Hoshizaki KM1900SAH, KM1900SAH3, KM1601SAH3, KM1601SRH, KM1601SRH3 Instruction Manual

...
Hoshizaki
Stackable Crescent Cuber
Models KM-1301SAH/3, SWH/3, SRH/3
“A Superior Degree
of Reliability”
www.hoshizaki.com
KM-1601SAH/3, SWH/3, SRH/3 KM-1900SAH/3, SWH/3, SRH/3 KM-2100SWH3, SRH3 KM-2500SWH3, SRH3
INSTRUCTION MANUAL
Issued: 6-25-2014
WARNING
Only qualied service technicians should install and service the appliance. To obtain the name and phone number of your local Hoshizaki Certied Service Representative, visit www.hoshizaki.com. No installation or service should be undertaken until the technician has thoroughly read this Instruction Manual. Likewise, the owner/manager should not proceed to operate the appliance until the installer has instructed them on its proper operation. Failure to install, operate, and maintain the appliance in accordance with this manual will adversely affect safety, performance, component life, and warranty coverage and may result in costly water damage. Proper installation is the responsibility of the installer. Product failure or property damage due to improper installation is not covered under warranty.
Hoshizaki provides this manual primarily to assist qualied service technicians in the installation, maintenance, and service of the appliance.
Should the reader have any questions or concerns which have not been satisfactorily addressed, please call, send an e-mail message, or write to the Hoshizaki Technical Support Department for assistance.
Phone: 1-800-233-1940; (770) 487-2331 Fax: 1-800-843-1056; (770) 487-3360
E-mail: techsupport@hoshizaki.com
HOSHIZAKI AMERICA, INC. 618 Highway 74 South Peachtree City, GA 30269 Attn: Hoshizaki Technical Support Department
NOTE: To expedite assistance, all correspondence/communication MUST include the
following information:
• Model Number
• Serial Number
• Complete and detailed explanation of the problem.
2
IMPORTANT
This manual should be read carefully before the appliance is installed and operated. Read the warnings and guidelines contained in this manual carefully as they provide essential information for the continued safe use and maintenance of the appliance. Retain this manual for any further reference that may be necessary.
CONTENTS
Important Safety Information ................................................................................................. 6
I. Specications ...................................................................................................................... 8
A. Electrical and Refrigerant Data ..................................................................................... 8
1. KM-1301S_H/3 ......................................................................................................... 8
2. KM-1601S_H/3 ........................................................................................................ 9
3. KM-1900S_H/3 ...................................................................................................... 10
4. KM-2100S_H3 ........................................................................................................11
5. KM-2500S_H3 ........................................................................................................11
B. Dimensions/Connections ............................................................................................ 12
1. Air-Cooled Models (SAH/3) .................................................................................... 12
2. Water-Cooled Models (SWH/3) .............................................................................. 13
3. Remote Models (SRH/3)........................................................................................ 14
4. Remote Condenser Unit URC-14F (use with KM-1301SRH/3) .............................. 15
5. Remote Condenser Unit URC-22F (use with KM-1601SRH/3 KM-1900SRH/3,
KM-2100SRH3) and URC-23F (use with KM-2500SRH3) .................................... 15
II. Installation and Operating Instructions ............................................................................ 16
A. Location ...................................................................................................................... 16
B. Checks Before Installation ........................................................................................... 16
C. How to Remove Panels ............................................................................................... 17
D. Setup ........................................................................................................................... 18
1. Dispenser Unit/Ice Storage Bin and Icemaker Setup ............................................. 18
2. Bin Control Installation ........................................................................................... 19
a) KM-1301/1601S_H/3 ........................................................................................... 19
b) KM-1900/2100/2500S_H/3 ................................................................................. 21
3. Installation of Upper Unit ....................................................................................... 22
E. Electrical Connection .................................................................................................. 24
F. Water Supply and Drain Connections .......................................................................... 26
1. Icemaker ................................................................................................................ 27
2. Water-Cooled Condenser....................................................................................... 28
G. Installation of Remote Condenser Unit ....................................................................... 30
1. Location ................................................................................................................. 30
2. Checks Before Installation ..................................................................................... 31
3. Setup ..................................................................................................................... 31
4. Line Set Size and Refrigerant Charge ................................................................... 31
5. Line Set Installation ............................................................................................... 32
6. Electrical Connection ............................................................................................. 35
7. Stacking Remote Condenser Unit .......................................................................... 36
H. Final Checklist ............................................................................................................. 37
I. Startup .......................................................................................................................... 38
3
III. Maintenance ................................................................................................................... 39
A. Maintenance Schedule ................................................................................................ 39
B. Cleaning and Sanitizing Instructions ........................................................................... 40
1. Cleaning Procedure ................................................................................................ 40
2. Sanitizing Procedure - Following Cleaning Procedure ........................................... 42
IV. Preparing the Icemaker for Periods of Non-Use ............................................................. 43
V. Disposal ........................................................................................................................... 45
4
Intentionally Left Blank
5

Important Safety Information

Throughout this manual, notices appear to bring your attention to situations which could result in death, serious injury, damage to the appliance, or damage to property.
WARNING Indicates a hazardous situation which could result in death or
serious injury.
NOTICE Indicates a situation which could result in damage to the
appliance or property.
IMPORTANT Indicates important information about the installation, use, and
care of the appliance.
WARNING
The appliance should be destined only to the use for which it has been expressly conceived. Any other use should be considered improper and therefore dangerous. The manufacturer cannot be held responsible for injury or damage resulting from improper, incorrect, and unreasonable use. Failure to install, operate, and maintain the appliance in accordance with this manual will adversely affect safety, performance, component life, and warranty coverage and may result in costly water damage.
To reduce the risk of death, electric shock, serious injury, or re, follow basic precautions including the following:
• Only qualied service technicians should install and service the appliance.
• The appliance must be installed in accordance with applicable national, state, and local codes and regulations.
• Electrical connection must be hard-wired and must meet national, state, and local electrical code requirements. Failure to meet these code requirements could result in death, electric shock, serious injury, re, or damage.
• The icemaker requires an independent power supply of proper capacity. See the nameplate for electrical specications. Failure to use an independent power supply of proper capacity can result in a tripped breaker, blown fuse, damage to existing wiring, or component failure. This could lead to heat generation or re.
THE ICEMAKER MUST BE GROUNDED. Failure to properly ground the icemaker could result in death or serious injury.
• To reduce the risk of electric shock, do not touch the control switch with damp hands.
• Move the control switch to the "OFF" position and turn off the power supply before servicing. Lockout/Tagout to prevent the power supply from being turned back on inadvertently.
• Do not make any alterations to the appliance. Alterations could result in electric shock, serious injury, re, or damage.
• The appliance is not intended for use by persons (including children) with reduced physical, sensory, or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
6
WARNING, continued
• Children should be properly supervised around the appliance.
• Do not climb, stand, or hang on the appliance or allow children or animals to do so. Serious injury could occur or the appliance could be damaged.
• Do not use combustible spray or place volatile or ammable substances near the appliance. They might catch re.
• Keep the area around the appliance clean. Dirt, dust, or insects in the appliance could cause harm to individuals or damage to the appliance.
Additional Warning for Remote Models
THE REMOTE CONDENSER UNIT MUST BE GROUNDED. The power supply and ground connection to the remote condenser unit are supplied from the icemaker. Failure to properly ground the remote condenser unit could result in death or serious injury.
• Wire routing (conduit) and disconnect (if required) must meet national, state, and local electrical code requirements. Failure to meet these code requirements could result in death, electric shock, serious injury, re, or damage.
NOTICE
• Follow the water supply, drain connection, and maintenance instructions carefully to reduce the risk of costly water damage.
• In areas where water damage is a concern, install in a contained area with a oor drain.
• Install the icemaker in a location that stays above freezing. Normal operating ambient temperature must be within 45°F to 100°F (7°C to 38°C).
• Do not leave the icemaker on during extended periods of non-use, extended absences, or in sub-freezing temperatures. To properly prepare the icemaker for these occasions, follow the instructions in "IV. Preparing the Icemaker for Periods of Non-Use."
• Do not place objects on top of the appliance.
• The dispenser unit/ice storage bin is for ice use only. Do not store anything else in the dispenser unit/ice storage bin.
7
I. Specications

A. Electrical and Refrigerant Data

The rating label and nameplate provide electrical and refrigerant data. The rating label can be seen by removing the front panel. The nameplate is located on the rear panel. For certication marks, see the nameplate. We reserve the right to make changes in specications and design without prior notice.

