timer starts. Once 10-min. timer terminates, normal freeze cycle begins. CB LED 1, 2, and 3 are on and Comp, FMR, and PM continue. HGV and WV de-energize.
3) Appliance Cycle Reset and CB Alarm Reset: Cycle Reset: Power supply or control switch turned off and on again: Appliance turns off, then re-starts at 1. Fill Cycle. Alarm Reset: CB "ALARM RESET" pressed during or after a freeze-time correction cycle with power supply on: Appliance continues cycle with no interruption or reset. CB red "POWER OK" LED blinking: CB red "POWER OK" LED resets to solid. CB yellow "EXT HARVEST" LED blinking: CB yellow "EXT HARVEST: LED turns off.
Legend: BC–bin control; CB–control board; Comp–compressor; CR–compressor relay;
CT–control transformer; DV–drain valve; FM–fan motor; FMR–fan motor remote; FS–oat switch; HGV–hot gas valve; HM–headmaster (C.P.R.); HPS–high-pressure switch; L LV–liquid line valve; PM–pump motor; TXV–thermostatic expansion valve; WRV–water regulating valve; WV–inlet water valve
23
Page 24

D. Control Board Check

Before replacing CB that does not show a visible defect and that you suspect is bad, always conduct the following check procedure. This procedure will help you verify your diagnosis.
Alarm Reset: If CB is in alarm (beeping), press the "ALARM RESET" button on CB
while CB is beeping. WARNING!Risk of electric shock. Care should be taken not to touch live terminals. Once reset, the icemaker starts at the 1-minute ll cycle. For audible alarm information, see "III.B. LED Lights and Audible Alarm Safeties."
1) Check the dip switch settings to assure that S4 dip switch 3, 4, 7, 8, 9, 10 and S5 dip switch 1 through 5 are in the factory default position. S4 dip switch 1, 2, 5,and 6 are cleaning adjustments and the settings are exible. For factory default settings, see "III.C.1. Default Dip Switch Settings."
2) Move the control switch to the "ON" position and the mode switch to the "ICE" position. If the red CB "POWER OK" LED is on, control voltage is good, continue to step 3. If CB "POWER OK" LED is off, check CT secondary circuit. CT output is 10.5VAC at 115VAC primary input. If the secondary circuit has proper voltage and the red LED is off, replace CB.
If the secondary circuit does not have proper voltage, check CT primary circuit. Check
for 115VAC at CB K1 connector pin #10 (BK) to neutral (W) for 115VAC. Always choose a white (W) neutral wire to establish a good neutral connection when checking voltages. For additional checks, see "II.J.1. No Ice Production."
3) The "OUTPUT TEST" button provides a relay sequence test. Make sure the control switch is in the "ON" position and the mode switch is in the "ICE" position, then press the "OUTPUT TEST" button. For the correct lighting sequence, see the table below. Note that the order of the LEDs from the outer edge of the control board is 1, 4, 5, 3, 2. Components (e.g., compressor) cycle during the test.
Following the test, the icemaker begins operation at the 1-minute ll cycle. If the LEDs do not light as described above, replace CB.
4) To verify voltage output from CB to the components, slide the CB K1 connector out far enough to allow multimeter lead contact. With the icemaker in the cycle to be tested, check output voltage from the corresponding pin on CB K1 connector to a neutral (Wwire). If output voltage is not found and the appropriate LED is on, replace CB.
5) Check CB control connectors K3, K4, and K5 for correct VDC per table below. Note: Pin #1 is DC ground (GND) on each connector
Legend: CB–control board; CT–control transformer
K3 Thermistor
Pin # VDC
#1 to #2 5VDC
#1 to #3 5VDC
#2 to #3 0VDC
K4 Jumper
Pin # VDC
#1 to #2 5VDC
#1 to #3 5VDC
#2 to #3 0VDC
K5 Float Switch
Pin # VDC
#1 to #2 1.2VDC
#1 to #3 2VDC
#2 to #3 1.2VDC
Thermistor
Jumper
Float Switch
CB
3
1
3
1
3
1
K3
RED WHITE
K4
BLACK
K5
24
Page 25

E. Bin Control Check and Adjustment

WARNING
• All parts are factory-adjusted. Improper adjustments may adversely affect safety, performance, component life, and warranty coverage.
• In Hoshizaki DB and DM dispenser applications, the bin control controller setting must be adjusted to 2. For Coca-Cola Freestyle® Dispenser and other dispenser applications, the bin control controller setting must be adjusted to 3. Increasing the ice level on any dispenser application could lead to icemaker movement, water leakage, or ice overow.
NOTICE
• Do not block the bin control lens with top kits or the icemaker will not operate properly.
• Failure to properly adjust the bin control setting could result in water leakage, ice backup, and icemaker damage.
1. Bin Control Check
The bin control is factory set for use on Hoshizaki America standard ice storage bins. If mounted on a dispenser application or if a change to the ice level in an ice storage bin application is desired, see "II.E.2. Bin Control Adjustment."
1) Remove the front panel and base cover. See Fig. 1.
2) Move the control switch to the "OFF" position.
3) Conrm the mode switch is in the "ICE" position, then move the control switch to the "ON" position. See Fig. 2. Turn on the power supply, and allow the icemaker to operate.
Mode Switch
Fig. 2
Base Cover
Control Switch
Fig. 1
25
Page 26
4) As water begins to ll the water tank (1-min. ll), place an object 5" to 7" (127 to 178mm) away from the bin control lens. See Fig. 3. 15 sec. later, the icemaker shuts down. Remove the object from the bin control lens. 30 sec. later, the icemaker restarts.
Bin Control Lens
Fig. 3
Cycle at Bin Control Activation
Fill Cycle 15 sec. after activation.
Harvest Cycle If engaged 15 sec. or longer, at the end of harvest cycle.
Freeze Cycle 15 sec. after activation if activated at least 15 sec. before the 5-min. short cycle
Ice Level in Bin Control Board
Empty OFF ON
Full ON OFF
Shutdown
protection timer terminates. Otherwise, at the end of the next harvest cycle.
Bin Control Controller
"OPEN/CLOSED" LED
LED 1
5) Once the icemaker restarts, move the control switch to the "OFF" position, then turn off the power supply.
6) Replace the base cover in its correct position.
7) Move the control switch to the "ON" position. Replace the front panel in its correct position, then turn on the power supply.
26
Page 27
2. Bin Control Adjustment
WARNING
• All parts are factory-adjusted. Improper adjustments may adversely affect safety, performance, component life, and warranty coverage.
• In Hoshizaki DB and DM dispenser applications, the bin control controller setting must be adjusted to 2. For Coca-Cola Freestyle® Dispenser and non-Hoshizaki dispenser applications, the bin control controller setting must be adjusted to 3. Increasing the ice level on any dispenser application could lead to icemaker movement, water leakage, or ice overow.
NOTICE
• Do not block the bin control lens with top kits or the icemaker will not operate properly.
• Failure to properly adjust the bin control setting could result in water leakage, ice backup, and icemaker damage.
The bin control is factory set to 1 for use on Hoshizaki America standard ice storage bins. See the table below for adjustments to ice level.
WARNING! Do not adjust outside of these settings.
1) If not already removed, remove the front, top, and right side panels.
2) Conrm bin control controller setting for proper application. See the table below for settings. See Fig. 4 for ice level reference.
Application Bin Control Ice Level Settings
Bin Control Controller
Setting Default: Standard Ice Storage Bins 1 254 mm (10") Hoshizaki DB and DM Dispensers 2 305 mm (12")
®
Coca-Cola Freestyle Non-Hoshizki Dispensers
Optional Settings 4 508 mm (20")
Recommended Setting for Hoshizaki DB or DM Dispenser
Factory Default for Standard Ice Storage Bins
Dispenser and
Recommended Setting for Coca-Cola Freestyle® Dispenser and Non-Hoshizaki Dispensers
3 406 mm (16")
5 610 mm (24")
Ice Detection Distance From Bin Control Lens
Bin Control
Lens
Setting #1
Setting #2 Setting #3 Setting #4 Setting #5
Bin Control Controller
Model Shown: KM-660MAJ-E with B-300SF
Fig. 4
27
Page 28

