Only qualied service technicians should install and service the appliance. To
obtain the name and phone number of your local Hoshizaki Certied Service
Representative, visit www.hoshizaki.com. No service should be undertaken until
the technician has thoroughly read this Service Manual. Failure to service and
maintain the appliance in accordance with this manual will adversely affect safety,
performance, component life, and warranty coverage and may result in costly water
damage. Proper installation is the responsibility of the installer. Product failure or
property damage due to improper installation is not covered under warranty.
Hoshizaki provides this manual primarily to assist qualied service technicians in the
service of the appliance.
Should the reader have any questions or concerns which have not been satisfactorily
addressed, please call, send an e-mail message, or write to the Hoshizaki Technical
Support Department for assistance.
HOSHIZAKI AMERICA, INC.
618 Highway 74 South
Peachtree City, GA 30269
Attn: Hoshizaki Technical Support Department
Web Site: www.hoshizaki.com
NOTE: To expedite assistance, all correspondence/communication MUST include the
following information:
• Model Number
• Serial Number
• Complete and detailed explanation of the problem.
2
Page 3
IMPORTANT
This manual should be read carefully before the appliance is serviced. Read
the warnings and guidelines contained in this manual carefully as they provide
essential information for the continued safe use, service, and maintenance of the
appliance. Retain this manual for any further reference that may be necessary.
CONTENTS
Important Safety Information ................................................................................................. 6
I. Construction and Water/Refrigeration Circuit Diagram ....................................................... 8
A. KM Construction............................................................................................................ 8
Throughout this manual, notices appear to bring your attention to situations which could
result in death, serious injury, damage to the appliance, or damage to property.
WARNING Indicates a hazardous situation which could result in death or
serious injury.
NOTICE Indicates a situation which could result in damage to the
appliance or property.
IMPORTANT Indicates important information about the use and care of the
appliance.
WARNING
The appliance should be destined only to the use for which it has been expressly
conceived. Any other use should be considered improper and therefore dangerous.
The manufacturer cannot be held responsible for injury or damage resulting from
improper, incorrect, and unreasonable use. Failure to service and maintain the
appliance in accordance with this manual will adversely affect safety, performance,
component life, and warranty coverage and may result in costly water damage.
To reduce the risk of death, electric shock, serious injury, or re, follow basic
precautions including the following:
• Only qualied service technicians should install and service this appliance.
• The appliance must be installed in accordance with applicable national, state, and
local codes and regulations. Failure to meet these code requirements could result in
death, electric shock, serious injury, re, or damage to the appliance.
• Electrical connection must be hard-wired and must meet national, state, and local
electrical code requirements. Failure to meet these code requirements could result
in death, electric shock, serious injury, re, or damage.
• The icemaker requires an independent power supply of proper capacity. See the
nameplate for electrical specications. Failure to use an independent power supply
of proper capacity can result in a tripped breaker, blown fuse, damage to existing
wiring, or component failure. This could lead to heat generation or re.
• THE ICEMAKER MUST BE GROUNDED. Failure to properly ground the icemaker
could result in death or serious injury.
• To reduce the risk of electric shock, do not touch the control switch with damp
hands.
• Move the control switch to the "OFF" position and turn off the power supply before
servicing. Lockout/Tagout to prevent the power supply from being turned back on
inadvertently.
• Do not make any alterations to the appliance. Alterations could result in electric
shock, serious injury, re, or damage.
6
Page 7
WARNING, continued
• The appliance is not intended for use by persons (including children) with reduced
physical, sensory, or mental capabilities, or lack of experience and knowledge,
unless they have been given supervision or instruction concerning use of the
appliance by a person responsible for their safety.
• Children should be properly supervised around the appliance.
• Do not climb, stand, or hang on the appliance or allow children or animals to do so.
Serious injury could occur or the appliance could be damaged.
• Do not use combustible spray or place volatile or ammable substances near the
appliance. They might catch re.
• Keep the area around the appliance clean. Dirt, dust, or insects in the appliance
could cause harm to individuals or damage to the appliance.
Additional Warning for Remote Models
• THE REMOTE CONDENSER UNIT MUST BE GROUNDED. The power supply and
ground connection to the remote condenser unit are supplied from the icemaker.
Failure to properly ground the remote condenser unit could result in death or
serious injury.
• Wire routing (conduit) and disconnect (if required) must meet national, state, and
local electrical code requirements. Failure to meet these code requirements could
result in death, electric shock, serious injury, re, or damage.
• Move the icemaker control switch to the "OFF" position and turn off the power
supply to the icemaker before servicing the remote condenser unit.
Lockout/Tagout to prevent the power supply from being turned back on
inadvertently.
NOTICE
• Follow the instructions in this manual carefully to reduce the risk of costly water
damage.
• In areas where water damage is a concern, install in a contained area with a oor
drain.
• Install the appliance in a location that stays above freezing. Normal operating
ambient temperature must be within 45°F to 100°F (7°C to 38°C).
• Do not leave the appliance on during extended periods of non-use, extended
absences, or in sub-freezing temperatures. To properly prepare the appliance for
these occasions, follow the instructions in "VI. Preparing the Icemaker for Periods of
Non-Use."
• Do not place objects on top of the appliance.
• The dispenser unit/ice storage bin is for ice use only. Do not store anything else in
the dispenser unit/ice storage bin.
7
Page 8
I. Construction and Water/Refrigeration Circuit Diagram
A. KM Construction
1. Air-Cooled Models (SAH/3)
Evaporator Assembly
Cleaning Valve
Check Valve
(water)
Water Pump
Inlet Water Valve
Spray Tubes
Low-Side Service Valve
High-Side Service Valve
Thermostatic Expansion Valves
Water Supply Inlet
Junction Box
Hot Gas Valve
Check Valves
(refrigeration)
Condenser
Control Box
Fan Blade
Float Switch
Compressor
Thermostatic
Bin Control
Control Switch
Model Shown: KM-1301SAH3
8
Fan Motor
Drier
Liquid Line Valve
Transformer Box (KM-1301SAH
Auxiliary Code D-1 and Later and
All 3 phase model)
High-Pressure
Switch
Page 9
2. Water-Cooled Models (SWH/3/-M)
Evaporator Assembly
Cleaning Valve
Check Valve
(water)
Water Pump
Float Switch
Inlet Water Valve
Compressor
Spray Tubes
Low-Side Service Valve
High-Side Service Valve
Thermostatic
Expansion Valves
Water Supply Inlet
Junction Box
Hot Gas Valve
Check Valves
(refrigeration)
Water-Cooled
Condenser
Water Regulating
Valve
Bin Control Thermostat
Control Switch
Transformer Box (KM-1301SWH
Auxiliary Code D-1 and Later and
All 3 phase model)
Model Shown: KM-1301SWH3
9
Drier
Control Box
Liquid Line Valve
Page 10
3. Remote Models (SRH/3)
Evaporator Assembly
Cleaning Valve
Check Valve
(water)
Water Pump
Inlet Water Valve
Float Switch
Spray Tubes
Low-Side Service Valve
High-Side Service Valve
High-Side Liquid Service Valve
Water Supply Inlet
Hot Gas Valve
Junction Boxes
Check Valves
(refrigeration)
Thermostatic
Expansion Valves
Receiver
Control Box
Compressor
Bin Control Thermostat
Note: KM-2500SRH3 Includes Headmaster (C.P.R.)
Control Switch
Transformer Box (KM-1301SRH
Auxiliary Code D-1 and Later and
All 3 phase model)
Model Shown: KM-1301SRH3
10
Access Valve
Drier
Liquid Line Valve
Page 11
B. KMH Construction
1. Water-Cooled Models (SWH/3)
Spray Tubes
Evaporator Assembly
Cleaning Valve
Check Valve
(water)
Water Pump
Float Switch
Low-Side Service Valve
Inlet Water Valve
High-Side Service Valve
Thermostatic
Expansion
Valves
Check Valves
(refrigeration)
Transformer Box
(3 phase model)
Control Box
Control Switch
Bin Control Thermostat
Model Shown: KMH-2000SWH3
High-Pressure Switch
Junction Box
Water Supply Inlet
Hot Gas Valve
Liquid Line Valve
Compressor
Drier
Model Shown: KMH-2000SWH3
Water Regulating Valve
Water-Cooled Condenser
11
Page 12
2. Remote Models (SRH/3)
Spray Tubes
Inlet Water Valve
Thermostatic
Expansion
Valves
Evaporator Assembly
Cleaning Valve
Check Valve
(water)
Water Pump
Float Switch
Low-Side Service Valve
Model Shown: KMH-2000SRH3
Check Valves
(refrigeration)
High-Side Service Valve
Transformer Box
(3 phase model)
Control Box
Control Switch
Bin Control Thermostat
High-Pressure Switch
Junction Box
Water Supply Inlet
Hot Gas Valve
Liquid Line Valve
Compressor
Drier
Model Shown: KMH-2000SRH3
Receiver
12
Page 13
C. Bin Control
1a. Single Thermostatic Bin Control
Bin Control Bulb Holder C
Bin Control Bulb Holder E
Bin Control Bulb Holder F
Bin Control Bulb Holder G
Spacer
Bin Control
Extension Bracket
Z Bracket Used for Hoshizaki
B-1300, B-1500, B-1650, and
Non-Hoshizaki Ice Stoarage
Bin
1b. Stacked Thermostatic Bin Control
Upper Bin Control Bulb Holder
Lower Bin Control Bulb Holder
Bin Control Bulb Holder C
Silicone Hose
Bin Control Bulb Holder
Bin Control Bulb Holder E
Bin Control Bulb Holder F
Bin Control Bulb Holder G
Spacer
Bin Control
Extension Bracket
Z Bracket Used for Hoshizaki
B-1300, B-1500, B-1650, and
Non-Hoshizaki Ice Stoarage
Bin
Silicone Hose
Upper Bin Control Bulb Holder
Lower Bin Control Bulb Holder
13
Page 14
2a. Single Mechanical Bin Control
Mechanical Bin Control Connection Overview
Wire Harness
Connector B
(for upper unit)
Thumbscrews
Bin Control Cable Connector to
Wire Harness Connector A
Wire Harness
Control Board
Red K4 Connector
Bin Control Bracket
Bin Control Assembly
Bin Control Cable
2b. Stacked Mechanical Bin Control
Wire Saddle
Bin Control
Cable Bracket
Wire Harness
Connector B
(for upper unit)
Bin Control
Cable Connector
Connection Detail
Wire Harness
Connector A
Control Board
Red K4 Connector
Upper Unit Connection Overview
Lower Unit Wire Harness Connector B to
Upper Unit Wire Harness Connector A
Upper Unit Wire Harness
Connector B (not used)
Bin Control
Cable
Bracket
Upper Unit Wire Harness
Control Board
Red K4 Connector
Lower
Unit Wire
Harness
Wire Saddle
Control Board
Red K4 Connector
Upper Unit Connection Detail
Upper Unit Wire Harness
Connector B (not used)
Lower Unit Wire Harness
Connector B
See "II.D.1. Dispenser
Unit/Ice Storage Bin
and Icemaker Setup"
and "II.D.2. Bin Control
Installation" for the
Lower Unit Connection
Upper Unit
Wire Harness
Connector A
Control Board
Red K4 Connector
14
Page 15
D. Water/Refrigeration Circuit Diagram
1. Air-Cooled Models (SAH/3)
Hot Gas
Val ve
High-Pressure
Switch
Check
Valves
Strainer
Drier
Suction Line
Fan
Condenser
Water Supply
Inlet Water Valve
Spray Tubes
Cleaning Valve
Liquid Line
Thermistor
Val ve
Heat Exchanger
Service
Val ve
Service
Val ve
Float Switch
Check Valve
Discharge Line
Compressor
Thermostatic Expansion Valves
Drain
Water Pump
Pump-Out
Spray Tubes
Evaporator
15
Water
Tank
Freeze/Harvest
Pump Timer
Refrigeration Circuit
Water Circuit
Page 16
2. Water-Cooled Models (SWH/3/-M)
Check
Valves
Water Regulating Valve
Drain/Return
Condenser
Water Supply
High-Pressure
Switch
Hot Gas
Val ve
Strainer
Drier
Service
Val ve
Discharge Line
Suction Line
Liquid Line
Val ve
Service
Val ve
Compressor
Thermostatic Expansion Valves
Heat Exchanger
Thermistor
Cleaning Valve
Float Switch
Drain
Water Supply
Inlet Water Valve
Spray Tubes
Check Valve
Water Pump
Pump-Out
Evaporator
Freeze/Harvest
Pump Timer
Water
Tank
Refrigeration Circuit
Water Circuit
Spray Tubes
16
Page 17
3a. Remote Models (SRH/3) Except KM-2500SRH3
Condenser Unit with Headmaster (CPR)
Check
Valves
Hot Gas
Service
Val ve
Fusible Plug
High Pressure
Switch
Val ve
Strainer
KM-2500SRH3: Headmaster
located in icemaker
Condenser
Water
Service
Val ve
Suction Line
Receiver
Drier
Headmaster
(C.P.R.)
Service
Liquid Line
Val ve
Fan
Thermistor
Cleaning Valve
Supply
Inlet Water Valve
Heat Exchanger
Val ve
Float Switch
Check Valve
Discharge Line
Compressor
Expansion Valves
Drain
Water Pump
Spray Tubes
Spray Tubes
Evaporator
17
Water
Tank
Pump-Out
Freeze/Harvest
Pump Timer
Refrigeration Circuit
Water Circuit
Page 18
3b. Remote Models (SRH3) KM-2500SRH3
Condenser Unit without Headmaster (CPR)
Shut-Off Valve
(Factory Use Only)
High-Pressure
Switch
Strainer
Fusible Plug
Hot Gas
Val ve
Check
Valves
Condenser
Water
Supply
Fan
Spray Tubes
Receiver
Service Valve
Liquid Line
Evaporator
Val ve
Thermistor
Cleaning Valve
Drier
Headmaster
(C.P.R.)
Inlet Water Valve
Suction Line
Service Valve
Service
Val ve
Discharge Line
Compressor
Drain
Check Valve
Water
Tank
Expansion Valves
Float Switch
Pump-Out
Freeze
18
Water Pump
Refrigeration Circuit
Water Circuit
Page 19
II. Sequence of Operation and Service Diagnosis
A. Sequence of Operation Flow Chart
1. "E" and "G" Control Board without Harvest Pump Timer Operation
10th cycle
(S4 dip switch 5 & 6)
2 sec., then reverses
for 10/20 sec. (S4 dip
• Factory set for every
4. Pump-Out Cycle
• Pump motor stops for
switch 3 & 4)
FS in control
Comp continues
FMR continues
HGV energized
FS opens or
freeze timer
terminates
PM de-energizes for 2 sec.,
then reverses for 10/20 sec.
FM de-energized
LLV de-energized
3. Freeze Cycle
2. Harvest Cycle
• Min. freeze time: 5 min.
• Max. freeze time: freeze timer
• Max. WV time: 6 min.
• Max. harvest time: 20 min.
setting
(S4 dip switch 9 & 10)
5-min. timer in
control
1 to 3-min. harvest
timer in control
(S4 dip switch 1 & 2)
Thermistor
in control
FS closed
FS check
Thermistor temperature
FS closed
FS check
Comp continues
FMR continues
reaches 48°F (9°C)
(3.9kΩ or less). Harvest
Comp energized
FMR energized
FM energized
LLV energized
FS open
timer starts (1 to 3 min.).
HGV energized
WV energized
FS open
PM energized
HGV de-energized
WV de-energized
Components Energized when the Control Switch is in the "WASH" Position
The "WASH" position on the control switch is used when cleaning and sanitizing the icemaker. When in the "WASH"
position, power is supplied to the pump motor. With the cleaning valve closed, the cleaner and sanitizer ow over the
outside of the evaporator plate assembly. With the cleaning valve open, the cleaner and sanitizer ow over both the
outside and the inside of the evaporator plate assembly.
Note: Close the cleaning valve after cleaning and sanitizing are complete, otherwise the icemaker will not restart
when the control switch is placed in the "ICE" position.
Startup
WV energized
If FS is open, Comp stops and cycle returns to 1-min. ll.
Legend:
BC–bin control
Comp–compressor
FM–fan motor
FMR–fan motor-remote
FS–oat switch
HGV–hot gas valve
LLV–liquid line valve
PM–pump motor
WV–inlet water valve
1. 1-Minute
Fill Cycle
"E" and "G" Control Board without Harvest Pump Timer Operation Flow Chart
Cycle
Steps
19
Page 20
2. "G" Control Board with Harvest Pump Timer Operation
10th cycle
(S4 dip switch 5 & 6)
2 sec., then reverses
for 10/20 sec.
• Factory set for every
4. Pump-Out Cycle
• Pump motor stops for
(S4 dip switch 3 & 4)
FS in control
Comp continues
FMR continues
HGV energized
FS opens or
freeze timer
terminates
PM de-energizes for 2 sec.,
then reverses for 10/20 sec.
FM de-energized
(FM continues on KM-1601SAH)
LLV de-energized
50 sec.
Timer
FS closed
Comp continues
FS check
PM energized
WV de-energized
FS closed
Comp energized
FS check
WV energized
FM continues
FMR continues
Thermistor temperature
reaches 48°F (9°C)
FMR energized
HGV energized
FS open
(3.9 kΩ or less).
PM continues
WV energized
LLV energized
FS open
Harvest timer starts.
HGV de-energized
Components Energized when the Control Switch is in the "WASH" Position
The "WASH" position on the control switch is used when cleaning and sanitizing the unit. When in the "WASH" position,
power is supplied to the pump motor. With the cleaning valve closed, the cleaner and sanitizer ow over the outside of the
evaporator plate assembly. With the cleaning valve open, the cleaner and sanitizer ow over both the outside and the inside
of the evaporator plate assembly.
Note: Close the cleaning valve after cleaning and sanitizing are complete, otherwise the unit will not restart when the control
switch is placed in the "ICE" position.
If FS is open, Comp stops and cycle returns to 1-Min. ll.
