Only qualified service technicians should attempt to service or maintain this
unit. No such service or maintenance should be undertaken until the technician
has thoroughly read this Service Manual.
HOSHIZAKI provides this manual primarily to assist qualified service technicians in the
service and maintenance of the unit.
Should the reader have any questions or concerns which have not been satisfactorily
addressed, please call, write or send an e-mail message to the HOSHIZAKI Technical
Support Department for assistance.
HOSHIZAKI AMERICA, INC.
618 Highway 74 South
Peachtree City, GA 30269
NOTE: To expedite assistance, all correspondence/communication MUST include the
following information:
• Model Number
• Serial Number
• Complete and detailed explanation of the problem
2
Page 3
Please review this manual. It should be read carefully before the unit is serviced or
maintenance operations are performed. Only qualified service technicians should service
and maintain the unit. This manual should be made available to the technician prior to
service or maintenance.
CONTENTS
I. Specifications ...................................................................................................................... 5
II. General Information ........................................................................................................... 6
A. Construction .................................................................................................................. 6
B. Sequence of Operation ................................................................................................. 7
1. One Minute Fill Cycle .............................................................................................. 7
C. Preparing the Icemaker for Long Storage ................................................................... 45
4
Page 5
AC SUPPLY VOLTAGE115/60/1
AMPERAGE13.3 A ( 5 Min. Freeze AT 104°F / WT 80°F)
MINIMUM CIRCUIT AMPACITY15 A
MAXIMUM FUSE SIZE15 A
APPROXIMATE ICE PRODUCTIONAmbientWATER TEMP. (°F)
PER 24 HR.Temp.(°F)507090
lbs./day ( kg/day )70*466 (211)448 (203)420 (191)
Reference without *marks80453 (205)425 (193)395 (179)
90448 (203)*406 (184)376 (170)
100390 (177)399 (181)*348 (158)
SHAPE OF ICECrescent Cube
ICE PRODUCTION PER CYCLE7.2 lbs. (3.2 kg) 360 pcs.
APPROXIMATE STORAGE CAPACITY200 lbs (91 Kg)
APPROXIMATE ICE DISPENSING SPEED13 lbs/min(6 kg/min)
ELECTRIC & WATER CONSUMPTION90/70°F70/50°F
ELECTRIC W (kWH/100 lbs.)1150 (6.8)1049 (5.4)
WATER gal./24HR (gal./100 lbs.)66 (16.3)110 (23.6)
EXTERIOR DIMENSIONS (WxDxH)30" x 28" x 77" With 6" Flanged Legs
EXTERIOR FINISHStainless Steel, Galvanized Steel (Rear)
INTERIOR FINISHPolyethylene 1 pc. Mol
d
INSULATIONPolyurethane Foam
WEIGHTNet 385 lbs. ( 175 kg ), Shipping 410 lbs. (186 kg)
CONNECTIONS - ELECTRICCord Connection
- WATER SUPPLYInlet 1/2" FPT
- DRAINOutlet 3/4" FPT x 2
CUBE CONTROL SYSTEMFloat Switch
HARVESTING CONTROL SYSTEMHot Gas and Water, Thermistor and Timer
ICE MAKING WATER CONTROLTimer Controlled. Overflow
COOLING WATER CONTROLN/A
BIN CONTROL SYSTEMProximity Switch with Delay
COMPRESSORHermetic, Model RS55C2E-CAA-219
CONDENSERAir-cooled, Fin and tube type
EVAPORATORVertical type, Stainless Steel and Copper
REFRIGERANT CONTROLThermostatic Expansion Valve
REFRIGERANT CHARGER-404A, 2lbs (907g)
DESIGN PRESSUREHigh 467 PSIG, Low 170 PSIG
P.C. BOARD CIRCUIT PROTECTIONHigh Voltage Cut-out ( Internal )
COMPRESSOR PROTECTIONAuto-reset Overload Protector ( Internal )
REFRIGERANT CIRCUIT PROTECTIONAuto-reset High Pressure Control Switch
LOW WATER PROTECTIONFloat Switch
ACCESSORIES -SUPPLIEDN/A
OPERATING CONDITIONSVOLTAGE RANGE104 - 127 V
AMBIENT TEMP.45 -100° F
WATER SUPPLY TEMP.45 - 90° F
WATER SUPPLY PRESSURE10 - 113 PSIG
I. Specifications
A. DKM-500BAH
Note: We reserve the right to make changes in specifications and design without prior
notice.