F. Float Switch Check and Cleaning

FS is used to determine that there is sufficient water in the water tank after the 1-min. ll cycle and after each harvest cycle. FS is also used to determine that the appropriate volume of water has been converted into ice before switching out of the freeze cycle. Noadjustment is required.
1. Float Switch Check
To check FS, follow the steps below.
1) Turn off the power supply.
2) Remove the front panel, then move the control switch to the "OFF" position.
3) Drain the water tank. Remove the base
Disconnect This End of Pump Tubing to Drain Water Tank
cover, then disconnect the water tank end of the pump tubing to drain the water tank. SeeFig. 5. After the water tank has
Base Cover
drained, reconnect the pump tubing.
4) Remove the top and right side panels.
Fig. 5
5) Disconnect the FS connector from CB K5connector.
6) Check for continuity across FS leads. With the water tank empty, FS should be open. If open, continue to step 7. If closed, follow the steps in "II.F.2. Float Switch Cleaning." After cleaning FS, check it again. Replace if necessary.
7) Reconnect FS connector to CB K5 connector, then replace the right side and top panels and the base cover in their correct positions.
8) Move the control switch to the "ICE" position. Replace the front panel in its correct position, then turn on the power supply. After 1 min., the 1-min. ll cycle should end and the initial harvest cycle should begin. If the initial harvest cycle begins, FS is good and the check is complete. If the initial harvest cycle does not begin, continue to step 9.
9) Turn off the power supply.
10) Remove the front panel. Move the control switch to the "OFF" position.
11) Remove the top and right side panels.
12) Disconnect FS connector from CB K5 connector.
13) Check for continuity across FS leads. With the water tank full, FS should be closed. IfFS is closed and the icemaker will not switch from the 1-min. ll cycle to the initial harvest cycle, replace CB. If FS is open, conrm that the water tank is full. If the water tank is not full, check the water supply, water lters, and inlet water valve. If the water tank is full, follow the steps in "II.F.2. Float Switch Cleaning." After cleaning FS, check it again. Replace if necessary.
14) Replace cube guide and base cover (if applicable) in their correct positions.
15) Replace the right side and top panels in their correct positions.
16) Move the control switch to the "ICE" position, then replace the front panel in its correct position. Turn on the power supply to start the automatic icemaking process.
Legend: CB–control board; FS–oat switch
28
Page 29
2. Float Switch Cleaning
Depending on local water conditions, scale may build up on FS. Scale on the switch can cause the oat to stick. In this case, FS should be cleaned.
1) Turn off the power supply.
2) Remove the front panel, then move the control switch to the "OFF" position.
3) Remove the base cover, disconnect the water tank end of the pump tubing to drain the water tank. See Fig. 5. After the water tank has drained, reconnect the pump tubing.
4) Remove the cube guide, then pull the tab on the oat switch bracket to release the oat switch assembly from the water tank.
5) Remove the spring retainer clip from the oat switch rod, then remove the oat. Be careful not to bend the spring retainer clip excessively when removing it. See Fig. 6.
6) Wipe down the oat switch bracket assembly, stem, and oat with a mixture of 1 part Hoshizaki "Scale Away" and 25 parts warm water. Rinse the parts thoroughly with clean water. WARNING! Do not remove the lock nut on the oat switch assembly. This is
factory sealed and must not be removed.
7) Reassemble the oat switch assembly and replace it in its correct position.
8) Move the control switch to the "ICE" position.
9) Replace the base cover, cube guide, and front panel in their correct positions.
10) Turn on the power supply to start the automatic icemaking process.
Legend: CB–control board; FS–oat switch
Float Switch Bracket Assembly
Water Sealed Connections
Float Switch Stem
Float
Spring Retainer Clip
Float Switch Bracket Assembly
Water Sealed Connections
Float Switch Stem
Float
Spring Retainer Clip
Float Switch Tab
Fig. 6
29
Float Switch Tab
Page 30

G. Thermistor Check

To check thermistor resistance, follow the steps below.
1) Turn off the power supply.
2) Remove the front panel. Move the control switch to the "OFF" position, then remove the top and right side panels.
3) Remove the thermistor from the refrigerant tubing.
4) Immerse the thermistor sensor portion in a glass containing ice and water for 2 or 3 min.
5) Disconnect the thermistor connector from CB K3 connector and check the resistance between thermistor leads. Normal range is 4.7 to 6.2 kΩ. If outside the normal range, replace the thermistor. See "IV.B. Component Service Information." If within the normal range, continue to the next step.
6) Replace the thermistor in its correct position. See "IV.B. Component Service Information."
7) Reconnect the thermistor connector to CB K3 connector.
8) Replace the right side and top panels in their correct positions.
9) Move the control switch to the "ICE" position.
10) Replace the front panel in its correct position.
11) Turn on the power supply.
12) Once the harvest cycle starts (Comp energizes), begin timing the harvest cycle.
13) The harvest timer and harvest cycle should terminate within 2 to 5 min. If the harvest cycle does not terminate within 2 to 5 min., replace CB.
Legend: CB–control board; Comp–compressor

H. Control Switch

The control switch has two positions: "ON for power on, "PUMP" to energize the pump motor and circulate the water in the water tank.

I. Mode Switch

The mode switch has two positions: "ICE" for icemaking cycle, "CLEAN" for initiating the cleaning and sanitizing program.
30
Page 31

J. Diagnostic Tables

1. No Ice Production
No Ice Production - Possible Cause
1. Power Supply a) Off, blown fuse, or tripped breaker.
b) Not within specications.
2. Fuse (Control Box) a) Blown.
3. Control Switch a) In "OFF" or "PUMP" position.
b) Defective.
4. High-Pressure Switch a) Dirty condenser.
b) Fan motor not operating.
c) Refrigerant overcharged.
d) Bad contacts.
e) Refrigerant lines or components plugged.
5. Control Transformer (115VAC/10.5VAC)
6. Control Board See "II.D. Control Board Check"
7. Bin Control See "II.E.1. Bin Control Check"
8. Mode Switch a) In "CLEAN" position.
9. Water Supply a) Water supply off or improper water pressure.
10. Inlet Water Valve a) Screen or orice clogged.
11. Float Switch See "II.F. Float Switch Check and Cleaning"
12. Compressor a) Compressor relay/magnetic contactor contacts bad or coil winding
13. Hot Gas Valve a) Closed in harvest cycle.
14. Thermistor See "II.G. Thermistor Check"
15. Pump Motor a) Motor winding open.
a) Coil winding open or shorted.
a) In alarm.
b) CB yellow "BC OPEN" LED on (bin full).
c) Defective.
a) Tripped with bin lled with ice.
b) Sensor lens dirty.
c) Defective.
b) Defective.
b) External water lters clogged.
b) Coil winding open.
c) Water valve open in freeze cycle.
a) Float does not move freely.
b) Defective.
open.
b) Start capacitor or run capacitor defective (single phase).
c) Internal protector open.
d) Start relay contacts bad or coil winding open (single phase).
e) Compressor defective.
b) Open in freeze cycle.
a) Loose, disconnected, or defective.
b) Bearing worn out or locked rotor.
c) Defective capacitor.
d) Mechanical seal worn out.
31
Page 32
No Ice Production - Possible Cause
16. Thermostatic Expansion Valve a) Bulb loose.
b) Operating erratically.
1 7. Liquid Line Valve a) Closed in freeze cycle.
b) Open in harvest cycle.
18. Fan Motor a) Motor winding open.
b) Bearing worn out or locked rotor.
c) Defective capacitor.
19. Water System a) Water leaks causing short freeze time.
2. Freeze-Up
Defrost and clean the icemaker prior to diagnosing freeze-up. Fill out a freeze-up checklist. See "II.K. Freeze Up Check List," the Hoshizaki America Technician's Pocket Guide, or contact your local distributor for a copy of the freeze-up checklist.
Freeze-Up - Possible Cause
Harvest Cycle
1. Evaporator a) Scaled up.
b) Damaged.
2. Cube Guides a) Out of position.
b) Damaged.
3. Spray Tubes and/or Spray Guides
4. Water Supply a) Low water pressure.
5. Inlet Water Valve a) Screen or orice clogged.
6. Float Switch See "II.F. Float Switch Check and Cleaning"
7. Refrigerant Charge a) Low.
8. Control Board See "III.C. Settings and Adjustments" and "II.D. Control Board Check"
9. Bin Control See "II.E.1. Bin Control Check"
10. Thermistor See "II.G. Thermistor Check"
11. Thermostatic Expansion Valve a) Defective.
12. Hot Gas Valve a) Defective.
13. Liquid Line Valve a) Defective.
a) Dirty.
b) Out of position.
b) External water lters clogged.
c) Insufficient water line size.
Minimum 1/4" Nominal ID (6 mm Nominal OD in the EU) copper water tubing or equivalent.
b) Defective.
a) Dirty, sticking.
b) Defective.
a) Harvest timer (S4 dip switch 1 & 2) set too short.
b) Harvest pump timer (S4 dip switch 7) not in factory default position.
c) Defective.
a) Defective.
a) Loose, disconnected, or defective.
32
Page 33
Freeze-Up - Possible Cause
Freeze Cycle
1. Evaporator a) Scaled up.
b) Damaged.
2. Spray Tubes and/or Spray Guides
3. Refrigerant Charge a) Low.
4. Control Board See "II.D. Control Board Check"
5. Inlet Water Valve a) Leaking by.
6. Float Switch See "II.F. Float Switch Check and Cleaning"
7. Pump Motor a) RPM too slow.
8. Thermostatic Expansion Valve a) Bulb loose or defective.
9. Liquid Line Valve a) Restricted.
10. Headmaster (C.P.R.) (remote models)
a) Dirty.
b) Out of position.
a) Freeze timer (S4 dip switch 9 & 10) set incorrectly.
b) Defective.
a) Float does not move freely.
b) Defective.
b) Impeller damaged.
a) Not bypassing.
3. Low Ice Production
Low Ice Production - Possible Cause
Long Harvest Cycle
1. Evaporator a) Scaled up.
2. Spray Tubes and/or Spray Guides
3. Refrigerant Charge a) Low.
4. Water Supply a) Low water pressure.
5. Control Board See "II.D. Control Board Check"
6. Thermistor See "II.G. Thermistor Check"
7. Hot Gas Valve a) Erratic or closed.
8. Inlet Water Valve a) Screen or orice clogged.
9. Compressor a) Inefficient or off.
10. Liquid Line Valve a) Erratic or open.
11. Thermostatic Expansion Valve a) Defective.
a) Dirty.
b) Out of position.
b) External water lters clogged.
c) Insufficient water line size.
Minimum 1/4" Nominal ID (6 mm Nominal OD in the EU) water tubing or equivalent.
d) Too cold.
a) Thermistor connection loose (K3).
b) Defective.
a) Loose, disconnected, or defective.
33
Page 34
Low Ice Production - Possible Cause
Long Freeze Cycle
1. Evaporator a) Scaled up, dirty.
2. Float Switch See "II.F. Float Switch Check and Cleaning"
3. Inlet Water Valve a) Leaking by.
4. Hot Gas Valve a) Erratic or open.
5. Condenser a) Clogged.
6. Control Board See "II.D. Control Board Check"
7. Refrigerant Charge a) Low.
8. Thermostatic Expansion Valve a) Bulb loose.
9. Compressor a) Inefficient or off.
10. Pump Motor a) RPM too slow.
11. Liquid Line Valve a) Erratic or restricted.
12. Headmaster (C.P.R.) (remote models)
13. Splash Guard a) Out of place.
a) Scaled up, dirty.
b) Float sticking.
c) Defective switch.
a) Float switch connection loose (K5).
b) Defective.
b) Defective.
a) Not bypassing.
b) Missing or damaged.
Freeze-Time Correction Cycle Initiated
1. Evaporator a) Scaled up, dirty.
2. Float Switch See "II.F. Float Switch Check and Cleaning"
3. Refrigerant Charge a) Low.
4. Splash Guard a) Out of place.
5. Distribution/Spray Tubes a) Scaled up, dirty.
6. Cube Guides a) Out of position.
7. See "2. Freeze Up" Above
a) Scaled up, dirty.
b) Float sticking.
c) Defective switch.
b) Missing or damaged.
b) Damaged.
34
Page 35