(S4 dip switch 9 & 10)
• Min. freeze time: 5 min.
• Max. freeze time: freeze timer setting
3. Freeze Cycle
"G" Control Board with Harvest Pump Timer Operation Flow Chart
2. Harvest Cycle
1. 1-Minute
sec. (S4 dip switch 7), whichever is shorter. Do not
• WV time: 6 min. or the length of harvest minus 50
Fill Cycle
adjust S4 dip switch 7 out of the factory position.
• Max. harvest time: 20 min.
5-min. timer
in control
1 to 3-min. harvest timer in
control (S4 dip switch 1 & 2)
Thermistor
in control
Harvest Pump
Legend:
BC–bin control
Comp–compressor
FM–fan motor
FMR–fan motor-remote
FS–oat switch
HGV–hot gas valve
LLV–liquid line valve
PM–pump motor
Cycle
Steps
Startup
WV–inlet water valve
20
Page 21
3a. Thermostatic Bin Control Shutdown
To 1. 1-Minute Fill Cycle
3. Ice Level Lowered
No ice touching TBC bulb.
Icemaker starts at
"1. 1-Minute Fill Cycle."
2. Icemaker Off
1. Bin Full
Shutdown
TBC closed
All components
de-energized.
TBC open
All components
de-energized
NOTE: "G" control board green "BC CLOSED" LED
on continuously when the K4 jumper is in place.
Within 10 sec. after ice contacts
TBC bulb, icemaker shuts down.
Ice contacts TBC bulb
TBC
and Restart
Operation
"E" and "G" Control Board with Thermostatic Bin Control Shutdown Sequence Flow Chart
Legend:
BC–bin control
TBC–themostatic bin control
21
Page 22
3b. Mechanical Bin Control Shutdown
Icemaker starts at
"1. 1-Minute Fill Cycle."
3. Ice Level Lowered
To 1. 1-Minute Fill Cycle
MBC closed
(MBC actuator paddle disengaged)
Green "BC CLOSED" LED on
Yellow "BC OPEN" LED off
2. Icemaker Off
All components
de-energized.
Yellow "BC OPEN" LED continues.
All components de-energized.
to 15 sec. into the freeze cycle if
activated at the end of the harvest cycle.
15 sec. before the 5-min. short cycle
• Fill Cycle–15 sec. after activation.
• Harvest Cycle–At the end of the harvest cycle, or up
"G" Control Board Mechanical Bin Control Shutdown Sequence Flow Chart
1. Bin Full
Shutdown Delay:
protection timer terminates.
• Freeze Cycle– 15 sec. after activation if activated at least
Otherwise, at the end of the next harvest cycle.
MBC open (MBC actuator paddle engaged)
Green "BC CLOSED" LED off
Yellow "BC OPEN" LED on
Shutdown
Legend:
BC–bin control
MBC
and Restart
Operation
MBC–mechanical bin control
22
Page 23
B. Service Diagnosis
WARNING
• The appliance should be diagnosed and repaired only by qualied service
personnel to reduce the risk of death, electric shock, serious injury, or re.
• Risk of electric shock. Control switch in "OFF" position does not de-energize all
loads Use extreme caution and exercise safe electrical practices.
• Moving parts (e.g., fan blade) can crush and cut. Keep hands clear.
• Before servicing the appliance, move the control switch to the "OFF" position and
turn off the power supply.
• CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews are
securely in place after the appliance is serviced. Make sure that none have fallen
into the dispenser unit/ice storage bin.
• Make sure all food zones in the appliance and dispenser unit/ice storage bin are
clean after service.
The diagnostic procedure is a sequence check that allows you to diagnose the electrical
system and components. Before proceeding, check for correct installation, proper voltage
per nameplate, and adequate water supply. Check CB using the steps in "II.C. Control
Board Check." Check dip switch settings to assure that S4 dip switch 3, 4, 7, 8, 9, 10 and
S5 dip switch 1 through 5 ("G" CB) are in the factory default position. S4 dip switch 1, 2,
5, 6 are cleaning adjustments and the settings are exible. For factory default settings,
see "III.C.1. Default Dip Switch Settings."
Note: • When checking high voltage (115VAC), always choose a white (W) neutral wire to
establish a good neutral connection.
• On models with a main transformer, the neutral (W) is provided through MT.
To conrm a good neutral, check for 60VAC from white (W) neutral to ground
(GND). If 60VAC is present, neutral is good. If 60VAC is not present, check
208-230VAC main power supply to MT. If 208-230VAC is present, check MT
continuity.
• When checking voltage from the CB K1 connector (10 pin connector), pull CB
K1connector out slightly to allow room for multimeter test leads contact.
1) Turn off the power supply, then access the control box. Move the control switch to the
"OFF" position. Clear any ice from TBC.
2) Check that BC is closed and the 115VAC 10A fuse is good.
23
Page 24
1. "E" and "G" Control Board without Harvest Pump Timer Diagnosis
3) Power On: Turn on the power supply, then move the control switch to the "ICE" position.
A 5-sec. delay occurs.
• "E" Control Board: CB red "POWER OK" LED turns on.
• "G" Control Board: CB red "POWER OK" LED and green "BC CLOSED" LEDturn on.
Note: • CB red "POWER" LED remains on unless the 10.5VAC power supply is
interrupted (K2 connector).
• Check CB using the steps in "II.C. Control Board Check."
• "G" CB: If yellow "BC OPEN" LED is on, check that CB red K4jumper is in place.
a) Power On Diagnosis: If CB red "POWER OK" LED is off, conrm closed TBC and
10A fuse is good. If TBC is open, remove ice from bulb and warm bulb in hand.
IfTBC does not close, replace TBC. See "II.D. Bin Control Check." Check for 115VAC
at control switch #1(BK) to neutral (W) then at control switch #2(P) to neutral (W).
If115VAC is present on control switch #1 (BK) and not on control switch #2(P),
replace control switch. If 115VAC is present on control switch #2 (P), check for
115VAC at HPS (P) to neutral (W), then HPS (BK) to neutral (W). If115VAC is present
at HPS (P) and not at HPS (BK), HPS is open. See HPS Diagnosis below. If115VAC
is present at HPS (BK), check for 10.5VAC at CB K2#1 (R) to CB K2#2(R).
If10.5VAC is not present, conrm that the cleaning valve interlock switch is closed.
Next, check CT continuity. Ifopen, replace CT.
b) HPS Diagnosis: Conrm FM is energized and fan blade turns freely. Conrm
condenser coil is not dirty. Conrm that the location meets installation requirements.
See the appliance's instruction manual for details. Conrm there are no restrictions in
the refrigeration circuit.
Harvest Cycle: HGV, strainer, or check valve.
Freeze Cycle: FM, FMR, TXV, HM, LLV, WRV, strainer, check valve, drier, damaged
line set or tting, and fan blade for binding.
Let refrigeration circuit pressures equalize. If HPS does not reset and pressures
are equalized, replace HPS. If pressures are not equalized, reclaim refrigerant and
diagnose refrigeration circuit restriction.
4) 1-Minute Fill Cycle – LED 4 is on. WV energizes. After 1 min., CB checks for a closed
FS. If FS is closed, harvest cycle begins. If harvest cycle begins (Comp, HGV, and FMR
energize), continue to step 5. If FS is open, WV remains energized through additional
1-min. ll cycles until water enters the water tank and FS closes (low water safety
protection during initial start up and at the end of each harvest). Diagnosis: Check
that water enters the water tank. If not, check that the water supply line shut-off valve
is open and screens or external lters are clear. Check for 115VAC at CB K1 #6(O)
to neutral(W). If 115VAC is not present, replace CB. If 115VAC is present, and WV
does not energize, check for 115VAC at WV. If 115VAC is present, check coil continuity.
Ifopen, replace WV. If the water tank lls, but the appliance fails to start harvest (Comp
energized), check for open FS. See "II.E. Float Switch Check and Cleaning." If FS is
closed and CB fails to start the harvest cycle after 1 min., replace CB.
24
Page 25
5) Initial Harvest Cycle – LEDs 1, 4, and 2 are on. WV continues. Comp, FMR, and
HGV energize. CB monitors the warming of the evaporator via the thermistor located
on the suction line. When the thermistor reaches 48°F (9°C), CB reads 3.9 kΩ from the
thermistor and turns harvest termination over to the harvest timer (S4 dip switch 1 & 2).
The harvest timer has settings of 60, 90, 120, and 180sec. Thepump-out timer (S4dip
switch 3 & 4) acts in place of the harvest timer during cycles with a pump-out (S4 dip
switch 5 & 6). WV remains energized during harvest for a maximum of 6min. or the
length of harvest, whichever is shorter.
a) Comp Diagnosis: Check that evaporator is warming. Ifnot, conrm that Comp
energizes. If not, check for 115VAC at CB K1 #1 (V) or #9 (V) to neutral (W).
If115VAC is not present, check for 115VAC at CB K1 #7 (BR) or #10 (BR) to neutral
(W). If115VAC is present at CB #7 (BR) or #10 (BR) and not at CB #1 (V) or #9 (V),
replace CB. If 115VAC is present, check for 115VAC at MC solenoid. If 115VAC is
present, conrm contacts are closed. If not, replace MC. If MC contacts are closed,
check Comp start and run capacitors, Comp start relay, and Comp motor winding.
b) HGV Diagnosis: If Comp is energized and evaporator is not warming, check that
HGV energizes and opens. Check for 115VAC at CB K1 #2 (P) to neutral (W).
If115VAC is not present, replace CB. If 115VAC is present, check for 115VAC at HGV
coil and check HGV coil continuity. Replace as needed.
c) LLV Diagnosis: Conrm that LLV is de-energized and closed (not bypassing).
Ifenergized, replace CB. If de-energized and bypassing, replace LLV.
d) WRV Diagnosis: Conrm WRV is not leaking by.
e) Initial Harvest Cycle Termination Diagnosis: When the thermistor reaches 48°F
(9°C), CB reads 3.9 kΩ from the thermistor and turns harvest termination over to
the harvest timer (S4 dip switch 1 & 2). Check discharge line temperature. For a
thermistor check, see "II.F.Thermistor Check." If 1-min. ll cycle starts after harvest
timer terminates, check that FS is clean and operating properly. See "II.E. Float
Switch Check and Cleaning." If FS is closed, CB proceeds to the next cycle. Ifnot,
replace CB.
Note: The min. total time allowed by CB for a complete harvest cycle is 2 min.
Max. harvest time allowed is 20 min.
NOTICE! On models with "G" control board and no harvest pump timer relays,
S4dip switch 7 must remain off. Otherwise, PM energizes in reverse direction the
last 50 seconds of harvest and empties water from water tank.
6) Freeze Cycle – LED 1 is on. Comp and FMR continue. PM, FM, and LLVenergize.
WV and HGV de-energize. Appliance is held in freeze by a 5-min. short cycle protection
timer. After 5-min. timer terminates and FSopens, freeze cycle terminates.
a) Freeze Cycle Diagnosis: Conrm Comp and FMR continue. Conrm that PM, FM,
and LLV energize. Conrm WRV opens. Next, conrm WV and HGV de-energize.
During the rst 5 min. of freeze, conrm evaporator is cooling. If not, conrm
WV de-energized (not leaking by), HGV de-energized (not bypassing), LLV and
FM energize, TXV and HM operate correctly, WRV opens, Comp is efficient, and
refrigerant charge is correct. See "VIII.A. Specication and Performance Data."
25
Page 26
b) Comp and FMR Diagnosis: If Comp and FMR de-energize once freeze begins,
check that appliance has not shut off on HPS ("POWER OK" LED off). If so, check
"3)b) HPS Diagnosis" above. If "POWER OK" LED is on, check for 115VAC at CB
K1#1 (V) or #9 (V) to neutral (W). If 115VAC is not present and LED 1 is on, replace
CB. If 115VAC is present, check for 115VAC at CR or MC coil. If 115VAC is present,
check CR or MC coil and contact continuity. Replace as needed. If CR or MC is ok,
check Comp external overload, start relay, and start and run capacitors. Next, check
Comp motor winding continuity. If Comp is energized but evaporator is not cooling,
check for an inefficient Comp. See "VIII.A. Specication and Performance Data."
If Comp is energized but FMR is not, check for 115VAC at the FMR junction box.
If115VAC is not present, check icemaker wiring connections. If 115VAC is present,
check for voltage at condenser unit. If115VAC is not present, check eld wiring
connections. If 115VAC is present, check FMR capacitor, motor winding, and fan
blade for binding.
c) WV and HGV Diagnosis: If WV is energized, check for 115VAC at CB K1 #6 (O) to
neutral (W). If 115VAC is present after PM energizes, replace CB. If 115VAC is not
present, replace WV (bypassing). If HGV did not de-energize, check for 115VAC at
CB K1 #2 (P) to neutral (W). If 115VAC is present after PM energizes, replace CB.
If115VAC is not present, replace HGV (bypassing).
d) PM Diagnosis: Conrm water is owing over evaporator from PM and not WV. If PM
de-energizes once freeze begins, check for 115VAC at CB K1 #4 (R) to neutral (W).
If 115VAC is not present, replace CB. If 115VAC is present and PM is de-energized,
check for 115VAC at control switch #5 (R) to neutral (W). If 115VAC is present at CB
K1 #4 (R) and not at control switch #5 (R), check control switch continuity between
#5 (R) and #4 (R). Replace as needed. If 115VAC is present at control switch #5(R)
to neutral (W), check PM impeller for binding, PM capacitor, and motor winding
continuity.
e) FM and LLV Diagnosis: If FM or LLV does not energize, check for 115VAC at CB
K1#3 (BK) to neutral (W). If 115VAC is not present, replace CB. If 115VAC is present:
For FM: check capacitor, motor winding, and blade for binding.
For LLV: check coil voltage and continuity.
f) Refrigerant Pressures, HM, and TXV Diagnosis: If evaporator is still not cooling,
check refrigerant pressures. See "VIII.A. Specication and Performance Data."
Next, check HM operation. If refrigeration pressures are above HM setpoint and
HMis bypassing, replace HM. Check TXV for proper operation. Remove TXV bulb
and hold it in your hand, refrigerant low-side pressure should rise, place TXV bulb in
ice water, refrigerant low-side pressure should drop. A 10 to 15 pound pressure swing
between warm and cold conditions indicate a good TXV. If a 10 to 15pound swing is
not present, replace TXV.
g) WRV Diagnosis: WRV is factory set and generally no adjustment is required.
IfWRV fails to open in freeze, check for proper refrigerant pressures. See "VIII.A.
Specication and Performance Data." If refrigerant pressures are correct and WRV
does not open, adjust or replace as needed. See "IV.C. Water Regulating Valve
Adjustment (water-cooled models)."
26
Page 27
h) Freeze Termination Diagnosis: After 5 min. in freeze, disconnect CB K5 FS
connector. 15 sec. later appliance should switch out of the freeze cycle (15 second
delay after FS opens before terminating the freeze cycle). If appliance remains in
freeze longer than 15 sec. after FS removed, replace CB. If appliance switches with
FS removed but would previously not switch out of freeze with FS connected (long
freeze - 3 beep alarm), see "II.E. Float Switch Check and Cleaning."
Note: Normal freeze cycle will last 20 to 40 min. depending on model and conditions.
Cycle times and pressures should follow performance data provided in this
manual. See "VIII.A. Specication and Performance Data."
i) Short Freeze Cycle Diagnosis: Conrm water tank lls and overows during 1 min.
ll and harvest cycles. If not, check water supply lters, shut-off valve, WV screen.
Ifwater tank empties before 5 min. timer terminates and freeze cycle is short, check
that CV is not leaking by (water owing down the potable drain). If CV is leaking by,
remove and clean CV, replace rubber seat and spring if necessary. If water tank is
full, see "II.E. Float Switch Check and Cleaning" for erratic operating FS.
7) Pump-Out Cycle – LEDs 1, 3, and 2 are on (10/20 second pump-out). Timing of the
rst pump-out is dependent on CB. "E" CB rst pump-out is after the rst freeze cycle.
"G" CB rst pump-out is determined by S4 dip switch 5 & 6. See the table below.
Comp and FMR continue, HGV energizes. If S4dip switch 3 & 4 are set to 3 off and
4on, LED 4 turns on and WV energizes. FM and LLVde-energize. PM stops for 2 sec.,
then reverses for 10/20 sec. depending on pump-out timer (S4 dip switch 3 & 4) setting.
When the pump-out timer terminates, pump-out is complete. The pump-out frequency
control (S4 dip switch 5 & 6) is factory set, and generally no adjustment is required.
However, the pump-out frequency control can be set to have a pump-out occur every
cycle, or every 2, 5, or 10 cycles. For details, see "III.C.4. Pump-Out Frequency Control
(S4 dip switch 5 & 6)."
Pump-Out Diagnosis: In the freeze cycle before pump-out (see table above),
disconnect CB black K5 connector (FS connector) after 5 min. of freeze. Check that PM
stops and re-starts and water is owing down the drain through CV. If PM does not stop
and re-start, check that CB LEDs 1, 3, and 2 are on. If not, replace CB. IfLEDs1,3,
and 2 are on and PM does not energize, check for 115VAC at CB K1 #5 (DBU) to
neutral (W). If 115VAC is not present, replace CB. If 115VAC is present, make sure the
drain line is not clogged and that CV is clean and operating properly.
Conrm FM and LLV de-energize. If FM or LLV is energized with LEDs 1, 3, and 2 on,
replace CB.
27
Page 28
8) Normal Harvest Cycle – Same as the initial harvest cycle. Return to step 5 above.
Note: Appliance continues to cycle until BC is satised or power is turned off. The
appliance always restarts at the 1-min. ll cycle.
9) Shutdown: "E" and "G" Control Board
When the appliance is running, hold ice in contact with the thermostatic bulb.
TBC switch opens within 10 sec., shutting down the appliance. TBC is factory set,
and generally no adjustment is required. However, adjustment may be needed in
some conditions, particularly at higher altitude locations. Diagnosis: See "II.D.
Bin Control Check." NOTICE! Donot adjust S4 dip switch 7 out of the factory
default position. This dip switch must be left in the factory default position or
the appliance will not operate correctly.