5
Page 6
II. General Information
A. Construction
1. DKM-500BAH
Bin Cover
Inlet Water Valve
Expansion
Valve
Water Pump
Float Switch
Mechanical Bin
Control
Circulating Valve
Hot Gas Valve
Spray Tubes
Drain Valve
Water Supply
Inlet
Ice Cube Guide
Bin
Front Panel
Dispense Switch
Condenser
Dispense Switch
Connector
Condenser
Fan Motor
Drain Pan
Control
Switches
Agitator
Shutter
Chain
Solenoid
Assembly
Spout
Extension
Gear Motor
Assembly
Drier
Compressor
Strainer
Control Box
6
Page 7
B. Sequence of Operation
The steps in the sequence are as outlined below. When power is supplied, a 5 second
delay occurs at startup. Note that the order of the LEDs from the outer edge of the board
is 1, 4, 3, 2.
1. One Minute Fill Cycle
LED 4 is on. WV opens and the fill period begins. After 1 minute, the board checks for a
closed F/S. If F/S is closed, the harvest cycle begins. If not, the unit will not start without
adequate water in the sump. This serves as a low water safety to protect the water pump.
WV will remain energized through additional 1 minute cycles until water enters the sump
and F/S closes.
2. Initial Harvest Cycle
LEDs 1, 4, and 2 are on. WV remains open, Comp energizes, HGV opens, and harvest
begins. As the evaporator warms, the thermistor located on the suction line checks for a
48°F (9°C) temperature. When 48°F (9°C) is reached, a 3.9 kΩ signal turns the harvest
over to the adjustable harvest timer which is factory set for normal conditions. The timer
has settings of 60, 90, 120, and 180 seconds (dip switch 1 & 2). When the harvest timer
completes its count down, the harvest cycle is complete and the freeze cycle starts. The
minimum total time allowed by the board for a complete harvest cycle is 2 minutes.
3. Freeze Cycle
LED 1 is on. Comp continues to run, PM and FMS energize, HGV and WV close and
the freeze cycle starts. For the first 5 minutes the control board will not accept a signal
from F/S. This 5 minute minimum freeze acts as a short cycle protection. At the end of
5 minutes, F/S assumes control. As ice builds on the evaporator the water level in the
sump lowers. The freeze continues until F/S opens and terminates ice production.
4. Pump-Out Cycle
LEDs 1, 3, and 2 are on. Comp continues to run, HGV opens, and FMS de-energizes.
PM stops for 2 seconds. SR energizes, restarting PM and taking water from the sump
and forcing it to go through DV and down the drain. When the pump-out timer stops
counting, the pump out is complete.
Pump out always occurs on the 2nd harvest after startup. Then, depending on the control
board setting, pump out occurs every cycle, or every 2nd, 5th or 10th cycle (dip switch
5 & 6).
5. Normal Harvest Cycle
LEDs 1, 4, and 2 are on. Comp continues to run, HGV remains open and WV opens.
As the evaporator warms, the thermistor reaches 48°F (9°C). The control board then
receives the thermistor's 3.9 kΩ signal and starts the harvest timer. The water valve is
open during harvest for a maximum of 6 minutes or the length of harvest, whichever is
shorter. When the harvest timer completes its count down, the harvest cycle is complete
and the next freeze cycle starts.
Note: The unit continues to cycle through 3, 4 and 5 sequence until the bin control is
activated (within first 5 minutes of freeze) and shuts the unit down.
Legend:
switch; HGV–hot gas valve; PM–pump motor; SR–Service Relay; WV–inlet water
valve
Comp–compressor; DV–Drain Valve; FMS–self-contained fan motor; F/S–float
7
Page 8
Cycle
4. Pump-Out
PM stops for 2 sec., SR
energizes, starting PM &
Comp continues
DV for 10/20 sec. each 1,
2, 5, or 10 cycles.