K. Freeze-Up Check List

Freeze-Up Check List
Please Complete When Diagnosing a Freeze-Up, Refrigerant Leak, or Low Charge
Technical Support Fax #: 770-487-3360
Make Copies And Use As Needed
Model #___________________________ Serial # _________________________Install Date______________Fail Date___________
List model and manufacture of bin or dispenser__________________________.
Date appliance was last cleaned:__________.
Freeze-Up Defrost
YES NO [ ] [ ] 1) After defrosting, was the appliance leak
checked?
[ ] [ ] 2) Were any leaks found?
If so where?_____________________.
[ ] [ ] 3) Was any refrigerant added to the unit?
If so, how much?_________________.
Set Up
[ ] [ ] 4) Is the appliance stand alone? [ ] [ ] 5) Is water line independent? [ ] [ ] 6) Is water line correct size? If not________”.
3/8" Nominal ID Copper Water Tubing or Equivalent.
7) What is water pressure?___________. Water Temperature_________.
[ ] [ ] 8) Does appliance have any water ltration?
If yes please list the following: Filter brand___________________. Model________________. Filter pressure gauge reading during the ll cycle___________. Date lter was last replaced?__________________________. GPM or LPM ow rate of lter system?__________________.
9) Ambient temperature at appliance? ______________.
At remote condenser (if applicable)?________.
Appliance Status
[ ] [ ] 10) Is the appliance and/or oat switch dirty?
11) List the S4 (1-10) and S5 (1-5) DIP switch settings.
S4: 1___2___3___4___5___6___7___8___9___10____ S5: 1_____2_____3_____4_____5______ [ ] [ ] 12) Is DIP switch number 7 ON (harvest pump
time (harvest assist) all models and freeze-time correction models with control board
2A7664-02? [ ] [ ] 13) Is the cube guide positioned correctly? [ ] [ ] 14) Are the evaporator separators positioned
properly? [ ] [ ] 15) Is the thermistor properly mounted, tight, and
insulated? [ ] [ ] 16) Is the TXV bulb properly mounted, tight, and
insulated? [ ] [ ] 17) Are splash guards in place?
Appliance Sequence of Operation
Fill YES NO [ ] [ ] 18) Does the water tank ll and overow?
60-90 sec. Note: Larger models may take up to 120 seconds to overow when empty.
[ ] [ ] 19) If NO in step 17, is water ow 5GPM for larger?
Harvest [ ] [ ] 20) Is the hot gas valve opening? [ ] [ ] 21) Is harvest pump time (harvest assist) utilized
(S4dip switch 7)? [ ] [ ] 22) Is hot gas valve opening in harvest? [ ] [ ] 23) Does water valve close completely when
de energized?
24) What was length of harvest?___________.
Freeze [ ] [ ] 25) Is pump motor energized in freeze cycle except
during 10-sec. anti-slush. If activated (S5 dip
switch 5 on)?
26) Water-cooled condenser outlet temperature 5-min. into freeze? ______________°F.
27) What was length of freeze?____________.
[ ] [ ] 28) Is the cube size consistent from inlet to outlet of
evaporator?
[ ] [ ] 29) Is ice still dropping when next freeze cycle starts?
30) What is the ice drop weight?___________.
31) What is head pressure? Freeze_________Harvest_______. (Freeze pressure should be taken 5 minutes into the cycle).
32) What is suction pressure? Freeze______Harvest_______. (Freeze pressure should be taken 5 minutes into the cycle).
[ ] [ ] 33) When activating bin control, did appliance
shutdown within 15seconds in the rst 5minutes of freeze cycle?
Note: Make copies of this form and use it when diagnosing a freeze up condition. Submit a completed copy of the checklist
along with the freeze-up labor claim form.
35
Page 36

III. Controls and Adjustments

• A Hoshizaki exclusive control board is employed in KM series appliances.
• All models are pretested and factory adjusted.
• For a control board check procedure, see "II.C. Control Board Check."
NOTICE
• Fragile, handle very carefully.
• The control board contains integrated circuits, which are susceptible to failure due to static discharge. It is especially important to touch the metal part of the icemaker when handling or replacing the control board.
• Do not touch the electronic devices on the control board or the back of the control board.
• Do not change wiring and connections. Do not misconnect K3 WHITE, K4RED, and K5 BLACK, because the same connector is used for the thermistor, bin control, and oat switch.
• Do not short out power supply to test for voltage.
• Always replace the whole control board assembly if it goes bad.
36
Page 37

A. Control Board Layout

1. "K" Control Board
"K" Control Board
• "ALARM RESET" Button
• Bin Control Switch Open LED (yellow)
• K9 (white)
(Cleaning and Sanitizing Circuit)
• Ext. Harvest LED (yellow)
(blinks when 3rd occurrence of freeze time correction initiates within 36 hr.)
• Alarm Buzzer
• POWER OK LED (red) (lights when
10.5VAC is supplied to K2 connector)
• Relay LEDs
(4) (indicate which relays are energized and which K1 connector pins are energized
• LED 2 (X2 Relay)
LED 2 on: K1 Connector Pin #3
• LED 3 (X3 Relay)
LED 3 on: K1 Connector Pin #4
• LED 5 (X5 Relay)
LED 5 on: K1 Connector Pin #5
• LED 4 (X4 Relay) K1 Connector Pin #6
• LED 1 (X1 Relay)
K1 Connector Pin #9
• S4 Dip Switch
• K2 Connector
Control Transformer (10.5VAC)
• "OUTPUT TEST" Button
(used to test relays on control board)
• K3 (white) Connector
Thermistor (harvest control and high temperature safety)
• K4 (red) Connector
Bin Control
• S5 Dip Switch
• K5 (black) Connector
Float Switch
• Part Number
• K1 Connector
Pins #1 through #10 #1 Hot Gas Valve (#2) and Fan Motor/Liquid Line Valve (#3) Power Supply #2 Hot Gas Valve #3 Fan Motor Liquid Line Valve #4 Pump Motor #5 Drain Valve #6 Inlet Water Valve #7, 8 Open #9 Compressor Relay, Pin #1 Power Supply (Hot Gas Valve (#2) and Fan Motor/Liquid Line Valve (#3)) #10 Component Power Supply
"K" Control Board
Part Number 2A8242-01
37
Page 38