"G" Control Board: CB red K4connector must have the jumper in place. When the
jumper is in place, the green "BC CLOSED" LED remains on. If the jumper is not in
place, yellow "BC OPEN" LED turns on and the icemaker turns off and remains off
until the jumper is replaced in its original position.
Comp–compressor; CV–check valve; FM–fan motor; FMR–fan motor-remote;
FS–oat switch; HGV–hot gas valve; HM–headmaster (C.P.R.); HPS–high-pressure switch; LLV–liquid line valve; MC–magnetic contactor; MT–main transformer;
PM–pump motor; TBC–thermostatic bin control; TXV–thermostatic expansion
valve; WRV–water regulating valve; WV–inlet water valve
28
Page 29
2. "G" Control Board with Harvest Pump Timer Diagnosis
3) Power On: Turn on the power supply, then move the control switch to the "ICE" position.
A 5-sec. delay occurs. CB red "POWER OK" LED and green "BC CLOSED" LED turn
on. If yellow "BC OPEN" LED is on, check CB K4 jumper.
Note: • CB red "POWER OK" LED remains on unless the 10.5VAC power supply is
interrupted (K2 connector).
• Check CB using the steps in "II.C. Control Board Check."
• Conrm CB green "BC CLOSED" LED is on. If CB yellow "BC OPEN" LED is on,
conrm CB K4 jumper is in place. Otherwise, CB yellow "BC OPEN" LED is on
and appliance will not start.
a) Power On Diagnosis: If CB red "POWER OK" LED is off, conrm 10A fuse is good.
Check for 115VAC at control switch #1 (BR or BK) to neutral (W) then at control
switch #2(P) to neutral (W). If 115VAC is present on #1 (BR or BK) and not on
#2(P), replace control switch. If 115VAC is present on control switch #2 (P), check
for 115VAC at HPS (P) to neutral (W) then HPS (BK) to neutral (W). If115VAC is
present at HPS (P) and not at HPS (BK), HPS is open. See HPS Diagnosis below.
If115VAC is present at HPS (BK), check for 10.5VAC at CB K2#1 red wire to CB K2
#2 red wire. If 10.5VAC is not present, check that the cleaning valve interlock switch
is closed. Next, check CT continuity. If open, replace CT.
b) HPS Diagnosis: Conrm FM is energized and fan blade turns freely. Conrm
condenser coil is not dirty. Conrm that the location meets installation requirements.
See the appliance's instruction manual for details. Conrm there are no restrictions in
the refrigeration circuit.
Harvest Cycle: HGV, strainer, or check valve.
Freeze Cycle: FM, FMR, TXV, HM, LLV, WRV, strainer, check valve, drier, damaged
line set or tting, and fan blade for binding.
Let refrigeration circuit pressures equalize. If HPS does not reset and pressures
are equalized, replace HPS. If pressures are not equalized, reclaim refrigerant and
diagnose refrigeration circuit restriction.
4) 1-Min. Fill Cycle – LED 4 is on. WV and X11 relay energize. After 1 min., CB checks
for a closed FS. If FS is closed, the harvest cycle begins. If harvest cycle begins (Comp,
HGV, FMR energized), continue to step 5a. If FS is open, WV remains energized
through additional 1-min. ll cycles until water enters the water tank and FS closes
(low water safety protection during initial start up and at the end of each harvest).
Diagnosis: Check that water enters the water tank. If not, check that the water supply
line shut-off valve is open and screens or external lters are clear. Check for 115VAC
at CB K1 #6 (O) to neutral (W). If 115VAC is not present, replace CB. If 115VAC is
present, and WV does not energize, check for 115VAC at WV. If 115VAC is present,
check coil continuity. Ifopen, replace WV. If the water tank lls, but the appliance fails to
start harvest (Comp energized), check for open FS. See "II.E. Float Switch Check and
Cleaning." If FS is closed and CB fails to start the harvest cycle after 1 min., replace
CB.
29
Page 30
5a) Initial Harvest Cycle – LEDs 1, 4, and 2 are on. WV and X11 relay continue. Comp,
FMR, HGV, and X10 relay energize. CBmonitors the warming of the evaporator via the
thermistor located on the suction line. When the thermistor reaches 48°F (9°C), CB
reads 3.9 kΩ from the thermistor and turns harvest termination over to the harvest timer
(S4 dip switch 1 & 2). The harvest timer has settings of 60, 90, 120, and 180 sec. The
pump-out timer (S4 dip switch 3 & 4) acts in place of the harvest timer during cycles
with a pump-out (S4 dip switch 5 & 6). WV and X11 relay are energized during harvest
for a maximum of 6 min. or the length of harvest minus 50sec., whichever is shorter.
50sec. before harvest terminates, PM energizes. See step 5b below.
a) Comp Diagnosis: Check that evaporator is warming. Ifnot, conrm that Comp
energizes. If not, check for 115VAC at CB K1 #1 (V) or #9 (V) to neutral (W).
If115VAC is not present, check for 115VAC at CB K1 #7 (BR) or #10 (BR) to neutral
(W). If115VAC is present at #7 (BR) or #10 (BR) and not at #1 (V) or #9 (V), replace
CB. If 115VAC is present, check for 115VAC at CR or MC solenoid. If 115VAC is
present, conrm contacts are closed. If not, replace CR or MC. If CR or MC contacts
are closed, check Comp external overload, Comp start and run capacitors, Comp
start relay, and Comp motor winding. If Comp is energized and evaporator is not
warming, check that HGV energizes and opens. Check for 115VAC at CB K1 #2 (P)
to a neutral(W). If 115VAC is not present and LED 2 is on, replace CB. If115VAC is
present, check coil voltage and continuity. Replace as needed. Conrm that LLV is
de-energized and closed (not bypassing). If energized, replace CB. Ifde-energized
and bypassing, replace LLV. Conrm WRV is not leaking by. If evaporator is warming,
PM energizes for the last 50sec. of harvest.
b) HGV Diagnosis: If Comp is energized and evaporator is not warming, check that
HGV energizes and opens. Check for 115VAC at CB K1 #2 (P) to neutral (W).
If115VAC is not present, replace CB. If 115VAC is present, check for 115VAC at HGV
coil and check HGV coil continuity. Replace as needed.
c) LLV Diagnosis: Conrm that LLV is de-energized and closed (not bypassing).
Ifenergized, replace CB. If de-energized and bypassing, replace LLV.
d) WRV Diagnosis: Conrm WRV is not leaking by.
5b) Harvest Pump Timer – LEDs 1, 3, and 2 are on. When the thermistor reaches 48°F
(9°C), CB reads 3.9 kΩ from the thermistor and turns harvest termination over to the
harvest timer (S4 dip switch 1 & 2). 50 sec. before the harvest timer terminates, LED
3turns on and PM energizes. Comp, FMR, HGV, and X10 relay continue. LED 4 turns
off, WV and X11 relay de-energize.
Diagnosis: Place a thermometer on the suction line next to the thermistor. Has it
warmed to 48°F (9°C) or warmer? Conrm thermistor status. See "II.F. Thermistor
Check." If the thermistor reading is in proper range, dip switch 7 is on, and PM does
not energize 50 sec. before harvest terminates, replace CB. If WV continues, check for
115VAC at CB K1 #6 (O). If115VAC is present, and LED 4 is off, replace CB. If LED 3is
on and PM is not energized, check for 115VAC at CB K1 #5(DBU). If115VAC is not
present, replace CB. If 115VAC is present and PM is not energized, check for 115VAC
at X10relay terminal #7 (Y) to neutral (W). If 115VAC is not present, check for 115VAC
at X10 relay terminal #3 (P) to neutral (W) and X10 relay terminal #5 (Y) to neutral (W).
30
Page 31
If 115VAC is present on terminal #3(P) and not on terminal #5 (Y), replace X10 relay.
If 115VAC is present on X10 relay terminal #7 (Y) and PM is not energized, check for
115VAC at X10 relay terminal #4 (R) to neutral (W) and terminal #6 (DBU) to neutral
(W). If 115VAC is present on terminal #6(DBU) and not on terminal #4 (R), replace X10
relay. If 115VAC is present on X10relay terminal #4 (R), check control switch contact
continuity between terminals #4(R) and #5(R). Ifcontacts are open, replace control
switch. If contacts are closed and 115VAC is present between control switch terminal #5
(R) and neutral (W), check PM capacitor and motor winding continuity.
5c) Initial Harvest Cycle Termination Diagnosis: When the thermistor reaches 48°F
(9°C), CB reads 3.9 kΩ from the thermistor and turns harvest termination over to the
harvest timer (S4 dip switch 1 & 2). Check discharge line temperature. For a thermistor
check, see "II.F.Thermistor Check." If 1-min. ll cycle starts after harvest timer
terminates, check that FS is clean and operating properly, see "II.E. Float Switch Check
and Cleaning." If FS is closed, CB proceeds to the next cycle. Ifnot, replace CB.
Note: The minimum total time allowed by CB for a complete harvest cycle is 2 min.
Maximum harvest time allowed is 20 min.
NOTICE! S4 dip switch 7 must remain on. Otherwise, PM will not energize during
the last 50 sec. of harvest.
6) Freeze Cycle – LED 1 is on. Comp, FMR, and PM continue. FM and LLV energize.
HGV and X10 relay de-energize. Appliance is held in freeze by a 5-min. short cycle
protection timer. After 5-min. timer terminates and FS opens, freeze cycle terminates.
Note: PM power supply switches from CBK1 #5(DBU) in harvest to K1 #4 (R) in freeze.
a) Freeze Cycle Diagnosis: Conrm Comp, FMR, and PM continue. Conrm that
FM and LLV energize. Conrm WRV opens. Next, conrm HGV and X10 relay
de-energize. During the rst 5 min. of freeze, conrm evaporator is cooling. If not,
conrm WV de-energized (not leaking by), HGV de-energized (not bypassing), LLV
and FM energize, TXV and HM operate correctly, WRV opens, Comp is efficient, and
refrigerant charge is correct. See "VIII.A. Specication and Performance Data."
b) Comp and FMR Diagnosis: If Comp and FMR de-energize once freeze begins,
check that appliance has not shut off on HPS ("POWER OK" LED off). If so, check
"3)b) HPS Diagnosis" above. If "POWER OK" LED is on, check for 115VAC at CB K1
#1 (V) or #9 (V) to neutral (W). If 115VAC is not present and LED 1 is on, replace CB.
If 115VAC is present, check for 115VAC at CR or MC coil. If 115VAC is present, check
CR or MC coil and contact continuity. Replace as needed. If CR or MC is okay, check
Comp start relay and start and run capacitors. Next, check Comp motor winding
continuity. If Comp is energized but evaporator is not cooling, check for an inefficient
Comp. See "VIII.A. Specication and Performance Data." If Comp is energized but
FMR is not, check for 115VAC at the FMR junction box. If 115VAC is not present,
check icemaker wiring connections. If 115VAC is present, check for voltage at
condenser unit. If115VAC is not present, check eld wiring connections. If 115VAC is
present, check FMR capacitor, motor winding, and fan blade for binding.
31
Page 32
c) WV and HGV Diagnosis: If WV is energized, check for 115VAC at CB K1 #6 (O) to
neutral (W). If 115VAC is present after PM energizes in harvest cycle, replace CB.
If 115VAC is not present, replace WV (bypassing). If HGV did not de-energize at
the end of harvest, check for 115VAC at CB K1 #2 (P) to neutral (W). If 115VAC is
present 50 sec. after PM energizes, replace CB. If 115VAC is not present, replace
HGV (bypassing).
d) PM Diagnosis: Conrm water is owing over evaporator from PM and not WV. If PM
de-energizes once freeze begins, check for 115VAC at CB K1 #4 (R) to neutral (W).
If 115VAC is not present, replace CB. If 115VAC is present and PM is de-energized,
check for 115VAC at control switch #5 (R) to neutral (W). If 115VAC is present at CB
K1 #4 (R) and not at control switch #5 (R), check control switch continuity between
#5 (R) and #4 (R). Replace as needed. If 115VAC is present at control switch #5 (R)
to neutral (W), check PM capacitor and motor winding continuity.
e) FM and LLV Diagnosis: If FM or LLV does not energize, check for 115VAC at CB
K1#3 (BK) to neutral (W). If 115VAC is not present, replace CB. If 115VAC is present:
For FM, check capacitor, motor winding, and blade for binding.
For LLV, check coil voltage and continuity.
f) Refrigerant Pressures, HM, and TXV Diagnosis: If evaporator is still not cooling,
check refrigerant pressures. See "VIII.A. Specication and Performance Data."
Next, check HM operation. If refrigeration pressures are above HM setpoint and
HMis bypassing, replace HM. Check TXV for proper operation. Remove TXV bulb
and hold it in your hand, refrigerant low-side pressure should rise, place TXV bulb in
ice water, refrigerant low-side pressure should drop. A 10 to 15 pound pressure swing
between warm and cold conditions indicate a good TXV. If a 10 to 15 pound swing is
not present, replace TXV.
g) WRV Diagnosis: WRV is factory set and generally no adjustment is required.
IfWRV fails to open in freeze, check for proper refrigerant pressures. See "VIII.A.
Specication and Performance Data." If refrigerant pressures are correct and WRV
does not open, adjust or replace as needed. See "IV.C. Water Regulating Valve
Adjustment (water-cooled models)."
h) Freeze Termination Diagnosis: After 5 min. in freeze, disconnect CB K5 FS
connector. 15 sec. later appliance should switch out of the freeze cycle (15 second
delay after FS opens before terminating the freeze cycle). If appliance remains in
freeze longer than 15 sec. after FS removed, replace CB. If appliance switches with
FS removed but would previously not switch out of freeze with FS connected (long
freeze - 3 beep alarm), see "II.E. Float Switch Check and Cleaning."
Note: Normal freeze cycle will last 20 to 40 min. depending on model and conditions.
Cycle times and pressures should follow performance data provided in this
manual. See "VIII.A. Specication and Performance Data."
i) Short Freeze Cycle Diagnosis: Conrm water tank lls and overows during 1 min.
ll and harvest cycles. If not, check water supply lters, shut-off valve, WV screen.
Ifwater tank empties before 5 min. timer terminates and freeze cycle is short, check
that CV is not leaking by (water owing down the potable drain). If CV is leaking by,
remove and clean CV, replace rubber seat and spring if necessary. If water tank is
full, see "II.E. Float Switch Check and Cleaning." for erratic FS.
32
Page 33
7) Pump-Out Cycle – LEDs 1, 3, and 2 are on (10/20 second pump-out). Timing of the
rst pump-out is determined by S4 dip switch 5& 6. See the table below.
"G" Control Board Settings
S4 Dip Switch Setting
No. 5No. 6
OFFOFFEvery cycleAfter 2nd freeze cycle
ONOFFEvery 2 cyclesAfter 3rd freeze cycle
OFFONEvery 5 cyclesAfter 6th freeze cycle
ONONEvery 10 cyclesAfter 11th freeze cycle
Pump-Out
Frequency
1st Pump-Out
"G" Control Board
Comp and FMR continue, HGV energizes. If S4dip switch 3 & 4 are set to 3 off
and 4 on, LED 4 turns on and WV and X11 relay energize, energizing X10relay.
NOTICE!S4dip switch 3 & 4 must not be set to 3 off and 4 on. Otherwise, PM
will rotate in freeze cycle direction instead of pump-out direction. FM and LLV
de-energize. PM stops for 2 sec., then reverses for 10/20 sec. depending on pump-out
timer (S4dip switch 3 & 4) setting. When the pump-out timer terminates, pump-out
is complete. The pump-out frequency control (S4 dip switch 5 & 6) is factory set, and
generally no adjustment is required. However, the pump-out frequency control can be
set to have a pump-out occur every cycle, or every 2, 5, or 10 cycles. For details, see
"III.C.4. Pump-Out Frequency Control (S4 dip switch 5 & 6)."
Pump-Out Diagnosis: In the freeze cycle before pump-out (see table above), after
5min. of freeze disconnect CB black K5 connector (FS connector). Check that PM
stops and re-starts and that PM rotation is correct (water owing down the drain through
CV). If PM does not stop and re-start, check that CB LEDs 1, 3, and 2 are on. If not,
replace CB. IfLEDs1,3, and 2 are on and PM does not energize, check for 115VAC
at CB K1 #5 (DBU) to neutral (W). If 115VAC is not present, replace CB. If 115VAC
is present, check that X10 relay is de-energized. If not, check X11 relay status. If X11
relay is energized, replace CB. If X11 relay is de-energized and X10 relay is energized,
replace X11 relay (contacts sticking). If X10 relay is de-energized, check for 115VAC
at terminal #6 (DBU) to neutral (W) and terminal #2 (DBU) to neutral (W). If 115VAC is
present on terminal #6 (DBU) and not on terminal #2 (DBU), replace X10 relay. If PM is
energized and rotating in pump-out rotation, make sure the drain line is not clogged and
that CV is clean and operating properly.
Conrm FM and LLV de-energize. If FM or LLV are energized with LEDs 1, 3, and 2 on,
replace CB.
33
Page 34
8) Normal Harvest Cycle – Same as the initial harvest cycle. Return to step 5a) above.
Note: Appliance continues to cycle until MBC is satised or power is switched off. The
appliance always restarts at the 1-min. ll cycle.
9) Shutdown: "G" Control Board
a) Thermostatic Bin Control (TBC):
When the appliance is running, hold ice in contact with the thermostatic bulb. TBC
switch opens within 10 sec., shutting down the appliance. TBC is factory set, and
generally no adjustment is required. However, adjustment may be needed in some
conditions, particularly at higher altitude locations.
Diagnosis: See "II.D.1. Thermostatic Bin Control Check." CB red K4connector must
have the jumper in place. When the jumper is in place, the green "BC CLOSED" LED
remains on. If the jumper is not in place, yellow "BC OPEN" LED turns on and the
icemaker turns off and remains off until the jumper is replaced in its original position.
NOTICE!CB red K4 connector jumper (4A4883G01) must be in place.