HGV energized
FMS de-energized
3. Freeze Cycle
2. Harvest Cycle
• Minimum freeze time: 5 minutes
• Maximum freeze time: freeze timer setting
• Bin control can only shut down unit within
F/S in
control
5 minute timer
in control
first 5 minutes of freeze cycle
1 to 3 minute timer
in control
F/S closed
F/S Check
F/S
Freeze cycle
operation turned
over to
Comp continues
HGV de-energized
WV de-energized
PM energized
Thermistor temp
reaches 48°F (9°C)
(3.9 kΩ or less)
Harvest timer starts
FMS energized
F/S open
If F/S is open, compressor stops and cycle returns to 1 minute fill
control
Thermistor in
• Maximum inlet water valve time: 6 minutes
• Maximum harvest time: 20 minutes
DKM-500BAH Sequence Flow Chart and Component Operation
Fill Cycle
1. One Minute
F/S closed
F/S Check
Comp energized
WV Energized
HGV energized
WV continues
F/S open
Cycle Steps
"E" board will have
Initial startup always
5 second delay
begins here
8
Comp–compressor; DV–drain valve; FMS–self-contained fan motor; F/S–float switch;
Legend:
HGV–hot gas valve; PM–pump motor; SR–service relay; WV–inlet water valve
Page 9
C. Control Board
• A HOSHIZAKI exclusive solid-state control is employed in the DKM-500BAH Crescent
Cube Icemaker / Dispenser.
• All units are pretested and factory-adjusted.
CAUTION
1. Fragile, handle very carefully.
2. A control board contains integrated circuits, which are susceptible to failure
due to static discharge. It is especially important to touch the metal part of
the unit when handling or replacing the board.
3. Do not touch the electronic devices on the board or the back of the board to
prevent damage to the board.
4. Do not change wiring and connections. Do not misconnect K3, K4 and K5,
because the same connector is used for the thermistor, float switch and
mechanical bin control.
5. Always replace the whole board assembly if it goes bad.
6. Do not short out power supply to test for voltage.
9
Page 10
1. Control Board Layout
Control Products "E" Control Board
Alarm Reset Switch
Backup Freeze
Timer LED
Backup Harvest
Timer LED
Alarm Buzzer
Dip Switch
Output Test Switch
(used to test relays on board)
Connector K3
Harvest Control
(thermistor)
Connector K4
Mechanical Bin
Control
Power LED
(lights when
power is supplied
to the board)
Relay LEDs (4)
(indicate which
relays are energized
as listed below)
LED 2
Hot Gas Valve (HGV)
Self-Contained Fan
Motor (FMS) (FMS
off when LED on)
LED 3
Pump Motor (PM)
(on at pump out only)
LED 4
Water Valve (WV)
LED 1
Compressor (Comp)
Transformer
Connector
Microprocessor
(board revision level
indicated by last 2
digits on label)
Connector K5
Float Switch
Part Number
Connector K1
Pins #1 through #10
#1, 9 Magnetic Contactor
#2 Hot Gas Valve
#3 Self-Contained Fan Motor (FMS)
#4 Pump Motor (icemaking)
#5 Pump Motor (drain)
#6 Water Valve
#7, 10 Power (line, bin control)
#8 Open
Switch for "C" board
and "ALPINE" board
(service boards only)
Control Board
Part Number2A1410-01 (factory); 2A1410-02 (service)
TypeHOS-001A (Control Products - 10 Pin)
10
Page 11
2. Features
a) Maximum Water Supply Period – 6 minutes
Inlet water valve opening, in the harvest cycle, is limited by the harvest timer. The water
valve cannot remain open longer than the maximum period. The water valve can close in
less than six minutes if the harvest cycle is completed.
b) Harvest Backup Timer and Freeze Timer
The harvest backup timer shuts down the icemaker if, for two cycles in a row, the harvest
cycle takes more than 20 minutes to complete. The control board will signal this problem
using 2 beeps every 3 seconds.