1. KM-1301S_H/3

Single Phase
Model Number KM-1301SAH KM-1301SWH KM-1301SRH
AC Supply Voltage 208-230/60/1 208-230/60/1 208-230/60/1 Compressor 208-230V 10.0RLA 61LRA 208-230V 8.2RLA 56LRA 208-230V 9.3RLA 56LRA Pump 120V 1.2FLA 60W 120V 1.2FLA 60W 120V 1.2FLA 60W Fan 115V 1.0FLA 1/15HP --- --- --- 120V 3A MAX (Fans in URC) Other 115-120V 0.3A 115-120V 0.3A 115-120V 0.3A Maximum Fuse Size 20 AMPS 20 AMPS 20 AMPS Max. HACR Breaker (USA Only) Max. Circuit Breaker (Canada Only) Minimum Circuit Ampacity Design Pressure HI-467PSI LO-230PSI HI-427PSI LO-230PSI HI-467PSI LO-230PSI Refrigerant 404A 3 LB. 15.4 OZ. 404A 2 LB. 2.4 OZ. 404A
20 AMPS 20 AMPS 20 AMPS
20 AMPS 20 AMPS 20 AMPS
20 AMPS 20 AMPS 20 AMPS
Total Refrigerant Charge with Hoshizaki Remote Condenser Unit URC-14F: 10 LB. 5.8 OZ.
Three Phase
Model Number KM-1301SAH3 KM-1301SWH3 KM-1301SRH3
AC Supply Voltage 208-230/60/3 208-230/60/3 208-230/60/3 Compressor 208-230V 7.1RLA 55LRA 208-230V 6.1RLA 51LRA 208-230V 6.2RLA 51LRA Pump 120V 1.2FLA 60W 120V 1.2FLA 60W 120V 1.2FLA 60W Fan 115V 1.0FLA 1/15HP --- --- --- 120V 3A MAX (Fans in URC) Other 115-120V 0.3A 115-120V 0.3A 115-120V 0.3A Maximum Fuse Size 20 AMPS 20 AMPS 20 AMPS Max. HACR Breaker (USA Only) Max. Circuit Breaker (Canada Only) Minimum Circuit Ampacity Design Pressure HI-467PSI LO-230PSI HI-427PSI LO-230PSI HI-467PSI LO-230PSI Refrigerant 404A 3 LB. 15.4 OZ. 404A 2 LB. 2.4 OZ. 404A
20 AMPS 20 AMPS 20 AMPS
20 AMPS 20 AMPS 20 AMPS
20 AMPS 20 AMPS 20 AMPS
Total Refrigerant Charge with Hoshizaki Remote Condenser Unit URC-14F: 10 LB. 5.8 OZ.
8

2. KM-1601S_H/3

Single Phase
Model Number KM-1601SAH KM-1601SWH KM-1601SRH
AC Supply Voltage 208-230/60/1 (3 Wire with
Neutral) Compressor 230V 12.1RLA 96LRA 230V 12.1RLA 82LRA 230V 12.8RLA 82LRA Pump 120V 1.2FLA 60W 120V 1.2FLA 60W 120V 1.2FLA 60W Fan 115V 1.0FLA 1/15HP --- --- --- 120V 3A MAX (Fans in URC) Other 115V 0.3A 115V 0.3A 115V 0.3A Maximum Fuse Size 20 AMPS 20 AMPS 20 AMPS Max. HACR Breaker (USA Only) Max. Circuit Breaker (Canada Only) Minimum Circuit Ampacity Design Pressure HI-467PSI LO-230PSI HI-427PSI LO-230PSI HI-467PSI LO-230PSI Refrigerant 404A 3 LB. 12.5 OZ. 404A 2 LB. 6.8 OZ. 404A
Model Number KM-1601SAH3 KM-1601SWH3 KM-1601SRH3
AC Supply Voltage 208-230/60/3 208-230/60/3 208-230/60/3 Compressor 230V 9.3RLA 55LRA 230V 7.3RLA 65.5LRA 230V 7.9RLA 65.5LRA Pump 120V 1.2FLA 60W 120V 1.2FLA 60W 120V 1.2FLA 60W Fan 115V 1.0FLA 1/15HP --- --- --- 120V 3A MAX (Fans in URC) Other 115V 0.3A 115V 0.3A 115V 0.3A Maximum Fuse Size 20 AMPS 20 AMPS 20 AMPS Max. HACR Breaker (USA Only) Max. Circuit Breaker (Canada Only) Minimum Circuit Ampacity Design Pressure HI-467PSI LO-230PSI HI-427PSI LO-230PSI HI-467PSI LO-230PSI Refrigerant 404A 3 LB. 12.5 OZ. 404A 2 LB. 6.8 OZ. 404A
20 AMPS 20 AMPS 20 AMPS
20 AMPS 20 AMPS 20 AMPS
20 AMPS 20 AMPS 20 AMPS
20 AMPS 20 AMPS 20 AMPS
20 AMPS 20 AMPS 20 AMPS
20 AMPS 20 AMPS 20 AMPS
208-230/60/1 (3 Wire with Neutral)
Three Phase
208-230/60/1 (3 Wire with Neutral)
Total Refrigerant Charge with Hoshizaki Remote Condenser Unit URC-22F: 22 LB. 15 OZ.
Total Refrigerant Charge with Hoshizaki Remote Condenser Unit URC-22F: 22 LB. 15 OZ.
9

3. KM-1900S_H/3

Single Phase
Model Number KM-1900SAH KM-1900SWH KM-1900SRH
AC Supply Voltage 208-230/60/1 (3 Wire with
Neutral) Compressor 230V 11.3RLA 73LRA 230V 11.1RLA 73LRA 230V 11.4RLA 73LRA Pump 120V 1.2FLA 60W 120V 1.2FLA 60W 120V 1.2FLA 60W Fan 115V 1.0FLA 1/15HP
(QTY 2) Other 115V 0.3A 115V 0.3A 115V 0.3A Maximum Fuse Size 30 AMPS 30 AMPS 30 AMPS Max. HACR Breaker (USA Only) Max. Circuit Breaker (Canada Only) Minimum Circuit Ampacity Design Pressure HI-467PSI LO-230PSI HI-427PSI LO-230PSI HI-467PSI LO-230PSI Refrigerant 404A 4 LB. 10.1 OZ. 404A 3 LB. 1.4 OZ. 404A
30 AMPS 30 AMPS 30 AMPS
30 AMPS 30 AMPS 30 AMPS
30 AMPS 30 AMPS 30 AMPS
208-230/60/1 (3 Wire with Neutral)
--- --- --- 120V 3A MAX (Fans in URC)
208-230/60/1 (3 Wire with Neutral)
Total Refrigerant Charge with Hoshizaki Remote Condenser Unit URC-22F: 21 LB. 7.7 OZ.
Three Phase
Model Number KM-1900SAH3 KM-1900SWH3 KM-1900SRH3
AC Supply Voltage 208-230/60/3 208-230/60/3 208-230/60/3 Compressor 230V 8.4RLA 66LRA 230V 7.8RLA 66LRA 230V 8.0RLA 66LRA Pump 120V 1.2FLA 60W 120V 1.2FLA 60W 120V 1.2FLA 60W Fan 115V 1.0FLA 1/15HP
(QTY 2) Other 115V 0.3A 115V 0.3A 115V 0.3A Maximum Fuse Size 20 AMPS 20 AMPS 20 AMPS Max. HACR Breaker (USA Only) Max. Circuit Breaker (Canada Only) Minimum Circuit Ampacity Design Pressure HI-467PSI LO-230PSI HI-427PSI LO-230PSI HI-467PSI LO-230PSI Refrigerant 404A 4 LB. 10.1 OZ. 404A 3 LB. 1.4 OZ. 404A
20 AMPS 20 AMPS 20 AMPS
20 AMPS 20 AMPS 20 AMPS
20 AMPS 20 AMPS 20 AMPS
--- --- --- 120V 3A MAX (Fans in URC)
Total Refrigerant Charge with Hoshizaki Remote Condenser Unit URC-22F: 21 LB. 7.7 OZ.
10

4. KM-2100S_H3

Three Phase
Model Number KM-2100SWH3 KM-2100SRH3
AC Supply Voltage 208-230/60/3 208-230/60/3 Compressor 230V 9.0RLA 75LRA 230V 9.2RLA 75LRA Pump 120V 1.2FLA 60W 120V 1.2FLA 60W Fan --- --- --- 120V 3A MAX (Fans in URC) Other 115V 0.3A 115V 0.3A Maximum Fuse Size 20 AMPS 20 AMPS Max. HACR Breaker (USA Only) Max. Circuit Breaker (Canada Only) Minimum Circuit Ampacity Design Pressure HI-427PSI LO-230PSI HI-467PSI LO-230PSI Refrigerant 404A 3 LB. 404A
20 AMPS 20 AMPS
20 AMPS 20 AMPS
20 AMPS 20 AMPS
Total Refrigerant Charge with Hoshizaki Remote Condenser Unit URC-22F: 16 LB. 2 OZ.