CT–control transformer; CV–check valve; FM–fan motor; FMR–fan motor remote;
FS–oat switch; HGV–hot gas valve; HM–headmaster (C.P.R.);
HPS–high-pressure switch; LLV–liquid line valve; MBC–mechanical bin control;
MC–magnetic contactor; PM–pump motor; TBC–thermostatic bin control;
TXV–thermostatic expansion valve; WRV–water regulating valve; WV–inlet water
valve
34
Page 35
C. Control Board Check
Before replacing CB that does not show a visible defect and that you suspect is bad,
always conduct the following check procedure. This procedure will help you verify your
diagnosis.
Alarm Reset: If CB is in alarm (beeping), press the "ALARM RESET" button on CB
while CB is beeping. WARNING!Risk of electric shock. Care should be taken not to touch live terminals. Once reset, the icemaker starts at the
1-minute ll cycle. For audible alarm information, see "III.B. LED Lights and
Audible Alarm Safeties."
1) Check the dip switch settings to assure that S4 dip switch 3, 4, 7, 8, 9, 10 and S5 dip
switch 1 through 5 ("G" CB) are in the factory default position. S4 dip switch 1, 2, 5,6
are cleaning adjustments and the settings are exible. For factory default settings, see
"III.C.1. Default Dip Switch Settings."
2) Move the control switch to the "ICE" position. If the red "POWER OK" LED is on, control
voltage is good, continue to step 3. If the "POWER OK" LED is off, check CT secondary
circuit. CT output is 10.5VAC at 115VAC primary input. If the secondary circuit has
proper voltage and the red LED is off, replace CB.
If the secondary circuit does not have proper voltage, check CT primary circuit. Check
for 115VAC at CB K1 connector pin #10 (BR) to neutral (W) for 115VAC. Always choose
a white (W) neutral wire to establish a good neutral connection when checking voltages.
For additional checks, see "II.G.1. No Ice Production."
3) The "OUTPUT TEST" button provides a relay sequence test. Make sure the control
switch is in the "ICE" position, then press the "OUTPUT TEST" button. For the correct
lighting sequence, see the table below. Note that the order of the LEDs from the outer
edge of the control board is 1, 4, 3, 2. Components (e.g., compressor) cycle during the
test.
Control
Board
"E"2, 3, 4, 1
"G"1, 4, 3, 2
Correct LED
Lighting Sequence
Following the test, the icemaker begins operation at the 1-minute ll cycle for both "E"
and "G" control boards. If the LEDs do not light as described above, replace CB.
4) To verify voltage output from CB to the components, slide the CB K1 connector out far
enough to allow multimeter lead contact. With the icemaker in the cycle to be tested,
check output voltage from the corresponding pin on CB K1 connector to a neutral
(Wwire). If output voltage is not found and the appropriate LED is on, replace CB.
Legend: CB–control board; CT–control transformer
35
Page 36
D. Bin Control Check
1. Thermostatic Bin Control Check
BC shuts down the icemaker within 10 sec. when ice contacts the thermostatic bulb,
regardless of the cycle at activation.
NOTICE
When the ambient temperature is below 45°F (7°C), BC opens and shuts down
the appliance even if the ice storage bin is empty. When BC is set in the prohibited
range, the appliance operates continuously even if the ice storage bin is lled with
ice. Setting in the prohibited range may result in severe damage to the appliance.
BC is factory set, and generally no adjustment is required. However, adjustment may be
needed in some conditions, particularly at higher altitude locations.
Note: On "G" control boards, a jumper (4A4883G01) must be placed on CB red
K4connector. Otherwise, CB yellow "BC OPEN" LED is on and appliance will not start.
To check BC, follow the steps below.
1) Turn off the power supply.
2) Remove the front panel, then move the control switch to the "OFF" position.
3) Remove the control box cover and base cover, then clear any ice away from BC bulb.
4) Disconnect BC wires from BC switch.
5) Hold your hand around the bulb to warm it up.
6) Check for continuity across BC switch. If closed, continue to step 6. If open, adjust or
replace BC.
7) With the multimeter test leads still in place, hold ice on BC bulb to lower the
temperature. Within 10 sec., BC switch should open. If it remains closed, adjust or
replace BC.
Legend: BC–thermostatic bin control
36
Page 37
2. Mechanical Bin Control Check
a) Mechanical Bin Control Check
This appliance uses a lever-actuated proximity switch to control the ice level in the
storage bin. No adjustment is required.
To check MBC, follow the steps below.
1) Turn off the power supply.
2) Remove the front panel, then move the control switch to the "OFF" position.
3) Remove the control box cover, then clear any ice away from
MBC.
4) Check MBC wire harness connections. See Fig. 1.
5) Disconnect MBC connector from CB K4 connector.
6) Check for continuity across the wires of
MBC connector. When the actuator paddle
Wire Harness
Connector B
(for upper unit)
is not engaged, MBC switch is closed.
If open, check that the wire harness
connector is properly connected and that
Bin Control
Cable Connector
the actuator paddle is not sticking. Clean if
necessary. See "II.D.2.b) Mechanical Bin
Control Cleaning." If MBC switch still reads
open, replace MBC.
Fig. 1
Connection Detail
Wire Harness
Connector A
Control Board
Red K4 Connector
7) Press and hold the actuator paddle; check for continuity across the wires of MBC
connector. When the actuator paddle is engaged, MBC switch is open. If closed, check
that the actuator paddle is not restricted. Clean if necessary. See "II.D.2.b) Mechanical
Bin Control Cleaning." If MBC switch still reads closed, replace MBC.
8) Reconnect MBC connector to CB K4 connector, then move the control switch to the
"ICE" position. Turn on the power supply.
9) Check that CB green "BC CLOSED" LED is on.
10) Allow the icemaker to cycle on. Press and hold the actuator paddle. CB yellow
"BCOPEN" LED should turn on and the icemaker should shut down according to the
chart below. If it does not, replace CB.
Cycle at
Mechanical Bin
Control Activation
Fill Cycle15 sec. after activation.
Harvest CycleAt the end of the harvest cycle, or up to 15 sec. into the freeze cycle if activated at the
Freeze Cycle15 sec. after activation if activated at least 15 sec. before the 5-min. short cycle
Shutdown
end of the harvest cycle.
protection timer terminates. Otherwise, at the end of the next harvest cycle.
Legend: MBC–mechanical bin control; CB–control board
37
Page 38
b) Mechanical Bin Control Cleaning
Scale may build up on MBC. Scale can cause the actuator paddle and magnet to stick. In
this case, MBC should be cleaned.
WARNING
CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews are
securely in place after the icemaker is serviced. Make sure that none have fallen
into the dispense unit/ice storage bin.
1) Turn off the power supply.
2) Remove the front panel, then move the control switch to the "OFF" position.
3) Clear any ice away from MBC.
4) Disconnect MBC connector from CB K4 connector, then remove MBC from the
icemaker.
5) Remove the actuator paddle from the switch mount. See Fig. 2.
6) Wipe down MBC with a mixture of 1 part of Hoshizaki "Scale Away" and 25 parts of
warm water. Rinse the parts thoroughly with clean water.
7) Reassemble MBC and replace it in its correct position.
Note: If the magnet was removed for cleaning, be sure to replace it in its correct
position.
8) Reconnect MBC connector to CB K4 connector, then move the control switch to the
"ICE" position.
9) Replace the control box cover in its correct position.
10) Turn on the power supply to start the automatic icemaking process.
11) Replace the front panel in its correct position.
Legend: MBC–mechanical bin control
KM-xxxxS_H/3
MBC Bracket
Switch Mount
Actuator
Paddle
Bin Control Proximity
Switch Closed
(calling for ice)
Bin Control
Proximity Switch
Open (bin full,
icemaker off or
shutting down)
Magnet
MBC Connector
Fig. 2
38
Page 39
E. Float Switch Check and Cleaning
FS is used to determine that there is sufficient water in the water tank after the 1-min.
ll cycle and after each harvest cycle. FS is also used to determine that the appropriate
volume of water has been converted into ice before switching out of the freeze cycle. No
adjustment is required.
1. Float Switch Check
To check FS, follow the steps below.
1) Turn off the power supply.
2) Remove the front panel, then move the control switch to the "OFF" position.
3) Remove the insulation panel, then remove the drain plug located on the lower front part
of the ice chute. See Fig. 3. Allow the water tank to drain.
4) Replace the drain plug in its correct position. Be careful not to cross thread it.
5) Remove the control box cover.
Drain Plug
Cleaning Valve
6) Disconnect FS connector from CB
K5connector.
7) Check for continuity across FS leads. With
the water tank empty, FS should be open.
If open, continue to step 8. If closed, follow
the steps in "II.E.2. Float Switch Cleaning."
After cleaning FS, check it again. Replace if
necessary.
8) Reconnect FS connector to CB K5
connector, then replace the control box
Ice Chute
Fig. 3
Float Switch Assembly
cover in its correct position.
9) Move the control switch to the "ICE" position. Replace the insulation panel and front
panel in their correct positions, then turn on the power supply. After 1 min., the 1-min.
ll cycle should end and the initial harvest cycle should begin. If the initial harvest cycle
begins, FS is good and the check is complete. If the initial harvest cycle does not begin,
continue to step 10.
10) Turn off the power supply.
11) Remove the front panel. Move the control switch to the "OFF" position.
12) Remove the control box cover.
13) Disconnect FS connector from CB K5 connector.
14) Check for continuity across FS leads. With the water tank full, FS should be closed.
IfFS is closed and the icemaker will not switch from the 1-min. ll cycle to the initial
harvest cycle, replace CB.
If FS is open, conrm that the water tank is full. If the water tank is not full, check the
water supply, water lters, and inlet water valve. If the water tank is full, follow the
steps in "II.E.2. Float Switch Cleaning." After cleaning FS, check it again. Replace if
necessary.
Legend: CB–control board; FS–oat switch
39
Page 40
2. Float Switch Cleaning
Depending on local water conditions, scale may build up on FS. Scale on the switch can
cause the oat to stick. In this case, FS should be cleaned.
1) Turn off the power supply.
2) Remove the front panel, then move the control switch to the "OFF" position.
3) Remove the insulation panel, then remove the drain plug located on the lower front part
of the ice chute. See Fig. 3. Allow the water tank to drain.
4) Replace the drain plug in its correct position. Be careful not to cross thread it.
5) Disconnect the vent tube and the ush tube from the top of FS, then remove FS
assembly and remove the rubber boot from the bottom of FS assembly. See Fig. 4.
6) Remove the retainer rod from the bottom of FS housing, then remove the oat.
Becareful not to bend the retainer rod excessively when removing it.
7) Wipe down FS housing, shaft, oat, and retainer rod with a mixture of 1 part Hoshizaki
"Scale Away" and 25 parts warm water. Clean the inside of the rubber boot and hose
with cleaning solution. Rinse the parts thoroughly with clean water.
8) Reassemble FS assembly and replace it and the rubber boot in their correct positions.
Reconnect the vent tube and the ush tube.
9) Move the control switch to the "ICE" position.
10) Replace the insulation panel and front panel in their correct positions.
11) Turn on the power supply to start the automatic icemaking process.
Legend: CB–control board; FS–oat switch
Vent
Flush
Shaft
Float Switch
Housing
Float
Retainer Rod
Rubber Boot
and Hose
Fig. 4
40
Page 41
F. Thermistor Check
To check thermistor resistance, follow the steps below.
1) Turn off the power supply.
2) Remove the front panel. Move the control switch to the "OFF" position.
3) Remove the control box cover.
4) Remove the thermistor from the refrigerant tubing.
5) Immerse the thermistor sensor portion in a glass containing ice and water for 2 or 3 min.
6) Disconnect the thermistor connector from CB K3 connector and check the resistance
between thermistor leads. Normal range is 4.7 to 6.2 kΩ. If outside the normal range,
replace the thermistor. See "IV.B. Component Service Information." If within the normal
range, continue to the next step.
7) Replace the thermistor in its correct position. See "IV.B. Component Service
Information."
8) Reconnect the thermistor connector to CB K3 connector.
9) Replace the control box cover in its correct position.
10) Move the control switch to the "ICE" position.
11) Replace the front panel in its correct position.
12) Turn on the power supply.
13) Once the harvest cycle starts (Comp energizes), begin timing the harvest cycle.
14) The harvest timer and harvest cycle should terminate within 2 to 5 min. If the harvest
cycle does not terminate within 2 to 5 min., replace CB.
Legend: CB–control board; Comp–compressor
Thermistor Lead Cable Tie
Foam Insulation Thermistor Holder
Fig. 5
41
Page 42
G. Diagnostic Tables
1. No Ice Production
No Ice Production - Possible Cause
1. Power Supplya) Off, blown fuse, or tripped breaker.
b) Not within specications.
2. Main Transformer
(KM-1301S_H auxiliary code D-1
and later and all 3 phase models)
3. Fuse (Control Box)a) Blown.
4. Thermostatic Bin Control
See "II.D. Bin Control Check"
5. Control Switcha) In "OFF" or "WASH" position.
6. High-Pressure Switch a) Dirty condenser.
7. Control Transformer
(115VAC/10.5VAC)
8. Control Board
See "II.C. Control Board Check"
9. Mechanical Bin Control
See "II.D. Bin Control Check."
10. Water Supplya) Water supply off or improper water pressure.
11. Inlet Water Valvea) Screen or orice clogged.
12. Float Switch
See "II.E. Float Switch Check
and Cleaning"
13. Compressora) Compressor relay/magnetic contactor contacts bad or coil winding
14. Hot Gas Valvea) Closed in harvest cycle.
a) Voltage tap switch not set to proper voltage.
b) Coil winding open or shorted.
a) Tripped with bin lled with ice.
b) Ambient temperature too cool.
c) Set too warm.
d) Bulb out of position.
e) Open contacts, defective.
b) Bad contacts.
b) Fan motor not operating.
c) Refrigerant overcharged.
d) Bad contacts.
e) Refrigerant lines or components plugged.
a) Coil winding open or shorted.
a) In alarm.
b) Yellow "BC OPEN" LED on (bin full) ("G" control board).
c) Defective.
a) Tripped with bin lled with ice.
b) Actuator does not move freely.
c) Defective.
b) External water lters clogged.
b) Coil winding open.
c) Water valve open in freeze cycle.
a) Float does not move freely.
b) Defective.
open.
b) Start capacitor or run capacitor defective (single phase model).
c) Internal protector open.
d) Start relay contacts bad or coil winding open (single phase model).
e) Compressor defective.
b) Open in freeze cycle.
42
Page 43
No Ice Production - Possible Cause
15. Thermistor
See "II.F. Thermistor Check"
16. Pump Motora) Motor winding open.
1 7. Thermostatic Expansion Valvea) Bulb loose.
18. Liquid Line Valve a) Closed in freeze cycle.
19. Fan Motora) Motor winding open.
20. Water Systema) Water leaks causing short freeze time.
a) Loose, disconnected, or defective.
b) Bearing worn out or locked rotor.
c) Defective capacitor.
d) Mechanical seal worn out.
b) Operating erratically.
b) Open in harvest cycle.
b) Bearing worn out or locked rotor.
c) Defective capacitor.
2. Freeze-Up
Defrost and clean the icemaker prior to diagnosing freeze-up. Fill out a freeze-up checklist.
See the Hoshizaki America Technician's Pocket Guide or contact your local distributor for a
copy of the freeze-up checklist.
Freeze-Up - Possible Cause
Harvest Cycle
1. Evaporatora) Scaled up.
b) Damaged.
2. Cube Guidesa) Out of position.
b) Damaged.
3. Spray Tubes and/or Spray
Guides
4. Water Supplya) Low water pressure.
5. Inlet Water Valvea) Screen or orice clogged.
6. Float Switch
See "II.E. Float Switch Check
and Cleaning"
7. Refrigerant Chargea) Low.
8. Control Board
See "II.C. Control Board
Check" and "III.C. Settings and
Adjustments"
9. Bin Control
See "II.D. Bin Control Check"
a) Dirty.
b) Out of position.
b) External water lters clogged.
c) Insufficient water line size.
Minimum 3/8" Nominal ID (10 mm Nominal OD in the EU) copper
water tubing or equivalent.
b) Defective.
a) Dirty, sticking.
b) Defective.
a) Harvest timer (S4 dip switch 1 & 2) set too short.
b) Harvest pump timer (S4 dip switch 7) not in factory default position
("G" control board).
c) Defective.
a) Thermostatic: Thermostat bulb loose or defective.
b) Mechanical: Actuator does not move or defective.
43
Page 44
Freeze-Up - Possible Cause
10. Thermistor
See "II.F. Thermistor Check"
11. Thermostatic Expansion Valvea) Defective.
12. Hot Gas Valvea) Closed or restricted.
13. Liquid Line Valve a) Open.
1. Evaporatora) Scaled up.
2. Spray Tubes and/or Spray
Guides
3. Refrigerant Chargea) Low.
4. Control Board
See "II.C. Control Board Check"
5. Inlet Water Valvea) Leaking by.
6. Float Switch
See "II.E. Float Switch Check
and Cleaning"
7. Pump Motora) RPM too slow.
8. Thermostatic Expansion Valvea) Bulb loose or defective.
9. Liquid Line Valve a) Restricted.
10. Headmaster (C.P.R.)
(remote models)
a) Loose, disconnected, or defective.
Freeze Cycle
b) Damaged.
a) Dirty.
b) Out of position.
a) Freeze timer (S4 dip switch 9 & 10) set incorrectly.
b) Defective.
a) Float does not move freely.
b) Defective.
b) Impeller damaged.
a) Not bypassing.
3. Low Ice Production
Low Ice Production - Possible Cause
Long Harvest Cycle
1. Evaporatora) Scaled up.
2. Spray Tubes and/or Spray
Guides
3. Refrigerant Chargea) Low.
4. Water Supplya) Low water pressure.
5. Control Board
See "II.C. Control Board Check"
6. Thermistor
See "II.F. Thermistor Check"
7. Hot Gas Valvea) Erratic or closed.
8. Inlet Water Valvea) Screen or orice clogged.
a) Dirty.
b) Out of position.
b) External water lters clogged.
c) Insufficient water line size.