B. LED Lights and Audible Alarm Safeties

Beep occurs and red CB "POWER OK" LED turns on when control switch is moved to "ICE" position.
Sequence
Green LEDs 1 through 5 turn on and sequence from initial startup as listed in the table below. Order of green LEDs from the outer edge of control board is 1, 4, 5, 3, 2.
Sequence Step LED
1-Minute Fill Cycle 4 WV Harvest Cycle 1, 4 Comp, FMR, HGV, WV 1 minute 20 minutes Harvest Pump Time
(harvest assist) Freeze Cycle 1, 2, 3 Comp, FM/FMR, PM, LLV 5 minutes freeze timer
Anti-Slush Control 1, 2 Comp, FM/FMR, LLV PM off 10 sec. when
Pump-Out Cycle 1, 4 *pump-out timer setting
1, 3 Comp, FMR, HGV, PM 0 seconds 50 seconds
*
, 5, 3 Comp, FMR, HGV, PM, WV*, DV 10 seconds 20 seconds
Energized
Components
Time LEDs are On
Min. Max.
setting
thermistor at 36°F (2°C)
Alarms
Type Alarm Notes
1
Beep
2
Beep
3
Beep
LED Blink Freeze-Time
To reset above safeties, press "ALARM RESET" button with power supply on.
6 Low Voltage
7 High Voltage
High Evaporator Temp. (temperature > 127°F) (53°C)
Harvest Backup Timer (harvest > 20 min. for two cycles in a row)
Freeze Timer (freeze > freeze timer setting for two cycles in a row)
Correction (maximum freeze time differential exceeded)
(92Vac±5% or less)
(147Vac±5% or more)
Check for harvest problem (stuck HGV or relay), hot water entering unit, stuck HM, or shorted thermistor.
Check thermistor (open), HGV not opening, TXV or LLV leaking by, low charge, inefficient Comp, or WRV leaking by.
Check FS stuck closed (up), WV leaking by, HGV leaking by, PM not pumping, TXV defective, LLV not opening, low charge, HMnot bypassing, or inefficient Comp.
CB red "POWER OK" LED blinks. 3rdfreeze-time correction cycle in 36hours starts CByellow "EXT HARVEST" LED blinking. Fill out freeze-up checklist.
Red LED turns off if voltage protection operates. Control voltage safeties automatically reset when voltage is corrected.
Legend: Comp–compressor; DV–drain valve; FM–fan motor; FMR–fan motor remote;
FS–oat switch; HGV–hot gas valve; HM–headmaster (C.P.R.); L LV –liquid line valve; PM–pump motor; TXV–thermostatic expansion valve; WRV–water regulating valve; WV–inlet water valve
38
Page 39

C. Settings and Adjustments

NOTICE
Dip switches are factory set. Failure to maintain factory settings may adversely affect performance and warranty coverage. For more information, contact your Hoshizaki Service Center.

1. Default Dip Switch Settings

The dip switches are factory-adjusted to the following positions:
S4 Dip Switch No. 1 2 3 4 5 6 7 8 9 10
KM-350MAJ, KM-350MWJ OFF OFF OFF ON ON OFF ON OFF ON ON
KM-520MAJ, KM-520MWJ, KM-520MRJ OFF OFF OFF OFF OFF OFF ON OFF ON ON
KM-660MAJ, KM-660MWJ, KM-660MRJ OFF OFF OFF OFF OFF OFF ON OFF ON ON
S5 Dip Switch (Do Not Adjust)
Dip Switch No.
All Models OFF OFF OFF OFF ON
1 2 3 4 5
ON
S4 Dip Switch
Freeze Timer (9 & 10)
Factory Use (8) Harvest Pump Time (Harvest Assist)/Freeze-Time Correction (7) (Do Not Adjust)
Harvest Pump Time (Harvest Assist) (6) (Do Not Adjust)
Pump-Out Frequency Control (5)
Pump-Out Time/Harvest Time During Pump-Out (3 & 4)
1 2 3 4 5 6 7 8 9 10
Harvest Time (1 & 2)
S5 Dip Switch
(Do Not Adjust)
Anti-Slush (5)
Minimum Harvest Time (4)
Rell Counter (2 and 3)
ON
1 2 3 4 5
Float Switch Selector (1)
39
Page 40

2. Harvest Time (S4 dip switch 1 & 2)

The harvest timer starts counting when the thermistor reaches 48°F (9°C) at the evaporator outlet and the control board reads 3.9 kΩ from the thermistor. The harvest timer is factory set, and generally no adjustment is required. However, a setting longer than the factory setting may be advised in cases where the drain provided at harvest needs to be prolonged for extra cleaning. Note that the pump-out timer (S4 dip switch 3&4) acts in place of the harvest timer during cycles with a pump out. For details, see "III.C.3. Pump-Out Timer (S4 dip switch 3& 4)."
Note: On models with a pump-out every cycle, the harvest timer is only relevant during
the initial harvest cycle since a pump out occurs every cycle thereafter.
Time
S4 Dip Switch Setting
No. 1 No. 2 S5-4 OFF S5-4 ON
OFF OFF 60 30
ON OFF 90 45
OFF ON 120 60
ON ON 180 75
(sec.)

3. Pump-Out Time/Harvest Time During Pump-Out (S4 dip switch 3 & 4)

When a pump-out is called for, the pump motor stops for 2 sec. After 2 sec. the drain valve and pump motor energize. On KM-350M_J models the inlet water valve also energizes. Water is removed from the bottom of the water tank and sent down the drain. The pump-out drains the water tank for the time determined by the pump-out timer. The pump-out timer also acts in place of the harvest timer during cycles with a pump-out. The pump-out timer is factory set, and generally no adjustment is required. However, where water quality is bad and the icemaker needs a longer pump-out time, the pump-out timer can be adjusted. The pump-out timer control can be set to pump-out for 10 or 20 sec. During pump-out cycles minimum harvest time is based on times given in the table below.
S4 Dip Switch Setting Time (sec.)
T1 T2
No. 3 No. 4
OFF OFF 10 150 100 Closed Closed
ON OFF 10 180 130 Closed Closed
OFF ON 10 120 70 Open Closed
ON ON 20 180 180 Closed Closed
T1: Time to drain the water tank T2: Harvest timer at pump out
Inlet Water
Valve
S5-4 OFF S5-4 ON S5-4 OFF S5-4 ON
40
Page 41

4. Pump-Out Frequency Control (S4 dip switch 5)

The pump-out frequency control is factory set to drain the water tank every 10 cycles. Generally no adjustment is required. However, where water quality is bad and the icemaker needs a pump-out more often, the pump-out frequency can be adjusted. The pump-out frequency control can be set to have a pump-out occur every cycle, or every 10 cycles.
The rst pump-out is dependent on S4 dip switch 5. See the table below.
S4 Dip Switch Setting
No. 5
OFF Every 10 cycles After 11th freeze cycle
ON Every cycle After 2nd freeze cycle
Pump-Out Frequency 1st Pump-Out

5. Harvest Pump Time (Harvest Assist) (S4 dip switch 6)

NOTICE
Factory set for proper operation. Do not adjust. Adjustment outside of the factory default setting may result in damage to the appliance.
Harvest pump time (harvest assist) is only active when S4 dip switch 7 is in the "ON" position. In the factory default position, the harvest pump time (harvest assist) starts with 50sec. left to go in harvest cycle (S4 dip switch 6) and after the thermistor reaches 48°F (9°C) at the evaporator outlet and the control board reads 3.9kΩ from the thermistor. The harvest pump time (harvest assist) is factory set, and no adjustment is required.
Harvest Pump Time
S4 Dip Switch Setting
No. 6 S5-4 OFF S5-4 ON
OFF 50 sec. 25 sec.
ON 25 sec. 15 sec.
(Harvest Assist)
41
Page 42

6. Harvest Pump Time (Harvest Assist)/Freeze-Time Correction (S4 dip switch 7)

NOTICE
Factory set for proper operation. Do not adjust. Adjustment outside of the factory default setting may result in damage to the appliance.
a) Harvest Pump Time (Harvest Assist)
Depending on S4 dip switch 7 setting, the pump motor either stays off or is energized during the last seconds of the harvest cycle. When the pump motor is energized (S4 dip switch 7 on), water circulates over the evaporator. The harvest water valve is open during harvest for a maximum of 6 minutes or the length of harvest minus the harvest pump time value(S4 dip switch 6), whichever is shorter.
When S4 dip switch 7 is in the on position and harvest begins, 50 sec. before harvest termination, LED 4 turns off, inlet water valve Next, LED 3 turns on and control board K1connector pin #4 (R) energizes, energizing the pump motor for the last seconds of harvest. Harvest pump time adjusted by S4 dip switch 1 & 2 and S5 dip switch 4settings. Contact Technical Support before adjusted these settings.
b) Freeze-Time Correction
When S4 dip switch 7 is in the on position, freeze-time correction enabled. See "II.C. Freeze-Time Correction Cycle (90 min.)."
S4 Dip Switch Setting Harvest Pump
Time (sec.)
No. 7
OFF 0 Disabled
ON 50 Enabled
(Harvest Assist)
Freeze-Time
Correction

7. Factory Use (S4 dip switch 8)

Factory set for proper operation. Do not adjust. This must be left in the factory default position.
42
Page 43

