Hoshizaki DKM-500BAJ, DKM-500BWJ User Manual

Service Manual
Crescent Cube Icemaker / Dispenser
Models DKM-500BAJ DKM-500BWJ
hoshizakiamerica.com
Number: 73212 Issued: 6-16-2017
WARNING
Only qualied service technicians should install and service the appliance. To obtain the name and phone number of your local Hoshizaki Certied Service Representative, visit www.hoshizaki.com. No service should be undertaken until the technician has thoroughly read this Service Manual. Failure to service and maintain the appliance in accordance with this manual will adversely affect safety, performance, component life, and warranty coverage. Proper installation is the responsibility of the installer. Product failure or property damage due to improper installation is not covered under warranty.
Hoshizaki provides this manual primarily to assist qualied service technicians in the service of the appliance.
Should the reader have any questions or concerns which have not been satisfactorily addressed, please call, send an e-mail message, or write to the Hoshizaki Technical Support Department for assistance.
Phone: 1-800-233-1940; (770) 487-2331 Fax: 1-800-843-1056; (770) 487-3360
E-mail: techsupport@hoshizaki.com
618 Highway 74 South Peachtree City, GA 30269 Attn: Hoshizaki Technical Support Department
Web Site: www.hoshizaki.com
NOTE: To expedite assistance, all correspondence/communication MUST include the
following information:
• Model Number
• Serial Number
• Complete and detailed explanation of the problem.
IMPORTANT
This manual should be read carefully before the appliance is serviced. Read the warnings and guidelines contained in this manual carefully as they provide essential information for the continued safe use, service, and maintenance of the appliance. Retain this manual for any further reference that may be necessary.
CONTENTS
Important Safety Information ................................................................................................. 5
I. Construction and Water/Refrigeration Circuit Diagram ....................................................... 7
A. Construction .................................................................................................................. 7
1. Air-Cooled Models (BAJ) .......................................................................................... 7
2. Water-Cooled Models (BWJ) ................................................................................... 8
B. Water/Refrigeration Circuit Diagram .............................................................................. 9
1. Air-Cooled Models (BAJ) .......................................................................................... 9
2. Water-Cooled Models (BWJ) ................................................................................. 10
II. Sequence of Operation and Service Diagnosis ................................................................11
A. Sequence of Operation Flow Chart .............................................................................. 11
B. Service Diagnosis ....................................................................................................... 12
C. Control Board Check ................................................................................................... 19
D. Bin Control Check ....................................................................................................... 20
E. Switches ...................................................................................................................... 22
1. Control Switch ........................................................................................................ 22
2. Service Switch ....................................................................................................... 22
F. Float Switch Check and Cleaning ................................................................................ 23
1. Float Switch Check ................................................................................................ 23
2. Float Switch Cleaning ............................................................................................ 24
G. Thermistor Check ........................................................................................................ 25
H. Diagnostic Tables ........................................................................................................ 26
III. Controls and Adjustments ............................................................................................... 30
A. Control Board Layout .................................................................................................. 31
B. LED Lights and Audible Alarm Safeties ....................................................................... 32
C. Settings and Adjustments ............................................................................................ 33
1. Default Dip Switch Settings .................................................................................... 33
2. Harvest Timer (S4 dip switch 1 & 2) ...................................................................... 33
3. Pump-Out Timer (S4 dip switch 3 & 4) .................................................................. 34
4. Pump-Out Frequency Control (S4 dip switch 5) ..................................................... 34
5. Harvest Pump Time (S4 dip switch 6) .................................................................... 35
6. Harvest Pump Timer Operation (S4 dip switch 7) .................................................. 35
7. Factory Use (S4 dip switch 8)................................................................................. 36
8. Freeze Timer (S4 dip switch 9 & 10) ...................................................................... 36
9. Float Switch Selector (S5 dip switch 1) ................................................................. 36
10. Rell Counter (S5 dip switch 2 and 3) .................................................................. 36
11. Minimum Harvest Time (S5 dip switch 4) ............................................................. 37
12. Anti-Slush (S5 dip switch 5) ................................................................................. 37
IV. Refrigeration Circuit and Component Service Information.............................................. 38
A. Refrigeration Circuit Service Information .................................................................... 38
B. Component Service Information .................................................................................. 41
C. Water Regulating Valve Adjustment (water-cooled model) .......................................... 41
V. Maintenance .................................................................................................................... 42
VI. Preparing the Appliance for Periods of Non-Use ............................................................ 43
VII. Disposal ......................................................................................................................... 45
VIII. Technical Information .................................................................................................... 46
A. Specication and Performance Data Sheets ............................................................... 46
1. DKM-500BAJ ......................................................................................................... 46
2. DKM-500BWJ ........................................................................................................ 47
B. Wiring Diagram ........................................................................................................... 48

Important Safety Information

Throughout this manual, notices appear to bring your attention to situations which could result in death, serious injury, damage to the appliance, or damage to property.
WARNING Indicates a hazardous situation which could result in death or
serious injury.
NOTICE Indicates a situation which could result in damage to the
appliance or property.
IMPORTANT Indicates important information about the use and care of the
appliance.
WARNING
The appliance should be destined only to the use for which it has been expressly conceived. Any other use should be considered improper and therefore dangerous. The manufacturer cannot be held responsible for injury or damage resulting from improper, incorrect, and unreasonable use. Failure to service and maintain the appliance in accordance with this manual will adversely affect safety, performance, component life, and warranty coverage and may result in costly water damage.
To reduce the risk of death, electric shock, serious injury, or re, follow basic precautions including the following:
• Only qualied service technicians should install and service this appliance.
• The appliance must be installed in accordance with applicable national, state, and local codes and regulations.
• The appliance requires an independent power supply of proper capacity. See the nameplate for electrical specications. Failure to use an independent power supply of proper capacity can result in a tripped breaker, blown fuse, damage to existing wiring, or component failure. This could lead to heat generation or re.
THE APPLIANCE MUST BE GROUNDED: The appliance is equipped with a NEMA5-20 three-prong grounding plug to reduce the risk of potential shock hazards. It must be plugged into a properly grounded, independent 3-prong wall outlet. If the outlet is a 2-prong outlet, it is your personal responsibility to have a qualied electrician replace it with a properly grounded, independent 3-prong wall outlet. Do not remove the ground prong from the power cord and do not use an adapter plug. Failure to properly ground the appliance could result in death or serious injury.
• Do not use an extension cord.
• To reduce the risk of electric shock, do not touch the control switch, service switch, or plug with damp hands. Make sure the control switch is in the "OFF" position before plugging in or unplugging the appliance.
• Do not use an appliance with a damaged power cord. The power cord should not be altered, jerked, bundled, weighed down, pinched, or tangled. Such actions could result in electric shock or re. To unplug the appliance, be sure to pull the plug, not the cord, and do not jerk the cord.
WARNING, continued
• Do not make any alterations to the appliance. Alterations could result in electric shock, injury, re, or damage to the appliance.
• The appliance is not intended for use by persons (including children) with reduced physical, sensory, or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
• Children should be properly supervised around the appliance.
• Do not climb, stand, or hang on the appliance or allow children or animals to do so. Serious injury could occur or the appliance could be damaged.
• Do not use combustible spray or place volatile or ammable substances near the appliance. They might catch re.
• Keep the area around the appliance clean. Dirt, dust, or insects in the appliance could cause harm to individuals or damage to the appliance.
NOTICE
• Follow the water supply, drain connection, and maintenance instructions carefully to reduce the risk of costly water damage.
• In areas where water damage is a concern, install in a contained area with a oor drain.
• Install the appliance in a location that stays above freezing. Normal operating ambient temperature must be within 45°F to 100°F (7°C to 38°C). If the normal operating ambient temperature is above 90°F (32°C), the compressor insulation cover must be removed.
• Do not leave the appliance on during extended periods of non-use, extended absences, or in sub-freezing temperatures. To properly prepare the appliance for these occasions, follow the instructions in "IV. Preparing the Appliance for Periods of Non-Use."
• Do not place objects on top of the appliance.
• The storage bin is for ice use only. Do not store anything else in the storage bin.

I. Construction and Water/Refrigeration Circuit Diagram

A. Construction

1. Air-Cooled Models (BAJ)

Mechanical Bin Control
Inlet Water Valve
Expansion Valve
Water Pump
Float Switch
Bin Cover
Wash Valve
Hot Gas Valve
Spray Tubes
Drain Valve
Water Supply Inlet
Ice Cube Guide
Bin
Agitator
Shutter
Chain
Dispense Switch
Front Panel
Condenser
Dispense Switch Connector
Condenser Fan Motor
Drain Pan
Solenoid Assembly
Spout Extension
Gear Motor Assembly
Drier
Compressor
Strainer
Control Switches
Control Box

2. Water-Cooled Models (BWJ)

Bin Cover
Mechanical Bin Control
Wash Valve
Hot Gas Valve
Spray Tubes
Inlet Water Valve
Expansion Valve
Dispense Switch
Water Pump
Float Switch
Drain Valve
Strainer
Water Supply Inlet
Ice Cube Guide
Bin
Agitator
Shutter
Chain
Solenoid Assembly
Spout Extension
Condenser
Line Valve
Front Panel
Drier
Dispense Switch Connector
Drain Pan
Control Switches
Gear Motor Assembly
Water Regulator
Compressor
Control Box