Minimum 3/8" Nominal ID (10 mm Nominal OD in the EU) water
tubing or equivalent.
d) Too cold.
a) Thermistor connection loose (K3).
b) Defective.
a) Loose, disconnected, or defective.
44
Page 45
Low Ice Production - Possible Cause
9. Compressora) Inefficient or off.
10. Liquid Line Valve a) Erratic or open.
11. Thermostatic Expansion Valvea) Defective.
Long Freeze Cycle
1. Evaporatora) Scaled up, dirty.
2. Float Switch
See "II.E. Float Switch Check
and Cleaning"
3. Inlet Water Valvea) Leaking by.
4. Hot Gas Valvea) Erratic or open.
5. Condensera) Clogged.
6. Control Board
See "II.C. Control Board Check"
7. Refrigerant Chargea) Low.
8. Thermostatic Expansion Valvea) Bulb loose.
9. Compressora) Inefficient or off.
10. Pump Motora) RPM too slow.
11. Liquid Line Valve a) Erratic or restricted.
12. Headmaster (C.P.R.)
(remote models)
a) Scaled up, dirty.
b) Float sticking.
c) Defective switch.
a) Float switch connection loose (K5).
b) Defective.
b) Defective.
a) Not bypassing.
45
Page 46
III. Controls and Adjustments
• A Hoshizaki exclusive control board is employed in KM and KMH series appliances.
• All models are pretested and factory adjusted.
• For a control board check procedure, see "II.C. Control Board Check."
NOTICE
• Fragile, handle very carefully.
• The control board contains integrated circuits, which are susceptible to failure
due to static discharge. It is especially important to touch the metal part of the
icemaker when handling or replacing the control board.
• Do not touch the electronic devices on the control board or the back of the control
board.
• Do not change wiring and connections. Do not misconnect K3 WHITE, K4RED,
and K5 BLACK, because the same connector is used for the thermistor,
mechanical bin control, and oat switch. K4 RED is not used on "E" control board
models.
• Do not short out power supply to test for voltage.
• Always replace the whole control board assembly if it goes bad.
46
Page 47
A. Control Board Layout
1. "E" Control Board
"E" Control Board
• "ALARM RESET" Button
• Freeze Timer
LED (yellow)
• Harvest Backup
Timer LED (orange)
• Alarm Buzzer
• POWER OK LED
(red) (lights when
10.5VAC is supplied
to K2 connector)
• Relay LEDs
(4) (indicate which
relays are energized
and which K1
connector pins are
energized
• LED 2 (X2 Relay)
LED 2 on:
K1 Connector Pin #2
LED 2 off:
K1 Connector Pin #3
• LED 3 (X3 Relay)
LED 3 on:
K1 Connector Pin #5
LED 3 off:
K1 Connector Pin #4
(energized in freeze)
• LED 4 (X4 Relay)
K1 Connector Pin #6
• LED 1 (X1 Relay)
K1 Connector Pin #1, #9
• S4 Dip Switch
• K2 Connector
Control Transformer
(10.5VAC)
• "OUTPUT TEST" Button
(used to test relays on control board)
• K3 (white) Connector
Thermistor
(harvest control and
high temperature safety)
• K4 (red) Connector
Open
• Part Number
• K5 (black) Connector
Float Switch
(water level)
Microprocessor
(control board revision
level indicated on label
on side of relay)
• K1 Connector
Pins #1 through #10
#1, 9 Magnetic Contactor or
Compressor Relay
#2 Hot Gas Valve
#3 Fan Motor
Liquid Line Valve
#4 Pump Motor (icemaking)
#5 Pump Motor (pump-out)
#6 Inlet Water Valve
#7, 10 Component Power
Supply
#8 Open
Switch for "C" control board
and "ALPINE" control board
(service control board only)
Set to "ALP" for appliances
covered in this manual.
"E" Control Board
Part Number 2A1410-02
47
Page 48
2. "G" Control Board
• Bin Control Switch
Closed LED (green)
(on continuously
in thermostatic bin
control application)
• "ALARM RESET" Button
"G" Control Board
• S4 Dip Switch
• "OUTPUT TEST" Button
(used to test relays on control board)
• Bin Control Switch
Open LED (yellow)
(mechanical bin
control application only)
• Part Number
• Alarm Buzzer
• POWER OK LED
(red) (lights when
10.5VAC is supplied
to K2 connector)
• Relay LEDs
(4) (indicate which
relays are energized
and which K1
connector pins are
energized
• LED 2 (X2 Relay)
LED 2 on:
K1 Connector Pin #2
LED 2 off:
K1 Connector Pin #3
• LED 3 (X3 Relay)
LED 3 on:
K1 Connector Pin #5
LED 3 off:
K1 Connector Pin #4
(energized in freeze)
• LED 4 (X4 Relay)
K1 Connector Pin #6
• LED 1 (X1 Relay)
K1 Connector Pin #1, #9
• K3 (white) Connector
Thermistor
(harvest control and
high temperature safety)
• K4 (red) Connector
Mechanical Bin Control or
K4 Jumper (thermostatic
bin control application)
• S5 Dip Switch
• K5 (black) Connector
Float Switch
(water level)
Label
(control board revision
level indicated on label
on side of relay)
• K1 Connector
Pins #1 through #10
#1, 9 Magnetic Contactor or
Compressor Relay
#2 Hot Gas Valve
#3 Fan Motor
Liquid Line Valve
#4 Pump Motor (icemaking)
#5 Pump Motor
(harvest pump timer and
pump-out)
#6 Inlet Water Valve
#7, 10 Component Power
Supply
#8 Open
• K2 Connector
Control Transformer
(10.5VAC)
"G" Control Board
Part Number 2A3792-01
48
Page 49
B. LED Lights and Audible Alarm Safeties
1. "E" Control Board
At startup, a 5-second delay occurs while the control board conducts an internal timer
check. A beep occurs when power is turned off. The red "POWER OK" LED indicates
proper control voltage and remains on unless a control voltage problem occurs. The
green LEDs 1 through 4 energize and sequence from initial startup as listed in the
table below. Note that the order of the LEDs from the outer edge of the control board
is 1, 4, 3, 2.
The built in safeties shut down the icemaker and have alarms as listed below.
No. of Beeps
(every 3 sec.)
1High Evaporator Temp.
(temperature > 127°F) (53°C)
2Harvest Backup Timer
(harvest > 20 min. for two cycles
in a row)
3Freeze Timer
(freeze > specied setting for
two cycles in a row)
To reset the above safeties, press the "ALARM RESET" button with the power supply on.
6Low Voltage
(92Vac±5% or less)
7High Voltage
(147Vac±5% or more)
Type of AlarmNotes
Check for harvest problem (stuck HGV or relay), hot
water entering icemaker, or shorted thermistor.
Orange "H TIMER" LED on.
Check for open thermistor, HGV not opening, TXV or
LLV leaking by, low charge, or inefficient Comp, or WRV
leaking by.
Yellow "F TIMER" LED on.
Check for FS stuck closed (up), WV leaking by, HGV
leaking by, PM not pumping, TXV not feeding properly,
LLV not opening, low charge, HM not bypassing, or
inefficient Comp.
Red LED turns off if voltage protection operates.
The control voltage safeties automatically reset when
voltage is corrected.
Legend: Comp–compressor; FM–fan motor; FMR–fan motor remote; FS–oat switch;
HGV–hot gas valve; HM–headmaster (C.P.R.); LLV–liquid line valve; PM–pump
motor; TXV–thermostatic expansion valve; WRV–water regulating valve;
WV–inlet water valve
49
Page 50
2. "G" Control Board
At startup, a 5-second delay occurs while the control board conducts an internal timer
check. A beep occurs when the control switch is moved to the "ICE" position. The red
"POWER OK" LED indicates proper control voltage and remains on unless a control
voltage problem occurs. The green LEDs 1 through 4 energize and sequence from
initial startup as listed in the table below. Note that the order of the LEDs from the
outer edge of the control board is 1, 4, 3, 2.
The built-in safeties shut down the icemaker and have alarms as listed below.
No. of Beeps
(every 3 sec.)
1High Evaporator Temp.
(temperature > 127°F) (53°C)
2Harvest Backup Timer
(harvest > 20 min. for two
cycles in a row)
3Freeze Timer
(freeze > freeze timer setting
for two cycles in a row)
To reset the above safeties, press the "ALARM RESET" button with the power supply on.
6Low Voltage
(92Vac±5% or less)
7High Voltage
(147Vac±5% or more)
Type of AlarmNotes
Check for harvest problem (stuck HGV or relay), hot
water entering icemaker, or shorted thermistor.
Check for open thermistor, HGV not opening, TXV or
LLV leaking by, low charge, or inefficient Comp, or WRV
leaking by.
Check for FS stuck closed (up), WV leaking by, HGV
leaking by, PM not pumping, TXV not feeding properly,
LLV not opening, low charge, HM not bypassing, or
inefficient Comp.
Red LED turns off if voltage protection operates.
The control voltage safeties automatically reset when
voltage is corrected.
Legend: Comp–compressor; FM–fan motor; FMR–fan motor remote; FS–oat switch;
HGV–hot gas valve; HM–headmaster (C.P.R.); LLV–liquid line valve; PM–pump
motor; TXV–thermostatic expansion valve; WRV–water regulating valve;
WV–inlet water valve
50
Page 51
C. Settings and Adjustments
NOTICE
Dip switches are factory set. Failure to maintain factory settings may adversely
affect performance and warranty coverage. For more information, contact your
Hoshizaki Service Center.
1. Default Dip Switch Settings
The dip switches are factory-adjusted to the following positions for both the "E" and "G"
control boards:
a) "E" and "G" Control Board without Harvest Pump Timer Operation
b) "G" Control Board with Harvest Pump Timer Operation
S4 Dip Switch
S4 Dip Switch No.12345678910
KM-1301SAH/3
KM-1301SWH/3
KM-1601SAH/3
KM-1301SRH/3
KM-1400SWH-M
KM-1400SWH3-M
OFF OFF ON ON ON ON ON OFF OFF OFF
OFF OFF ON ON ON ON ON OFF ON OFF
OFF OFF OFF OFF OFF OFF ON OFF OFF OFF
c) "G" Control Board S5 Dip Switch
S5 Dip Switch (Do Not Adjust)
S5 Dip Switch No.
AllOFF OFF OFF OFF OFF
12345
S4 Dip Switch
"E" and "G" Control Boards
ON
1 2 3 4 5 6 7 8 9 10
Freeze Timer (9 & 10)
Factory Use (8)
Bin Control Selector (7) "E" Control Board
Harvest Pump Timer (7) "G" Control Board
(Do Not Adjust)
Pump-Out Frequency Control (5 & 6)
Pump-Out Timer (3 & 4)
Harvest Timer (1 & 2)
S5 Dip Switch
"G" Control Board
Rell Counter (2 through 5)
1 2 3 4 5
ON
Float Switch Selector (1)
2. Harvest Timer (S4 dip switch 1 & 2)
The harvest timer starts counting when the thermistor reaches 48°F (9°C) at the
evaporator outlet and the control board reads 3.9 kΩ from the thermistor. The harvest
timer is factory set, and generally no adjustment is required. However, a setting longer
than the factory setting may be advised in cases where the drain provided at harvest
needs to be prolonged for extra cleaning. Note that the pump-out timer (S4 dip switch
3 & 4) acts in place of the harvest timer during cycles with a pump out. For details, see
"III.C.3. Pump-Out Timer (S4 dip switch 3& 4)."
Note: On models with a pump-out every cycle, the harvest timer is only relevant during
the initial harvest cycle since a pump out occurs every cycle thereafter.
S4 Dip Switch SettingTime
No. 1No. 2
OFFOFF60
ONOFF90
OFFON120
ONON180
(sec.)
52
Page 53
3. Pump-Out Timer (S4 dip switch 3 & 4)
NOTICE
On models with harvest pump timer, do not adjust 3 off and 4 on. Pump does not
run in pump-out rotation in this setting.
When a pump-out is called for, the pump motor stops for 2 sec., then energizes in the
reverse direction, taking water from the bottom of the water tank and forcing pressure
against the check valve seat allowing water to go through the check valve and down
the drain. At the same time, water ows through the small tube to power ush the oat
switch. The pump motor drains the water tank for the time determined by the pump-out
timer. The pump-out timer also acts in place of the harvest timer during cycles with a
pump-out. The pump-out timer is factory set, and generally no adjustment is required.
However, where water quality is bad and the icemaker needs a longer pump-out time, the
pump-out timer can be adjusted. The pump-out timer control can be set to pump-out for
10 or 20 sec.
S4 Dip Switch SettingTime (sec.)
OFFOFF10150Closed
ONOFF10180Closed
OFFON10120Open
ONON20180Closed
T1: Time to drain the water tank
T2: Harvest timer at pump out
T1
T2
Inlet Water
ValveNo. 3No. 4
53
Page 54
4. Pump-Out Frequency Control (S4 dip switch 5 & 6)
The pump-out frequency control is factory set. Generally no adjustment is required.
However, where water quality is bad and the icemaker needs a pump-out more often, the
pump-out frequency can be adjusted. The pump-out frequency control can be set to have
a pump-out occur every cycle, or every 2, 5, or 10 cycles.
Timing of the rst pump-out is dependent on the control board. On "E" control boards, the
rst pump-out is after the rst freeze cycle. On "G" control boards, the rst pump-out is
dependent on S4 dip switch 5 & 6. See the table below.
5. Bin Control Selector or Harvest Pump Timer Operation (S4 dip switch 7)
Depending on the control board, S4 dip switch 7 is used for either bin control selection or
harvest pump timer operation.
• "E" Control Board: Bin Control Selector (thermostatic or mechanical).
• "G" Control Board: Harvest Pump Timer Operation.
a) Bin Control Selector: "E" Control Board
NOTICE
Do not adjust. This dip switch must be left in the factory default position or the
icemaker will not operate correctly.
When set to on position on an icemaker with a thermostatic bin control, a 5-beep alarm
sounds (open circuit) and the icemaker does not operate.
"E" Control Board
S4 Dip Switch Setting
No. 7
ONMechanical (requires resistor wire harness)
OFFThermostatic
Bin Control
54
Page 55
b) Harvest Pump Timer: "G" Control Board
NOTICE
Factory set for proper operation. Do not adjust. Adjustment outside of the factory
default setting may result in damage to the appliance.
Depending on the harvest pump timer setting, the pump motor either stays off or is
energized the last 50 seconds of harvest. When the pump motor is energized, water
circulates over the evaporator. The harvest water valve is open during harvest for a
maximum of 6 minutes or the length of harvest minus 0 or 50 seconds (determined by
the harvest pump timer setting), whichever is shorter.
When S4 dip switch 7 is in the on position and harvest begins, X11 and X10 relays
energize. A latching circuit is created through the X11 and X10 relays. For further details,
see "VIII.C. Wiring Diagrams."
50 sec. before harvest termination, LED 4 turns off, inlet water valve and X11 relay
de-energize. X10 relay remains energized through the latching circuit. Next, LED 3 turns
on and control board K1 connector pin #5 (DBU wire) energizes, energizing the pump
motor for the last 50 sec. of harvest.
"G" Control Board
S4 Dip Switch Setting
No. 7
ON50
OFF0
Pump Motor
Time (sec.)
6. Factory Use (S4 dip switch 8)
Factory set for proper operation. Do not adjust. This must be left in the factory default
position.
7. Freeze Timer (S4 dip switch 9 & 10)
NOTICE
Adjust to proper specication, or the icemaker may not operate correctly.
The freeze timer setting determines the maximum allowed freeze time to prevent
possible freeze-up issues. Upon termination of the freeze timer, the control board initiates
the harvest cycle or pump-out cycle. After 2 consecutive freeze timer terminations, the
control board shuts down the icemaker. In this case, see "II.G.3. Low Ice Production"
for possible solutions. The freeze timer is factory set and no adjustment is required.
Before changing this setting, contact Hoshizaki Technical Support at 1-800-233-1940 for
recommendations.
Do not adjust. This must be left in the factory default position or the icemaker will
not operate correctly.
9. Rell Counter (S5 dip switch 2 through 5): "G" Control Board
NOTICE
Do not adjust. These must be left in the factory default position or the icemaker will
not operate correctly.
D. Control Switch
The control switch has three positions: "OFF" for power off, "ICE" for icemaking, and
"WASH" to energize the pump motor when cleaning and sanitizing.
56
Page 57
IV. Refrigeration Circuit and Component Service Information
WARNING
• This appliance should be diagnosed and repaired only by qualied service
personnel to reduce the risk of death, electric shock, serious injury, or re.
• Move the control switch to the "OFF" position and turn off the power supply. Place
the disconnect in the "OFF" position. Lockout/Tagout to prevent the power supply
from being turned back on inadvertently.
• CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews are
securely in place after the icemaker is serviced. Make sure that none have fallen
into the dispenser unit/ice storage bin.
• Make sure all food zones in the icemaker and dispenser unit/ice storage bin are
clean after service.
A. Refrigeration Circuit Service Information
WARNING
• Repairs requiring the refrigeration circuit to be opened must be performed by
properly trained and EPA-certied service personnel.
• Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of
refrigerant to the system (if using an electronic leak detector), and then raise the
pressure using nitrogen gas (140 PSIG). Do not use R-404A as a mixture with
pressurized air for leak testing.
NOTICE
• Always recover the refrigerant and store it in an approved container. Do not
discharge the refrigerant into the atmosphere.
• Do not leave the system open for longer than 15 min. when replacing or servicing
parts. The Polyol Ester (POE) oils used in R-404A applications can absorb
moisture quickly. Therefore it is important to prevent moisture from entering the
system when replacing or servicing parts.
• Always install a new drier every time the sealed refrigeration system is opened.
Do not replace the drier until after all other repair or replacement has been made.
Install the new drier with the arrow on the drier in the direction of the refrigerant
ow.