The freeze timer shuts down the icemaker if, for two cycles in a row, the freeze cycle
takes longer than the time specified to complete. The control board will signal this
problem using 3 beeps every 3 seconds. The time is factory set using dip switches 9 &
10.
The reset button on the control board must be pressed with power on to reset either of
these safeties.
c) High Temperature Safety
The temperature of the suction line in the refrigeration circuit is limited by the high
temperature safety. This protects the unit from excessively high temperatures. If the
evaporator temperature rises above 127 ± 7°F (53 ± 4°C), the thermistor operates the
safety. This shuts down the circuit and the icemaker automatically stops.
The control board will signal this problem using 1 beep every 3 seconds. The reset button
on the control board must be pressed with power on to reset the safety.
d) Low Water Safety
The control board checks the position of the float switch at the end of the initial one
minute water fill cycle and at the end of each harvest cycle.
If the float switch is in the up position (electrical circuit closed), the control board changes
to the ice making cycle. If the float switch is in the down position (electrical circuit open),
the control board changes to additional one minute water fill cycles until water enters
the sump and the float switch closes. When the float switch closes, the control board
changes to the ice making cycle. The unit will not start without adequate water in the
sump. This serves as a low water safety to protect the water pump.
e) High Voltage and Low Voltage Cut-outs
The maximum and minimum allowable supply voltages of this icemaker are limited by the
high voltage and low voltage cut-outs.
If miswiring (especially on single phase 3 wire models) causes excessive voltage
(147Vac ±5% or more) on the control board, the high voltage cut-out shuts down the
circuit in 3 seconds and the icemaker automatically stops. The control board will signal
this problem using 7 beeps every 3 seconds.
The icemaker also automatically stops in cases of insufficient voltage (92Vac ±5% or
less). The control board will signal this problem using 6 beeps every 3 seconds.
When the proper supply voltage is resumed, the icemaker automatically starts running
again.
11
Page 12
f) LED Lights and Audible Alarm Safeties
The red LED indicates proper control voltage and will remain on unless a control voltage
problem occurs. At startup a 5 second delay occurs while the board conducts an internal
timer check. A short beep occurs when the power switch is turned OFF.
The green LEDs 1 through 4 energize and sequence from initial startup as listed in the
table below. Note that the order of the LEDs from the outer edge of the board is 1, 4, 3, 2.
For more information, see "II.B. Sequence of Operation."
Sequence StepLED
1 Minute Fill Cycle
Harvest Cycle
Freeze Cycle
Pump Out1, 3, and 2Comp, HGV,
The built in safeties shut down the unit and have alarms as follows:
No. of Beeps
(every 3 sec.)
1High Evaporator Temp.
2Harvest Backup Timer
4WV60 seconds
1, 4, and 2WV, HGV,
1Comp, PM,
Type of Alarm
(temperature > 127°F)
(53°C)
(harvest > 20 min. for two
cycles in a row)
Energized
Components
Comp
FMS
PM, SR, DV
Min.Max.Avg.
2 minutes20 minutes3 to 5 minutes
5 minutesfreeze timer
10 seconds 20 seconds factory setting
Check for harvest problem (stuck HGV or
relay), hot water entering unit, or shorted
thermistor.
Orange LED marked H TIMER lights up.
Check for open thermistor, HGV not
opening, TXV leaking by, low charge, or
inefficient compressor.
Time LEDs are On
setting
Notes
30 to 35 minutes
3Freeze Timer
(freeze > specified setting
for two cycles in a row)
Timer is factory set using
dip switches 9 & 10
4Short Circuit
(between the K4 connection on the control board
and the bin control)
5Open Circuit
(between the K4 connection on the control board
and the bin control)
To manually reset the above safeties, press the alarm reset button with the power
supply on.
Yellow LED marked F TIMER lights up.
Check for F/S stuck closed (up), WV
leaking by, HGV leaking by, TXV not
feeding properly, low charge, or inefficient
compressor.
Resistor wire harness shorted. Check
and replace wire harness if necessary.
Resistor wire harness circuit open or
control board open. Check and replace
component if necessary.
12
Page 13
No. of Beeps
(every 3 sec.)