8. Freeze Timer (S4 dip switch 9 & 10)

NOTICE
Adjust to proper specication, or the icemaker may not operate correctly.
The freeze timer setting determines the maximum allowed freeze time to prevent possible freeze-up issues. Upon termination of the freeze timer, the control board initiates the harvest cycle or pump-out cycle. After 2 consecutive freeze timer terminations, the control board shuts down the icemaker. In this case, see "II.J.3. Low Ice Production" for possible solutions. The freeze timer is factory set and no adjustment is required. Before changing this setting, contact Hoshizaki Technical Support at 1-800-233-1940 for recommendations.
S4 Dip Switch Setting Time
No. 9 No. 10
OFF OFF 60
OFF ON 50
ON OFF 70
ON ON 75

9. Pump-Out Pump Motor Direction (S5 dip switch 1)

(min.)
NOTICE
Do not adjust. This must be left in the factory default position or the icemaker will not operate correctly.
The pump-out pump motor direction setting determines pump motor rotation during pump-out. On models with a drain valve pump motor rotation doesn't change at pump-out. Pump motor rotates in forward direction and drain valve is energized for pump-out. On models with a check valve, pump motor rotation reverses at pump-out. Pump motor rotates in reverse direction and opens check valve for pump-out.
S5 Dip Switch Setting
Pump-Out ComponentsNo. 1
OFF Pump Motor Forward Rotation and Drain Valve
ON Pump Motor Reverse Rotation and Check Valve
43
Page 44
10. Rell Counter (S5 dip switch 2 and 3)
NOTICE
Do not adjust. These must be left in the factory default position or the icemaker will not operate correctly.
S5 Dip Switch Setting Rell
No. 2 No. 3
OFF OFF 0
OFF ON 1 rell
ON OFF 9 rells
ON ON 10 rells
Counter

11. Minimum Harvest Time (S5 dip switch 4)

NOTICE
Factory set for proper operation. Do not adjust. Adjustment outside the factory default setting may result in damage to the appliance.
S5 Dip Switch Setting Minimum
No. 4
OFF 120 sec.
ON 70 sec.
Harvest Timer

12. Anti-Slush (S5 dip switch 5)

This dip switch setting provides anti-slush control during the freeze cycle. When the evaporator temperature reaches 36°F (2.2°C) the control board reads a 5.8 kΩ signal from the thermistor and de-energizes the water pump for 10 sec. to melt the ice slush and prevent the ice slush from blocking the water supply tubing, causing irregular freeze patterns.
NOTICE
Factory set for proper operation. Do not adjust. Adjustment outside the factory default setting may result in damage to the appliance.
S5 Dip Switch Setting
Anti-SlushNo. 5
OFF Disabled
ON Enabled
44
Page 45

IV. Refrigeration Circuit and Component Service Information

WARNING
• This appliance should be diagnosed and repaired only by qualied service personnel to reduce the risk of death, electric shock, serious injury, or re.
• Move the control switch to the "OFF" position and turn off the power supply. Place the disconnect in the "OFF" position. Lockout/Tagout to prevent the power supply from being turned back on inadvertently.
CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews are securely in place after the icemaker is serviced. Make sure that none have fallen into the dispenser unit/ice storage bin.
• Make sure all food zones in the icemaker and dispenser unit/ice storage bin are clean after service.

A. Refrigeration Circuit Service Information

WARNING
• Repairs requiring the refrigeration circuit to be opened must be performed by properly trained and EPA-certied service personnel.
• Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of refrigerant to the system (if using an electronic leak detector), and then raise the pressure using nitrogen gas (140 PSIG). Do not use R-404A as a mixture with pressurized air for leak testing.
NOTICE
• Always recover the refrigerant and store it in an approved container. Do not discharge the refrigerant into the atmosphere.
• Do not leave the system open for longer than 15 min. when replacing or servicing parts. The Polyol Ester (POE) oils used in R-404A applications can absorb moisture quickly. Therefore it is important to prevent moisture from entering the system when replacing or servicing parts.
• Always install a new drier every time the sealed refrigeration system is opened. Do not replace the drier until after all other repair or replacement has been made. Install the new drier with the arrow on the drier in the direction of the refrigerant ow.
• When brazing, protect the drier by using a wet cloth to prevent the drier from overheating. Do not allow the drier to exceed 250°F (121°C).
1. Refrigerant Recovery
The icemaker is provided with refrigerant access valves. Using proper refrigerant practices, recover the refrigerant. Store the refrigerant in an approved container. Do not discharge the refrigerant into the atmosphere.
45
Page 46
2. Brazing
WARNING
• R-404A itself is not ammable at atmospheric pressure and temperatures up to 176°F (80°C).
• R-404A itself is not explosive or poisonous. However, when exposed to high temperatures (open ames), R-404A can be decomposed to form hydrouoric acid and carbonyl uoride both of which are hazardous.
• Do not use silver alloy or copper alloy containing arsenic.
1) Braze all ttings while purging with nitrogen gas owing at a pressure of 3 to 4 PSIG. Note: Because the pipes in the evaporator case are specially coated to resist corrosion,
it is important to make connections outside the evaporator case when possible. Ifit is necessary to braze inside the evaporator case, use sandpaper to remove the coating from the brazing connections before unbrazing the components.
NOTICE
• Always install a new drier every time the sealed refrigeration system is opened.
• Do not replace the drier until after all other repair or replacement has been made. Install the new drier with the arrow on the drier in the direction of the refrigerant ow.
• When brazing, protect the drier by using a wet cloth to prevent the drier from overheating. Do not allow the drier to exceed 250°F (121°C).
2) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of refrigerant to the system (if using an electronic leak detector), and then raise the pressure using nitrogen gas (140 PSIG). Do not use R-404A as a mixture with pressurized air for leak testing.
3. Evacuation and Recharge (R-404A)
1) Attach a vacuum pump to the system. Be sure to connect the charging hoses to both high and low-side refrigerant access valves.
IMPORTANT
The vacuum level and vacuum pump may be the same as those for current refrigerants. However, the rubber hose and gauge manifold to be used for evacuation and refrigerant charge should be exclusively for POE oils.
2) Turn on the vacuum pump. Open the gauge manifold valves. Never allow the oil in the vacuum pump to ow backwards.
3) Allow the vacuum pump to pull down to a 29.9" Hg vacuum. Evacuating period depends on pump capacity.
4) Close the low-side valve and high-side valve on the gauge manifold.
46
Page 47
5) Disconnect the gauge manifold hose from the vacuum pump and attach it to a refrigerant service cylinder. Remember to loosen the connection and purge the air from the hose. For the required refrigerant charge, see the rating label inside the icemaker. Hoshizaki recommends only virgin refrigerant or reclaimed refrigerant which meets ARI Standard 700 (latest edition) be used.
6) A liquid charge is required when charging an R-404A system (to prevent fractionation). Place the service cylinder on the scales; if the service cylinder is not equipped with a dip tube, invert the service cylinder, then place it on the scales. Open the high-side valve on the gauge manifold.
7) Allow the system to charge with liquid until the proper charge weight is met.
8) If necessary, add any remaining charge to the system through the low-side.
NOTICE!To prevent compressor damage, use a throttling valve or liquid dispensing device to add the remaining liquid charge through the low-side refrigerant access valve with the icemaker running.
9) Close the high and low-side gauge manifold valves, then disconnect the gauge manifold hoses.
10) Cap the refrigerant access valves to prevent a possible leak.
47
Page 48

B. Component Service Information

NOTICE
When replacing a component listed below, see the notes to help ensure proper operation.
Component Notes
Compressor 1 phase: Install a new start capacitor, run capacitor, and start relay.
Thermostatic Expansion Valves
Hot Gas Valves Liquid Line Valves
Fan Motors Install a new capacitor.
Pump Motor Install a new capacitor.
Thermistor • Attach the new thermistor to the suction line in the same location as the previous
• Attach the thermostatic expansion valve bulb to the suction line in the same location as the previous bulb.
• The bulb should be between the 10 and 2 o'clock positions on the tube.
• Secure the bulb with the clamp and holder, then insulate it.
• Replace the strainer if applicable.
• Use copper tube of the same diameter and length when replacing valve lines.
thermistor.
• The thermistor should be at the 12 o'clock position on the tube.
• Smoothly ll the recessed area of the thermistor holder with high thermal conductive type sealant. Hoshizaki America part number 4A0683-01 (Silicone Heat Sink Compound 10-8108 manufactured by GC Electronics), KE-4560 RTV (manufactured by ShinEtsu Silicones), or equivalent are recommended.
• Secure the thermistor with the holder, then insulate it.
• Be very careful to prevent damage to the leads.
48
Page 49

C. Water Regulating Valve Adjustment (water-cooled model)

The water regulating valve is factory set, and generally no adjustment is required. However, when necessary, adjust the water regulator using the following procedure.
1) Prepare a thermometer to check the condenser drain temperature. Attach a pressure gauge to the high-side line of the system.
2) 5 min. after a freeze cycle starts, conrm that the thermometer reads 104°F to 115°F (40°C to 46°C). If it does not, rotate the adjustment screw by using a at blade screwdriver until the temperature is in the proper range. See Fig. 7. Next, check that the reference pressure is in the range indicated in the Head Pressure table in the Performance Data section. If it is not in the
Top View
proper range, verify the refrigerant charge.
3) Check that the condenser drain temperature is stable.
Adjustment Screw
CW – Higher CCW – Lower
Fig. 7
49
Page 50