• When brazing, protect the drier by using a wet cloth to prevent the drier from
overheating. Do not allow the drier to exceed 250°F (121°C).
1. Refrigerant Recovery
The icemaker is provided with refrigerant service valves. Using proper refrigerant practices,
recover the refrigerant. Store the refrigerant in an approved container. Do not discharge the
refrigerant into the atmosphere.
57
Page 58
2. Brazing
WARNING
• R-404A itself is not ammable at atmospheric pressure and temperatures up to
176°F (80°C).
• R-404A itself is not explosive or poisonous. However, when exposed to high
temperatures (open ames), R-404A can be decomposed to form hydrouoric
acid and carbonyl uoride both of which are hazardous.
• Do not use silver alloy or copper alloy containing arsenic.
1) Braze all ttings while purging with nitrogen gas owing at a pressure of 3 to 4 PSIG.
Note: Because the pipes in the evaporator case are specially coated to resist corrosion,
it is important to make connections outside the evaporator case when possible. If
it is necessary to braze inside the evaporator case, use sandpaper to remove the
coating from the brazing connections before unbrazing the components.
NOTICE
• Always install a new drier every time the sealed refrigeration system is opened.
• Do not replace the drier until after all other repair or replacement has been made.
Install the new drier with the arrow on the drier in the direction of the refrigerant
ow.
• When brazing, protect the drier by using a wet cloth to prevent the drier from
overheating. Do not allow the drier to exceed 250°F (121°C).
2) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of
refrigerant to the system (if using an electronic leak detector), and then raise the
pressure using nitrogen gas (140 PSIG). Do not use R-404A as a mixture with
pressurized air for leak testing.
3. Evacuation and Recharge (R-404A)
1) Attach a vacuum pump to the system. Be sure to connect the charging hoses to both
high and low-side refrigerant access valves.
IMPORTANT
The vacuum level and vacuum pump may be the same as those for current
refrigerants. However, the rubber hose and gauge manifold to be used for
evacuation and refrigerant charge should be exclusively for POE oils.
2) Turn on the vacuum pump. Open the gauge manifold valves, then open the high and
low-side service valves. Never allow the oil in the vacuum pump to ow backwards.
3) Allow the vacuum pump to pull down to a 29.9" Hg vacuum. Evacuating period depends
on pump capacity.
58
Page 59
4) Close the low-side valve and high-side valve on the gauge manifold.
5) Disconnect the gauge manifold hose from the vacuum pump and attach it to a
refrigerant service cylinder. Remember to loosen the connection and purge the air from
the hose. For the required refrigerant charge, see the rating label inside the icemaker.
Hoshizaki recommends only virgin refrigerant or reclaimed refrigerant which meets
ARI Standard 700 (latest edition) be used.
6) A liquid charge is required when charging an R-404A system (to prevent fractionation).
Place the service cylinder on the scales; if the service cylinder is not equipped with
a dip tube, invert the service cylinder, then place it on the scales. Open the high-side
valve on the gauge manifold.
7) Allow the system to charge with liquid until the proper charge weight is met.
8) If necessary, add any remaining charge to the system through the low-side.
NOTICE!To prevent compressor damage, use a throttling valve or liquid
dispensing device to add the remaining liquid charge through the low-side
refrigerant service valve with the icemaker running.
9) Close the high and low-side service valves, then close the high and low-side gauge
manifold valves. Disconnect the gauge manifold hoses.
10) Cap the refrigerant service valves to prevent a possible leak.
59
Page 60
B. Component Service Information
NOTICE
When replacing a component listed below, see the notes to help ensure proper
operation.
ComponentNotes
Compressor1 phase: Install a new start capacitor, run capacitor, and start relay.
3 phase: Install a new magnetic contactor.
Thermostatic
Expansion Valves
Hot Gas Valves
Liquid Line Valves
Fan MotorsInstall a new capacitor.
Pump MotorInstall a new capacitor.
Thermistor• Attach the new thermistor to the suction line in the same location as the previous
• Attach the thermostatic expansion valve bulb to the suction line in the same location
as the previous bulb.
• The bulb should be between the 10 and 2 o'clock positions on the tube.
• Secure the bulb with the clamp and holder, then insulate it.
• Replace the strainer if applicable.
• Use copper tube of the same diameter and length when replacing valve lines.
thermistor.
KM-1400SWH-M,
KM-1400SWH3-M
Water Regulating
Valve
• The thermistor should be at the 12 o'clock position on the tube.
• Smoothly ll the recessed area of the thermistor holder with high thermal
conductive type sealant. Hoshizaki America part number 4A0683-01 (Silicone
Heat Sink Compound 10-8108 manufactured by GC Electronics), KE-4560 RTV
(manufactured by ShinEtsu Silicones), or equivalent are recommended.
• Secure the thermistor with the holder, then insulate it.
• Be very careful to prevent damage to the leads.
Tighten the water regulating valve are nut to a torque of 39.8 ft-lb/53.9N·m.
60
Page 61
C. Water Regulating Valve Adjustment (water-cooled models)
The water regulating valve is factory set, and generally no adjustment is required. However,
when necessary, adjust the water regulator using the following procedure.
1) Prepare a thermometer to check the condenser drain temperature. Attach a pressure
gauge to the high-side line of the system.
2) 5 min. after a freeze cycle starts, conrm that the thermometer reads 104°F to 115°F
(40°C to 46°C). If it does not, rotate the adjustment screw by using a at blade
screwdriver until the temperature is in the proper range (rotate counterclockwise to
raise temperature or clockwise to lower temperature). See Fig. 6. Next, check that the
reference pressure is in the range indicated in "VIII.A. Specication and Performance
Data." If it is not in the proper range, verify the refrigerant charge.
3) Check that the condenser drain temperature is stable.
Adjustment Screw
CW – Lower
CCW – Higher
Top View
Fig. 6
61
Page 62
V. Maintenance
The maintenance schedule below is a guideline. More frequent maintenance may be
required depending on water quality, the appliance's environment, and local sanitation
regulations
WARNING
• Only qualied service technicians should service the appliance.
• To reduce the risk of electric shock, do not touch the control switch or service
switch with damp hands
• Before servicing: Move the control switch to the "OFF" position and turn off the
power supply. Place the disconnect in the "OFF" position.
Lockout/Tagout to prevent the power supply from being turned back on
inadvertently.
• CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews are
securely in place after any maintenance is done to the icemaker. Make sure that
none have fallen into the dispenser unit/ice storage bin.
Maintenance Schedule
Frequency AreaTask
DailyScoopClean the ice scoop using a neutral cleaner. Rinse thoroughly after
cleaning.
Bi-WeeklyAir FiltersInspect. Wash with warm water and neutral cleaner if dirty.
MonthlyExternal Water
Filters
Icemaker Exterior Wipe down with a clean, soft cloth. Use a damp cloth containing a
YearlyIcemaker and
Dispenser Unit/Ice
Storage Bin Liner
Water Supply Inlet Close the icemaker water supply line shut-off valve and drain the water
CondenserInspect. Clean if necessary by using a brush or vacuum cleaner. More
Water HosesInspect the water hoses and clean/replace if necessary.
As Needed Marine Model
Condenser
Check for proper pressure and change if necessary.
neutral cleaner to wipe off oil or dirt build up. Clean any chlorine staining
(rust colored spots) using a non-abrasive cleanser.
Clean and sanitize per the cleaning and sanitizing instructions provided
in the instruction manual or maintenance label on the icemaker.
system. Clean the water supply inlet screen.
frequent cleaning may be required depending on location.
If contaminated seawater enters the system, ush with clean seawater or
fresh water as soon as possible to minimize damage to the condenser.
62
Page 63
VI. Preparing the Icemaker for Periods of Non-Use
NOTICE
• When storing the appliance for an extended time or in sub-freezing temperatures,
follow the instructions below to prevent damage.
• To prevent damage to the water pump, do not operate the appliance with the
control switch in the "WASH" position when the water tank is empty.
When the appliance is not used for two or three days under normal conditions, it is
sufficient to move the control switch to the "OFF" position. When storing the appliance for
an extended time or in sub-freezing temperatures, follow the instructions below.
1. Remove the water from the icemaker water supply line:
1) Turn off the power supply, then remove the front panel.
2) Move the control switch to the "OFF" position.
3) Close the icemaker water supply line shut-off valve, then open the icemaker water
supply line drain valve.
4) Allow the line to drain by gravity.
5) Attach a compressed air or carbon dioxide supply to the icemaker water supply line
drain valve.
6) Move the control switch to the "ICE" position.
7) Replace the front panel in its correct position, then turn on the power supply.
8) Blow the icemaker water supply line out using the compressed air or carbon dioxide
supply.
9) Close the icemaker water supply line drain valve.
2. Drain the water tank:
1) Turn off the power supply, then remove the front panel.
2) Move the control switch to the "OFF" position.
3) Remove the insulation panel. Remove the drain plug located on the lower front part of
the ice chute. See Fig. 7. Allow the water tank to drain.
4) Replace the drain plug and the insulation panel in their correct positions. Be careful not
to cross thread the drain plug.
5) Remove all ice from the dispenser unit/ice
Drain Plug
Cleaning Valve
storage bin. Clean the dispenser unit/ice
storage bin liner using a neutral cleaner.
Rinse thoroughly after cleaning.
6) Replace the front panel in its correct
position.
Fig. 7
63
Ice Chute
Float Switch Assembly
Page 64
3. On water-cooled model, remove the water from the water-cooled condenser:
1) Make sure the power supply is off, then remove the front, top, and right side panels.
2) Close the condenser water supply line shut-off valve. If connected to a closed loop
system, also close the condenser return line shut-off valve.
3) Open the condenser water supply line drain valve. If connected to a closed loop system,
also open the condenser return line drain valve.
4) Attach a compressed air or carbon dioxide supply to the condenser water supply line
drain valve.
5) Open the water regulating valve by using a screwdriver to pry up on the spring retainer
underneath the spring. While holding the valve open, blow out the condenser using the
compressed air or carbon dioxide supply until water stops coming out.
6) Close the drain valve(s).
7) Replace the right side, top, and front panels in their correct positions.
64
Page 65
VII. Disposal
The appliance contains refrigerant and must be disposed of in accordance with
applicable national, state, and local codes and regulations. Refrigerant must be
recovered by properly certied service personnel.
65
Page 66
VIII. Technical Information
We reserve the right to make changes in specications and design without prior notice.
A. Specication and Performance Data
Pressure data is recorded at 5 min. into freezing cycle. The data not in bold
should be used for reference only.
1. KM-1301SAH
SPECIFICATION SHEET
AC SUPPLY VOLTAGE208-230/60/1 (3 wire with neutral for 115V) or 208-230/60/1
AMPERAGE12.4 A ( 5 Min. Freeze AT 104°F / WT 80°F)
MINIMUM CIRCUIT AMPACITY20 A
MAXIMUM FUSE SIZE20 A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)2250 (4.63)2160 (3.9)
WATER gal./24HR (gal./100 lbs.)183 (15.7)605 (45.5)
ICE PRODUCTION PER CYCLE29.8 lbs. (13.5 kg) 1440pcs.
REFRIGERANT CHARGER404A, 3 lb. 15.5 oz. (1800g)
PERFORMANCE DATA
APPROXIMATE ICE
PRODUCTION PER 24 HR.
lbs./day kg./day100/3812535681140517965438
APPROXIMATE ELECTRIC
CONSUMPTION
watts100/38
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
gal./day m3/day100/383451.301790.681520.58
FREEZING CYCLE TIME
SPECIFICATION SHEET
AC SUPPLY VOLTAGE208-230/60/3
AMPERAGE9.5 A ( 5 Min. Freeze AT 104°F / WT 80°F)
MINIMUM CIRCUIT AMPACITY20 A
MAXIMUM FUSE SIZE20 A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)2220(4.6)2090(3.9)
WATER gal./24HR (gal./100 lbs.)181(15.6)511(39.4)
ICE PRODUCTION PER CYCLE30.4 lbs. (13.8 kg) 1440pcs.
REFRIGERANT CHARGER404A, 3 lb. 15.5 oz. (1800g)
PERFORMANCE DATA
APPROXIMATE ICE
PRODUCTION PER 24 HR.
lbs./day kg./day100/3812255561133514947430
APPROXIMATE ELECTRIC
CONSUMPTION
watts100/38
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
gal./day m3/day100/383051.151760.671390.53
FREEZING CYCLE TIME
SPECIFICATION SHEET
AC SUPPLY VOLTAGE208-230/60/1 (3 wire with neutral for 115V) or 208-230/60/1
AMPERAGE8.2 A ( 5 Min. Freeze AT 104°F / WT 80°F)
MINIMUM CIRCUIT AMPACITY20 A
MAXIMUM FUSE SIZE20 A
ELECTRIC & WATER CONSUMPTION
ELECTRIC W (kWH/100 lbs.)1760(3.2)1740(3.2)
WATER gal./24HR (gal./100 lbs.)257(19.4)546(41.4)
WATER COOLED CONDENSER1561(118)861(65)
gal./24HR (gal./100 lbs.)
ICE PRODUCTION PER CYCLE31 lbs. (14.1 kg) 1440pcs.
REFRIGERANT CHARGER404A, 2 lb. 8.2 oz. (1140g)
PERFORMANCE DATA
APPROXIMATE ICE PRODUCTION
PER 24 HR.
lbs./day kg./day100/38128158113015901141518
APPROXIMATE ELECTRIC
CONSUMPTION
watts100/38
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
gal./day m3/day100/3818617.0419697.46306011.58
FREEZING CYCLE TIME
TOTAL HEAT OF REJECTION FROM CONDENSER17,400 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
TOTAL HEAT OF REJECTION FROM COMPRESSOR2,300 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
WATER FLOW FOR CONDENSER119 gal./h [AT 100ºF (38ºC) / WT 90ºF (32ºC)]
PRESSURE DROP OF COOLING WATER LINE less than 10 PSIG
69
Page 70
5. KM-1301SRH with URC-14F
SPECIFICATION SHEET
AC SUPPLY VOLTAGE208-230/60/1 (3 wire with neutral for 115V) or 208-230/60/1
AMPERAGE13.5A ( 5 Min. Freeze AT 104°F / WT 80°F)
MINIMUM CIRCUIT AMPACITY20 A
MAXIMUM FUSE SIZE20 A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)2090(4.1)2010(3.6)
WATER gal./24HR (gal./100 lbs.)203(16.6)479(35.4)
ICE PRODUCTION PER CYCLE31.1 lbs. (14.1 kg) 1440pcs.
TOTAL REFRIGERANT CHARGER404A, 10 lbs. 5.8 oz. (4700g)
REFRIGERANT CHARGE BY UNIT(Icemaker 5 lbs. 15.2 oz. Cond. Unit 4 lbs. 6.5 oz.)
PERFORMANCE DATA
APPROXIMATE ICE
PRODUCTION PER 24 HR.
lbs./day kg./day100/38128158111965421008457
APPROXIMATE ELECTRIC
CONSUMPTION
watts100/38
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
gal./day m3/day100/383031.151960.741460.55
FREEZING CYCLE TIME
TOTAL HEAT OF REJECTION FROM CONDENSER17,500 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
TOTAL HEAT OF REJECTION FROM COMPRESSOR2,400 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
CONDENSER VOLUME133 CU. IN (URC-14F)
71
Page 72
7. KM-1400SWH-M
y
SPECIFICATION SHEET
AC SUPPLY VOLTAGE208-230/60/1 (2 Wire)
AMPERAGE9.7 A ( 5 Min. Freeze AT 104°F / WT 80°F)
MINIMUM CIRCUIT AMPACITY15 A
MAXIMUM FUSE SIZE15 A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)1820(3.4)1800(3.2)
POTABLE WATER gal./24HR (gal./100 lbs.)244(18.9)462(33.7)
WATER COOLED CONDENSER2078(161)1108(81)
gal./24HR (gal./100 lbs.)
ICE PRODUCTION PER CYCL 32.5 lbs. (14.7 kg) 1440pcs.
REFRIGERANT CHARGER404A, 2 lb. 2.4 oz. (975g)
PERFORMANCE SHEET
APPROXIMATE ICE
PRODUCTION PER 24 HR.
lbs./day kg./da
APPROXIMATE ELECTRIC
CONSUMPTION
watts100/38
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
TOTAL HEAT OF REJECTION FROM CONDENSER
TOTAL HEAT OF REJECTION FROM COMPRESSOR2,500 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
WATER FLOW FOR CONDENSER138 gal./h [AT 100ºF (38ºC) / WT 90ºF (32ºC)]
PRESSURE DROP OF COOLING WATER LINE less than 10 PSIG
22,800 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
72
Page 73
8. KM-1400SWH3-M
y
SPECIFICATION SHEET
AC SUPPLY VOLTAGE208-230/60/3
AMPERAGE7.1 A ( 5 Min. Freeze AT 104°F / WT 80°F)
MINIMUM CIRCUIT AMPACITY15 A
MAXIMUM FUSE SIZE15 A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)1720(3.3)1700(3.0)
POTABLE WATER gal./24HR (gal./100 lbs.)225(17.9)449(33.4)
WATER COOLED CONDENSER1829(146)1030(77)
gal./24HR (gal./100 lbs.)
ICE PRODUCTION PER CYC 31.9 lbs. (14.5 kg) 1440pcs.
REFRIGERANT CHARGER404A, 2 lb. 2.4 oz. (975g)
PERFORMANCE SHEET
APPROXIMATE ICE
PRODUCTION PER 24 HR.
lbs./day kg./da
APPROXIMATE ELECTRIC
CONSUMPTION
watts100/38
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
TOTAL HEAT OF REJECTION FROM CONDENSER
TOTAL HEAT OF REJECTION FROM COMPRESSOR2,500 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
WATER FLOW FOR CONDENSER136 gal./h [AT 100ºF (38ºC) / WT 90ºF (32ºC)]
PRESSURE DROP OF COOLING WATER LINE less than 10 PSIG
23,500 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
73
Page 74
9. KM-1601SAH
T
T
SPECIFICATION SHEE
AC SUPPLY VOLTAGE208-230/60/1 (3 wire with neutral for 115V)
AMPERAGE15.0 A (5 Min. Freeze AT 104°F/WT 80°F)
MINIMUM CIRCUIT AMPACITY20 A
MAXIMUM FUSE SIZE20 A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)2630(4.70)2450(4.03)
WATER gal./24HR (gal./100 lbs.)228(17.0)709(48.5)
ICE PRODUCTION PER CYCLE31.4 lbs. (14.3 kg) 1440pcs.