5. KM-2500S_H3

Three Phase
Model Number KM-2500SWH3 KM-2500SRH3
AC Supply Voltage 208-230/60/3 208-230/60/3 Compressor 230V 12.2RLA 105LRA 230V 15.38RLA 130LRA Pump 120V 1.2FLA 60W 120V 1.2FLA 60W Fan --- --- --- 120V 3A MAX (Fans in URC) Other 115V 0.8A 115V 0.8A Maximum Fuse Size 30 AMPS 30 AMPS Max. HACR Breaker (USA Only) Max. Circuit Breaker (Canada Only) Minimum Circuit Ampacity Design Pressure HI-427PSI LO-230PSI HI-467PSI LO-230PSI Refrigerant 404A 3 LB. 7.6 OZ. 404A
30 AMPS 30 AMPS
30 AMPS 30 AMPS
30 AMPS 30 AMPS
Total Refrigerant Charge with Hoshizaki Remote Condenser Unit URC-23F: 24 LB. 9.5 OZ.
11

B. Dimensions/Connections

1. Air-Cooled Models (SAH/3)

Model Shown: KM-1301SAH
KM-1301SAH/3
KM-1601SAH/3 A 695 [27-3/8] 925 [36-3/8] B 643 [25-3/8] 873 [34-3/8] C 115 [4-1/2] 130 [5-1/8]
Side
KM-1900SAH/3
Units: mm [in.]
Rear
Model Shown: KM-1301SAH
Bottom
NOTICE
• For all models except KM-1601SAH/3, allow 6" (15 cm) clearance at rear, sides, and top for proper air circulation and ease of maintenance and/or service should they be required. For KM-1601SAH/3, allow 9" (23 cm) clearance at rear, sides, and top.
• The ice storage bin opening must match the bottom opening as in the illustration.
Model Shown: KM-1301SAH
12

2. Water-Cooled Models (SWH/3)

Side
Model Shown: KM-1301SWH
KM-1301SWH/3 KM-1601SWH/3 KM-1900SWH/3
KM-2100SWH3 A 695 [27-3/8] 695 [27-3/8] 925 [36-3/8] 925 [36-3/8] B 643 [25-3/8] 643 [25-3/8] 873 [34-3/8] 873 [34-3/8] C 115 [4-1/2] 115 [4-1/2] 130 [5-1/8] 130 [5-1/8] D 164 [6-1/2] 199 [7-7/8] 297 [11-3/4] 162 [6-3/8] E 74 [2-7/8] 85 [3-3/8] 65 [2-1/2] 110 [4-3/8]
KM-2500SWH3
Units: mm [in.]
Rear
KM-1301/1601/1900/2100SWH/3
Model Shown: KM-1301SWH
Rear
KM-2500SWH3
NOTICE
• Allow 6" (15 cm) clearance at rear, sides, and top for proper air circulation and ease of maintenance and/or service should they be required.
• The ice storage bin opening must match the bottom opening as in the illustration.
Model Shown: KM-2500SWH3
Bottom
Model Shown: KM-1301SWH
13

3. Remote Models (SRH/3)

Units: mm [in.]
Side
Model Shown: KM-1301SRH
KM-1301SRH/3 KM-1601SRH/3 KM-1900SRH/3
KM-2100SRH3 A 695 [27-3/8] 695 [27-3/8] 925 [36-3/8] 925 [36-3/8] B 643 [25-3/8] 643 [25-3/8] 873 [34-3/8] 873 [34-3/8] C 115 [4-1/2] 115 [4-1/2] 130 [5-1/8] 130 [5-1/8] D 442 [17-3/8] 442 [17-3/8] 673 [26-1/2] 410 [16-1/8] E 115 [4-1/2] 115 [4-1/2] 115 [4-1/2] 120 [4-3/4] F 76 [3] 100 [3-7/8] 74 [2-7/8] 75 [3]
KM-2500SRH3
Rear
Model Shown: KM-1301SRH
Bottom
NOTICE
• Allow 6" (15 cm) clearance at rear, sides, and top for proper air circulation and ease of maintenance and/or service should they be required.
• The ice storage bin opening must match the bottom opening as in the illustration.
Model Shown: KM-1301SRH
14

4. Remote Condenser Unit URC-14F (use with KM-1301SRH/3)

NOTICE
Allow 24" (61cm) clearance at front and rear for proper air circulation and ease of maintenance and/or service should they be required.
URC-14F Heat of Rejection Icemaker Model
KM-1301SRH 17,600 BTU/hr KM-1301SRH3 17,500 BTU/hr
AT 90°F (32°C)
WT 70°F (21°C)
Top
Rear
Units: mm [in.]
Units: mm [in.]
5. Remote Condenser Unit URC-22F (use with KM-1601SRH/3 KM-1900SRH/3,
KM-2100SRH3) and URC-23F (use with KM-2500SRH3)
Units: mm [in.]
NOTICE
Allow 24" (61cm) clearance at front and rear for proper air circulation and ease of maintenance and/or service should they be required.
Heat of
Rejection Icemaker Model URC Model
KM-1601SRH URC-22F 21,000 BTU/hr KM-1601SRH3 URC-22F 26,400 BTU/hr KM-1900SRH URC-22F 26,500 BTU/hr KM-1900SRH3 URC-22F 25,700 BTU/hr KM-2100SRH3 URC-22F 30,400 BTU/hr KM-2500SRH3 URC-23F 40,600 BTU/hr
AT 90°F (32°C)
WT 70°F (21°C)
Top
Rear
15

II. Installation and Operating Instructions

WARNING
• The appliance must be installed in accordance with applicable national, state, and local codes and regulations.
• Failure to install, operate, and maintain the appliance in accordance with this manual will adversely affect safety, performance, component life, and warranty coverage and may result in costly water damage.
CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews are securely in place after installation. Make sure that none have fallen into the dispenser unit/ice storage bin.

A. Location

NOTICE
• The icemaker is not intended for outdoor use. Normal operating ambient temperature must be within 45°F to 100°F (7°C to 38°C); Normal operating water temperature must be within 45°F to 90°F (7°C to 32°C). Operation of the icemaker, for extended periods, outside of these normal temperature ranges may affect icemaker performance.
• The icemaker will not work at sub-freezing temperatures. To prevent damage to the water supply line, drain the icemaker if the air temperature is going to go below 32°F (0°C). See "IV. Preparing the Icemaker for Periods of Non-Use."
• The icemaker should not be located next to ovens, grills, or other high heat producing equipment.
• For all models except KM-1601SAH/3, allow 6" (15 cm) clearance at rear, sides, and top for proper air circulation and ease of maintenance and/or service should they be required. For KM-1601SAH/3, allow 9" (23 cm) clearance at rear, sides, and top.
• The location should provide a rm and level foundation for the appliance.

B. Checks Before Installation

• Visually inspect the exterior of the shipping container and immediately report any damage to the carrier. Upon opening the container, any concealed damage should also be immediately reported to the carrier.
• Remove the shipping carton, tape, and packing material. If any are left in the appliance, it will not work properly.
• See the nameplate on the rear panel, and check that your voltage supplied corresponds with the voltage specied on the nameplate.
• Remove the panels to prevent damage when installing the appliance. See "II.C. How to Remove Panels."
• Remove the package containing the accessories.
16
• Remove the protective plastic lm from the panels. If the appliance is exposed to the sun or to heat, remove the lm after the appliance cools.
• Check that the refrigerant lines do not rub or touch lines or other surfaces, and that the fan blade (if applicable) turns freely.
• Check that the compressor is snug on all mounting pads.
• The icemaker can be installed on a dispenser unit or ice storage bin. The ice storage bins listed below are recommended.
Model Number Bin Width Recommended Hoshizaki Ice Storage Bin
KM-1301S_H/3 KM-1601S_H/3 KM-1900S_H/3 KM-2100S_H3 KM-2500S_H3
48" or Wider B-800 Series
For further options, contact your local Hoshizaki distributor.
NOTICE! Remote models must be connected to an appropriate remote condenser unit. The remote condenser units listed below are recommended. Connection to a different remote condenser unit will void the warranty unless Hoshizaki approves a different remote condenser unit for your specic application. For further details, contact your local Hoshizaki distributor.
Model Number Recommended Hoshizaki Remote Condenser Unit
KM-1301SRH/3 URC-14F KM-1601SRH/3 KM-1900SRH/3 KM-2100SRH3 KM-2500SRH3 URC-23F
URC-22F

C. How to Remove Panels

See Fig. 1
• Front Panel: Remove the screws. Lift up and pull towards you.
• Top Panel: Remove the screws, then lift off.
• Side Panel (R): Remove the screw. Slide forward slightly and lift off.
• Insulation Panel: Remove the thumbscrew. Lift up slightly and pull towards you.
• Top Insulation: Lift off.
Top Insulation
Insulation Panel
Front Panel
Top Panel
Side Panel (R)
Fig. 1
17