B. Water/Refrigeration Circuit Diagram

1. Air-Cooled Models (BAJ)

2. Water-Cooled Models (BWJ)

10

II. Sequence of Operation and Service Diagnosis

A. Sequence of Operation Flow Chart

10th cycle
2 sec., then reverses
for 10/20 sec.
4. Pump-Out Cycle
• Pump motor stops for
(S4 dip switch 3 & 4)
FS opens or
freeze timer
FS in control
terminates
• Factory set for every
Comp continues
FMR continues
HGV energized
PM de-energizes for 2 sec.,
Anti-Slush
reaches 36°F (2.2°C)
then energizes for 10/20 sec.
FM de-energized
(5.8 kΩ).
PM de-energized for
10 sec.
LLV de-energized
3. Ice Level Lowered
Icemaker starts at
"1. 1-Minute Fill Cycle."
To 1 above
MBC closed
(MBC actuator paddle disengaged)
Green "BC CLOSED" LED on
Yellow "BC OPEN" LED off
3. Freeze Cycle
2. Harvest Cycle
• Minimum freeze time: 5 min.
• Maximum freeze time: freeze timer
• Maximum inlet water valve time: 6 min. or the length of
harvest minus 50 sec. (S4 dip switch 7), whichever is shorter.
setting (S4 dip switch 9 & 10)
• Maximum harvest time: 20 min.
5-min. minimum
freeze timer in
Harvest Pump
1 to 3-min. harvest timer in
control (S4 dip switch 1 & 2)
Thermistor in
control
control
Timer
FS closed
50 sec.
FS closed
All components
de-energized.
2. Icemaker Off
Comp continues
FMR continues
FM energized
LLV energized
PM energized
HGV de-energized
Yellow "BC OPEN" LED continues. All
FS check
FS open
PM energized
WV de-energized
Thermistor temperature reaches
48°F (9°C) (3.9 kΩ or less). Harvest
timer starts (1 to 3 min.).
Comp energized
FM energized
HGV energized
WV energized
components de-energized.
Components Energized when the Control Switch is in the "WASH" Position
The "WASH" position on the control switch is used when cleaning and sanitizing the icemaker. When in the "WASH" position, power is
supplied to the pump motor. With the cleaning valve closed, the cleaner and sanitizer ow over the outside of the evaporator plate assembly.
With the cleaning valve open, the cleaner and sanitizer ow over both the outside and the inside of the evaporator plate assembly.
Note: Close the cleaning valve after cleaning and sanitizing are complete, otherwise the icemaker will not restart when the control switch is
placed in the "ICE" position.
freeze cycle if activated at the end of the harvest cycle.
Fill Cycle–15 sec. after activation.
"J" Control Board With Harvest Pump Timer Operation Sequence Flow Chart
FS open
1. 1-Minute
Cycle
Fill Cycle
Steps
FS check
WV energized
Startup
Shutdown Delay:
1. Bin Full
If FS is open, Comp stops and cycle returns to 1-min. ll.
Shutdown
and Restart
the 5-min. short cycle protection timer terminates.
Harvest Cycle–At the end of the harvest cycle, or up to 15 sec. into the
Freeze Cycle–15 sec. after activation if activated at least 15 sec. before
Otherwise, at the end of the next harvest cycle.
MBC open (MBC actuator paddle engaged)
Green "BC CLOSED" LED off
Yellow "BC OPEN" LED on
Legend:
Comp–compressor
FM–fan motor
FS–oat switch
HGV–hot gas valve
LLV–liquid line valve
MBC–mechanical bin control
PM–pump motor
MBC Operation
WV–inlet water valve
11