V. Maintenance

The maintenance schedule below is a guideline. More frequent maintenance may be required depending on water quality, the appliance's environment, and local sanitation regulations
WARNING
• Only qualied service technicians should service the appliance.
• To reduce the risk of electric shock, do not touch the control switch or service switch with damp hands
• Before servicing: Move the control switch to the "OFF" position and turn off the power supply. Place the disconnect in the "OFF" position. Lockout/Tagout to prevent the power supply from being turned back on inadvertently.
CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews are securely in place after any maintenance is done to the icemaker. Make sure that none have fallen into the dispenser unit/ice storage bin.
Maintenance Schedule
Frequency Area Task
Daily Scoop Clean the ice scoop using a neutral cleaner. Rinse thoroughly after
cleaning. Bi-Weekly Air Filters Inspect. Wash with warm water and neutral cleaner if dirty. Monthly External Water
Filters Icemaker Exterior Wipe down with a clean, soft cloth. Use a damp cloth containing a
Underside of Icemaker and Top Kits; Bin Door and Snout
Yearly Icemaker and
Dispenser Unit/Ice Storage Bin Liner
Water Supply Inlet Close the icemaker water supply line shut-off valve and drain the water
Condenser Inspect. Clean if necessary by using a brush or vacuum cleaner. More
Water Hoses Inspect the water hoses and clean/replace if necessary.
Check for proper pressure and change if necessary.
neutral cleaner to wipe off oil or dirt build up. Clean any chlorine staining
(rust colored spots) using a non-abrasive cleanser.
Wipe down with a clean cloth and warm water.
Clean and sanitize per the cleaning and sanitizing instructions provided
in the instruction manual or maintenance label on the icemaker.
system. Clean the water supply inlet screen.
frequent cleaning may be required depending on location.
50
Page 51

VI. Preparing the Appliance for Periods of Non-Use

NOTICE
• When storing the appliance for an extended time or in sub-freezing temperatures, follow the instructions below to prevent damage.
• To prevent damage to the water pump, do not operate the appliance with the control switch in the "WASH" position when the water tank is empty.
When the appliance is not used for two or three days under normal conditions, it is sufficient to move the control switch to the "OFF" position. When storing the appliance for an extended time or in sub-freezing temperatures, follow the instructions below.
1. Remove the water from the icemaker water line:
1) Turn off the power supply, then remove the front panel.
2) Close the icemaker water supply line shut-off valve and open the icemaker water supply line drain valve.
3) Allow the line to drain by gravity.
4) Attach a compressed air or carbon dioxide supply to the icemaker water supply line drain valve.
5) Make sure at least 3 min. have elapsed since you turned off the power supply. Make sure the control switch is in the "ICE" position. Replace the front panel in its correct position, then turn on the power supply.
6) Blow the icemaker water supply line out using the compressed air or carbon dioxide supply.
7) Close the icemaker water supply line drain valve.
2. Remove the water from the water tank:
1) Turn off the power supply, then remove the front panel.
2) Move the control switch to the "OFF" position.
3) Drain the water tank. remove the base cover, then disconnect one end of the
Disconnect This End of Pump Tubing to Drain Water Tank
pump tubing to drain the water tank. SeeFig. 8. After the water tank has drained, reconnect the pump tubing.
4) Replace the base cover (if applicable) and front panel in their correct positions.
Base Cover
Fig. 8
5) Remove all ice from the dispensing unit/ice storage bin. Clean the storage bin liner using a neutral cleaner. Rinse thoroughly after cleaning.
51
Page 52
3. On water-cooled model, remove the water from the water-cooled condenser:
1) Make sure the power supply is off, then remove the front panel and right side panel.
2) Close the condenser water supply line shut-off valve. If connected to a closed loop system, also close the condenser return line shut-off valve.
3) Open the condenser water supply line drain valve. If connected to a closed loop system, also open the condenser return line drain valve.
4) Attach a compressed air or carbon dioxide supply to the condenser water supply line drain valve.
5) Open the water regulating valve by using a screwdriver to pry up on the spring retainer underneath the spring. While holding the valve open, blow out the condenser using the compressed air or carbon dioxide supply until water stops coming out.
6) Close the drain valve(s).
7) Replace the right side panel and front panel in their correct positions.
52
Page 53

VII. Disposal

The appliance contains refrigerant and must be disposed of in accordance with applicable national, state, and local codes and regulations. Refrigerant must be recovered by properly certied service personnel.
53
Page 54

VIII. Technical Information

We reserve the right to make changes in specications and design without prior notice.
A. Specication and Performance Data Sheets
Pressure data is recorded at 5 min. into freezing cycle. The data not in bold should be used for reference only.

1. KM-350MAJ

Specification Sheet
AC SUPPLY VOLTAGE 115/60/1 AMPERAGE 9.05 A ( 5 Min. Freeze AT 104°F / WT 80°F) MINIMUM CIRCUIT AMPACITY 15 A MAXIMUM FUSE SIZE 15 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 890 (5.42) 810 (3.99) WATER gal./24HR (gal./100 lbs.) 57 (14.5) 136 (27.8) ICE PRODUCTION PER CYCLE 10.5 lbs. (4.8 kg) 480 pcs. BIN CONTROL SYSTEM Ultra-Sonic Sensor REFRIGERANT CHARGE R404A, 1 lb. 3.4 oz. (550g)
Performance Data Sheet
APPROXIMATE ICE PRODUCTION PER 24 HR.
lbs./day kg./day APPROXIMATE ELECTRIC CONSUMPTION
watts 100/38 APPROXIMATE WATER CONSUMPTION PER 24 HR.
gal./day m3/day FREEZING CYCLE TIME
min. 100/38 HARVEST CYCLE TIME
min. 100/38 HEAD PRESSURE
PSIG kg/cm2G SUCTION PRESSURE
PSIG kg/cm2G
AMBIENT TEMP.
(ºF/ºC)
70/21 489 222 80/27 468 212 424 192 407 185 90/32 461 209 393 178 372 169
100/38 461 209 388 176 353 160
70/21 80/27 90/32
70/21 136 0.52 80/27 119 0.45 82 0.31 85 0.32 90/32 113 0.43 57 0.22 54 0.20
100/38 87 0.33 56 0.21 51 0.19
70/21 80/27 90/32
70/21 80/27 90/32
70/21 233 16.4
80/27 245 17.2 270 19.0 304 21.4 90/32 249 17.5 287 20.2 320 22.5
100/38 257 18.1 295 20.7 350 24.6
70/21 58 4.1 59 4.1 60 4.2 80/27 58 4.1 59 4.2 60 4.2 90/32 59 4.1 60 4.2 61 4.3
100/38 59 4.1 60 4.2 62 4.4
50/10 70/21 90/32
810
828 833 852
29
31 31 31
3.1
2.9
2.8
2.4
WATER TEMP. (ºF/ºC)
461 209 437 198
833 864
890
905
113 0.43 103 0.39
31 34
37
37
2.8
2.3
2.0
2.0
249 17.5 278 19.6
888 931 953
1010
33 36 38 40
2.7
2.4
2.0
2.0
TOTAL HEAT OF REJECTION FROM CONDENSER TOTAL HEAT OF REJECTION FROM COMPRESSOR 1,000 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
5,700 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
54
Page 55