D. Setup

1. Dispenser Unit/Ice Storage Bin and Icemaker Setup

WARNING
The installer must ensure the dispenser unit/ice storage bin is compatible with the icemaker, and the dispenser unit/ice storage bin and icemaker are properly attached and secured.
1a) Dispenser Unit: Follow the dispenser unit's setup procedure.
1b) Ice Storage Bin: Unpack the ice storage bin and attach the 4 adjustable legs provided
(bin accessory) to the bottom of the ice storage bin.
2) Position the dispenser unit/ice storage bin in its permanent location.
3) If required, install an adapter kit or top kit. Contact your local Hoshizaki distributor for recommendations.
4) Level the dispenser unit/ice storage bin in both the left-to-right and front-to-rear directions. Ifusing an ice storage bin, adjust the ice storage bin legs to level.
5) Place the icemaker on top of the dispenser unit/ice storage bin.
6a) Dispenser Unit: Follow the dispenser unit, adapter kit, or top kit instructions for
securing the icemaker. If no instructions are available, secure the icemaker using the mounting brackets provided. Rotate the mounting brackets so that they t ush to the dispenser unit. SeeFig.2a. Secure the mounting brackets to the icemaker with the bolts provided. Secure the mounting brackets to the dispenser unit with self-tapping screws (not provided). NOTICE! Use care to avoid damage to dispenser unit components
when attaching the mounting brackets.
6b) Ice Storage Bin: Follow the ice storage bin, adapter kit, or top kit instructions for
securing the icemaker. If no instructions are available, secure the icemaker using the 2mounting brackets and the bolts provided. See Fig.2b.
Icemaker
Mounting Brackets
Bolts
Fig. 2a
Self-Tapping Screws (Not Provided)
Icemaker
Dispenser Unit
Fig. 2b
Ice Storage Bin
Model Shown: KM-1601SRHModel Shown: KM-1301SRH
Mounting Brackets
Bolts
18

2. Bin Control Installation

NOTICE
Before operating the icemaker, the bin control must be installed. Failure to properly install the bin control could result in ice backup and icemaker damage.
a) KM-1301/1601S_H/3
1) Install the bin control thermostat as follows: a. Remove the baffle from the ice storage bin. b. Remove the tie securing the bin control thermostat assembly. Remove the
2 thumbscrews below the bin control thermostat assembly.
c. Remove the bin control thermostat assembly from the shipping hook by lifting it up
and shifting it to the right. Lower the thermostat extension bracket (stainless) with the thermostat bulb attachment and thermostat bulb through the hole located at the bottom of the icemaker. Next, lower the thermostat bracket (plastic) through the hole. See Fig. 3.
d. Make sure the left side and bottom of the assembly are ush against the wall and
base panel.
e. Secure the assembly into place with the thumbscrews unless you are installing
anupper unit. If you are installing an upper unit, complete steps f and g and then see "II.D.3. Installation of Upper Unit."
f. Insert the plug into the receptacle on the assembly until it locks into place. SeeFig.4.
Wall
Shipping Hook
Thermostat Bracket (plastic)
Tie
Thermostat Bulb Attachment (plastic) and Thermostat Bulb
Fig. 3
Bin Control Thermostat Assembly
Thermostat Extension Bracket (stainless)
Receptacle
Thumbscrew
Hole
Plug
Hook
Bushing
Thumbscrews
Fig. 4
19
g. Remove the 2 screws from the lower part of the thermostat bracket (plastic) and use
them to attach the thermostat extension bracket (stainless) to the thermostat bracket (plastic). See Fig. 5.
Thermostat Extension Bracket (stainless)
Thermostat Bracket (plastic)
Thermostat Bulb Attachment (plastic)
Fig. 5
2) Replace the panels and baffle in their correct positions unless you are installing anupper unit. If you are installing an upper unit, see "II.D.3. Installation of Upper Unit."
20
b) KM-1900/2100/2500S_H/3
6) Install the bin control thermostat as follows: a. Remove the baffle from the ice storage bin. b. Remove the tie securing the bin control thermostat assembly. Remove the
2 thumbscrews and the "Z" bracket.
c. Remove the bin control thermostat assembly from the shipping hook by lifting it up
and shifting it to the right. Lower the thermostat extension bracket (stainless) with the thermostat bulb attachment and thermostat bulb through the hole located at the bottom of the icemaker. Next, lower the thermostat bracket (plastic) through the hole. See Fig. 6.
d. Slide the left side of the upper part of the assembly towards you and make sure it
is hooked on the wall. Make sure the left side and bottom of the assembly are ush against the wall and base panel.
e. Secure the assembly into place with the thumbscrews unless you are installing
anupper unit. If you are installing an upper unit, complete steps f through h or fthroughi (depending on the ice storage bin used) and then see "II.D.3. Installation of Upper Unit."
f. Insert the plug into the receptacle on the assembly until it locks into place. See Fig. 7.
Wall
Shipping Hook
Bin Control Thermostat Assembly
Thermostat Bracket (plastic)
Tie
Thermostat Bulb Attachment (plastic) and Thermostat Bulb
Thermostat Extension Bracket (stainless)
Receptacle
"Z" Bracket
Plug
Fig. 7
Thumbscrews
Hole
Fig. 6
If a Hoshizaki B-800, B-900, or B-1150 ice storage bin is used:
g. Put aside the "Z" bracket; it is not needed
with the ice storage bins listed above.
h. Remove the 2 screws from the lower part
of the thermostat bracket (plastic) and use them to attach the thermostat extension bracket (stainless) to the thermostat bracket (plastic). See Fig. 8.
Fig. 8
Thermostat Extension Bracket (stainless)
Hook
Bushing
Thumbscrews
Thermostat Bracket (plastic)
21
If a Hoshizaki B-1300, B-1500, B-1650, or non-Hoshizaki ice storage bin is used:
g. Remove the 2 screws securing the thermostat bulb attachment (plastic) to the
thermostat extension bracket (stainless). Use the 2 screws to attach the "Z" bracket (plastic) to the thermostat extension bracket (stainless).
h. Use the two 4×10 stainless steel screws in the accessory bag to attach the
thermostat bulb attachment (with attached thermostat bulb) to the "Z" bracket.
i. Remove the 2 screws from the lower part of the thermostat bracket (plastic) and use
them to attach the thermostat extension bracket (stainless) to the thermostat bracket (plastic). See Fig. 9.
Thermostat Bracket (plastic)
Thermostat Bulb Attachment (plastic)
Thermostat Extension Bracket (stainless)
"Z" Bracket (plastic)
Fig. 9
7) Replace the panels and baffle in their correct positions unless you are installing anupper unit. If you are installing an upper unit, see "II.D.3. Installation of Upper Unit." Note: The bin control thermostat must be checked for proper operation at startup.

3. Installation of Upper Unit

Icemaker (Upper Unit)
1) See "II.D.1. Dispenser Unit/Ice Storage Bin and Icemaker Setup" and "II.D.2. Bin Control Installation" for the lower unit installation.
2) Remove the top panel and the top
Mounting Brackets
insulation of the lower unit. These pieces must be removed when installing an upper unit.
3) Unpack the upper unit, and remove the shipping carton, tape, and packing material.
Bolts
4) Remove the panels of the upper unit.
5) Stack the upper unit on top of the lower unit.
6) Secure the upper unit to the lower unit using the 2 mounting brackets and the bolts provided. See Fig. 10.
7) Remove the tie securing the upper unit's bin control thermostat assembly.
Icemaker (Lower Unit)
Ice Storage Bin
Fig. 10
22
8) Remove the bin control thermostat assembly from the shipping hook by lifting it up and shifting it to the right.
9) Remove the thermostat bulb attachment (plastic) of the upper unit from the thermostat extension bracket (stainless).
10) Carefully remove the thermostat bulb from the thermostat bulb attachment (plastic) of the upper unit.
11) Carefully route the thermostat bulb and capillary tubing of the upper unit through the bottom hole of the upper unit. Remove the bushing from the lower bin control thermostat assembly. Route the bulb and tubing through the hole in the assembly and down into the ice storage bin. Reattach the bushing.
12) Secure the lower bin control thermostat assembly into place with the thumbscrews.
13) Carefully insert the thermostat bulb of the upper unit back into the thermostat bulb attachment (plastic).
14) Secure the thermostat bulb attachment (plastic) of the upper unit to the thermostat bulb attachment (plastic) of the lower unit with the screws of the upper unit. See Fig. 11.
15) Insert the plug of the upper unit into the receptacle of the upper unit's bin control thermostat assembly until it locks into place.
16) Replace the panels and baffle in their correct positions.
Thermostat Extension Bracket (stainless) or "Z" Bracket (plastic) Depending on Icemaker and Ice Storage Bin Model
Thermostat Bulb Attachment Removed from Upper Unit
Thermostat Bulb Attachment of Lower Unit
Thermostat Capillary Tubing
Thermostat Bulb
Fig. 11
23