B. Service Diagnosis

WARNING
• The appliance should be diagnosed and repaired only by qualied service personnel to reduce the risk of death, electric shock, serious injury, or re.
• Risk of electric shock. Control switch in "OFF" position does not de-energize all loads Use extreme caution and exercise safe electrical practices.
• Moving parts (e.g., fan blade) can crush and cut. Keep hands clear.
• Before servicing the appliance, move the control switch to the "OFF" position and turn off the power supply.
CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews are securely in place after the appliance is serviced. Make sure that none have fallen into the dispenser unit/ice storage bin.
• Make sure all food zones in the appliance and dispenser unit/ice storage bin are clean after service.
The diagnostic procedure is a sequence check that allows you to diagnose the electrical system and components. Before proceeding, check for correct installation, proper voltage per nameplate, and adequate water supply. Check CB using the steps in "II.C. Control Board Check." Check dip switch settings to assure that S4 dip switch 3, 4, 7, 8, 9, 10 and S5 dip switch 1 through 5 are in the factory default position. S4 dip switch 1, 2, 5, 6 are cleaning adjustments and the settings are exible. For factory default settings, see "III.C.1. Default Dip Switch Settings."
Note: • When checking high voltage (115VAC), always choose a white (W) neutral wire to
establish a good neutral connection.
• When checking voltage from the CB K1 connector (10 pin connector), pull CBK1connector out slightly to allow room for multimeter test leads contact.
Conrm that the location meets installation requirements:
• The appliance is not intended for outdoor use. Normal operating ambient temperature should be within 45°F to 100°F (7°C to 38°C).
• Allow 6" (15 cm) clearance at rear, sides, and top for proper air circulation and ease of maintenance and/or service should they be required.
• The appliance should not be located in a corrosive environment.
1) Turn off the power supply, then access the control box. Move the control switch to the "OFF" position. Clear any ice from BC.
2) Check that the 115VAC 10A fuse is good.
12
1. Diagnosis
3) Power On: Turn on the power supply, then move the control switch to the "ICE" position. A 5-sec. delay occurs. CB red "POWER OK" LED and green "BC CLOSED" LED turn on. If yellow "BC OPEN" LED is on (indicating a full bin), check MBC. Move ice away from MBC actuator paddle. If yellow "BC OPEN" LED stays on, see"II.D. Mechanical Bin Control Check."
Note: • CB red "POWER OK" LED remains on unless the 10.5VAC power supply is
interrupted (K2 connector).
• Check CB using the steps in "II.C. Control Board Check."
• Conrm CB green "BC CLOSED" LED is on. If CB yellow "BC OPEN" LED is on, remove ice from BC. If no ice is around BC and yellow "BC OPEN" LED is on, see "II.D. Mechanical Bin Control Check."
a) Power On Diagnosis: If CB red "POWER OK" LED is off, conrm 10A fuse is good.
Check for 115VAC at control switch #2 (BK) to neutral (W) then at control switch #3(P) to neutral (W). If 115VAC is present on #2 (BK) and not on #3(P), replace control switch. If 115VAC is present on control switch #3 (P), check for 115VAC at HPS pink (P) wire to neutral (W) then HPS black (BK) wire to neutral (W). If115VAC is present at HPS pink (P) wire and not at HPS black (BK) wire, HPS is open. See HPS Diagnosis below. If 115VAC is present at HPS black (BK) wire, check for 10.5VAC at CB K2#1 red (R) wire to CB K2 #2 red (R) wire. If 10.5VAC is not present, check CT continuity. If open, replace CT.
b) HPS Diagnosis: Let refrigeration circuit pressures equalize. If HPS does not
reset and pressures are equalized, replace HPS. Check that the condenser coil is not clogged or restricted and the FM is operating correctly. If pressures are not equalized, reclaim refrigerant and diagnose refrigeration circuit restriction. Check that there are no restrictions in the refrigeration circuit. Harvest Cycle: HGV, strainer, or check valve. Freeze Cycle: FM, TXV, WRV, HM, LLV, strainer, check valve, drier, and damaged line set or tting.
4) 1-Min. Fill Cycle – LED 4 is on. WV and X11 relay energize. Water begins to ll the water tank. After 1 min., CB checks for a closed FS. If FS is closed, the harvest cycle begins (X10, X12, Comp, and HGV energize). Continue to step 5a. If FS is open, WV remains energized through additional 1-min. ll cycles until water enters the water tank and FS closes (low water safety protection during initial start up and at the end of each harvest). Diagnosis: Check that water enters the water tank. If not, check that the water supply line shut-off valve is open and screens or external lters are clear. Check for 115VAC at CB K1 #6(O) to neutral (W). If 115VAC is not present, replace CB. If 115VAC is present, and WV does not energize, check for 115VAC at WV. If 115VAC is present, check coil continuity. Ifopen, replace WV. If the water tank lls, but the appliance fails to start harvest (Comp energized), check for open FS. See "II.E. Float Switch Check and Cleaning." If FS is closed and CB fails to start the harvest cycle after 1 min., replace CB.
13
5a) Initial Harvest Cycle – LEDs 1, 4, and 2 are on. WV and X11 relay continue. Comp,
HGV, X12, and X10 relays energize. CBmonitors the warming of the evaporator via the thermistor located on the suction line. When the thermistor reaches 48°F (9°C), CB reads 3.9 kΩ from the thermistor and turns harvest termination over to the harvest timer (S4 dip switch 1 & 2). The harvest timer has settings of 60, 90, 120, and 180 sec. The pump-out timer (S4 dip switch 3 & 4) acts in place of the harvest timer during cycles with a pump-out (S4 dip switch 5). WV and X11 relay are energized during harvest for a maximum of 6 min. or the length of harvest minus 50sec., whichever is shorter. 50sec. before harvest terminates, PM energizes. See step 5b below.
a) Comp Diagnosis: Check that evaporator is warming. Ifnot, conrm that Comp
energizes. If not, check for 115VAC at CB K1 #1 or #9 (V) to neutral (W). If 115VAC is not present, check for 115VAC at CB K1 #7 or #10 (BK) to neutral (W). If115VAC is present at #7 or #10 (BK) and not at #1 or #9 (V), replace CB. If 115VAC is present, check for 115VAC at CR solenoid. If 115VAC is present, conrm contacts are closed. If not, replace CR. If CR contacts are closed, check Comp start and run capacitors, Comp start relay, and Comp motor winding.
b) HGV Diagnosis: If Comp is energized and evaporator is not warming, check that
HGV energizes and opens. Check for 115VAC at CB K1 #2 (P) to neutral (W). If115VAC is not present, replace CB. If 115VAC is present, check for 115VAC at HGV coil and check HGV coil continuity. Replace as needed.
c) LLV Diagnosis: Conrm that LLV is de-energized and closed (not bypassing).
If energized, replace CB. If de-energized and bypassing, replace LLV.
d) WRV Diagnosis: Conrm WRV is not leaking by.
5b) Harvest Pump Time – LEDs 1, 3, and 2 are on. When the thermistor reaches 48°F
(9°C), CB reads 3.9 kΩ from the thermistor and turns harvest termination over to the harvest timer (S4 dip switch 1 & 2). 50 sec. before the harvest timer terminates, LED3turns on and PM energizes. Comp, HGV, X10, and X12 relays continue. LED4turns off, WV and X11 relay de-energize.
a) Thermistor Diagnosis: Place a thermometer on the suction line next to the
thermistor. Has it warmed to 48°F (9°C) or warmer? Conrm thermistor status. See"II.F. Thermistor Check."
b) Contorl Board Diagnosis: If the thermistor reading is in proper range, dip switch7is
on and WV continues, check for 115VAC at CB K1 #6(O) to neutral (W). If115VAC is present, and LED 4 is off, replace CB. If LED 3is on and PM is not energized, check for 115VAC at CB K1 #5(DBU) to neutral (W). If115VAC is not present, replace CB.
c) Relay Diagnosis: If 115VAC is present and PM is not energized, check for 115VAC
at X12relay terminal #8 (P) to terminal #7neutral (W). If115VAC is present, check for 115VAC at X12 relay terminal #6 (DBU) to neutral (W) and terminal #4 (Y) to neutral(W). If 115VAC is present on terminal #6(DBU) and not on terminal #4(Y), replace X12 relay.
d) Pump Motor Diagnosis: If 115VAC is present on X12 terminal #4(Y) to neutral (W)
and PM is not energized, check PM capacitor and motor winding continuity.
14
5c) Initial Harvest Cycle Termination Diagnosis: When the harvest timer (S4 dip switch
1 & 2) terminates, harvest cycle terminates. If 1-min. ll cycle starts after harvest timer terminates, check that FS is clean and operating properly, see "II.E. Float Switch Check and Cleaning." If FS is closed, CB proceeds to the next cycle. Ifnot, replace CB. Note: The minimum total time allowed by CB for a complete harvest cycle is 2 min.
Maximum harvest time allowed is 20 min.
IMPORTANT! S4 dip switch 7 must remain on. Otherwise, PM will not energize during the last 50 sec. of harvest.
6) Freeze Cycle – LED 1 is on. Comp and PM continue. FM and LLV (if applicable) energize. HGV, X10, and X12 relays de-energize. Appliance is held in freeze by a 5-min. short cycle protection timer. After 5-min. timer terminates and FS opens, freeze cycle terminates. When the thermistor reaches 36°F (2.2°C), CB reads 5.8 kΩ from the thermistor and de-energizes the PM for 10 sec. (anti-slush). After 10 sec. CB energizes PM and freeze cycle continues. Note: PM power supply switches from CBK1 #5(DBU) in harvest to K1 #4 (R) in freeze.
a) Freeze Cycle Diagnosis: Conrm Comp and PM continue. Conrm that FM and
LLV (if applicable) energize. Conrm WRV (if applicable) opens. Next, conrm HGV, X10, and X12 relays de-energize. During the rst 5 min. of freeze, conrm evaporator is cooling. If not, conrm WV de-energized (not leaking by), HGV de-energized (not bypassing), LLV (if applicable) and FM energize, TXV operating correctly, WRV (ifapplicable) opens, Comp is efficient, and refrigerant charge is correct. See "VIII.A. Specication and Performance Data Sheet." When the thermistor reaches 36°F (2.2°C), CB reads 5.8 kΩ from the thermistor and de-energizes the PM for 10 sec. then, energizes PM for the duration of the freeze cycle.
b) Comp Diagnosis: If Comp de-energizes once freeze begins, check that appliance
has not shut off on HPS ("POWER OK" LED off). If so, check "3)b) HPS Diagnosis." If "POWER OK" LED is on, check for 115VAC at CB K1 #1 (V) or #9 (V) to neutral(W). If 115VAC is not present and LED 1 is on, replace CB. If 115VAC is present, check for 115VAC at CR coil. If 115VAC is present, check CR coil and contact continuity. Replace as needed. If CR is okay, check Comp start relay and start and run capacitors. Next, check Comp motor winding continuity. If Comp is energized but evaporator is not cooling, check for an inefficient Comp. See "VIII.B. Performance Data Sheets."
c) WV and HGV Diagnosis: If WV is energized, check for 115VAC at CB K1 #6 (O) to
neutral (W). If 115VAC is present after PM energizes in harvest cycle, replace CB. If 115VAC is not present, replace WV (bypassing). If HGV did not de-energize at the end of harvest, check for 115VAC at CB K1 #2 (P) to neutral (W). If 115VAC is present 50 sec. after PM energizes, replace CB. If 115VAC is not present, replace HGV (bypassing).
15
d) PM Diagnosis: Conrm water is owing over evaporator from PM and not WV.
If PM de-energizes once freeze begins or fails to energize after 10 sec. anti-slush, check for 115VAC at CB K1 #4 (R) to neutral (W). If 115VAC is not present, replace CB. If 115VAC is present and PM is de-energized, check for 115VAC at control switch #6 (R) to neutral (W) and control switch #5 (Y) to neutral (W). If 115VAC is present at CB K1 #6 (R) and not at control switch #5 (Y), check control switch continuity. Replace as needed. If 115VAC is present at control switch #5 (Y) to neutral (W), check PM capacitor and motor winding continuity.
e) FM and LLV Diagnosis: If FM or LLV (if applicable) does not energize, check for
115VAC at CB K1#3 (BK) to neutral (W). If 115VAC is not present, replace CB. If115VAC is present: For FM, check capacitor, motor winding, and blade for binding. For LLV, check coil voltage and continuity.
f) Refrigerant Pressures and TXV Diagnosis: If evaporator is still not cooling, check
refrigerant pressures. See "VIII.B. Performance Data Sheets." Check TXV for proper operation. Remove TXV bulb and hold it in your hand, refrigerant low-side pressure should rise, place TXV bulb in ice water, refrigerant low-side pressure should drop. A 10 to 15 pound pressure swing between warm and cold conditions indicate a good TXV. If a 10 to 15 pound swing is not present, replace TXV.
g) WRV Diagnosis: WRV is factory set and generally no adjustment is required.
IfWRV fails to open in freeze, check for proper refrigerant pressures. See "VIII.B. Performance Data Sheet." If refrigerant pressures are correct and WRV does not open, adjust or replace as needed. See "IV.C. Water Regulating Valve Adjustment (water-cooled models)."
h) Freeze Termination Diagnosis: After 5 min. in freeze, disconnect CB K5 FS
connector. 15 sec. later appliance should switch out of the freeze cycle (15 second delay after FS opens before terminating the freeze cycle). If appliance remains in freeze longer than 15 sec. after FS removed, replace CB. If appliance switches with FS removed but would previously not switch out of freeze with FS connected (long freeze - 3 beep alarm), see "II.E. Float Switch Check and Cleaning."
Note: Normal freeze cycle will last 20 to 40 min. depending on model and conditions.
Cycle times and pressures should follow performance data provided in this manual. See "VIII.B. Performance Data Sheet."
i) Short Freeze Cycle Diagnosis: Conrm water tank lls and overows during 1 min.
ll and harvest cycles. If not, check water supply lters, shut-off valve, WV screen. Ifwater tank empties before 5 min. timer terminates and freeze cycle is short, check that DV is not leaking by or energized (water owing through DV). If DV is leaking by, remove and clean DV, replace as needed. If water tank is full, see "II.E. Float Switch Check and Cleaning." for erratic operating FS.
16
7) Pump-Out Cycle – LEDs 1, 3, and 2 are on (10/20 second pump-out). Timing of the rst pump-out is determined by S4 dip switch 5. See the table below.
Control Board Settings
S4 Dip Switch Setting
No. 5
OFF Every 10 cycles After 11th freeze cycle
ON Every cycle After 2nd freeze cycle
Pump-Out
Frequency
1st Pump-Out
Comp continues, HGV energizes, LLV (if applicable) de-energizes. NOTICE!S4dip switch 3 & 4 must not be set to 3 off and 4 on. Otherwise, LED 4 truns on energizing WV, X11, and X10 relay. Once X10 relay energizes, the DV cannot energize. PM stops for 2 sec., then PM and DV energize for 10/20 sec. depending on
pump-out timer (S4 dip switch 3 & 4) setting. When pump-out timer terminates, pump­out is complete. The pump-out frequency control (S4 dip switch 5) is factory set, and generally no adjustment is required. However, the pump-out frequency control can be set to have a pump-out occur every cycle, or every cycle, or every 10 cycles. For details, see "III.C.4. Pump-Out Frequency Control (S4 dip switch 5)."
a) Pump-Out Diagnosis: In the freeze cycle before pump-out (see table above), after
5min. of freeze disconnect CB black K5 connector (FS connector). Check that CB LEDs 1, 3, and 2are on, PM stops, then re-starts, DV energizes, and water is owing down the drain through DV.
b) CB Diagnosis: Conrm LLV (if applicable) de-energizes. If LLV (if applicable) is
energized with LEDs 1, 3, and 2 on, replace CB. If PM does not stop and re-start and DV does not energize, check that CB LEDs 1, 3, and 2 are on. If not, replace CB. IfLEDs 1, 3, and 2 are on and PM and DV do not energize, check for 115VAC at CB K1 #5 (DBU) to neutral (W). If 115VAC is not present, replace CB. If 115VAC is present at CB K1 #5 (DBU) and PM and DV are not energized, check 115VAC at CB K1 #2 (P) to neutral (W). If LED 2 is on and 115VAC is not present at CB K1 #2 (P), replace CB.
c) X12 Relay PM Diagnosis: If 115VAC is present at CB K1 #2 (P) and PM and DV
are not energized, check for 115VAC at X12 relay #8 (P) to neutral (W). If 115VAC is not present, check wiring connections from CB. If 115VAC is present, and X12 is de-enrgized, check relay coil continuity. Replace as needed.
(1) For PM and X12 Relay; Check for 115VAC at X12 terminal #6 (DBU) to neutral
(W). If 115VAC is not present, see "CB Diagnosis" above. Next, check for 115VAC at X12 terminal #4 (Y) to neutral (W). If 115VAC is not present, replace X12 relay (contacts sticking). If 115VAC is present and PM is not energized, check PM capacitor, motor winding, and impeller for binding.
17
(2) For DV, X12 and X12 Relays; If PM is energized and DV is de-energized, conrm
X10 relay is de-energized. If X10 relay is energized, check X11 contacts for sticking. Replace as needed. If X10 relay is de-energized and DV is de-energized, check for 115VAC at X10 terminal #1 (DBU) to neutral (W). If 115VAC is not present, conrm 115VAC at X10 terminal #5 (DBU). If 115VAC is present at X10 terminal #5 (DBU) and not at X10 terminal #1 (DBU), replace X10 relay (contacts sticking open). If 115VAC is present at X10 terminal #1 (DBU), check for 115VAC at X12 #3 (W/ BU) to neutral (W). If 115VAC is not present at X12 #3 (W/BU) and X12 relay is energized, replace X12 relay (contacts sticking open). If 115VAC is present at X12 #3 (W/BU) and DV is de-energized, check DV coil continuity, make sure the drain line is not clogged and that DV is clean and operating properly.
8) Normal Harvest Cycle – Same as the initial harvest cycle. Return to step 5a) above. Note: Appliance continues to cycle until BC is satised or power is switched off. The
appliance always restarts at the 1-min. ll cycle.
9) Shutdown
Mechanical Bin Control:
See "II.D.2. Mechanical Bin Control Check."
Legend: BC–bin control; CB–control board; Comp–compressor; DV–drain valve;
FM–fan motor; FS–oat switch; HGV–hot gas valve; HPS–high-pressure switch; LLV –liquid line valve; MBC–mechanical bin control; PM–pump motor; TXV–thermostatic expansion valve; WRV–water regulating Valve; WV–inlet water valve
18