Type of Alarm
Notes
Legend:
6Low Voltage
(92Vac ±5% or less)
7High Voltage
(147Vac ±5% or more)
Comp–compressor; DV–Drain Valve; FMS–self-contained fan motor; F/S–float
Red LED will turn off if voltage protection
operates.
The control voltage safeties automatically
reset when voltage is corrected.
switch; HGV–hot gas valve; PM–pump motor; SR–Service Relay; TXV– thermostatic expansion valve; WV–inlet water valve
3. Controls and Adjustments
a) Default Dip Switch Settings
The dip switch is factory-adjusted to the following positions:
Dip Switch No.12345678910
DKM-500BAHON OFF OFF OFF ON ON ON OFF OFF ON
Freeze Timer (9 & 10)
Normally in the OFF position.
Mechanical Bin Control
Pump-Out Frequency Control (5 & 6)
Pump-Out Timer (3 & 4)
Harvest Timer (1 & 2)
b) Harvest Control – Thermistor
A thermistor (semiconductor) is used for a harvest control sensor. The resistance varies
depending on the suction line temperatures. The thermistor detects the temperature of
the evaporator outlet to start the harvest timer. No adjustment is required. If necessary,
check for resistance between thermistor leads, and visually check the thermistor
mounting, located on the suction line next to the evaporator outlet.
Check a thermistor for resistance by using the following procedure:
1) Disconnect the connector K3 on the board.
2) Remove the thermistor. See "V.H. Removal and Replacement of Thermistor."
3) Immerse the thermistor sensor portion in a glass containing ice and water for 2 or 3
minutes.
4) Verify the temperature of the glass, then check for resistance between thermistor leads.
See the table above for temperature and resistance values. Normal reading is within
3.5 to 7 kΩ. Replace the thermistor if it exceeds the normal reading.
c) Harvest Timer (dip switch 1 & 2)
The harvest timer starts counting when the thermistor reads 48°F (9°C) at the
evaporator outlet.
No adjustment is required under normal use, as the harvest timer is adjusted to the
suitable position. However, a setting longer than the factory setting may be advised in
cases where the flush provided at harvest needs to be prolonged for extra cleaning.
Before changing this setting, call the HOSHIZAKI Technical Support Department at
1-800-233-1940 for recommendations. Keep in mind that setting the harvest timer to a
longer setting will decrease 24 hour production.
Dip Switch SettingTime
No. 1No. 2
(seconds)
OFFOFF60
ONOFF90
OFFON120
ONON180
d) Pump-Out Timer (dip switch 3 & 4)
When a freeze cycle is completed, the pump motor stops, and the icemaker resumes
operation in 2 seconds. Then, during cycles when a pump out is called for, the pump
motor drains the water tank for the time determined by the pump-out timer. The pumpout timer also acts in place of the harvest timer during cycles with a pump out.
The pump-out timer is factory-adjusted, and no adjustment is required.
Dip Switch Setting
No. 3No. 4
OFFOFF10150
ONOFF10180
OFFON10120
ONON20180
T1: Time to drain the water tank
T2: Harvest timer at pump out
Time (seconds)
T1
T2
Pump out always occurs on the 2nd harvest after startup. Then, depending on the pumpout frequency control setting (dip switch 5 & 6), pump out occurs every cycle, or every
2nd, 5th or 10th cycle.
14
Page 15
e) Pump-Out Frequency Control (dip switch 5 & 6)
The pump motor drains the water tank at the frequency set by the pump-out frequency
control.
The pump-out frequency control is factory-adjusted to drain the water tank every 10
cycles, and no adjustment is required. However, where water quality is bad and the
icemaker needs a pump drain more often, the pump-out frequency can be adjusted as
shown in the table below.
Dip Switch Setting
No. 5No. 6
OFFOFFevery cycle
ONOFFevery 2 cycles
OFFONevery 5 cycles
ONONevery 10 cycles
f) Freeze Timer (dip switch 9 & 10)
Frequency
CAUTION
Adjust to proper specification, or the unit may not operate correctly.