E. Electrical Connection

WARNING
For All Models
• Electrical connection must be hard-wired and must meet national, state, and local electrical code requirements. Failure to meet these code requirements could result in death, electric shock, serious injury, re, or damage.
• The icemaker requires an independent power supply of proper capacity. See the nameplate for electrical specications. Failure to use an independent power supply of proper capacity can result in a tripped breaker, blown fuse, damage to existing wiring, or component failure. This could lead to heat generation or re.
THE ICEMAKER MUST BE GROUNDED. Failure to properly ground the icemaker could result in death or serious injury.
• Electrical connection must be made in accordance with the instructions on the "WARNING" tag, provided with the pig tail leads in the junction box. See Fig. 12.
Additional Warnings for Remote Models
THE REMOTE CONDENSER UNIT MUST BE GROUNDED. Power supply and ground connection to the remote condenser unit are supplied from the icemaker. See "II.G.6. Electrical Connection." Failure to properly ground the remote condenser unit could result in death or serious injury.
• To reduce the risk of electric shock, make all remote condenser unit connections before connecting the icemaker power supply.
NOTICE
On remote models, the appliance must have power for a minimum of 4hours prior to startup to prevent compressor damage.
• Usually an electrical permit and services of a licensed electrician are required.
• The maximum allowable voltage variation is ±10 percent of the nameplate rating.
NOTICE! On single phase KM-1301S_H models, the transformer’s voltage tap switch
must be positioned to match incoming voltage at startup.
NOTICE! On single phase KM-1601S_H and KM-1900S_H models, the white lead must be connected to the neutral conductor of the power source. Miswiring may result in severe damage to the icemaker.
NOTICE! On three phase models, the transformer’s voltage tap switch must be positioned to match incoming voltage at startup.
NOTICE! On three phase models, connect the highest incoming voltage supply ("stinger leg") to the power wire dedicated to the compressor. See the wiring label on the icemaker.
• The opening for the power supply connection is 7/8" DIA to t a 1/2" trade size conduit.
24
KM-1301S_H
 WARNING
208-230
V
KM-1601S_H KM-1900S_H
KM-1301S_H3 KM-1601S_H3 KM-1900S_H3 KM-2100S_H3 KM-2500S_H3
 WARNING
ELECTRICAL CONNECTION
THIS UNIT MUST BE GROUNDED
Failure to properly ground or wire this unit could result in death, serious injury, or severe damage to the icemaker. The transformer’s voltage tap switch must be positioned to match incoming voltage at startup. See diagram below.
208-230/60/1
JUNCTION BOX
L1
BROWN
V
208-230
L2
BLACK
4A4741-011
Fig. 12
ELECTRICAL CONNECTION
THIS UNIT MUST BE GROUNDED
Failure to properly ground or wire this unit could result in death, serious injury, or severe damage to the icemaker. This unit must be connected to a three-phase power source. The transformer’s voltage tap switch must be positioned to match incoming voltage at startup. See diagram below.
208-230/60/3
208-
230V
208-
230V
L1
L2
L3
JUNCTION BOX
BROWN
RED
BLACK
25

F. Water Supply and Drain Connections

See Figs. 13 through 15
WARNING
Water supply and drain connections must be installed in accordance with applicable national, state, and local regulations.
NOTICE
• Normal operating water temperature should be within 45°F to 90°F (7°C to 32°C). Operation of the appliance, for extended periods, outside of this normal temperature range may affect appliance performance.
• Water supply pressure must be a minimum of 10 PSIG and a maximum of 113PSIG. If the pressure exceeds 113 PSIG, the use of a pressure reducing valve is required.
• To prevent damage to the appliance, do not operate the appliance when the water supply is off, or if the pressure is below 10 PSIG. Do not run the appliance until the proper water pressure is reached.
• External lters, strainers, or softeners may be required depending on water quality. Contact your local Hoshizaki Certied Service Representative or local Hoshizaki distributor for recommendations.
• A plumbing permit and services of a licensed plumber may be required in some areas.
• The icemaker drain line, dispenser unit/ice storage bin drain line, and water-cooled condenser drain line (if applicable) must be run separately. The condensation drain line can be connected to the icemaker drain line or can be run separately.
• Drain lines must have 1/4" fall per foot (2 cm per 1 m) on horizontal runs to get a good ow. A vented tee connection is also required for proper ow.
• Drain lines should not be piped directly to the sewer system. An air gap of a minimum of 2vertical inches (5 cm) should be between the end of the drain pipes from the icemaker and condensation drain, dispenser unit/ice storage bin, and water-cooled condenser (if applicable) and the oor drain.
26

1. Icemaker

Icemaker Water Supply Inlet
1/2" Female Pipe Thread (FPT)
Minimum Icemaker Water Supply Line Size
3/8" Nominal ID Copper Water Tubing or Equivalent
Icemaker Drain Outlet
3/4" Female Pipe Thread (FPT)
Minimum Icemaker Drain Line Size
3/4" Nominal ID Hard Pipe or Equivalent
Condensation Drain Outlet
3/8" OD Hard Tube
• An icemaker water supply line shut-off valve and drain valve must be installed.
• Be sure there is sufficient extra water supply line and drain line for the appliance to be pulled out for service.
Icemaker Water Supply Inlet 1/2" FPT
Remote Condenser Line Set Connections
Icemaker
Minimum 3/8" Nominal ID Copper Water Tubing or Equivalent
Shut-Off Valve
Icemaker Drain Outlet 3/4" FPT
Vent Tube
Bin Drain Outlet 3/4" FPT
Icemaker Condensation Drain Outlet 3/8" OD Hard Tube
Ice Storage Bin
Minimum 3/4" Nominal ID Hard Pipe or Equivalent
Drain Valve
Be sure there is sufficient extra water supply line and drain line for the appliance to be pulled out for service.
Separate piping to approved drain. Leave a 2-inch (5-cm) vertical air gap between the end of each pipe and the drain.
2-inch (5-cm) air gap
Fig. 13
Model Shown: KM-1601SRH
Air-Cooled and Remote Models
27
Floor
Drain

2. Water-Cooled Condenser

a) Connection to an Open Drain System
Condenser Water Supply Inlet
1/2" Female Pipe Thread (FPT)
Minimum Condenser Water Supply Line Size
3/8" Nominal ID Copper Water Tubing or Equivalent
Condenser Drain Outlet
3/8" Female Pipe Thread (FPT)
Minimum Condenser Drain Line Size
3/8" Nominal ID Hard Pipe or Equivalent
• A condenser water supply line shut-off valve and drain valve must be installed.
• In some areas, a back ow preventer may be required in the cooling water circuit.
• In order to maintain the proper high side pressure, the condenser water supply inlet temperature should not drop below 45°F (7°C) and the condenser drain outlet temperature must be in the 104°F to 115°F (40°C to 46°C) range. Once the icemaker installation is complete, conrm the condenser drain outlet temperature 5 minutes after a freeze cycle starts. If the condenser drain outlet temperature is not in the proper range, use a at blade screwdriver to rotate the adjustment screw on the water-regulating valve until the temperature is in the proper range (rotate counterclockwise to raise temperature or clockwise to lower temperature).
Minimum 3/8" Nominal ID Copper
Icemaker Water Supply Inlet 1/2" FPT
Vent Tube
Icemaker
Water Tubing or Equivalent
Shut-Off Valve
Condenser Water Supply Inlet 1/2" FPT
Condenser Drain Outlet 3/8" FPT
Icemaker Drain Outlet 3/4" FPT
Bin Drain Outlet 3/4" FPT
Minimum 3/8" Nominal ID Hard Pipe or Equivalent
Fig. 14
Model Shown: KM-1601SWH
Ice Storage Bin
Vent Tube
Minimum 3/4" Nominal ID Hard Pipe or Equivalent
Icemaker Condensation Drain Outlet 3/8" OD Hard Tube
Water-Cooled Models
Connection to an Open Drain System
Minimum 3/8" Nominal ID Copper Water Tubing or Equivalent
Drain Valve
Be sure there is sufficient extra water supply line and drain line for the appliance to be pulled out for service.
Separate piping to approved drain. Leave a 2-inch (5-cm) vertical air gap between the end of each pipe and the drain.
2-inch (5-cm) air gap
Floor
Drain
28
b) Connection to a Closed Loop System
Condenser Water Supply Inlet
1/2" Female Pipe Thread (FPT)
Minimum Condenser Water Supply Line Size
3/8" Nominal ID Copper Water Tubing or Equivalent
Condenser Return Outlet
3/8" Female Pipe Thread (FPT)
Minimum Condenser Return Line Size
3/8" Nominal ID Copper Water Tubing or Equivalent
• Shut-off valves and drain valves must be installed at both the condenser water supply inlet and condenser return outlet.
• Minimum water ow to the condenser is 4 GPM.
• The pressure differential between the condenser water supply inlet and condenser return outlet must be no less than 10 PSIG.
• When using a glycol blend, the solution mixture should be less than 30% glycol.
• In order to maintain the proper high side pressure, the condenser water supply inlet temperature should not drop below 45°F (7°C) and the condenser return outlet temperature must be in the 104°F to 115°F (40°C to 46°C) range. Once the icemaker installation is complete, conrm the condenser return outlet temperature 5 minutes after a freeze cycle starts. If the condenser return outlet temperature is not in the proper range, use a at blade screwdriver to rotate the adjustment screw on the water-regulating valve until the temperature is in the proper range (rotate counterclockwise to raise temperature or clockwise to lower temperature).
Icemaker Water Supply Inlet 1/2" FPT
Vent Tube
Condenser Water Supply Inlet 1/2" FPT
Condenser Return Outlet 3/8" FPT
Icemaker Drain Outlet 3/4" FPT
Bin Drain Outlet 3/4" FPT
Minimum 3/8" Nominal ID Copper Water Tubing or Equivalent
Icemaker
Ice Storage Bin
Vent Tube
Minimum 3/4" Nominal ID Hard Pipe or Equivalent
Icemaker Condensation Drain Outlet 3/8" OD Hard Tube
Shut-Off Valve
Minimum 3/8" Nominal ID Copper Water Tubing or Equivalent
Drain Valve
Be sure there is sufficient extra water supply line and drain line for the appliance to be pulled out for service.
Separate piping to approved drain. Leave a 2-inch (5-cm) vertical air gap between the end of each pipe and the drain.
2-inch (5-cm) air gap
Fig. 15
Model Shown: KM-1601SWH
Water-Cooled Models
Connection to a Closed Loop System
29
Floor
Drain

G. Installation of Remote Condenser Unit

WARNING
• Installation of remote condenser unit must be performed by properly trained and EPA-certied service personnel.
• The remote condenser unit must be installed in accordance with applicable national, state, and local codes and regulations.
• Failure to install the remote condenser unit within these guidelines may adversely affect safety, performance, component life, and warranty coverage.
• Power supply and ground wire to the remote condenser unit are supplied from the icemaker. For details, see section "II.G.6. Electrical Connection."