C. Control Board Check

Before replacing CB that does not show a visible defect and that you suspect is bad, always conduct the following check procedure. This procedure will help you verify your diagnosis.
Alarm Reset: If CB is in alarm (beeping), press the "ALARM RESET" button on CB
while CB is beeping. WARNING!Risk of electric shock. Care should be taken not to touch live terminals. Once reset, the icemaker starts at the 1-minute ll cycle. For audible alarm information, see "III.B. LED Lights and Audible Alarm Safeties."
1) Check the dip switch settings to assure that S4 dip switch 3, 4, 7, 8, 9, 10 and S5 dip switch 1 through 5 are in the factory default position. S4 dip switch 1, 2, 5,6 are cleaning adjustments and the settings are exible. For factory default settings, see "III.C.1. Default Dip Switch Settings."
2) Move the control switch to the "ICE" position. If the red "POWER OK" LED is on, control voltage is good, continue to step 3. If the "POWER OK" LED is off, check CT secondary circuit. CT output is 10.5VAC at 115VAC primary input. If the secondary circuit has proper voltage and the red LED is off, replace CB.
If the secondary circuit does not have proper voltage (10.5VAC), check CT primary
circuit. Check for 115VAC at control switch terminal #2 (BK) and control switch terminal #3 (P) to neutral (W). If 115VAC is present at control switch terminal #2 (BK) and not at control switch terminal #3 (P), replace control switch. If 115VAC is present at control switch terminal #3 (P), check for 115VAC at HPS (BK) to neutral (W). If 115VAC is not present, see "B.1. or 2. 3)b) HPS Diagnosis." If 115VAC is present check CT coil continuity. Replace as needed. For additional checks, see "II.G.1. No Ice Production."
3) The "OUTPUT TEST" button provides a relay sequence test. Make sure the control switch is in the "ICE" position, then press the "OUTPUT TEST" button. For the correct lighting sequence, see the table below. Note that the order of the LEDs from the outer edge of the control board is 1, 4, 3, 2. Components (e.g., compressor) cycle during the test.
Control
Board
"J" 1, 4, 3, 2
Correct LED
Lighting Sequence
Following the test, the icemaker begins operation at the 1-minute ll cycle. If the LEDs do not light as described above, replace CB.
4) To verify voltage output from CB to the components, slide the CB K1 connector out far enough to allow multimeter lead contact. With the icemaker in the cycle to be tested, check output voltage from the corresponding pin on CB K1 connector to a neutral (W) wire. If output voltage is not found and the appropriate LED is on, replace CB.
Legend: CB–control board; CT–control transformer
19

D. Bin Control Check

1. Mechanical Bin Control Check
This appliance uses a lever-actuated proximity switch to control the ice level in the storage bin. No adjustment is required.
To check MBC, follow the steps below.
1) Turn off the power supply.
2) Remove the front panel, then move the control switch to the "OFF" position.
3) Remove the control box cover, then clear any ice away from MBC.
4) Check MBC wire harness connections. See Fig. 1.
MBC Connector (to control board K4 (red) connector)
5) Disconnect MBC connector from CB K4 connector.
6) Check for continuity across the wires of MBC connector. When the actuator paddle is not engaged, MBC switch is closed. If open, check that the wire harness connector is properly connected and that the actuator paddle is not sticking. Clean if necessary. See "II.D.2.b) Mechanical Bin Control Cleaning." If MBC switch still reads
MBC
MBC Wire Harness (white) Connector
Actuator Paddle
Fig. 1
open, replace MBC.
7) Press and hold the actuator paddle; check for continuity across the wires of MBC connector. When the actuator paddle is engaged, MBC switch is open. If closed, check that the actuator paddle is not restricted. Clean if necessary. See "II.D.2.b) Mechanical Bin Control Cleaning." If MBC switch still reads closed, replace MBC.
8) Reconnect MBC connector to CB K4 connector, then move the control switch to the "ICE" position. Turn on the power supply.
9) Check that CB green "BC CLOSED" LED is on.
10) Allow the icemaker to cycle on. Press and hold the actuator paddle. CB yellow "BCOPEN" LED should turn on and the icemaker should shut down according to the chart below. If it does not, replace CB.
Cycle at Mechanical Bin Control Activation
Fill Cycle 15 sec. after activation.
Harvest Cycle At the end of the harvest cycle, or up to 15 sec. into the freeze cycle if activated at the
Freeze Cycle 15 sec. after activation if activated at least 15 sec. before the 5-min. short cycle
Shutdown
end of the harvest cycle.
protection timer terminates. Otherwise, at the end of the next harvest cycle.
Legend: MBC–mechanical bin control; CB–control board
20
2. Mechanical Bin Control Cleaning
Scale may build up on MBC. Scale can cause the actuator paddle and magnet to stick. In this case, MBC should be cleaned.
WARNING
CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews are
securely in place after the icemaker is serviced. Make sure that none have fallen into the dispense unit/ice storage bin.
1) Turn off the power supply.
2) Remove the front panel, then move the control switch to the "OFF" position.
3) Clear any ice away from MBC.
4) Disconnect MBC connector from CB K4 connector, then remove MBC from the icemaker.
5) Remove the actuator paddle from the switch mount. See Fig. 2.
6) Wipe down MBC with a mixture of 1 part of Hoshizaki "Scale Away" and 25 parts of warm water. Rinse the parts thoroughly with clean water.
7) Reassemble MBC and replace it in its correct position. Note: If the magnet was removed for cleaning, be sure to replace it in its correct
position.
8) Reconnect MBC connector to CB K4 connector, then move the control switch to the "ICE" position.
9) Replace the control box cover in its correct position.
10) Turn on the power supply to start the automatic icemaking process.
11) Replace the front panel in its correct position.
Legend: MBC–mechanical bin control
MBC Wire
Bin Control Proximity Switch Closed (calling for ice)
Bin Control Proximity Switch Open (bin full, icemaker off or shutting down)
KM-901M_H/3 MBC Bracket
Switch Mount
Actuator Paddle
Fig. 2
Magnet
Harness (white) Connector
MBC Connector (to control board K4 (red) connector)
21

E. Switches

Two control switches are used to control operation. These switches are referred to as the "control switch" and the "service switch" and are located on the control box.

1. Control Switch

The control switch has three positions: "OFF" for power off, "ICE" for icemaking, and "SERVICE" to activate the service switch.

2. Service Switch

When the control switch is in the "SERVICE" position, the control switch supplies power to the service switch and the machine is in service mode. The service switch has three positions: "DRAIN, "CIRCULATE," and "WASH." See the information below for details of each function.
Note:
1. When the service switch is activated, power is supplied to the water pump in all three positions.
2. When the control switch is in the "OFF" position or in the "ICE" position, the service switch has no power and can be left in any position.
a) DRAIN
This model utilizes a pump-out drain system. When the service switch is active and placed in the "DRAIN" position, power is supplied to the pump, service relay, and drain valve.
b) CIRCULATE
When the service switch is active and placed in the "CIRCULATE" position, power is supplied to the pump only. This operation can be used to circulate cleaner for extended periods of time over the outside surface of the evaporator.
c) WASH
This model utilizes a solenoid operated wash (bypass) valve. When the service switch is active and placed in the "WASH" position, power is supplied to the pump and the wash valve. This operation is used to circulate cleaner and sanitizer over both the inside and outside of the evaporator.
22

F. Float Switch Check and Cleaning

FS is used to determine that there is sufficient water in the water tank after the 1-min. ll cycle and after each harvest cycle. FS is also used to determine that the appropriate volume of water has been converted into ice before switching out of the freeze cycle. No adjustment is required.