The freeze timer setting determines the maximum allowed freeze time to prevent
possible freeze-up issues. Upon termination of freeze timer, machine initiates the harvest
cycle. After 2 consecutive timer terminations, machine will shut down, possibly indicating
a problem.
The freeze timer is factory adjusted and no adjustment is required.
Dip Switch SettingTime
No. 9No. 10
OFFOFF60
(minutes)
OFFON50
ONOFF70
ONON60
g) Bin Control
CAUTION
Dip Switch No. 7 must be set to the ON position. If No. 7 is set to the OFF
position, the machine will run continuously, causing a freeze-up condition.
This machine uses a lever-actuated proximity switch (mechanical bin control) to control
the ice level in the storage bin. No adjustment is required. The bin control is factoryadjusted.
(1) Explanation of Operation
A resistor wire harness connects the bin control to the K4 connector on the control
board. When the bin control is calling for ice (proximity switch closed), a 7.9 KΩ reading
is sent to the control board to continue operation. When the bin control is activated in the
bin full position (proximity switch open), a 15.8 KΩ signal is sent to the control board to
15
Page 16
shut down the unit. However, to prevent incomplete batches of ice from forming on the
evaporator, the control board will only shut down the machine within the first 5 minutes of
the freeze cycle. If ice pushes the lever in after the first five minutes of the freeze cycle,
the control board will allow the machine to complete the freeze cycle and the following
harvest cycle before shutting down the machine.
Dip switch number 7 must be in the ON position for the control board to receive input
from the bin control.
4. Bin Control Troubleshooting
a) Machine Will Not Start
1) Move dip switch no. 7 to the OFF position. If the machine starts up within a few
seconds, the bin control is the likely problem. If the machine does not start up, refer to
section "IV. Service Diagnosis" to verify that non-bin control related issues are resolved.
2) Check to make sure shipping tape has been removed and the wires are connected
properly.
3) Check to make sure no obstruction prevents the lever from moving to the bin empty
position.
4) Check proximity switch continuity to make sure it is not stuck open.
b) Machine Will Not Shut Off
1) Refer to Section "IV. Service Diagnosis" to verify that non-bin control related issues are
resolved.
2) Dip switch no. 7 should be in the ON position. If the switch is in the OFF position, the
control board will not receive input from the bin control.
3) Check to make sure no obstruction prevents the lever from moving to the bin full
position.
4) Push the lever in within the first 5 minutes of the freeze cycle. If the machine does not
shut off, check the resistance values of the resistor wire harness. You should read
approximately 15.8 K
the K4 connector on the control board when the lever is in the bin full position (proximity
switch open). If this reads approximately 7.9 KΩ, the resistors may be miswired or the
proximity switch may be stuck closed. Switch the black and white wires in the terminal
housing or order a replacement wire harness. If this does not resolve the problem,
replace the bin control assembly.
5. Control Board Check Procedure
Before replacing a control board that does not show a visible defect and that you suspect
is bad, always conduct the following check procedure. This procedure will help you verify
your diagnosis.
Ω between the black terminal and the red terminal that connect to
1) Check the dip switch settings to assure that #3, 4, 7, 8, 9, & 10 are in the factory default
position. Output test switch S3 should be OFF. Switches 1, 2, 5, & 6 are cleaning
adjustments and the settings are flexible.
2) Turn the control switch to ICE and check for proper control voltage. If the red LED is ON,
the control voltage is good. If the red LED is OFF, check the control transformer circuit.
16
Page 17
3) Check the 115 volt input at the 10-pin connector. Check the brown wire at pin #10 to a
white neutral wire for 115 volts. (Always choose a white neutral wire to establish a good
neutral connection when checking voltages.) A jumper also feeds 115 volts into pin #7.
If no voltage is present, check the 115 volt supply circuit.
4) The output test switch S3 provides a relay sequence test. With the control switch in the
OFF position, place S3 ON and then move the control switch to the ICE position. The
correct lighting sequence should be none, 2, 3, 4, 1, and 4, normal sequence every 5
seconds. Components (e.g., the compressor) will cycle during the test. Note that the
order of the relays from the outer edge of the board is 1, 4, 3, 2.