1. Location

NOTICE
• The remote condenser unit is intended for outdoor use. Normal operating ambient temperature must be within -20°F to +122°F (-29°C to +50°C). Operation of the remote condenser unit, for extended periods, outside of this normal temperature range may affect appliance performance.
• The maximum line length for the standard line sizes and refrigerant charge is 66' (20 m). With larger line sizes and/or additional refrigerant, the maximum line length is 100' (30.5 m). For details, see "II.G.4 Line Set Size and Refrigerant Charge."
• The maximum vertical distance between the remote condenser unit and the icemaker is 33' (10 m) above or 10' (3 m) below the icemaker. These distances are measured tting to tting. See Fig. 16.
The remote condenser unit must be positioned in a permanent site under the following guidelines:
• A rm and at site.
• A dry and well ventilated area with 24" (61cm) clearance at front and rear for proper air circulation and ease of maintenance and/or service should they be required. See Fig. 17.
Icemaker
Min. 24" (61 cm) Clearance
Air Air
Max. 33' (10 m)
Remote Condenser Unit
Icemaker
Max. 10' (3 m)
Service Loop
Fig. 16
Service Loop
Remote Condenser Unit
30
Fig. 17

2. Checks Before Installation

1) Remove the shipping carton, tape, and packing material.
2) Check that the refrigerant lines do not rub or touch lines or other surfaces, and that the fan blades move freely.

3. Setup

1) Assemble 2 sets of legs using the legs, bolts, and nuts provided. See Fig. 18.
2) Position 1 of the plates provided between a set of legs and the remote condenser unit, then secure the legs to the remote condenser unit with the
Plate
Nut
bolts and nuts provided. Repeat on the other side with the remaining set of legs.
Leg
3) The bottom of each leg has a mounting hole. Secure the legs to the permanent site with 4 bolts (not included).
Bolt with Split Lock Washer and Flat Washer
Fig. 18

4. Line Set Size and Refrigerant Charge

NOTICE
The icemaker, line set, and remote condenser unit must contain the same type of refrigerant. Mixing of refrigerants will result in improper operation and possible damage to the refrigeration system.
Line Set Size and Refrigerant Charge
Line Set Hoshizaki Remote
Hoshizaki Icemaker
KM-1301SRH/3 URC-14F 3/8" OD1/2" OD Not
KM-1601SRH/3 KM-1900SRH/3 KM-2100SRH3
KM-2500SRH3 URC-23F
Condenser Unit
URC-22F 3/8" OD5/8" OD Not
Line Set Up to 66' (20 m) Liquid Line
Discharge Line
Charge Adjustment
Applicable
Applicable
Greater than 66' (20 m)
Maximum 100' (30.5 m)
Liquid
Line
3/8" OD1/2" OD Add 0.4 oz. for each
3/8" OD5/8" OD Add 0.4 oz. for each
Discharge Line
Charge Adjustment (R-404A)
foot over 66' (40g for each meter over 20m). Write new total charge on icemaker's rating label.
foot over 66' (40g for each meter over 20m). Write new total charge on icemaker's rating label.
Nut
31

5. Line Set Installation

Precharged factory line sets, available as optional equipment from Hoshizaki America, are recommended. For details, see "II.G.5.a) Factory Line Set Installation." Field fabricated line sets are allowed. For details, see "II.G.5.b) Field Fabricated Line Set Installation."
a) Factory Line Set Installation
1) Route the factory line set (see "II.G.4 Line Set Size and Refrigerant Charge" for details) from the remote condenser unit to the icemaker. Leave a service loop behind the icemaker to allow the icemaker to be pulled out for service. See Fig. 19. Factory fabricated line sets are precharged and do not need to be evacuated. If the line set is too long or too short, see "II.G.5.a)(1) Factory Line Set Modication."
NOTICE
• Ensure that there are no traps and no kinks in the line set. The service loop is not considered an oil trap.
• Do not coil extra line set.
2) Connect the refrigerant lines to the appropriate male ttings on the remote condenser unit rst and then at the icemaker. Make a proper connection as follows:
a. Remove the protective covers from the male tting and female coupling. b. Apply Polyol Ester (POE) refrigerant oil or Parker Super O Lube to the entire male
tting, including O-ring, diaphragm, and threads before making the connection. SeeFig. 20. NOTICE! Do not use thread sealant on the ttings. Use POE
refrigerant oil or Parker Super O Lube only. Couplings are one-time use only.
c. Make sure the male tting and female coupling are properly aligned, then start the
connection by hand to ensure that it is not cross threaded.
d. Place a backup wrench on the back of the female coupling, then tighten the
connection with a wrench until it is tight. At this point, the nut has covered most of the threads on the male tting. NOTICE! Failure to use a backup wrench may
result in damage to the line set and possible refrigerant leaks.
e. Mark a reference line on the female coupling and the remote condenser unit or
icemaker panel. Using a backup wrench on the back of the female coupling, tighten the six-sided nut of the female coupling an additional 1/6 turn. See Fig. 21.
NOTICE! Conrm connection is free of leaks.
3) If you lengthened the line set as outlined in "II.G.5.a)(1) Factory Line Set Modication" and it exceeds 66' (20 m), see "II.G.4. Line Set Size and Refrigerant Charge" for proper charging of the appliance.
32
(1) Factory Line Set Modication
1) Recover the line set charge through the Schrader access ports on the Parker quick connect couplings and store it in an approved container. Do not discharge the refrigerant into the atmosphere. Remove the extra line set length or add extra tubing. When adding extra tubing, insulate the additional copper tubes separately.
2) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of refrigerant to the lines through the Schrader access ports on the Parker quick connect couplings (if using an electronic leak detector), and then raise the pressure using nitrogen gas (140 PSIG). WARNING! Do not use R-404A as a mixture with
pressurized air for leak testing.
3) Evacuate through the Schrader access ports on the Parker quick connect couplings and charge with R-404A refrigerant vapor to a pressure of 15 to 30 PSIG. Go to step 2 in "II.G.5.a) Factory Line Set Installation."
b) Field Fabricated Line Set Installation
1) Route the copper tube liquid line and copper tube discharge line (see "II.G.4 Line Set Size and Refrigerant Charge" for details) from the remote condenser unit to the icemaker. Leave a service loop behind the icemaker to allow the icemaker to be pulled out for service. See Fig. 19.
NOTICE
• Ensure that there are no traps and no kinks in the line set. The service loop is not considered an oil trap.
• Do not coil extra line set. Fabricate the line set to the proper length.
2) Insulate the two copper tubes separately.
3) Install Parker quick connect couplings on each end. OS-QUICK, a universal quick connect coupling kit available as optional equipment from Hoshizaki America, is recommended. NOTICE! Before brazing, remove the Schrader valve core from the
access port. When brazing, protect the coupling by using a wet cloth to prevent the coupling from overheating. Do not use silver alloy or copper alloy containing arsenic.
4) Allow the coupling to cool, then replace the Schrader valve core.
5) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of refrigerant to the lines through the Schrader access ports on the Parker quick connect couplings (if using an electronic leak detector), and then raise the pressure using nitrogen gas (140 PSIG). WARNING! Do not use R-404A as a mixture with
pressurized air for leak testing.
6) Evacuate through the Schrader access ports on the Parker quick connect couplings and charge with R-404A refrigerant vapor to a pressure of 15 to 30 PSIG.
33
7) Connect the refrigerant lines to the appropriate male ttings on the remote condenser unit rst and then at the icemaker. Make a proper connection as follows:
a. Remove the protective covers from the male tting and female coupling. b. Apply Polyol Ester (POE) refrigerant oil or Parker Super O Lube to the entire male
tting, including O-ring, diaphragm, and threads, before making the connection. SeeFig. 20. NOTICE! Do not use thread sealant on the ttings. Use POE
refrigerant oil or Parker Super O Lube only. Couplings are one-time use only.
c. Make sure the male tting and female coupling are properly aligned, then start the
connection by hand to ensure that it is not cross threaded.
d. Place a backup wrench on the back of the female coupling, then tighten the
connection with a wrench until it is tight. At this point, the nut has covered most of the threads on the male tting. NOTICE! Failure to use a backup wrench may
result in damage to the line set and possible refrigerant leaks.
e. Mark a reference line on the female coupling and the remote condenser unit or
icemaker panel. Using a backup wrench on the back of the female coupling, tighten the six-sided nut of the female coupling an additional 1/6 turn. See Fig. 21.
NOTICE! Conrm connection is free of leaks.
8) If the line set exceeds 66' (20 m), see "II.G.4. Line Set Size and Refrigerant Charge" for proper charging of the appliance.
Fig. 19
Fig. 20
Fig. 21
Remote Condenser Unit
Male Fitting
Brush
Threads
Reference Line
Diaphragm
O-Ring
Wrench
Male Fitting
Female Coupling
Discharge Line (Insulated) See "II.G.4 Line Set Size and Refrigerant Charge" for details.
Liquid Line (Insulated) See "II.G.4 Line Set Size and Refrigerant Charge" for details.
Apply POE Oil or Parker Super O Lube to Entire Male Fitting
After Tight, Tighten an Additional 1/6 Turn
Icemaker
Service Loop
DO NOT USE
THREAD SEALANT
1/6 Tu r n
Backup Wrench
34
Backup Wrench
Wrench