1. Float Switch Check

To check FS, follow the steps below.
1) Remove the front panel. Disconnect the dispense solenoid wire harness and set front panel aside. Move the control switch to the "SERVICE" position, then move the service switch to the "DRAIN" position.
2) Allow the water to drain from the water tank. Move the control switch to the "OFF" position, then turn off the power supply.
3) Remove the control box cover.
4) Disconnect FS connector from CB K5(black) connector.
5) Check for continuity across FS leads. With the water tank empty, FS should be open. If open, continue to step 6. If closed, follow the steps in "II.E.2. Float Switch Cleaning." After cleaning FS, check it again. Replace if necessary.
6) Reconnect FS connector to CB K5 connector, then replace the control box cover in its correct position.
7) Move the control switch to the "ICE" position. Turn on the power supply. After 1 min., the 1-min. ll cycle should end and the initial harvest cycle should begin. If the initial harvest cycle begins, FS is good and the check is complete. Reconnect the dispense solenoid wire harness, then replace the front panel in its correct position. If the initial harvest cycle does not begin, continue to step 8.
8) Turn off the power supply.
9) Move the control switch to the "OFF" position.
10) Remove the control box cover.
11) Disconnect FS connector from CB K5 connector.
12) Check for continuity across FS leads. With the water tank full, FS should be closed. IfFS is closed and the icemaker will not switch from the 1-min. ll cycle to the initial harvest cycle, replace CB.
If FS is open, conrm that the water tank is full. If the water tank is not full, check the water supply, water lters, and inlet water valve. If the water tank is full, follow the steps in "II.E.2. Float Switch Cleaning." After cleaning FS, check it again. Replace if necessary.
13) After repair is complete, replace the control box cover, move the control switch to the "ICE" position. Reconnect the dispense solenoid wire harness, then replace the front panel in its correct position. Next, turn on the power supply.
Legend: CB–control board; FS–oat switch
23

2. Float Switch Cleaning

Depending on local water conditions, scale may build up on FS. Scale on the switch can cause the oat to stick. In this case, FS should be cleaned.
1) Remove the front panel. Disconnect the dispense solenoid wire harness and set front panel aside. Move the control switch to the "SERVICE" position, then move the service switch to the "DRAIN" position.
2) Allow the water to drain from the water tank. Move the control switch to the "OFF" position, then turn off the power supply.
3) Remove the 3 FS assembly mounting screws and remove FS assembly from the water tank. See Fig. 3.
5) Remove the retainer rod from the bottom of FS housing, then remove the oat. Be careful not to bend the retainer rod excessively when removing it. See Fig. 4.
6) Wipe down FS mounting bracktes, housing, shaft, oat, and retainer rod with a mixture of 1 part Hoshizaki "Scale Away" and 25 parts warm water. Clean the inside of the vent hose with cleaning solution. Rinse the parts thoroughly with clean water.
7) Reassemble FS assembly and replace it in its correct position.
8) Move the control switch to the "ICE" position.
9) Reconnect the dispense solenoid wire harness and replace the front panel in its correct position.
10) Turn on the power supply to start the automatic icemaking process.
Legend: CB–control board; FS–oat switch
FS Assembly Mounting Screws
Water Tank
Shaft
Mounting Brackets
Vent Hose
Float Switch Housing
Fig. 3
Float
Retainer Rod
Foat Switch Assembly
Fig. 4
24

G. Thermistor Check

To check thermistor resistance, follow the steps below.
1) Turn off the power supply.
2) Remove the front panel. Disconnect the dispense solenoid wire harness and set front panel aside. Move the control switch to the "OFF" position.
3) Remove the control box cover.
4) Remove the thermistor from the refrigerant tubing.
5) Immerse the thermistor sensor portion in a glass containing ice and water for 2 or 3 min.
6) Disconnect the thermistor connector from CB K3 connector and check the resistance between thermistor leads. Normal range is 4.7 to 6.2 kΩ. If outside the normal range, replace the thermistor. See "IV.B. Component Service Information." If within the normal range, continue to the next step.
7) Replace the thermistor in its correct position. See "IV.B. Component Service Information."
8) Reconnect the thermistor connector to CB K3 connector.
9) Replace the control box cover in its correct position.
10) Move the control switch to the "ICE" position.
11) Reconnect the dispense solenoid wire harness and replace the front panel in its correct position.
12) Turn on the power supply.
13) Once the harvest cycle starts (Comp energizes), begin timing the harvest cycle.
14) The harvest timer and harvest cycle should terminate within 2 to 5 min. If the harvest cycle does not terminate within 2 to 5 min., replace CB.
Legend: CB–control board; Comp–compressor
25

H. Diagnostic Tables

1. No Ice Production
No Ice Production - Possible Cause
1. Power Supply a) Off, blown fuse, or tripped breaker.
b) Not within specications.
3. Fuse (control box) a) Blown or tripped.
5. Control Switch a) In "OFF" or "SERVICE" position.
b) Bad contacts.
6. High-Pressure Switch a) Dirty condenser.
b) Fan motor not operating.
c) Refrigerant overcharged.
d) Bad contacts.
e) Refrigerant lines or components plugged.
7. Control Transformer (115VAC/10.5VAC)
8. Control Board See "II.C. Control Board Check"
9. Mechanical Bin Control See "II.D. Bin Control Check"
10. Water Supply a) Water supply off or improper water pressure.
11. Inlet Water Valve a) Screen or orice clogged.
12. Float Switch See "II.E. Float Switch Check and Cleaning"
13. Compressor a) Compressor relay contacts bad or coil winding open.
14. Hot Gas Valve a) Closed in harvest cycle.
15. Thermistor See "II.F. Thermistor Check"
16. Pump Motor a) Motor winding open.
1 7. Thermostatic Expansion Valve a) Bulb loose.
a) Coil winding open or shorted.
a) In alarm.
b) Yellow "BC OPEN" LED on (bin full).
c) Defective.
a) Tripped with bin lled with ice.
b) Actuator does not move freely.
c) Defective.
b) External water lters clogged.
b) Coil winding open.
c) Water valve open in freeze cycle.
a) Float does not move freely.
b) Defective.
b) Start capacitor or run capacitor defective.
c) Internal protector open.
d) Start relay contacts bad or coil winding open.
e) Defective.
b) Open in freeze cycle.
a) Loose, disconnected, or defective.
b) Bearing worn out or locked rotor.
c) Defective capacitor.
d) Mechanical seal worn out.
b) Operating erratically.
26
No Ice Production - Possible Cause
18. Liquid Line Valve a) Closed in freeze cycle.
b) Open in harvest cycle.
19. Fan Motor a) Motor winding open.
b) Bearing worn out or locked rotor.
c) Defective capacitor.
20. Water System (drain valve, bypass valve)
a) Water leaks causing short freeze time or freeze up.
2. Freeze-Up
Defrost and clean the icemaker prior to diagnosing freeze-up. Fill out a freeze-up checklist. See the Hoshizaki America Technician's Pocket Guide or contact your local distributor for a copy of the freeze-up checklist.
Freeze-Up - Possible Cause
Harvest Cycle
1. Evaporator a) Scaled up.
b) Damaged.
2. Cube Guides a) Out of position.
b) Damaged.
3. Spray Tubes and/or Spray Guides
4. Water Supply a) Low water pressure.
5. Inlet Water Valve a) Screen or orice clogged.
6. Float Switch See "II.E. Float Switch Check and Cleaning"
7. Refrigerant Charge a) Low.
8. Control Board
See "III.C. Settings and Adjustments" and "II.C. Control Board Check"
9. Bin Control See "II.D. Bin Control Check"
10. Thermistor See "II.F. Thermistor Check"
11. Thermostatic Expansion Valve a) Defective.
12. Hot Gas Valve a) Closed or restricted.
13. Liquid Line Valve a) Open.
a) Dirty.
b) Out of position.
b) External water lters clogged.
c) Insufficient water line size.
Minimum 1/4" Nominal ID (6 mm Nominal OD in the EU) copper water tubing or equivalent.
b) Defective.
a) Dirty, sticking.
b) Defective.
a) Harvest timer (S4 dip switch 1 & 2) set too short.
b) Harvest pump timer (S4 dip switch 7) not in factory default position.
c) Defective.
a) Actuator does not move freely.
a) Loose, disconnected, or defective.
27
Freeze-Up - Possible Cause
Freeze Cycle
1. Evaporator a) Scaled up.
b) Damaged.
2. Spray Tubes and/or Spray Guides
3. Refrigerant Charge a) Low.
4. Control Board See "II.C. Control Board Check"
5. Inlet Water Valve a) Leaking by.
6. Float Switch See "II.E. Float Switch Check and Cleaning"
7. Pump Motor a) RPM too slow.
8. Thermostatic Expansion Valve a) Bulb loose or defective.
9. Liquid Line Valve a) Restricted.
a) Dirty.
b) Out of position.
a) Freeze timer (S4 dip switch 9 & 10) set incorrectly.
b) Defective.
a) Float does not move freely.
b) Defective.
b) Impeller damaged.
3. Low Ice Production
Low Ice Production - Possible Cause
Long Harvest Cycle
1. Evaporator a) Scaled up.
2. Spray Tubes and/or Spray Guides
3. Refrigerant Charge a) Low.
4. Water Supply a) Low water pressure.
5. Control Board See "II.C. Control Board Check"
6. Thermistor See "II.F. Thermistor Check"
7. Hot Gas Valve a) Erratic or closed.
8. Inlet Water Valve a) Screen or orice clogged.
9. Compressor a) Inefficient or off.
10. Liquid Line Valve a) Erratic or open.
11. Thermostatic Expansion Valve a) Defective.
a) Dirty.
b) Out of position.
b) External water lters clogged.
c) Insufficient water line size.
Minimum 1/4" Nominal ID (6 mm Nominal OD in the EU) water tubing or equivalent.
d) Too cold.
a) Thermistor connection loose (K3).
b) Defective.
a) Loose, disconnected, or defective.
28
Low Ice Production - Possible Cause
Long Freeze Cycle
1. Evaporator a) Scaled up, dirty.
2. Float Switch See "II.E. Float Switch Check and Cleaning"
3. Inlet Water Valve a) Leaking by.
4. Hot Gas Valve a) Erratic or open.
5. Condenser a) Clogged.
6. Control Board See "II.C. Control Board Check"
7. Refrigerant Charge a) Low.
8. Thermostatic Expansion Valve a) Bulb loose.
9. Compressor a) Inefficient or off.
10. Pump Motor a) RPM too slow.
11. Liquid Line Valve a) Erratic or restricted.
a) Scaled up, dirty.
b) Float sticking.
c) Defective switch.
a) Float switch connection loose (K5).
b) Defective.
b) Defective.
29

III. Controls and Adjustments

• A Hoshizaki exclusive control board is employed in KM series appliances.
• All models are pretested and factory adjusted.
• For a control board check procedure, see "II.C. Control Board Check."
NOTICE
• Fragile, handle very carefully.
• The control board contains integrated circuits, which are susceptible to failure due to static discharge. It is especially important to touch the metal part of the icemaker when handling or replacing the control board.
• Do not touch the electronic devices on the control board or the back of the control board.
• Do not change wiring and connections. Do not misconnect K3 WHITE, K4RED, and K5 BLACK, because the same connector is used for the thermistor, mechanical bin control, and oat switch.
• Do not short out power supply to test for voltage.
• Always replace the whole control board assembly if it goes bad.
30