Note: If the LEDs light in a different sequence or the 5–second interval does not occur,
the control board is bad and should be replaced.
5) After checking the sequence, place S3 back in the OFF position. The S3 switch must
remain in the OFF position during normal operation. This completes the output test and
the unit is now in the 1 minute fill cycle.
6. Control Board Replacement
The application switch located between relay X3 & X4 must be set to match the original
board application. Place this switch in the ALP position if there is no white wire supplied
to the K1 connector. If there is a white wire, place the switch in the C position. If this
switch is placed in the wrong position either the compressor contactor will remain
energized with the control switch OFF or the unit will not start.
The dip switches should be adjusted to the factory default settings as outlined in this
manual. 8 must remain in the OFF position.
D. Switches
Two control switches are used to control operation. These switches are referred to as the
"control switch" and the "service switch" and are located on the control box.
1. Control Switch
The control switch has three positions: OFF for power off; ICE for icemaking, and
SERVICE to activate the service switch.
2. Service Switch
When the control switch is in the SERVICE position, the control switch supplies power
to the service switch and the machine is in service mode. The service switch has three
positions: DRAIN, CIRCULATE, and WASH. See the information below for details of each
function.
Note:
1. When the service switch is activated, power is supplied to the water pump in all
three positions.
2. When the control switch is in the OFF position or in the ICE position, the service
switch has no power and can be left in any position.
a) DRAIN
This model utilizes a pump-out drain system. When the service switch is active and
placed in the DRAIN position, power is supplied to the pump, service relay and drain
valve.
17
Page 18
b) CIRCULATE
When the service switch is active and placed in the CIRCULATE position, power is
supplied to the pump only. This operation can be used to circulate cleaner for extended
periods of time over the outside surface of the evaporator.
c) WASH
This model utilizes a solenoid operated cleaning (bypass) valve. When the service
switch is active and placed in the WASH position, power is supplied to the pump and the
cleaning valve. This cleans both the inside and outside of the evaporator plate assembly.
18
Page 19
III. Technical Information
A. Water Circuit and Refrigeration Circuit
1. DKM-500BAH
19
Page 20
B. Wiring Diagram
1. DKM-500BAH
(12V)
* Pressure Switch
Cut-out412.5 PSIG
Cut-in327±21.3 PSIG
*
(Service
Relay)
20
Page 21
C. Timing Chart
*1 The icemaker does not complete a defrost cycle in the first 2 or 3 minutes. See "II.C.3.
Controls and Adjustments."
21
Page 22
*1 The pump motor waits for 2 seconds before starting a drain cycle. See "II.C.3. Controls
and Adjustments."
*2 The icemaker does not complete a defrost cycle in the first 2 or 3 minutes. See "II.C.3.
Controls and Adjustments."
22
Page 23
70/21466211448203420191
80/27453205425193395179
90/32448203406184376170
lbs./day kg./da
y
100/38390177399181348158
70/21
80/27
90/32
watts100/38
70/211100.42
970.37880.33
80/271000.38800.30750.29
90/32970.37660.25590.22
gal./day m3/day
100/381440.55650.24530.20
70/21
80/27
90/32
min.100/38
70/21
80/27
90/32
min.100/38
70/2126218.4
28219.830521.5
80/2727719.530821.732923.2
90/3228219.833023.235324.8
PSIG kg/cm2G
100/3828420.033523.637426.3
70/21563.9574.0584.1
80/27574.0584.1604.2
90/32574.0594.2614.3
PSIG kg/cm2G
100/38574.0604.2624.4
SUCTION PRESSURE
HARVEST CYCLE TIME
HEAD PRESSURE
2.0
3.9
2.6
3.3
2.6
2.0
3.5
19
19
19
21
WATER TEMP. (ºF/ºC)
AMBIENT TEMP.
(ºF/ºC)
50/1070/2190/32
APPROXIMATE ICE
PRODUCTION PER 24 HR.