2. KM-350MWJ

y
Specification Sheet
AC SUPPLY VOLTAGE 115/60/1 AMPERAGE 7.5 A ( 5 Min. Freeze AT 104°F / WT 80°F) MINIMUM CIRCUIT AMPACITY 15 A MAXIMUM FUSE SIZE 15 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 780 (4.90) 770 (4.47) WATER gal./24HR (gal./100 lbs.) 59 (15.5) 96 (23.2) WATER COOLED CONDENSER 415 (109) 139 (34) gal./24HR (gal./100 lbs.) ICE PRODUCTION PER CYCLE 10.5 lbs. (4.8 kg) 480pcs. BIN CONTROL SYSTEM Ultra-Sonic Sensor REFRIGERANT CHARGE R404A, 0 lb. 11.6 oz. (330g)
Performance Data Sheet
APPROXIMATE ICE PRODUCTION PER 24 HR.
lbs./day kg./da APPROXIMATE ELECTRIC CONSUMPTION
watts 100/38 APPROXIMATE WATER CONSUMPTION PER 24 HR.
gal./day m3/day FREEZING CYCLE TIME
min. 100/38 HARVEST CYCLE TIME
min. 100/38 HEAD PRESSURE
PSIG kg/cm2G SUCTION PRESSURE
PSIG kg/cm2G
AMBIENT TEMP.
(ºF/ºC)
70/21 414 188 405 184 390 177 80/27 407 185 393 178 376 171 90/32 405 184 383 174 366 166
100/38 401 182 379 172 351 159
70/21 80/27 90/32
70/21 236 0.89 306 1.16 416 1.57 80/27 289 1.09 398 1.51 516 1.95 90/32 306 1.16 475 1.80 592 2.24
100/38 417 1.58 502 1.90 699 2.65
70/21 80/27 90/32
70/21 80/27 90/32
70/21 228 16.0 228 16.0 233 16.4 80/27 228 16.0 228 16.0 235 16.5 90/32 228 16.0 228 16.0 234 16.5
100/38 231 16.2 229 16.1 240 16.9
70/21 59 4.1 59 4.2 59 4.2 80/27 59 4.2 60 4.2 60 4.2 90/32 59 4.2 60 4.2 60 4.2
100/38 59 4.2 60 4.2 60 4.2
50/10 70/21 90/32
770 773 774 772 777 776 773 780 780 772
34 35 36 35 36 37 35 37 38 35 37
2.8 2.6 2.5
2.7 2.4 2.3
2.6 2.2 2.1
2.4
WATER TEMP. (ºF/ºC)
780 780
38
2.1 2.0
TOTAL HEAT OF REJECTION FROM CONDENSER TOTAL HEAT OF REJECTION FROM COMPRESSOR 900 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)] WATER FLOW FOR CONDENSER 27 gal./h [AT 100ºF (38ºC) / WT 90ºF (32ºC)]
6,600 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
55
Page 56

3. KM-520MAJ

lbs./day
kg./day
Specification Sheet
AC SUPPLY VOLTAGE 115/60/1 AMPERAGE 10.6 A ( 5 Min. Freeze AT 104°F / WT 80°F) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 940 (4.68) 840 (3.64) WATER gal./24HR (gal./100 lbs.) 71 (14.7) 180 (32.4) ICE PRODUCTION PER CYCLE 10.3 lbs. (4.7 kg) 480pcs. BIN CONTROL SYSTEM Ultra-Sonic Sensor REFRIGERANT CHARGE R404A, 1 lb. 10.8 oz. (760g)
Performance Data Sheet
APPROXIMATE ICE PRODUCTION PER 24 HR.
APPROXIMATE ELECTRIC CONSUMPTION
watts 100/38 APPROXIMATE WATER CONSUMPTION PER 24 HR.
gal./day m3/day FREEZING CYCLE TIME
min. 100/38 HARVEST CYCLE TIME
min. 100/38 HEAD PRESSURE
PSIG kg/cm2G SUCTION PRESSURE
PSIG kg/cm2G
AMBIENT TEMP.
(ºF/ºC)
70/21 556 252 80/27 539 245 505 229 465 211 90/32 534 242 480 218 441 200
100/38 524 238 471 214 405 184
70/21 80/27 90/32
70/21 180 0.68 80/27 156 0.59 106 0.40 107 0.41 90/32 148 0.56 71 0.27 65 0.25
100/38 112 0.42 69 0.26 59 0.23
70/21 80/27 90/32
70/21 80/27 90/32
70/21 200 14.1 80/27 214 15.1 243 17.1 275 19.3 90/32 218 15.4 263 18.5 295 20.7
100/38 226 15.9 270 19.0 324 22.8
70/21 46 3.2 49 3.4 52 3.6 80/27 48 3.4 52 3.7 55 3.9 90/32 49 3.4 55 3.9 58 4.1
100/38 49 3.5 56 3.9 61 4.3
50/10 70/21
840 869 891 862 908 919 869 940 956 867
24 25 28 25 27 31 25 29 32 26 30 35
3.4 3.0 2.9
3.1 2.4 2.6
3.0 2.0
2.6
WATER TEMP. (ºF/ºC)
90/32
534 242 497 226
944 970
148 0.56 133 0.50
2.0
2.0 2.0
218 15.4 248 17.4
TOTAL HEAT OF REJECTION FROM CONDENSER TOTAL HEAT OF REJECTION FROM COMPRESSOR 1,100 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
6,600 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
56
Page 57

4. KM-520MWJ

y
Specification Sheet
AC SUPPLY VOLTAGE 115/60/1 AMPERAGE 8.45 A ( 5 Min. Freeze AT 104°F / WT 80°F) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 860 (4.65) 880 (4.45) WATER gal./24HR (gal./100 lbs.) 66 (14.8) 114 (24.1) WATER COOLED CONDENSER 333 (75) 149 (31) gal./24HR (gal./100 lbs.) ICE PRODUCTION PER CYCLE 10.7 lbs. (4.8 kg) 480pcs. BIN CONTROL SYSTEM Ultra-Sonic Sensor REFRIGERANT CHARGE R404A, 0 lb. 12.7 oz. (360g)
Performance Data Sheet
APPROXIMATE ICE PRODUCTION PER 24 HR.
lbs./day kg./da APPROXIMATE ELECTRIC CONSUMPTION
watts 100/38 APPROXIMATE WATER CONSUMPTION PER 24 HR.
gal./day m3/day FREEZING CYCLE TIME
min. 100/38 HARVEST CYCLE TIME
min. 100/38 HEAD PRESSURE
PSIG kg/cm2G SUCTION PRESSURE
PSIG kg/cm2G
AMBIENT TEMP.
(ºF/ºC)
70/21 474 215 465 211 451 204 80/27 467 212 454 206 438 199 90/32 465 211 444 201 428 194
100/38 462 209 440 200 414 188
70/21 80/27 90/32
70/21 263 1.00 80/27 294 1.11 355 1.34 438 1.66 90/32 303 1.15 399 1.51 479 1.81
100/38 371 1.40 418 1.58 552 2.09
70/21 80/27 90/32
70/21 80/27 90/32
70/21 284 20.0 284 19.9 282 19.8 80/27 284 20.0 283 19.9 280 19.7 90/32 284 19.9 283 19.9 280 19.7
100/38 283 19.9 282 19.9 278 19.5
70/21 54 3.8 54 3.8 55 3.9 80/27 54 3.8 55 3.8 56 3.9 90/32 54 3.8 55 3.9 56 3.9
100/38 55 3.8 55 3.9 57 4.0
50/10 70/21 90/32
880 874 864 876 866 856 874 860 850 872
30 30 31 30 31 32 30 32 33 30 32
3.1 2.8 2.7
2.9 2.4 2.5
2.8 2.0 2.0
2.5
WATER TEMP. (ºF/ºC)
858 840
303 1.15 376 1.42
33
2.0 2.0
TOTAL HEAT OF REJECTION FROM CONDENSER TOTAL HEAT OF REJECTION FROM COMPRESSOR 2,100 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)] WATER FLOW FOR CONDENSER 20 gal./h [AT 100ºF (38ºC) / WT 90ºF (32ºC)]
14,700 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
57
Page 58

5. KM-520MRJ with URC-5F

y
Specification Sheet
AC SUPPLY VOLTAGE 115/60/1 AMPERAGE 12.05 A ( 5 Min. Freeze AT 104°F / WT 80°F) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 990 (4.80) 920 (4.05) WATER gal./24HR (gal./100 lbs.) 67 (13.6) 173 (31.6) ICE PRODUCTION PER CYCLE 10.6 lbs. (4.8 kg) 480pcs. BIN CONTROL SYSTEM Ultra-Sonic Sensor REFRIGERANT CHARGE TOTAL R404A, 4 lb. 2.7 oz. (1890g)
ICEMAKER, 2 lb. 4.7 oz. (1040g) CONDENSER, 1 lb. 14 oz. (850g)
Performance Data Sheet
APPROXIMATE ICE PRODUCTION PER 24 HR.
lbs./day kg./da APPROXIMATE ELECTRIC CONSUMPTION
watts 100/38 APPROXIMATE WATER CONSUMPTION PER 24 HR.
gal./day m3/day FREEZING CYCLE TIME
min. 100/38 HARVEST CYCLE TIME
min. 100/38 HEAD PRESSURE
PSIG kg/cm2G SUCTION PRESSURE
PSIG kg/cm2G
AMBIENT TEMP.
(ºF/ºC)
70/21 547 248 532 241 507 230 80/27 535 243 512 232 484 220 90/32 532 241 495 225 468 212
100/38 525 238 489 222 444 201
70/21 80/27 90/32
70/21 173 0.65 142 0.54 129 0.49 80/27 149 0.57 101 0.38 105 0.40 90/32 142 0.54 67 0.25 64 0.24
100/38 108 0.41 66 0.25 60 0.23
70/21 80/27 90/32
70/21 80/27 90/32
70/21 207 14.6 223 15.6 249 17.5 80/27 219 15.4 243 17.1 272 19.1 90/32 223 15.6 260 18.3 289 20.3
100/38 230 16.1 267 18.8 315 22.1
70/21 50 3.5 50 3.5 53 3.7 80/27 50 3.5 51 3.6 55 3.9 90/32 50 3.5 51 3.6 55 3.8
100/38 52 3.6 52 3.6 58 4.1
50/10 70/21 90/32
920 941 963 936 968 986 941 990 1011 943 995 1030
25 26 28 26 28 30 26 29 32 26 30
3.4 3.0
3.1 2.5 2.6
3.0 2.0 2.0
2.6 2.0 2.0
WATER TEMP. (ºF/ºC)
34
2.9
TOTAL HEAT OF REJECTION FROM CONDENSER TOTAL HEAT OF REJECTION FROM COMPRESSOR 1,000 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)] CONDENSER VOLUME 43 CU. IN. URC-5F
6,200 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
58
Page 59