A. Control Board Layout

• Bin Control Switch Closed LED (green)
(on continuously in thermostatic bin control application)
• "ALARM RESET" Button
"J" Control Board
• S4 Dip Switch
• "OUTPUT TEST" Button
(used to test relays on control board)
• Bin Control Switch Open LED (yellow)
(mechanical bin control application only)
• Alarm Buzzer
• Ext. Harvest LED (blue) (lights when
water line thermistor initiates extended harvest) Not used this model
• POWER OK LED (red) (lights when
10.5VAC is supplied to K2 connector)
• Relay LEDs
(4) (indicate which relays are energized and which K1 connector pins are energized
• LED 2 (X2 Relay)
LED 2 on: K1 Connector Pin #2 LED 2 off: K1 Connector Pin #3
• LED 3 (X3 Relay)
LED 3 on: K1 Connector Pin #5 LED 3 off: K1 Connector Pin #4 (energized in freeze)
• LED 4 (X4 Relay) K1 Connector Pin #6
• LED 1 (X1 Relay)
K1 Connector Pin #1, #9
• K3 (white) Connector
Thermistor (harvest control and high temperature safety)
• K4 (red) Connector
Mechanical Bin Control or K4 Jumper (thermostatic bin control application)
• S5 Dip Switch
• K5 (black) Connector
Float Switch (water level)
• Part Number
• K1 Connector
Pins #1 through #10 #1, 9 Compressor Relay #2 Hot Gas Valve, X12 Relay #3 Fan Motor Liquid Line Valve #4 Pump Motor (icemaking) #5 Pump Motor (harvest pump timer and pump-out) #6 Inlet Water Valve, X11 Relay #7, 10 Component Power Supply #8 Open
• K2 Connector
Control Transformer (10.5VAC)
"J" Control Board
Part Number 2A7664-01
31

B. LED Lights and Audible Alarm Safeties

At startup, a 5-second delay occurs while the control board conducts an internal timer check. A beep occurs when the control switch is moved to the "ICE" position. The red "POWER OK" LED indicates proper control voltage and remains on unless a control voltage problem occurs. The green LEDs 1 through 4 energize and sequence from initial startup as listed in the table below. Note that the order of the LEDs from the outer edge of the control board is 1, 4, 3, 2.
Sequence Step LED
1-Minute Fill Cycle 4 WV 1 minute Harvest Cycle 1, 4, 2 Comp, HGV, WV 2 minutes 20 minutes 3 to 5 minutes Harvest Pump Timer 1, 3, 2 Comp, HGV, PM 0 seconds 50 seconds harvest pump timer
Freeze Cycle 1 Comp, FM, PM, LLV 5 minutes freeze timer
Pump-Out Cycle 1, 4*, 3, 2 Comp, HGV, PM, WV* 10 seconds 20 seconds *pump-out timer
Energized
Components
Min. Max. Avg.
Time LEDs are On
setting 30 to 35 minutes
setting
setting
The built-in safeties shut down the icemaker and have alarms as listed below.
No. of Beeps
(every 3 sec.)
1 High Evaporator Temp.
(temperature > 127°F) (53°C)
2 Harvest Backup Timer
(harvest > 20 min. for two cycles in a row)
3 Freeze Timer
(freeze > freeze timer setting for two cycles in a row)
To reset the above safeties, press the "ALARM RESET" button with the power supply on.
6 Low Voltage
(92VAC±5% or less)
7 High Voltage
(147VAC±5% or more)
Type of Alarm Notes
Check for harvest problem (stuck HGV or relay), hot water entering icemaker, or shorted thermistor.
Check for open thermistor, HGV not opening, TXV or LLV leaking by, low charge, or inefficient Comp, or WRV leaking by.
Check for FS stuck closed (up), WV leaking by, HGV leaking by, PM not pumping, TXV not feeding properly, LLV not opening, low charge, HM not bypassing, or inefficient Comp.
Red LED turns off if voltage protection operates. The control voltage safeties automatically reset when voltage is corrected.
Legend: Comp–compressor; FM–fan motor; FS–oat switch; HGV–hot gas valve;
LLV –liquid line valve; PM–pump motor; TXV–thermostatic expansion valve; WRV–water regulating valve; WV–inlet water valve
32

C. Settings and Adjustments

NOTICE
Dip switches are factory set. Failure to maintain factory settings may adversely affect performance and warranty coverage. For more information, contact your Hoshizaki Service Center.

1. Default Dip Switch Settings

The dip switches are factory-adjusted to the following positions for the "J"control board:
S4 Dip Switch No. 1 2 3 4 5 6 7 8 9 10
All Models OFF OFF OFF OFF OFF OFF ON OFF OFF OFF
S5 Dip Switch (Do Not Adjust)
"J" Control Board
Dip Switch No.
All Models OFF OFF OFF OFF ON
1 2 3 4 5
S4 Dip Switch "J" Control Board
Freeze Timer (9 & 10)
Factory Use (8)
Harvest Pump Time (7) (Do Not Adjust)
Harvest Pump Timer (6) (Do Not Adjust)
Pump-Out Frequency Control (5)
Pump-Out Timer (3 & 4)
1 2 3 4 5 6 7 8 9 10
ON
Harvest Timer (1 & 2)
S5 Dip Switch (Do Not Adjust) "J" Control Board
Anti-Slush (5)
Minimum Harvest Time (4)
Rell Counter (2 and 3)
1 2 3 4 5
ON
Float Switch Selector (1)

2. Harvest Timer (S4 dip switch 1 & 2)

The harvest timer starts counting when the thermistor reaches 48°F (9°C) at the evaporator outlet and the control board reads 3.9 kΩ from the thermistor. The harvest timer is factory set, and generally no adjustment is required. However, a setting longer than the factory setting may be advised in cases where the drain provided at harvest needs to be prolonged for extra cleaning. Before changing this setting, contact Hoshizaki Technical Support at 1-800-233-1940 for recommendations. Keep in mind that setting the harvest timer to a longer setting decreases 24-hour production. Note that the pump-out timer (S4 dip switch 3 & 4) acts in place of the harvest timer during cycles with a pump out. For details, see "III.C.3. Pump-Out Timer (S4 dip switch 3& 4)."
Note: On models with a pump-out every cycle, the harvest timer is only relevant during
the initial harvest cycle since a pump out occurs every cycle thereafter.
S4 Dip Switch Setting Time
No. 1 No. 2
OFF OFF 60
ON OFF 90
OFF ON 120
ON ON 180
(sec.)
33

3. Pump-Out Timer (S4 dip switch 3 & 4)

NOTICE
Do not adjust 3 off and 4 on. Drain valve does not energize in this setting.
When a pump-out is called for, the pump motor stops for 2 sec. After 2 sec. the drain valve and pump motor energize. The pump motor drains the water tank for the time determined by the pump-out timer. The pump-out timer also acts in place of the harvest timer during cycles with a pump-out. The pump-out timer is factory set, and generally no adjustment is required. However, where water quality is bad and the icemaker needs a longer pump-out time, the pump-out timer can be adjusted. The pump-out timer control can be set to pump-out for 10 or 20 sec.
S4 Dip Switch Setting Time (sec.)
T1
OFF OFF 10 150 Closed
ON OFF 10 180 Closed
OFF ON 10 120 Open
ON ON 20 180 Closed
T2
Inlet Water
ValveNo. 3 No. 4
T1: Time to drain the water tank T2: Harvest timer at pump out

4. Pump-Out Frequency Control (S4 dip switch 5)

The pump-out frequency control is factory set to drain the water tank every 10 cycles. Generally no adjustment is required. However, where water quality is bad and the icemaker needs a pump-out more often, the pump-out frequency can be adjusted. The pump-out frequency control can be set to have a pump-out occur every cycle, or every 2, 5, or 10 cycles.
The rst pump-out is dependent on S4 dip switch 5. See the table below.
S4 Dip Switch Setting
No. 5
OFF Every 10 cycles After 11th freeze cycle
ON Every cycle After 2nd freeze cycle
Pump-Out
Frequency
1st Pump-Out
34

5. Harvest Pump Time (S4 dip switch 6)

NOTICE
Factory set for proper operation. Do not adjust. Adjustment outside of the factory default setting may result in damage to the appliance.
The harvest pump time starts with 50 sec. left to go in the harvest time (S4 dip switches 1 & 2) after the thermistor reaches 48°F (9°C) at the evaporator outlet and the control board reads 3.9kΩ from the thermistor. The harvest pump time is factory set, and no adjustment is required.
S5 Dip Switch Setting Harvest Pump Time
No. 6
OFF 50 sec.
ON 25 sec.
6. Harvest Pump Time Operation (S4 dip switch 7)
S4 dip switch 7 is used for harvest pump timer operation.
NOTICE
Factory set for proper operation. Do not adjust. Adjustment outside of the factory default setting may result in damage to the appliance.
Depending on the harvest pump time operation setting, the pump motor either stays off or is energized the last 50 seconds of harvest. When the pump motor is energized, water circulates over the evaporator. The inlet water valve is open during harvest for a maximum of 6 minutes or the length of harvest minus 0 or 50 sec. (determined by the harvest pump time setting), whichever is shorter.
When S4 dip switch 7 is in the on position and harvest begins, X10, X11, and X12 relays energize. A latching circuit is created through the X11 and X10 relays. For further details, see "VIII.C. Wiring Diagrams." 50 sec. before harvest termination, LED 4 turns off, inlet water valve and X11 relay de-energize. X10 relay remains energized through the latching circuit and X12 relay remains energized through the pink (P) wire. Next, LED 3 turns on and control board K1 connector pin #5 (DBU) wire energizes, energizing the pump motor through the X12 relay for the last 50 sec. of harvest.
"J" Control Board
S4 Dip Switch Setting
No. 7
OFF Disabled
ON Enabled
Pump Motor
Time (sec.)
35

7. Factory Use (S4 dip switch 8)

Factory set for proper operation. Do not adjust. This must be left in the factory default position.