6. Electrical Connection

WARNING
• Electrical connection must meet national, state, and local electrical code requirements. Failure to meet these code requirements could result in death, electric shock, serious injury, re, or damage.
• To reduce the risk of electric shock, make all remote condenser unit connections before connecting the icemaker power supply.
THE REMOTE CONDENSER UNIT MUST BE GROUNDED. Install a ground wire from the icemaker fan motor junction box to the remote condenser unit junction box. Use wire of an appropriate gage and outdoor rating. Failure to properly ground the remote condenser unit could result in death or serious injury.
• Install line and neutral wires from the fan motor leads in the icemaker fan motor junction box to the leads in the remote condenser unit junction box. Use wire of an appropriate gage and outdoor rating.
• Do not connect the fan motor leads in the icemaker to incoming power source. Do not connect the fan motor leads in the icemaker together. Do not allow the leads to contact the junction box walls.
• Do not connect the remote condenser unit to an external power source.
NOTICE
On remote models, the appliance must have power for a minimum of 4hours prior to startup to prevent compressor damage.
• Usually an electrical permit and services of a licensed electrician are required.
• The opening for the power supply connection is 7/8" DIA to t a 1/2" trade size conduit.
1) Remove the remote condenser unit louver panel. See Fig. 22.
2) Remove the icemaker fan motor junction box cover. Remove the remote condenser unit junction box cover.
Remote Condenser Unit
Screws
Louver Panel
Fan Motor Junction Box Cover
Icemaker
Fig. 22
Junction Box Cover
Screw
35
3) Install a ground wire from the icemaker fan motor junction box to the remote condenser unit junction box. Use wire of an appropriate gage and outdoor rating.
4) Install line and neutral wires from the fan motor leads in the icemaker fan motor junction box to the leads in the remote condenser unit junction box. Use wire of an appropriate gage and outdoor rating.
5) Replace the junction box covers and the louver panel in their correct positions.

7. Stacking Remote Condenser Unit

1) Install the lower remote condenser unit as described earlier in this section.
2) Place the upper remote condenser unit on top of the lower remote condenser unit. See Fig. 23.
3) Secure the upper remote condenser unit to the lower remote condenser unit with the 4screws provided.
4) Install refrigerant lines and make electrical connection as described earlier in this section.
Upper Remote Condenser Unit
Screws
Screws
Lower Remote Condenser Unit
Fig. 23
36

H. Final Checklist

WARNING
CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews
are securely in place after installation. Make sure that none have fallen into the dispenser unit/ice storage bin.
1) Is the icemaker level?
2) Is the icemaker in a site where the ambient temperature is within 45°F to 100°F (7°C to 38°C) and the water temperature within 45°F to 90°F (7°C to 32°C) all year around?
3) All models except KM-1601SAH/3: Is there at least 6" (15 cm) clearance at rear, sides, and top of the icemaker? KM-1601SAH/3: Is there at least 9" (23 cm) clearance at rear, sides, and top of the icemaker?
4) Have the shipping carton, tape, and packing material been removed from the appliance? Is the cube guide in the correct position? Are the separators between the evaporator banks properly attached to their holding clips?
5) Have all electrical and water connections been made? Do electrical and water connections meet applicable national, state, and local code and regulation requirements?
6) Has the power supply voltage been checked or tested against the nameplate rating? Has a proper ground been installed to the icemaker? On remote models, has a proper ground also been installed to the remote condenser unit? On single phase KM-1301S_H models and on all three phase models, has the transformer's voltage tap switch been positioned to match incoming voltage?
7) Are the water supply and drain lines sized as specied? Are the water supply line shut-off valve(s) and drain valve(s) installed? Has the water supply pressure been checked to ensure a minimum of 10 PSIG and a maximum of 113 PSIG?
8) Is the compressor snug on all mounting pads? Have the refrigerant lines been checked to make sure they do not rub or touch other lines or surfaces? Have the fan blades (if applicable) been checked to make sure they turn freely?
9) On remote models:
• Is the line set sized as specied, insulated, tightened, and free of leaks and kinks?
• If the line set exceeds 66' (20 m), has the charge been adjusted as specied?
• Has the appliance power supply been on for a minimum of 4 hours?
• Is the remote condenser unit in a site where the ambient temperature is within
-20°F to +122°F (-29°C to +50°C) all year around?
• Is there at least 24" (61 cm) clearance around the remote condenser unit?
10) Are all components, fasteners, and thumbscrews securely in place?
11) Has the end user been given the instruction manual, and instructed on how to operate the appliance and the importance of the recommended periodic maintenance?
12) Has the end user been given the contact information of an authorized service agent?
13) Has the warranty card been lled out and forwarded to the factory for warranty registration?
37

I. Startup

WARNING
All parts are factory-adjusted. Improper adjustments may adversely affect safety, performance, component life, and warranty coverage.
NOTICE
• If the icemaker is turned off, wait for at least 3 minutes before restarting the icemaker to prevent damage to the compressor.
• To prevent damage to the water pump seal, do not leave the control switch in the "WASH" position for extended periods when the water tank is empty.
• At startup, conrm that all internal and external connections are free of leaks.
Additional Notice for Remote Models
• The icemaker must have power for a minimum of 4hours prior to startup to prevent compressor damage.
1) Open the water supply line shut-off valve(s).
2) Remove the front panel.
3) Move the control switch on the control box to the "ICE" position.
4) Replace the front panel in its correct position.
5) Turn on the power supply, and allow the icemaker to operate for a total of 10 minutes.
6) Turn off the power supply, then remove the front panel.
7) Remove the insulation panel. Remove the drain plug located on the lower front part of the ice chute. See Fig. 24. Allow the water tank to drain.
8) Replace the drain plug, insulation panel, and front panel in their correct positions. Be careful not to cross thread the drain plug.
9) Clean the dispenser unit/ice storage bin liner using a neutral cleaner. Rinse thoroughly after cleaning.
10) Turn on the power supply to start the automatic icemaking process.
11) When the icemaker is running, hold an ice cube in contact with the bulb. The icemaker should stop within 10 seconds. Adjustment may be needed, particularly at higher altitude locations.
12) On water-cooled models, conrm proper condenser drain outlet/return outlet temperature as outlined in "II.F.2.Water-Cooled Condenser."
Drain Plug
Cleaning Valve
Fig. 24
Ice Chute
Float Switch Assembly
38

III. Maintenance

The appliance must be maintained in accordance with the instruction manual and labels provided. Consult with your local Hoshizaki Certied Service Representative about maintenance service.
WARNING
• Only qualied service technicians should service the appliance.
• To reduce the risk of electric shock, do not touch the control switch with damp hands.
• Move the control switch to the "OFF" position and turn off the power supply before servicing. Lockout/Tagout to prevent the power supply from being turned back on inadvertently.
CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews are securely in place after any maintenance is done to the appliance. Make sure that none have fallen into the dispenser unit/ice storage bin.