6. KM-660MAJ

y
Specification Sheet
AC SUPPLY VOLTAGE 115/60/1 AMPERAGE 15.2 A ( 5 Min. Freeze AT 104°F / WT 80°F) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 1320 (5.12) 1200 (4.34) WATER gal./24HR (gal./100 lbs.) 91 (14.8) 204 (30.6) ICE PRODUCTION PER CYCLE 10.7 lbs. (4.8 kg) 480pcs. BIN CONTROL SYSTEM Ultra-Sonic Sensor REFRIGERANT CHARGE R404A, 1 lb. 9.8 oz. (730g)
Performance Data Sheet
APPROXIMATE ICE PRODUCTION PER 24 HR.
lbs./day kg./da APPROXIMATE ELECTRIC CONSUMPTION
watts 100/38 APPROXIMATE WATER CONSUMPTION PER 24 HR.
gal./day m3/day FREEZING CYCLE TIME
min. 100/38 HARVEST CYCLE TIME
min. 100/38 HEAD PRESSURE
PSIG kg/cm2G SUCTION PRESSURE
PSIG kg/cm2G
AMBIENT TEMP.
(ºF/ºC)
70/21 665 301 80/27 654 297 632 287 607 275 90/32 650 295 617 280 591 268
100/38 645 292 611 277 569 258
70/21 80/27 90/32
70/21 204 0.77 80/27 178 0.68 127 0.48 131 0.50 90/32 171 0.65 91 0.35 87 0.33
100/38 134 0.51 90 0.34 84 0.32
70/21 80/27 90/32
70/21 80/27 90/32
70/21 212 14.9 80/27 227 16.0 257 18.1 292 20.6 90/32 232 16.3 279 19.6 313 22.0
100/38 240 16.9 287 20.2 345 24.3
70/21 37 2.6 39 2.8 46 3.2 80/27 39 2.7 42 3.0 51 3.6 90/32 39 2.8 45 3.2 53 3.7
100/38 42 2.9 47 3.3 60 4.2
50/10 70/21 90/32
1200 1235 1278 1227 1281 1321 1235 1320 1362 1242 1330 1400
20 21 23 21 22 24 21 24 25 21 24 27
3.4 3.0 2.8
3.1 2.4
3.0 2.0 2.0
2.5 2.0 2.0
WATER TEMP. (ºF/ºC)
650 295 627 285
171 0.65 157 0.59
2.5
232 16.3 264 18.5
TOTAL HEAT OF REJECTION FROM CONDENSER TOTAL HEAT OF REJECTION FROM COMPRESSOR 1,500 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
8,000 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
59
Page 60

7. KM-660MWJ

y
Specification Sheet
AC SUPPLY VOLTAGE 115/60/1 AMPERAGE 12.35 A ( 5 Min. Freeze AT 104°F / W T 80°F) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 1190 (4.28) 1130 (4.07) WATER gal./24HR (gal./100 lbs.) 107 (16.1) 194 (29.1) WATER COOLED CONDENSER 1017 (152) 483 (72) gal./24HR (gal./100 lbs.) ICE PRODUCTION PER CYCLE 10.8 lbs. (4.9 kg) 480pcs. BIN CONTROL SYSTEM Ultra-Sonic Sensor REFRIGERANT CHARGE R404A, 0 lb. 15.2 oz. (430g)
Performance Data Sheet
APPROXIMATE ICE PRODUCTION PER 24 HR.
lbs./day kg./da APPROXIMATE ELECTRIC CONSUMPTION
watts 100/38 APPROXIMATE WATER CONSUMPTION PER 24 HR.
gal./day m3/day FREEZING CYCLE TIME
min. 100/38 HARVEST CYCLE TIME
min. 100/38 HEAD PRESSURE
PSIG kg/cm2G SUCTION PRESSURE
PSIG kg/cm2G
AMBIENT TEMP.
(ºF/ºC)
70/21 669 303 669 303 644 292 80/27 669 303 668 303 630 286 90/32 669 303 668 303 635 288
100/38 655 297 661 300 605 274
70/21 80/27 90/32
70/21 677 2.56 808 3.06 998 3.78 80/27 777 2.94 981 3.71 1176 4.45 90/32 808 3.06 1125 4.26 1322 5.00
100/38 1010 3.82 1171 4.43 1503 5.69
70/21 80/27 90/32
70/21 80/27 90/32
70/21 228 16.0 229 16.1 231 16.2 80/27 228 16.1 229 16.1 232 16.3 90/32 229 16.1 230 16.2 233 16.4
100/38 229 16.1 231 16.2 235 16.5
70/21 40 2.8 41 2.9 44 3.1 80/27 41 2.9 43 3.1 46 3.2 90/32 41 2.9 45 3.2 48 3.3
100/38 42 3.0 46 3.2 50 3.5
50/10 70/21 90/32
1130 1148 1130 1143 1171 1130 1148 1190 1159 1130 1183 1130
19 19 19 19 20 19 19 20 19 19 20
3.1 2.8
2.9 2.4 2.4
2.8 2.0 2.0
2.4 2.0 2.0
WATER TEMP. (ºF/ºC)
19
2.7
TOTAL HEAT OF REJECTION FROM CONDENSER TOTAL HEAT OF REJECTION FROM COMPRESSOR 1,400 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)] WATER FLOW FOR CONDENSER 59 gal./h [AT 100ºF (38ºC) / WT 90ºF (32ºC)]
8,900 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
60
Page 61

8. KM-660MRJ with URC-5F

y
Specification Sheet
AC SUPPLY VOLTAGE 115/60/1 AMPERAGE 16.1 A ( 5 Min. Freeze AT 104°F / WT 80°F) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kWH/100 lbs.) 1400 (5.60) 1270 (4.72) WATER gal./24HR (gal./100 lbs.) 88 (14.7) 213 (32.9) ICE PRODUCTION PER CYCLE 10.4 lbs. (4.7 kg) 480pcs. BIN CONTROL SYSTEM Ultra-Sonic Sensor REFRIGERANT CHARGE TOTAL R404A, 4 lb. 2.7 oz. (1890g)
ICEMAKER, 2 lb. 4.7 oz. (1040g) CONDENSER, 1 lb. 14 oz. (850g)
Performance Data Sheet
APPROXIMATE ICE PRODUCTION PER 24 HR.
lbs./day kg./da APPROXIMATE ELECTRIC CONSUMPTION
watts 100/38 APPROXIMATE WATER CONSUMPTION PER 24 HR.
gal./day m3/day FREEZING CYCLE TIME
min. 100/38 HARVEST CYCLE TIME
min. 100/38 HEAD PRESSURE
PSIG kg/cm2G SUCTION PRESSURE
PSIG kg/cm2G
AMBIENT TEMP.
(ºF/ºC)
70/21 646 293 80/27 636 289 616 279 592 269 90/32 633 287 602 273 578 262
100/38 628 285 596 270 557 253
70/21 80/27 90/32
70/21 213 0.80 80/27 185 0.70 128 0.49 134 0.51 90/32 176 0.67 88 0.33 85 0.32
100/38 136 0.52 87 0.33 82 0.31
70/21 80/27 90/32
70/21 80/27 90/32
70/21 215 15.1 80/27 228 16.0 254 17.9 285 20.0 90/32 232 16.3 273 19.2 303 21.3
100/38 239 16.8 280 19.7 330 23.2
70/21 40 2.8 41 2.9 44 3.1 80/27 41 2.9 43 3.1 46 3.2 90/32 41 2.9 45 3.2 48 3.3
100/38 42 3.0 46 3.2 50 3.5
50/10 70/21 90/32
1270 1308 1359 1299 1358 1409 1308 1400 1452 1318 1412 1500
20 21 22 20 22 24 21 23 25 21 24
3.5 3.0
3.1 2.5 2.6
3.0 2.0 2.0
2.6 2.0 2.0
WATER TEMP. (ºF/ºC)
633 287 612 277
176 0.67 162 0.61
26
2.9
232 16.3 260 18.3
TOTAL HEAT OF REJECTION FROM CONDENSER TOTAL HEAT OF REJECTION FROM COMPRESSOR 1,500 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)] CONDENSER VOLUME 43 CU. IN. URC-5F
8,100 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
61
Page 62

B. Wiring Diagrams

1. KM-350M_J, KM-520M_J, KM-660M_J

* High-Pressure Switch
PSIG
0
22
PSIG 412±
0
22
Water-Cooled Model Air and Remote Models
*
Cut-in 284±22 PSIG 327±22 PSIG
Cut-out 384±
62
Loading...