8. Freeze Timer (S4 dip switch 9 & 10)

NOTICE
Adjust to proper specication, or the icemaker may not operate correctly.
The freeze timer setting determines the maximum allowed freeze time to prevent possible freeze-up issues. Upon termination of the freeze timer, the control board initiates the harvest cycle or pump-out cycle. After 2 consecutive freeze timer terminations, the control board shuts down the icemaker. In this case, see "II.G.3. Low Ice Production" for possible solutions. The freeze timer is factory set and no adjustment is required. Before changing this setting, contact Hoshizaki Technical Support at 1-800-233-1940 for recommendations.
S4 Dip Switch Setting Time
No. 9 No. 10
OFF OFF 60
ON OFF 70
OFF ON 50
ON ON 85
(min.)

9. Float Switch Selector (S5 dip switch 1)

This dip switch setting allows use of this control board in single and dual oat switch models. This model uses a single oat switch style.
NOTICE
Do not adjust. This must be left in the factory default position or the icemaker will not operate correctly.
S5 Dip Switch Setting
OFF Bottom Float Switch Enabled
ON Top Float Switch Enabled
Top or Bottom Float Switch
ControlNo. 1
10. Rell Counter (S5 dip switch 2 and 3)
NOTICE
Do not adjust. These must be left in the factory default position or the icemaker will not operate correctly. This model does not utilize rell.
S5 Dip Switch Setting Rell
No. 2 No. 3
OFF OFF 0
ON OFF 9 rells
OFF ON 1 rell
ON ON 10 rells
Counter
36

11. Minimum Harvest Time (S5 dip switch 4)

NOTICE
Factory set for proper operation. Do not adjust. Adjustment outside of the factory default setting may result in damage to the appliance.
S5 Dip Switch Setting
Minimum Harvest TimeNo. 4
OFF 120 sec.
ON 70 sec.

12. Anti-Slush (S5 dip switch 5)

This dip switch setting provides anti-slush control during the freeze cycle. When the evaporator temperature reaches 36°F (2.2°C) the control board reads a 5.8kΩ signal from the thermistor and de-energizes the water pump for 10 sec. to melt the ice slush and prevent the ice slush from blocking the water supply tubing, causing irregular freeze patterns.
NOTICE
Factory set for proper operation. Do not adjust. Adjustments outside of the factory default setting may result in damage to the appliance and may adversely affect performance and warranty coverage.
S5 Dip Switch Setting
OFF Disabled
ON Enabled
Anti-SlushNo. 5
37

IV. Refrigeration Circuit and Component Service Information

WARNING
• This appliance should be diagnosed and repaired only by qualied service personnel to reduce the risk of death, electric shock, serious injury, or re.
• Move the control switch to the "OFF" position and turn off the power supply. Place the disconnect in the "OFF" position. Lockout/Tagout to prevent the power supply from being turned back on inadvertently.
CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews are securely in place after the icemaker is serviced. Make sure that none have fallen into the dispenser unit/ice storage bin.
• Make sure all food zones in the icemaker and dispenser unit/ice storage bin are clean after service.

A. Refrigeration Circuit Service Information

WARNING
• Repairs requiring the refrigeration circuit to be opened must be performed by properly trained and EPA-certied service personnel.
• Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of refrigerant to the system (if using an electronic leak detector), and then raise the pressure using nitrogen gas (140 PSIG). Do not use R-404A as a mixture with pressurized air for leak testing.
NOTICE
• Always recover the refrigerant and store it in an approved container. Do not discharge the refrigerant into the atmosphere.
• Do not leave the system open for longer than 15 min. when replacing or servicing parts. The Polyol Ester (POE) oils used in R-404A applications can absorb moisture quickly. Therefore it is important to prevent moisture from entering the system when replacing or servicing parts.
• Always install a new drier every time the sealed refrigeration system is opened. Do not replace the drier until after all other repair or replacement has been made. Install the new drier with the arrow on the drier in the direction of the refrigerant ow.
• When brazing, protect the drier by using a wet cloth to prevent the drier from overheating. Do not allow the drier to exceed 250°F (121°C).
1. Refrigerant Recovery
The icemaker is provided with refrigerant access valves. Using proper refrigerant practices, recover the refrigerant. Store the refrigerant in an approved container. Do not discharge the refrigerant into the atmosphere.
38
2. Brazing
WARNING
• R-404A itself is not ammable at atmospheric pressure and temperatures up to 176°F (80°C).
• R-404A itself is not explosive or poisonous. However, when exposed to high temperatures (open ames), R-404A can be decomposed to form hydrouoric acid and carbonyl uoride both of which are hazardous.
• Do not use silver alloy or copper alloy containing arsenic.
1) Braze all ttings while purging with nitrogen gas owing at a pressure of 3 to 4 PSIG. Note: Because the pipes in the evaporator case are specially coated to resist corrosion,
it is important to make connections outside the evaporator case when possible. If it is necessary to braze inside the evaporator case, use sandpaper to remove the coating from the brazing connections before unbrazing the components.
NOTICE
• Always install a new drier every time the sealed refrigeration system is opened.
• Do not replace the drier until after all other repair or replacement has been made. Install the new drier with the arrow on the drier in the direction of the refrigerant ow.
• When brazing, protect the drier by using a wet cloth to prevent the drier from overheating. Do not allow the drier to exceed 250°F (121°C).
2) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of refrigerant to the system (if using an electronic leak detector), and then raise the pressure using nitrogen gas (140 PSIG). Do not use R-404A as a mixture with pressurized air for leak testing.
3. Evacuation and Recharge (R-404A)
1) Attach a vacuum pump to the system. Be sure to connect the charging hoses to both high and low-side refrigerant access valves.
IMPORTANT
The vacuum level and vacuum pump may be the same as those for current refrigerants. However, the rubber hose and gauge manifold to be used for evacuation and refrigerant charge should be exclusively for POE oils.
2) Turn on the vacuum pump. Open the gauge manifold valves. Never allow the oil in the vacuum pump to ow backwards.
3) Allow the vacuum pump to pull down to a 29.9" Hg vacuum. Evacuating period depends on pump capacity.
4) Close the low-side valve and high-side valve on the gauge manifold.
39
5) Disconnect the gauge manifold hose from the vacuum pump and attach it to a refrigerant service cylinder. Remember to loosen the connection and purge the air from the hose. For the required refrigerant charge, see the rating label inside the icemaker. Hoshizaki recommends only virgin refrigerant or reclaimed refrigerant which meets ARI Standard 700 (latest edition) be used.
6) A liquid charge is required when charging an R-404A system (to prevent fractionation). Place the service cylinder on the scales; if the service cylinder is not equipped with a dip tube, invert the service cylinder, then place it on the scales. Open the high-side valve on the gauge manifold.
7) Allow the system to charge with liquid until the proper charge weight is met.
8) If necessary, add any remaining charge to the system through the low-side.
NOTICE!To prevent compressor damage, use a throttling valve or liquid dispensing device to add the remaining liquid charge through the low-side refrigerant access valve with the icemaker running.
9) Close the high and low-side gauge manifold valves, then disconnect the gauge manifold hoses.
10) Cap the refrigerant access valves to prevent a possible leak.
40

B. Component Service Information

NOTICE
When replacing a component listed below, see the notes to help ensure proper operation.
Component Notes
Compressor Install a new start capacitor, run capacitor, and start relay.
Thermostatic Expansion Valves
Hot Gas Valves Liquid Line Valves
Fan Motors Install a new capacitor.
Pump Motor Install a new capacitor.
Thermistor • Attach the new thermistor to the suction line in the same location as the previous
• Attach the thermostatic expansion valve bulb to the suction line in the same location as the previous bulb.
• The bulb should be between the 10 and 2 o'clock positions on the tube.
• Secure the bulb with the clamp and holder, then insulate it.
• Replace the strainer if applicable.
• Use copper tube of the same diameter and length when replacing valve lines.
thermistor.
• The thermistor should be at the 12 o'clock position on the tube.
• Smoothly ll the recessed area of the thermistor holder with high thermal conductive type sealant. Hoshizaki America part number 4A0683-01 (Silicone Heat Sink Compound 10-8108 manufactured by GC Electronics), KE-4560 RTV (manufactured by ShinEtsu Silicones), or equivalent are recommended.
• Secure the thermistor with the holder, then insulate it.
• Be very careful to prevent damage to the leads.

C. Water Regulating Valve Adjustment (water-cooled model)

The water regulating valve is factory set, and generally no adjustment is required. However, when necessary, adjust the water regulator using the following procedure.
1) Prepare a thermometer to check the condenser drain temperature. Attach a pressure gauge to the high-side line of the system.
2) 5 min. after a freeze cycle starts, conrm that the thermometer reads 104°F to 115°F (40°C to 46°C). If it does not, rotate the adjustment screw by using a at blade screwdriver until the temperature is in the proper range. See Fig. 5. Next, check that the reference pressure is in the range indicated in the Head Pressure table in the Performance Data section. If it is not in the
Top View
proper range, verify the refrigerant charge.
3) Check that the condenser drain temperature is stable.
Adjustment Screw
CW – Higher CCW – Lower
Fig. 5
41