A. Maintenance Schedule

The maintenance schedule below is a guideline. More frequent maintenance may be required depending on water quality, the appliance's environment, and local sanitation regulations.
Maintenance Schedule
Frequency Area Task
Daily Scoop Clean the ice scoop using a neutral cleaner. Rinse thoroughly after cleaning. Bi-Weekly Air Filters Inspect. Wash with warm water and neutral cleaner if dirty. Monthly External Water
Filters Icemaker Exterior Wipe down with a clean, soft cloth. Use a damp cloth containing a neutral
Underside of Icemaker and Top Kits; Bin Door and Snout
Yearly Icemaker and
Dispenser Unit/Ice Storage Bin
Water Supply Inlet Close the icemaker water supply line shut-off valve and drain the water
Condenser Inspect. Clean if necessary by using a brush or vacuum cleaner. More
Water Hoses Inspect the water hoses and clean/replace if necessary.
Check for proper pressure and change if necessary.
cleaner to wipe off oil or dirt build up. Clean any chlorine staining (rust colored spots) using a non-abrasive cleanser.
Wipe down with a clean cloth and warmwater.
Clean and sanitize per the cleaning and sanitizing instructions provided in this manual. See "III.B. Cleaning and Sanitizing Instructions."
system. Clean the water supply inlet screen.
frequent cleaning may be required depending on location.
39

B. Cleaning and Sanitizing Instructions

The icemaker must be cleaned and sanitized at least once a year. More frequent cleaning and sanitizing may be required in some water conditions.
WARNING
• To prevent injury to individuals and damage to the icemaker, do not use ammonia type cleaners.
• Carefully follow any instructions provided with the bottles of cleaning and sanitizing solution.
• Always wear liquid-proof gloves and goggles to prevent the cleaning and sanitizing solutions from coming into contact with skin or eyes.
NOTICE
To prevent damage to the water pump seal, do not leave the control switch in the "WASH" position for extended periods when the water tank is empty.
IMPORTANT
• The cleaning valve is opened during cleaning and sanitizing to allow solution ow to the inside of the evaporator. It should be closed for all icemaking operation. The compressor will not operate unless this valve is completely closed.
• To close the cleaning valve, the valve handle should be at a right angle to the valve body. To open the cleaning valve, the valve handle should be parallel to the valve body.
CLOSED
Icemaking Operation
Cleaning and Sanitizing Operation
(allows solution ow to the inside of the evaporator)
OPEN

1. Cleaning Procedure

1) Dilute Hoshizaki "Scale Away" with warm water. Refer to the table.
Model Scale Away Warm Water
KM-1601 and Smaller 27 . oz. (800 ml) 5 gal. (19 l) KM-1900 and Larger 38 . oz. (1,124 ml) 7 gal. (26 l)
2) Remove all ice from the evaporator and the dispenser unit/ice storage bin. Note: To remove cubes on the evaporator, turn off the power supply and turn it back on
after 3 minutes. The harvest cycle starts and the cubes will be removed from the evaporator.
3) Turn off the power supply.
4) Remove the front panel, then remove the insulation panel by removing the thumbscrew, lifting up the panel slightly, and pulling it towards you.
5) Remove the drain plug located on the lower front part of the ice chute. See Fig. 24. Allow the water tank to drain.
40
6) Replace the drain plug in its correct position. Be careful not to cross thread it.
7) In bad or severe water conditions, clean the oat switch assembly as described below. Otherwise, continue to step 8.
a. Disconnect the vent tube and the ush tube from the top of the oat switch, then
remove the oat switch assembly. Remove the rubber boot from the bottom of the assembly.
b. Remove the retainer rod from the bottom of the oat switch housing, then remove
the oat. Be careful not to bend the retainer rod excessively when removing it.
c. Wipe down the oat switch housing, shaft, oat, and retainer rod with cleaning
solution. Clean the inside of the rubber boot and hose with cleaning solution. Rinse the parts thoroughly with clean water.
d. Reassemble the oat switch assembly and replace it and the rubber boot in their
correct positions. Reconnect the vent tube and the ush tube.
8) Pour the cleaning solution into the water tank.
9) Fully open the cleaning valve on the left side wall of the machine compartment.
10) Move the control switch to the "WASH" position.
11) Replace the insulation panel and the front panel in their correct positions.
12) Turn on the power supply to start the washing process.
13) Turn off the power supply after 30 minutes.
14) Remove the front panel and the insulation panel.
15) Remove the drain plug. Allow the water tank to drain. Replace the drain plug and the insulation panel in their correct positions.
16) Move the control switch to the "ICE" position.
17) Close the cleaning valve. Note: The icemaker will not operate unless the cleaning valve is completely closed.
18) Replace the front panel in its correct position.
19) Turn on the power supply to ll the water tank with water.
20) Turn off the power supply after 3 minutes.
21) Remove the front panel and fully open the cleaning valve.
22) Move the control switch to the "WASH" position.
23) Replace the front panel in its correct position.
24) Turn on the power supply to rinse off the cleaning solution.
25) Turn off the power supply after 5 minutes.
26) Remove the front panel and the insulation panel.
27) Remove the drain plug. Allow the water tank to drain. Replace the drain plug and the insulation panel in their correct positions. Note: Do not replace the insulation panel when you proceed to "2. Sanitizing
Procedure."
28) Repeat steps 16 through 27 three more times to rinse thoroughly. Note: If you do not sanitize the icemaker, go to step 9 in "2. Sanitizing Procedure."
41

2. Sanitizing Procedure - Following Cleaning Procedure

1) Dilute a 5.25% sodium hypochlorite solution (chlorine bleach) with warm water. Refer to the table.
Model
KM-1601 and Smaller 2.5 . oz. (74 ml) 5 gal. (19 l) KM-1900 and Larger 3.5 . oz. (104 ml) 7 gal. (26 l)
5.25% Sodium Hypochlorite Solution (Chlorine Bleach)
Warm Water
2) Pour the sanitizing solution into the water tank.
3) Replace the insulation panel and the front panel in their correct positions. Note: Make sure the control switch is in the "WASH" position and the cleaning valve is
open.
4) Turn on the power supply to start the sanitizing process.
5) Turn off the power supply after 15 minutes.
6) Remove the front panel and the insulation panel.
7) Remove the drain plug. Allow the water tank to drain. Replace the drain plug and the insulation panel in their correct positions.
8) Repeat steps 16 through 27 in "1. Cleaning Procedure" two times to rinse thoroughly.
9) Close the cleaning valve.
10) Move the control switch to the "ICE" position.
11) Replace the front panel in its correct position.
12) Clean the dispenser unit/ice storage bin liner using a neutral cleaner. Rinse thoroughly after cleaning.
13) Turn on the power supply to start the automatic icemaking process.
42

IV. Preparing the Icemaker for Periods of Non-Use

NOTICE
• When storing the icemaker for an extended time or in sub-freezing temperatures, follow the instructions below to prevent damage.
• To prevent damage to the water pump seal, do not leave the control switch in the "WASH" position for extended periods when the water tank is empty.
When the icemaker is not used for two or three days under normal conditions, it is sufficient to move the control switch to the "OFF" position. When storing the icemaker for an extended time or in sub-freezing temperatures, follow the instructions below.
1. Remove the water from the icemaker water supply line:
1) Turn off the power supply, then remove the front panel.
2) Move the control switch to the "OFF" position.
3) Close the icemaker water supply line shut-off valve, then open the icemaker water supply line drain valve.
4) Allow the line to drain by gravity.
5) Attach a compressed air or carbon dioxide supply to the icemaker water supply line drain valve.
6) Move the control switch to the "ICE" position.
7) Replace the front panel in its correct position, then turn on the power supply.
8) Blow the icemaker water supply line out using the compressed air or carbon dioxide supply.
9) Close the icemaker water supply line drain valve.
2. Drain the water tank:
1) Turn off the power supply, then remove the front panel.
2) Move the control switch to the "OFF" position.
3) Remove the insulation panel. Remove the drain plug located on the lower front part of the ice chute. See Fig. 24. Allow the water tank to drain.
4) Replace the drain plug and the insulation panel in their correct positions. Be careful not to cross thread the drain plug.
5) Remove all ice from the dispenser unit/ice storage bin. Clean the dispenser unit/ice storage bin liner using a neutral cleaner. Rinse thoroughly after cleaning.
6) Replace the front panel in its correct position.
3. On water-cooled model only, rst remove the water from the water-cooled
condenser:
1) Make sure the power supply is off, then remove the front, top, and right side panels.
2) Close the condenser water supply line shut-off valve. If connected to a closed loop system, also close the condenser return line shut-off valve.
43
3) Open the condenser water supply line drain valve. If connected to a closed loop system, also open the condenser return line drain valve.
4) Attach a compressed air or carbon dioxide supply to the condenser water supply line drain valve.
5) Open the water regulating valve by using a screwdriver to pry up on the spring retainer underneath the spring. While holding the valve open, blow out the condenser using the compressed air or carbon dioxide supply until water stops coming out.
6) Close the drain valve(s).
7) Replace the right side panel, top panel, and front panel in their correct positions.
44

V. Disposal

The appliance contains refrigerant and must be disposed of in accordance with applicable national, state, and local codes and regulations. Refrigerant must be recovered by properly certied service personnel.
45
HOSHIZAKI AMERICA, INC.
618 Hwy. 74 S., Peachtree City, GA 30269 USA TEL (770) 487-2331 FAX (770) 487-3360 www.hoshizaki.com 1A3553-010
46
Loading...