REFRIGERANT CHARGER404A, 3 lb. 12.5 oz. (1715g)
PERFORMANCE DATA SHEE
APPROXIMATE ICE
PRODUCTION PER 24 HR.
lbs./day kg./day100/38137962513095941064483
APPROXIMATE ELECTRIC
CONSUMPTION
watts100/38
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
gal./day m3/day100/384111.562230.841850.70
FREEZING CYCLE TIME
AC SUPPLY VOLTAGE208-230/60/3
AMPERAGE12.0 A (5 Min. Freeze AT 104°F/WT 80°F)
MINIMUM CIRCUIT AMPACITY20 A
MAXIMUM FUSE SIZE20 A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)2610(4.65)2370(3.91)
WATER gal./24HR (gal./100 lbs.)249(18.5)708(48.6)
ICE PRODUCTION PER CYCLE32.5 lbs. (14.8 kg) 1440pcs.
REFRIGERANT CHARGER404A, 3 lb. 12.5 oz. (1715g)
PERFORMANCE DATA SHEET
APPROXIMATE ICE
PRODUCTION PER 24 HR.
lbs./day kg./day100/38137962613145961088494
APPROXIMATE ELECTRIC
CONSUMPTION
watts100/38
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
gal./day m3/day100/384221.602430.921980.75
FREEZING CYCLE TIME
AC SUPPLY VOLTAGE208-230/60/1 (3 wire with neutral for 115V)
AMPERAGE13.4 A (5 Min. Freeze AT 104°F/WT 80°F)
MINIMUM CIRCUIT AMPACITY20 A
MAXIMUM FUSE SIZE20 A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)2410(3.8)2300(3.7)
WATER gal./24HR (gal./100 lbs.)373(24.5)698(46.8)
WATER COOLED CONDENSER1493(98)930(62)
gal./24HR (gal./100 lbs.)
ICE PRODUCTION PER CYCLE30.2 lbs. (13.7 kg) 1440 pcs.
REFRIGERANT CHARGER-404A, 3 lbs. 1 oz. ( 1400g )
PERFORMANCE DATA SHEET
APPROXIMATE ICE
PRODUCTION PER 24 HR.
lbs./day kg./day100/38145365914966791303591
APPROXIMATE ELECTRIC
CONSUMPTION
watts100/38
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
gal./day m3/day100/3819087.2219677.44269310.20
FREEZING CYCLE TIME
TOTAL HEAT OF REJECTION FROM CONDENSER23,100 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
TOTAL HEAT OF REJECTION FROM COMPRESSOR3,300 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
WATER FLOW FOR CONDENSER101 gal./h [AT 100ºF (38ºC) / WT 90ºF (32ºC)]
PRESSURE DROP OF COOLING WATER LINEless than 10 PSIG
76
Page 77
12. KM-1601SWH3
SPECIFICATION SHEET
AC SUPPLY VOLTAGE208-230/60/3
AMPERAGE9.0 A (5 Min. Freeze AT 104°F/WT 80°F)
MINIMUM CIRCUIT AMPACITY20 A
MAXIMUM FUSE SIZE20 A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)2390(3.66)2270(3.5)
WATER gal./24HR (gal./100 lbs.)372(23.8)804(51.7)
WATER COOLED CONDENSER1565(100)910(59)
gal./24HR (gal./100 lbs.)
ICE PRODUCTION PER CYCLE30.2 lbs. (13.7 kg) 1440 pcs.
REFRIGERANT CHARGER-404A, 3 lbs. 1 oz. ( 1400g )
PERFORMANCE DATA SHEET
APPROXIMATE ICE
PRODUCTION PER 24 HR.
lbs./day kg./day100/38150768415366971326601
APPROXIMATE ELECTRIC
CONSUMPTION
watts100/38
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
gal./day m3/day100/3820137.6220597.79293011.09
FREEZING CYCLE TIME
TOTAL HEAT OF REJECTION FROM CONDENSER23,500 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
TOTAL HEAT OF REJECTION FROM COMPRESSOR3,200 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
WATER FLOW FOR CONDENSER111 gal./h [AT 100ºF (38ºC) / WT 90ºF (32ºC)]
PRESSURE DROP OF COOLING WATER LINEless than 10 PSIG
77
Page 78
13. KM-1601SRH with URC-21F Auxiliary Codes: R-0, R-1, and some S-1
This data applies to units with an 8 l/min water valve. The 8 l/min water valve is part
number 3U0111-02 and has J248-032 stamped on the side of the valve facing the
rear of the unit.
SPECIFICATION SHEET
AC SUPPLY VOLTAGE208-230/60/1 (3 wire with neutral for 115V)
AMPERAGE12.8 A (5 Min. Freeze AT 104°F/WT 80°F)
MINIMUM CIRCUIT AMPACITY20 A
MAXIMUM FUSE SIZE20 A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)2640(4.3)2440(3.7)
WATER gal./24HR (gal./100 lbs.)255(17.3)503(31.8)
ICE PRODUCTION PER CYCLE29.4 lbs. (13.3 kg) 1440 pcs.
TOTAL REFRIGERANT CHARGER404A, 24 lb. 14.6 oz. (11300g)
REFRIGERANT CHARGE BY UNIT(Icemaker 15 lb. 3.4 oz. Cond. Unit 9 lb. 11.2 oz.)
PERFORMANCE DATA SHEET
APPROXIMATE ICE
PRODUCTION PER 24 HR.
lbs./day kg./day100/38150368214396531203546
APPROXIMATE ELECTRIC
CONSUMPTION
watts100/38
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
gal./day m3/day100/383481.322510.952260.86
FREEZING CYCLE TIME
TOTAL HEAT OF REJECTION FROM CONDENSER24,600 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
TOTAL HEAT OF REJECTION FROM COMPRESSOR3,300 BTU/h [AT 90ºF (32ºC) / W T 70ºF (21ºC)]
CONDENSER VOLUME441 CU. IN (URC-21F)
78
Page 79
14. KM-1601SRH with URC-21F Auxiliary Codes: some S-1 and S-2 and Later
This data applies to units with a 15 l/min or 11 l/min water valve. The 15 l/min water
valve is part number 3U0111-01 and has J248-030 stamped on the side of the valve
facing the rear of the unit. The 11 l/min water valve is either part number 4A1176-04
or 4A5251-04 and has the part number stamped on the side of the valve facing the
front of the unit.
SPECIFICATION SHEET
AC SUPPLY VOLTAGE208-230/60/1 (3 wire with neutral for 115V)
AMPERAGE12.8 A (5 Min. Freeze AT 104°F/WT 80°F)
MINIMUM CIRCUIT AMPACITY20 A
MAXIMUM FUSE SIZE20 A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)2700(4.30)2610(4.00)
WATER gal./24HR (gal./100 lbs.)375(24.9)785(50.2)
ICE PRODUCTION PER CYCLE31.2 lbs. (14.2 kg) 1440 pcs.
TOTAL REFRIGERANT CHARGER404A, 24 lb. 14.6 oz. (11300g)
REFRIGERANT CHARGE BY UNIT(Icemaker 15 lb. 3.4 oz. Cond. Unit 9 lb. 11.2 oz.)
PERFORMANCE DATA SHEET
APPROXIMATE ICE
PRODUCTION PER 24 HR.
lbs./day kg./day100/38151268614826721317597
APPROXIMATE ELECTRIC
CONSUMPTION
watts100/38
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
gal./day m3/day100/385191.973611.372661.01
FREEZING CYCLE TIME
TOTAL HEAT OF REJECTION FROM CONDENSER22,800 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
TOTAL HEAT OF REJECTION FROM COMPRESSOR3,300 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
CONDENSER VOLUME441 CU. IN (URC-21F)
79
Page 80
15. KM-1601SRH with URC-22F Auxiliary Codes: S-2 and Later
T
T
This data applies to units with an 11 l/min water valve. The 11 l/min water valve is
either part number 4A1176-04 or 4A5251-04 and has the part number stamped on
the side of the valve facing the front of the unit.
SPECIFICATION SHEE
AC SUPPLY VOLTAGE208-230/60/1 (3 wire with neutral for 115V)
AMPERAGE12.8 A ( 5 Min. Freeze AT 104°F / WT 80°F)
MINIMUM CIRCUIT AMPACITY20 A
MAXIMUM FUSE SIZE20 A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)2710(4.36)2560(4.01)
WATER gal./24HR (gal./100 lbs.)352(23.6)755(49.3)
ICE PRODUCTION PER CYCLE31.6 lbs. (14.3 kg) 1440 pcs.
TOTAL REFRIGERANT CHARGER404A, 22 lb. 14.8 oz. (10400g)
REFRIGERANT CHARGE BY UNIT(Icemaker 15 lb. 3.4 oz. Cond. Unit 7 lb. 11.5 oz.)
PERFORMANCE DATA SHEE
APPROXIMATE ICE
PRODUCTION PER 24 HR.
lbs./day kg./day100/38147566914626631261572
APPROXIMATE ELECTRIC
CONSUMPTION
watts100/38
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
gal./day m3/day100/384931.873381.282410.91
FREEZING CYCLE TIME
TOTAL HEAT OF REJECTION FROM CONDENSER21,000 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
TOTAL HEAT OF REJECTION FROM COMPRESSOR2,800 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
CONDENSER VOLUME214 CU. IN (URC-22F)
80
Page 81
16. KM-1601SRH3 with URC-21F Auxiliary Codes: R-0, R-1, and some S-1
T
T
This data applies to units with an 8 l/min water valve. The 8 l/min water valve is part
number 3U0111-02 and has J248-032 stamped on the side of the valve facing the
rear of the unit.
SPECIFICATION SHEE
AC SUPPLY VOLTAGE208-230/60/3
AMPERAGE7.9 A (5 Min. Freeze AT 104°F/WT 80°F)
MINIMUM CIRCUIT AMPACITY20 A
MAXIMUM FUSE SIZE20 A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)2580(4.3)2450(3.7)
WATER gal./24HR (gal./100 lbs.)261(17.9)504(31.6)
ICE PRODUCTION PER CYCLE29.4 lbs. (13.3 kg) 1440 pcs.
TOTAL REFRIGERANT CHARGER404A, 24 lb. 14.6 oz. (11300g)
REFRIGERANT CHARGE BY UNIT(Icemaker 15 lb. 3.4 oz. Cond. Unit 9 lb. 11.2 oz.)
PERFORMANCE DATA SHEE
APPROXIMATE ICE
PRODUCTION PER 24 HR.
lbs./day kg./day100/38151068514266471184537
APPROXIMATE ELECTRIC
CONSUMPTION
watts100/38
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
gal./day m3/day100/383511.332560.972260.86
FREEZING CYCLE TIME
TOTAL HEAT OF REJECTION FROM CONDENSER24,300 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
TOTAL HEAT OF REJECTION FROM COMPRESSOR3,200 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
CONDENSER VOLUME441 CU. IN (URC-21F)
81
Page 82
17. KM-1601SRH3 with URC-21F Auxiliary Codes: some S-1 and S-2 and Later
This data applies to units with a 15 l/min or 11 l/min water valve. The 15 l/min water
valve is part number 3U0111-01 and has J248-030 stamped on the side of the valve
facing the rear of the unit. The 11 l/min water valve is either part number 4A1176-04
or 4A5251-04 and has the part number stamped on the side of the valve facing the
front of the unit.
SPECIFICATION SHEET
AC SUPPLY VOLTAGE208-230/60/3
AMPERAGE7.9 A ( 5 Min. Freeze AT 104°F / WT 80°F)
MINIMUM CIRCUIT AMPACITY20 A
MAXIMUM FUSE SIZE20 A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)2960(4.70)2580(3.90)
WATER gal./24HR (gal./100 lbs.)363(24.0)781(49.3)
ICE PRODUCTION PER CYCLE31.2 lbs. (14.2 kg) 1440 pcs.
TOTAL REFRIGERANT CHARGER404A, 24 lb. 14.6 oz. (11300g)
REFRIGERANT CHARGE BY UNIT(Icemaker 15 lb. 3.4 oz. Cond. Unit 9 lb. 11.2 oz.)
PERFORMANCE DATA SHEET
APPROXIMATE ICE
PRODUCTION PER 24 HR.
lbs./day kg./day100/38152068914826721273577
APPROXIMATE ELECTRIC
CONSUMPTION
watts100/38
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
gal./day m3/day100/385141.953521.332761.05
FREEZING CYCLE TIME
TOTAL HEAT OF REJECTION FROM CONDENSER22,000 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
TOTAL HEAT OF REJECTION FROM COMPRESSOR3,200 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
CONDENSER VOLUME441 CU. IN (URC-21F)
82
Page 83
18. KM-1601SRH3 with URC-22F Auxiliary Codes: S-2 and Later
T
T
This data applies to units with an 11 l/min water valve. The 11 l/min water valve is
either part number 4A1176-04 or 4A5251-04 and has the part number stamped on
the side of the valve facing the front of the unit.
SPECIFICATION SHEE
AC SUPPLY VOLTAGE208-230/60/3
AMPERAGE7.9 A (5 Min. Freeze AT 104°F/WT 80°F)
MINIMUM CIRCUIT AMPACITY20 A
MAXIMUM FUSE SIZE20 A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)2780(4.46)2490(3.90)
WATER gal./24HR (gal./100 lbs.)348(23.2)704(46.0)
ICE PRODUCTION PER CYCLE32.1 lbs. (14.6 kg) 1440 pcs.
TOTAL REFRIGERANT CHARGER404A, 22 lb. 14.8 oz. (10400g)
REFRIGERANT CHARGE BY UNIT(Icemaker 15 lb. 3.4 oz. Cond. Unit 7 lb. 11.5 oz.)
PERFORMANCE DATA SHEE
APPROXIMATE ICE
PRODUCTION PER 24 HR.
lbs./day kg./day100/38146866614656651231558
APPROXIMATE ELECTRIC
CONSUMPTION
watts100/38
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
gal./day m3/day100/384741.793371.272590.98
FREEZING CYCLE TIME
TOTAL HEAT OF REJECTION FROM CONDENSER26,400 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
TOTAL HEAT OF REJECTION FROM COMPRESSOR3,500 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
CONDENSER VOLUME214 CU. IN (URC-22F)
83
Page 84
19. KM-1900SAH
SPECIFICATION SHEET
AC SUPPLY VOLTAGE208-230/60/1 (3 wire with neutral 115V)
AMPERAGE14.4 A (5 Min. Freeze AT 104°F / WT 80°F)
MINIMUM CIRCUIT AMPACITY30 A
MAXIMUM FUSE SIZE30 A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)2670(4.1)2480(3.2)
WATER gal./24HR (gal./100 lbs.)293(18.8)579(31.0)
ICE PRODUCTION PER CYCLE45.3 lbs. (20.5 kg) 2160pcs.
REFRIGERANT CHARGER404A, 4 lb. 10.1 oz. (2100g)
PERFORMANCE DATA SHEET
APPROXIMATE ICE
PRODUCTION PER 24 HR.
lbs./day kg./day100/38174479115266921278580
APPROXIMATE ELECTRIC
CONSUMPTION
watts100/38
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
gal./day m3/day100/383961.502861.082320.88
FREEZING CYCLE TIME
AC SUPPLY VOLTAGE208-230/60/3
AMPERAGE8.59 A (5 Min. Freeze AT 104°F/WT 80°F)
MINIMUM CIRCUIT AMPACITY20 A
MAXIMUM FUSE SIZE20 A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)2610(4.1)2510(3.2)
WATER gal./24HR (gal./100 lbs.)260(17.0)548(29.5)
ICE PRODUCTION PER CYCLE45.5 lbs. (20.6 kg) 2160pcs.
REFRIGERANT CHARGER404A, 4 lb. 10.1 oz. (2100g)
PERFORMANCE DATA SHEET
APPROXIMATE ICE
PRODUCTION PER 24 HR.
lbs./day kg./day100/38173878814996801277579
APPROXIMATE ELECTRIC
CONSUMPTION
watts100/38
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
gal./day m3/day100/383681.392550.972200.83
FREEZING CYCLE TIME
AC SUPPLY VOLTAGE208-230/60/1 (3 wire with neutral 115V)
AMPERAGE12.5 A (5 Min. Freeze AT 104°F/WT 80°F)
MINIMUM CIRCUIT AMPACITY30 A
MAXIMUM FUSE SIZE30 A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)2390(3.1)2330(3.0)
POTABLE WATER gal./24HR (gal./100 lbs.)348(18.8)628(33.5)
WATER COOLED CONDENSER1832(99)1022(55)
gal./24HR (gal./100 lbs.)
ICE PRODUCTION PER CYCLE47 lbs. (21.3 kg) 2160pcs.
REFRIGERANT CHARGER404A, 3 lb. 1.4 oz. (1400g)
PERFORMANCE DATA SHEET
APPROXIMATE ICE
PRODUCTION PER 24 HR.
lbs./day kg./day100/38180081618098201511685
APPROXIMATE ELECTRIC
CONSUMPTION
watts100/38
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
gal./day m3/day100/3821037.9622778.62298311.29
FREEZING CYCLE TIME
TOTAL HEAT OF REJECTION FROM CONDENSER
TOTAL HEAT OF REJECTION FROM COMPRESSOR3,200 BTU/h [AT 90ºF (32ºC) / W T 70ºF (21ºC)]
WATER FLOW FOR CONDENSER113 gal./h [AT 100ºF (38ºC) / WT 90ºF (32ºC)]
PRESSURE DROP OF COOLING WATER LINE less than 10 PSIG
26,800 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
86
Page 87
22. KM-1900SWH3
SPECIFICATION SHEET
AC SUPPLY VOLTAGE208-230/60/3
AMPERAGE8.4 A (5 Min. Freeze AT 104°F/WT 80°F)
MINIMUM CIRCUIT AMPACITY20 A
MAXIMUM FUSE SIZE20 A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)2490(3.3)2410(3.2)
POTABLE WATER gal./24HR (gal./100 lbs.)341(18.8)584(32.0)
WATER COOLED CONDENSER1796(99)982(54)
gal./24HR (gal./100 lbs.)