V. Maintenance

The maintenance schedule below is a guideline. More frequent maintenance may be required depending on water quality, the appliance's environment, and local sanitation regulations
WARNING
• Only qualied service technicians should service the appliance.
• To reduce the risk of electric shock, do not touch the control switch or service switch with damp hands
• Before servicing: Move the control switch to the "OFF" position and turn off the power supply. Place the disconnect in the "OFF" position. Lockout/Tagout to prevent the power supply from being turned back on inadvertently.
CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews are securely in place after any maintenance is done to the icemaker. Make sure that none have fallen into the dispenser unit/ice storage bin.
Maintenance Schedule
Frequency Area Task
Daily Scoop Clean the ice scoop using a neutral cleaner. Rinse thoroughly after
cleaning. Bi-Weekly Air Filters Inspect. Wash with warm water and neutral cleaner if dirty. Monthly External Water
Filters Icemaker Exterior Wipe down with a clean, soft cloth. Use a damp cloth containing a
Underside of Icemaker and Top Kits; Bin Door and Snout
Yearly Icemaker and
Dispenser Unit/Ice Storage Bin Liner
Water Supply Inlet Close the icemaker water supply line shut-off valve and drain the water
Condenser Inspect. Clean if necessary by using a brush or vacuum cleaner. More
Water Hoses Inspect the water hoses and clean/replace if necessary.
Check for proper pressure and change if necessary.
neutral cleaner to wipe off oil or dirt build up. Clean any chlorine staining
(rust colored spots) using a non-abrasive cleanser.
Wipe down with a clean cloth and warm water.
Clean and sanitize per the cleaning and sanitizing instructions provided
in the instruction manual or maintenance label on the icemaker.
system. Clean the water supply inlet screen.
frequent cleaning may be required depending on location.
42

VI. Preparing the Appliance for Periods of Non-Use

NOTICE
• When storing the appliance for an extended time or in sub-freezing temperatures, follow the instructions below to prevent damage.
• To prevent damage to the water pump, do not operate the appliance with the control switch in the "WASH" position when the water tank is empty.
When the appliance is not used for two or three days under normal conditions, it is sufficient to move the control switch to the "OFF" position. When storing the appliance for an extended time or in sub-freezing temperatures, follow the instructions below.
1. Remove the water from the icemaker water line:
1) Turn off the power supply, then remove the front panel. Disconnect the dispense solenoid wire harness and set the front panel aside.
2) Move the control switch on the control box to the "OFF" position.
3) Close the icemaker water supply line shut-off valve and open the icemaker water supply line drain valve.
4) Allow the line to drain by gravity.
5) Attach a compressed air or carbon dioxide supply to the icemaker water supply line drain valve.
6) Make sure at least 3 min. have elapsed since you turned off the power supply. Make sure the control switch is in the "ICE" position.
7) Replace the front panel in its correct position, then turn on the power supply.
8) Blow the icemaker water supply line out using the compressed air or carbon dioxide supply.
2. Remove the water from the water tank:
1) Turn off the power supply, then remove the front panel.
2) Move the service switch to the "DRAIN" position, then move the control switch to the "SERVICE" position.
3) Replace the front panel in its correct position, then turn on the power supply for 2minutes.
4) After 2 min., turn off the power supply, then remove the front panel.
5) Move the control switch to the "OFF" position.
6) Reconnect the dispense solenoid wire harness and replace the front panel in its correct position.
7) Turn on the power supply and dispense all ice from the icemaker. After dispensing all of the ice, turn off the power supply.
8) Close the icemaker water supply line drain valve.
43
3. On water-cooled model, remove the water from the water-cooled condenser:
1) Make sure the power supply is off, then remove the front panel. Disconnect the dispense solenoid wire harness and set front panel aside. Remove the left side panel.
2) Close the condenser water supply line shut-off valve. If connected to a closed loop system, also close the condenser return line shut-off valve.
3) Open the condenser water supply line drain valve. If connected to a closed loop system, also open the condenser return line drain valve.
4) Attach a compressed air or carbon dioxide supply to the condenser water supply line drain valve.
5) Open the water regulating valve by using a screwdriver to pry up on the spring retainer underneath the spring. While holding the valve open, blow out the condenser using the compressed air or carbon dioxide supply until water stops coming out.
6) Close the drain valve(s).
7) Replace the left side panel in its correct position, then reconnect the dispense solenoid wire harness and replace the front panel in its correct position.
44

VII. Disposal

The appliance contains refrigerant and must be disposed of in accordance with applicable national, state, and local codes and regulations. Refrigerant must be recovered by properly certied service personnel.
45

VIII. Technical Information

We reserve the right to make changes in specications and design without prior notice.
A. Specication and Performance Data Sheets
Pressure data is recorded at 5 min. into freezing cycle. The data not in bold should be used for reference only.

1. DKM-500BAJ

Specification Sheet
AC SUPPLY VOLTAGE 115/60/1 AMPERAGE 13.5 A ( 5 Min. Freeze AT 104°F / WT 80°F) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kW H/100 lbs.) 1240(5.56) 1130(4.98) WATER gal./24HR (gal./100 lbs.) 89(16.6) 202(37.0) ICE PRODUCTION PER CYCLE 7.2 lbs. (3.3 kg) 360pcs. APPROXIMATE STORAGE CAPACITY 140 lbs. (64 kg) APPROXIMATE ICE DISPENSE RATE 13 lbs/min. (6 kg/min) BIN CONTROL SYSTEM Proximity Switch with Delay REFRIGERANT CHARGE R404A, 1 lb. 12.2 oz. (800g)
Performance Data Sheet
APPROXIMATE ICE PRODUCTION PER 24 HR.
lbs./day kg./day APPROXIMATE ELECTRIC CONSUMPTION
watts 100/38 APPROXIMATE WATER CONSUMPTION PER 24 HR.
gal./day m3/day FREEZING CYCLE TIME
min. 100/38 HARVEST CYCLE TIME
min. 100/38 HEAD PRESSURE
PSIG kg/cm2G SUCTION PRESSURE
PSIG kg/cm2G
AMBIENT TEMP.
(ºF/ºC)
70/21 545 247
100/38 540 245 533 242 523 237
70/21 80/27 90/32
70/21 202 0.76 80/27 176 0.67 125 0.47 130 0.49 90/32 169 0.64 89 0.34 86 0.33
100/38 133 0.50 88 0.33 84 0.32
70/21 80/27 90/32
70/21 80/27 90/32
70/21 242 17.0 80/27 258 18.1 290 20.4 324 22.8 90/32 263 18.5 313 22.0 347 24.4
100/38 270 19.0 321 22.6 378 26.6
70/21 51 3.6 53 3.7 54 3.8 80/27 53 3.7 56 3.9 56 3.9 90/32 53 3.7 58 4.1 59 4.1
100/38 53 3.7 58 4.1 59 4.1
50/10 70/21 90/32
1130 1162 1177 1155 1205 1203 1162 1240 1245 1155 1241 1250
15 16 17 16 17 16 18 19 16 18 20
3.5 3.1 2.9
3.2 2.6 2.6
3.1 2.1 2.1
2.6 2.1 2.1
WATER TEMP. (ºF/ºC)
542 246 536 243
169 0.64 156 0.59
263 18.5 295 20.7
18
TOTAL HEAT OF REJECTION FROM CONDENSER TOTAL HEAT OF REJECTION FROM COMPRESSOR 1,700 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
9,100 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
46

2. DKM-500BWJ

Specification Sheet
AC SUPPLY VOLTAGE 115/60/1 AMPERAGE 12 A ( 5 Min. Freeze AT 104°F / WT 80°F) MINIMUM CIRCUIT AMPACITY 20 A MAXIMUM FUSE SIZE 20 A ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F ELECTRIC W (kW H/100 lbs.) 1000(4.79) 960(4.26) WATER gal./24HR (gal./100 lbs.) 90(18.0) 126(23.4) WATER COOLED CONDENSER 515(103) 266(49) gal./24HR (gal./100 lbs.) ICE PRODUCTION PER CYCLE 7.2 lbs. (3.3 kg) 360pcs. APPROXIMATE STORAGE CAPACITY 140 lbs. (64 kg) APPROXIMATE ICE DISPENSE RATE 13 lbs/min. (6 kg/min) BIN CONTROL SYSTEM Proximity Switch with Delay REFRIGERANT CHARGE R404A, 1 lb. 2 oz. (510g)
Performance Data Sheet
APPROXIMATE ICE PRODUCTION PER 24 HR.
lbs./day kg./day APPROXIMATE ELECTRIC CONSUMPTION
watts 100/38 APPROXIMATE WATER CONSUMPTION PER 24 HR.
gal./day m3/day FREEZING CYCLE TIME
min. 100/38 HARVEST CYCLE TIME
min. 100/38 HEAD PRESSURE
PSIG kg/cm2G SUCTION PRESSURE
PSIG kg/cm2G
AMBIENT TEMP.
(ºF/ºC)
70/21 540 245 80/27 531 241 513 233 492 223 90/32 528 240 500 227 479 217
100/38 523 237 495 225 460 209
70/21 80/27 90/32
70/21 393 1.49 80/27 440 1.67 537 2.03 635 2.41 90/32 455 1.72 605 2.29 704 2.66
100/38 552 2.09 628 2.38 794 3.01
70/21 80/27 90/32
70/21 80/27 90/32
70/21 278 19.5 80/27 280 19.7 283 19.9 286 20.1 90/32 280 19.7 285 20.0 289 20.3
100/38 281 19.8 286 20.1 292 20.5
70/21 53 3.7 54 3.8 55 3.8 80/27 53 3.8 54 3.8 55 3.9
90/32 54 3.8 55 3.9 56 3.9
100/38 54 3.8 55 3.9 57 4.0
50/10 70/21 90/32
960 972 983 969 987 996 972 1000 1010 973 1002 1020
18 18 19 18 19 18 19 20 18 19 21
2.6 2.4 2.4
2.5 2.2 2.3
2.4 2.1 2.0
2.3 2.0 2.0
WATER TEMP. (ºF/ºC)
528 240 509 231
455 1.72 549 2.08
19
280 19.7 283 19.9
TOTAL HEAT OF REJECTION FROM CONDENSER TOTAL HEAT OF REJECTION FROM COMPRESSOR 1,400 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)] WATER FLOW FOR CONDENSER 30 gal./h [AT 100ºF (38ºC) / W T 90ºF (32ºC)] PRESSURE DROP OF COOLING WATER LINE less than 10 PSIG
7,700 BTU/h [AT 90ºF (32ºC) / W T 70ºF (21ºC)]
47

B. Wiring Diagram

1. DKM-500B_J
*
48
* High-Pressure Switch
Air-Cooled Model Water-Cooled Model
PSIG
0
22
PSIG 384±
0
22
Cut-in 327±22 PSIG 284±22 PSIG
Cut-out 412±
Loading...