ICE PRODUCTION PER CYCLE45.4 lbs. (20.6 kg) 2160pcs.
REFRIGERANT CHARGER404A, 3 lb. 1.4 oz. (1400g)
PERFORMANCE DATA SHEET
APPROXIMATE ICE
PRODUCTION PER 24 HR.
lbs./day kg./day100/38175479617748051484673
APPROXIMATE ELECTRIC
CONSUMPTION
watts100/38
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
gal./day m3/day100/3820637.8122498.51305411.56
FREEZING CYCLE TIME
TOTAL HEAT OF REJECTION FROM CONDENSER
TOTAL HEAT OF REJECTION FROM COMPRESSOR3,200 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
WATER FLOW FOR CONDENSER117 gal./h [AT 100ºF (38ºC) / WT 90ºF (32ºC)]
PRESSURE DROP OF COOLING WATER LINE less than 10 PSIG
27,100 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
87
Page 88
23. KM-1900SRH with URC-21F
SPECIFICATION SHEET
AC SUPPLY VOLTAGE208-230/60/1 (3 wire with neutral 115V)
AMPERAGE14.9 A (5 Min. Freeze AT 104°F/WT 80°F)
MINIMUM CIRCUIT AMPACITY30 A
MAXIMUM FUSE SIZE30 A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)2630(3.9)2460(3.1)
WATER gal./24HR (gal./100 lbs.)323(20.0)585(30.5)
ICE PRODUCTION PER CYCLE46.3 lbs. (21 kg) 2160pcs.
TOTAL REFRIGERANT CHARGER404A, 23 lb. 7.7 oz. (10650g)
REFRIGERANT CHARGE BY UNIT(Icemaker 13 lbs. 12.5 oz. Cond. Unit 9 lbs. 11.2 oz.)
PERFORMANCE DATA SHEET
APPROXIMATE ICE
PRODUCTION PER 24 HR.
lbs./day kg./day100/38178681015777151299589
APPROXIMATE ELECTRIC
CONSUMPTION
watts100/38
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
gal./day m3/day100/384191.583171.202741.04
FREEZING CYCLE TIME
TOTAL HEAT OF REJECTION FROM CONDENSER
TOTAL HEAT OF REJECTION FROM COMPRESSOR
CONDENSER VOLUME441 CU. IN (URC-21F)
27,400 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
3,300 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
88
Page 89
24. KM-1900SRH with URC-22F
SPECIFICATION SHEET
AC SUPPLY VOLTAGE208-230/60/1 (3 wire with neutral 115V)
AMPERAGE14.9 A (5 Min. Freeze AT 104°F/WT 80°F)
MINIMUM CIRCUIT AMPACITY30 A
MAXIMUM FUSE SIZE30 A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)2790(4.09)2500(3.23)
WATER gal./24HR (gal./100 lbs.)328(20.0)609(32.8)
ICE PRODUCTION PER CYCLE46 lbs. (20.9 kg) 2160pcs.
TOTAL REFRIGERANT CHARGER404A, 21 lb. 7.9 oz. (9750g)
REFRIGERANT CHARGE BY UNIT(Icemaker 13 lbs. 12.5 oz. Cond. Unit 7 lbs. 11.5 oz.)
PERFORMANCE DATA SHEET
APPROXIMATE ICE
PRODUCTION PER 24 HR.
lbs./day kg./day100/38173878915977241289585
APPROXIMATE ELECTRIC
CONSUMPTION
watts100/38
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
gal./day m3/day100/384281.623201.212620.99
FREEZING CYCLE TIME
TOTAL HEAT OF REJECTION FROM CONDENSER
TOTAL HEAT OF REJECTION FROM COMPRESSOR
CONDENSER VOLUME214 CU. IN (URC-22F)
26,500 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
3,200 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
89
Page 90
25. KM-1900SRH3 with URC-21F
SPECIFICATION SHEET
AC SUPPLY VOLTAGE208-230/60/3
AMPERAGE11.0 A ( 5 Min. Freeze AT 104°F / WT 80°F)
MINIMUM CIRCUIT AMPACITY20 A
MAXIMUM FUSE SIZE20 A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)2840(4.1)2680(3.3)
WATER gal./24HR (gal./100 lbs.)332(20.0)590(30.0)
ICE PRODUCTION PER CYCLE46.5 lbs. (21.1 kg) 2160pcs.
TOTAL REFRIGERANT CHARGER404A, 23 lb. 7.7 oz. (10650g)
REFRIGERANT CHARGE BY UNIT(Icemaker 13 lbs. 12.5 oz. Cond. Unit 9 lbs. 11.2 oz.)
PERFORMANCE DATA SHEET
APPROXIMATE ICE
PRODUCTION PER 24 HR.
lbs./day kg./day100/38182782916177331304591
APPROXIMATE ELECTRIC
CONSUMPTION
watts100/38
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
gal./day m3/day100/384251.613251.232781.05
FREEZING CYCLE TIME
TOTAL HEAT OF REJECTION FROM CONDENSER
TOTAL HEAT OF REJECTION FROM COMPRESSOR
CONDENSER VOLUME441 CU. IN (URC-21F)
26,100 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
3,200 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
90
Page 91
26. KM-1900SRH3 with URC-22F
SPECIFICATION SHEET
AC SUPPLY VOLTAGE208-230/60/3
AMPERAGE11.0 A (5 Min. Freeze AT 104°F/WT 80°F)
MINIMUM CIRCUIT AMPACITY20 A
MAXIMUM FUSE SIZE20 A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)2780(4.04)2640(3.33)
WATER gal./24HR (gal./100 lbs.)345(20.9)634(33.3)
ICE PRODUCTION PER CYCLE46.8 lbs. (21.2 kg) 2160pcs.
TOTAL REFRIGERANT CHARGER404A, 21 lb. 7.9 oz. (9750g)
REFRIGERANT CHARGE BY UNIT(Icemaker 13 lbs. 12.5 oz. Cond. Unit 7 lbs. 11.5 oz.)
PERFORMANCE DATA SHEET
APPROXIMATE ICE
PRODUCTION PER 24 HR.
lbs./day kg./day100/38178280816107301323600
APPROXIMATE ELECTRIC
CONSUMPTION
watts100/38
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
gal./day m3/day100/384481.703371.282801.06
FREEZING CYCLE TIME
TOTAL HEAT OF REJECTION FROM CONDENSER
TOTAL HEAT OF REJECTION FROM COMPRESSOR
CONDENSER VOLUME214 CU. IN (URC-22F)
25,700 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
3,100 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
91
Page 92
27. KM-2100SWH3
SPECIFICATION SHEET
AC SUPPLY VOLTAGE208-230/60/3
AMPERAGE10.5 A (5 Min. Freeze AT 104°F/WT 80°F)
MINIMUM CIRCUIT AMPACITY20 A
MAXIMUM FUSE SIZE20 A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)2860(3.35)2740(3.14)
POTABLE WATER gal./24HR (gal./100 lbs.)410(20.0)673(32.1)
WATER COOLED CONDENSER1948(95)1121(54)
gal./24HR (gal./100 lbs.)
ICE PRODUCTION PER CYCLE46.8 lbs. (21.2 kg) 2160pcs.
REFRIGERANT CHARGER404A, 3 lb. 6.7 oz. (1550g)
PERFORMANCE DATA SHEET
APPROXIMATE ICE
PRODUCTION PER 24 HR.
lbs./day kg./day100/38200591020039081662754
APPROXIMATE ELECTRIC
CONSUMPTION
watts100/38
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
gal./day m3/day100/3822258.4224249.18290511.00
FREEZING CYCLE TIME
TOTAL HEAT OF REJECTION FROM CONDENSER
TOTAL HEAT OF REJECTION FROM COMPRESSOR3,800 BTU/h [AT 90ºF (32ºC) / W T 70ºF (21ºC)]
WATER FLOW FOR CONDENSER109 gal./h [AT 100ºF (38ºC) / WT 90ºF (32ºC)]
PRESSURE DROP OF COOLING WATER LINE less than 10 PSIG
31,100 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
92
Page 93
28. KM-2100SRH3 with URC-22F
SPECIFICATION SHEET
AC SUPPLY VOLTAGE208-230/60/3
AMPERAGE12.5 A (5 Min. Freeze AT 104°F/WT 80°F)
MINIMUM CIRCUIT AMPACITY20 A
MAXIMUM FUSE SIZE20 A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)3210(4.26)2900(3.42)
WATER gal./24HR (gal./100 lbs.)382(21.1)687(33.8)
ICE PRODUCTION PER CYCLE46.8 lbs. (21.2 kg) 2160pcs.
TOTAL REFRIGERANT CHARGER404A, 16 lb. 1.5 oz. (7300g)
REFRIGERANT CHARGE BY UNIT(Icemaker 8 lbs. 6 oz. Cond. Unit 7 lbs. 11.5 oz.)
PERFORMANCE DATA SHEET
APPROXIMATE ICE
PRODUCTION PER 24 HR.
lbs./day kg./day100/38190886617648001432650
APPROXIMATE ELECTRIC
CONSUMPTION
watts100/38
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
gal./day m3/day100/384901.853721.413021.14
FREEZING CYCLE TIME
TOTAL HEAT OF REJECTION FROM CONDENSER
TOTAL HEAT OF REJECTION FROM COMPRESSOR
CONDENSER VOLUME214 CU. IN (URC-22F)
30,400 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
3,800 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
93
Page 94
29. KM-2500SWH3
SPECIFICATION SHEET
AC SUPPLY VOLTAGE208-230/60/3
AMPERAGE14.2 A (5 Min. Freeze AT 104°F/WT 80°F)
MINIMUM CIRCUIT AMPACITY30 A
MAXIMUM FUSE SIZE30 A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)3720(3.78)3510(3.5)
WATER gal./24HR (gal./100 lbs.)459(19.4)744(30.9)
WATER COOLED CONDENSER2389(101)1430(59)
gal./24HR (gal./100 lbs.)
ICE PRODUCTION PER CYCLE46.3 lbs. (21 kg) 2160pcs.
REFRIGERANT CHARGER404A, 4 lb. 11.5 oz. (2140g)
PERFORMANCE DATA SHEET
APPROXIMATE ICE
PRODUCTION PER 24 HR.
lbs./day kg./day100/3823271055232310542018915
APPROXIMATE ELECTRIC
CONSUMPTION
watts100/38
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
gal./day m3/day100/38268510.16292411.07347313.15
FREEZING CYCLE TIME
TOTAL HEAT OF REJECTION FROM CONDENSER
TOTAL HEAT OF REJECTION FROM COMPRESSOR4,900 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
WATER FLOW FOR CONDENSER130 gal./h [AT 100ºF (38ºC) / WT 90ºF (32ºC)]
PRESSURE DROP OF COOLING WATER LINE less than 10 PSIG
35,500 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
94
Page 95
30. KM-2500SRH3 with URC-23F
SPECIFICATION SHEET
AC SUPPLY VOLTAGE208-230/60/3
AMPERAGE17.7 A (5 Min. Freeze AT 104°F/WT 80°F)
MINIMUM CIRCUIT AMPACITY30 A
MAXIMUM FUSE SIZE30 A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)4190(4.5)3780(3.7)
WATER gal./24HR (gal./100 lbs.)416(18.6)791(32.6)
ICE PRODUCTION PER CYCLE46.1 lbs. (20.9 kg) 2160pcs.
TOTAL REFRIGERANT CHARGER404A, 24 lb. 7.5 oz. (11100g)
REFRIGERANT CHARGE BY UNIT(Icemaker 14 lbs. 12.3 oz. Cond. Unit 9 lbs. 11.2 oz.)
PERFORMANCE DATA SHEET
APPROXIMATE ICE
PRODUCTION PER 24 HR.
lbs./day kg./day100/382301104421869921837833
APPROXIMATE ELECTRIC
CONSUMPTION
watts100/38
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
gal./day m3/day100/385512.094061.543341.27
FREEZING CYCLE TIME
TOTAL HEAT OF REJECTION FROM CONDENSER
TOTAL HEAT OF REJECTION FROM COMPRESSOR
CONDENSER VOLUME441 CU. IN (URC-23F)
40,600 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
5,600 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
95
Page 96
31. KMH-2000SWH
SPECIFICATION SHEET
AC SUPPLY VOLTAGE208-230/60/1 (3 wire with neutral 115V)
AMPERAGE12.1 A (5 Min. Freeze AT 104°F/WT 80°F)
MINIMUM CIRCUIT AMPACITY30 A
MAXIMUM FUSE SIZE30 A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)2420(3.3)2410(3.2)
POTABLE WATER gal./24HR (gal./100 lbs.)308(17.5)535(29.4)
WATER COOLED CONDENSER1484(84)929(51)
gal./24HR (gal./100 lbs.)
ICE PRODUCTION PER CYCLE45.4 lbs. (20.6 kg) 2160pcs.
REFRIGERANT CHARGER404A, 3 lb. 1.4 oz. (1400g)
PERFORMANCE DATA SHEET
APPROXIMATE ICE
PRODUCTION PER 24 HR.
lbs./day kg./day100/38175379517287841497679
APPROXIMATE ELECTRIC
CONSUMPTION
watts100/38
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
gal./day m3/day100/3818176.8819067.22273110.34
FREEZING CYCLE TIME
TOTAL HEAT OF REJECTION FROM CONDENSER
TOTAL HEAT OF REJECTION FROM COMPRESSOR3,300 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
WATER FLOW FOR CONDENSER103 gal./h [AT 100ºF (38ºC) / WT 90ºF (32ºC)]
PRESSURE DROP OF COOLING WATER LINE less than 10 PSIG
28,000 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
96
Page 97
32. KMH-2000SWH3
SPECIFICATION SHEET
AC SUPPLY VOLTAGE208-230/60/3
AMPERAGE7.7 A (5 Min. Freeze AT 104°F/WT 80°F)
MINIMUM CIRCUIT AMPACITY20 A
MAXIMUM FUSE SIZE20 A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)2330(3.2)2280(2.9)
POTABLE WATER gal./24HR (gal./100 lbs.)296(17.1)540(29.0)
WATER COOLED CONDENSER1369(79)1001(54)
gal./24HR (gal./100 lbs.)
ICE PRODUCTION PER CYCLE48.1 lbs. (21.8 kg) 2160pcs.
REFRIGERANT CHARGER404A, 3 lb. 1.4 oz. (1400g)
PERFORMANCE DATA SHEET
APPROXIMATE ICE
PRODUCTION PER 24 HR.
lbs./day kg./day100/38176780116907671409639
APPROXIMATE ELECTRIC
CONSUMPTION
watts100/38
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
gal./day m3/day100/3818226.9018186.88291411.03
FREEZING CYCLE TIME
TOTAL HEAT OF REJECTION FROM CONDENSER
TOTAL HEAT OF REJECTION FROM COMPRESSOR3,200 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
WATER FLOW FOR CONDENSER111 gal./h [AT 100ºF (38ºC) / WT 90ºF (32ºC)]
PRESSURE DROP OF COOLING WATER LINE less than 10 PSIG
26,600 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
97
Page 98
33. KMH-2000SRH with URC-22F
SPECIFICATION SHEET
AC SUPPLY VOLTAGE208-230/60/1 (3 wire with neutral 115V)
AMPERAGE14.9 A (5 Min. Freeze AT 104°F/WT 80°F)
MINIMUM CIRCUIT AMPACITY30 A
MAXIMUM FUSE SIZE30 A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)2680(3.8)2570(3.2)
WATER gal./24HR (gal./100 lbs.)307(18.1)570(29.3)
ICE PRODUCTION PER CYCLE47.7 lbs. (21.6 kg) 2160pcs.
TOTAL REFRIGERANT CHARGER404A, 16 lb. 1.5 oz. (7300g)
REFRIGERANT CHARGE BY UNIT(Icemaker 8 lbs. 6 oz. Cond. Unit 7 lbs. 11.5 oz.)
PERFORMANCE DATA SHEET
APPROXIMATE ICE
PRODUCTION PER 24 HR.
lbs./day kg./day100/38183483216607531418643
APPROXIMATE ELECTRIC
CONSUMPTION
watts100/38
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
gal./day m3/day100/384021.523001.142540.96
FREEZING CYCLE TIME
TOTAL HEAT OF REJECTION FROM CONDENSER
TOTAL HEAT OF REJECTION FROM COMPRESSOR
CONDENSER VOLUME214 CU. IN (URC-22F)
27,600 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
3,300 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
98
Page 99
34. KMH-2000SRH3 with URC-22F
SPECIFICATION SHEET
AC SUPPLY VOLTAGE208-230/60/3
AMPERAGE9.9 A (5 Min. Freeze AT 104°F/WT 80°F)
MINIMUM CIRCUIT AMPACITY20 A
MAXIMUM FUSE SIZE20 A
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)2600(3.7)2430(3.0)
WATER gal./24HR (gal./100 lbs.)281(16.8)507(26.3)
ICE PRODUCTION PER CYCLE46.9 lbs. (21.3 kg) 2160pcs.
TOTAL REFRIGERANT CHARGER404A, 16 lb. 1.5 oz. (7300g)
REFRIGERANT CHARGE BY UNIT(Icemaker 8 lbs. 6 oz. Cond. Unit 7 lbs. 11.5 oz.)
PERFORMANCE DATA SHEET
APPROXIMATE ICE
PRODUCTION PER 24 HR.
lbs./day kg./day100/38181682416407441388630
APPROXIMATE ELECTRIC
CONSUMPTION
watts100/38
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
gal./day m3/day100/383641.382771.052420.91
FREEZING CYCLE TIME