APPROXIMATE ELECTRIC
CONSUMPTION
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
FREEZING CYCLE TIME
1100
1078
1117
1150
1155
1049
1071
1078
2.0
2.0
1103
1133
1170
1189
21
23
24
26
3.3
22
19
23
22
3.1
2.7
TOTAL HEAT OF REJECTION8098 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
D. Performance Data
1. DKM-500BAH
Note:
1. Pressure data is recorded at 5 minutes into freezing cycle. The data not in bold
2. We reserve the right to make changes in specifications and design without prior
should be used for reference only.
notice.
23
Page 24
IV. Service Diagnosis
A. 10-Minute Diagnostic Procedure
The 10 minute check out procedure is basically a sequence check which can be used
at unit start-up or for system diagnosis. Using this check out procedure will allow you
to diagnose electrical system and component failures in approximately 10 minutes
under normal operating conditions of 70°F or warmer air and 50°F or warmer water
temperatures. Before conducting a 10 minute checkout, check for correct installation,
proper voltage per unit nameplate and adequate water supply. As you go through the
procedure, check to assure the components energize and de-energize correctly. If not,
those components and controls are suspect. Check for voltage at the 10-pin connector.
Note that an activated bin control may have the machine off (bin control will only shut
down the machine within the first 5 minutes of the freeze cycle).
1) Turn power OFF and access the control box.
2) Turn power ON and place the control switch in ICE position. A 5 second delay occurs.
3) One Minute Fill Cycle – The inlet water valve is energized. After 1 minute, the control
board checks the float switch. If the float switch is closed, the unit cycles to harvest. If
closed, continue to step 4. If the float switch is open, the unit repeats the 1 minute fill
cycle until water enters and the float switch closes (low water safety protection during
initial start up and at the end of each harvest). Diagnosis: If the water valve does not
open, check for no supply voltage at water valve terminals, bad coil, or plugged screen
or external filter (no water flow). If unit fails to start harvest, check for open float switch
or bad 1 minute timer in board.
4) Initial Harvest Cycle – Inlet water valve remains energized, contactor coil energizes
to start the compressor, and the hot gas valve energizes. The evaporator warms and
the thermistor senses 48°F (9°C). The control board then receives the thermistor's
3.9 kΩ signal and turns operation of harvest over to the harvest timer. The timer
completes counting (1 to 3 minutes). The unit then cycles to freeze. Diagnosis: Check
if compressor is running, hot gas valve is open, water valve still open. Average harvest
cycle at factory setting is 2 to 3 minutes. How long does initial harvest last? 1.5 minutes
after initial harvest begins, touch the compressor discharge line. Is it hot? If not check
refrigerant pressures and compressor operation. If it is hot, touch the inlet line to the
evaporator. Is it hot? If it is hot and the freeze cycle is not starting, check the harvest
timer adjustment, the thermistor for open circuit, the discharge line temperature,
compressor efficiency, and if the hot gas valve is fully open.
5) Freeze Cycle – Compressor remains energized, pump motor and fan motor energize.
The inlet water valve and hot gas valve de-energize. The unit is held in freeze by a
5 minute short cycle protection timer. After 5 minutes, the freeze cycle operation is
transferred to the float switch for freeze termination. During the first 5 minutes of freeze,
confirm that the evaporator temperature drops. After 7 minutes in freeze, remove the
black float switch lead from the K5 connector. The unit should immediately switch to the
pump-out cycle. Diagnosis: If the evaporator is not cold, check to see if the hot gas
valve is still open or if the expansion valve is not opening properly, if the water valve
is continuing to fill the reservoir, if there are improper unit pressures, or an inoperative
compressor. If the unit remains in freeze with the float switch removed, replace the
board.
Note: Normal freeze cycle will last 20 to 40 minutes depending on model and
24
Page 25
conditions. Cycle times and pressures should follow performance data provided
in this manual.
6) Pump-Out Cycle (10/20 second pump out) – the compressor remains energized,
the hot gas valve energizes, the fan motor de-energizes, the pump motor stops for
2 seconds. The service relay energizes, restarting the pump motor and taking water
from the sump and forcing it to go through the drain valve and down the drain for 10/20
seconds. This removes contaminants from the water reservoir. Check for clear tubing at
the drain valve housing and check the unit drain for water flow. Diagnosis: If the pump
motor does not run, check the circuit, service relay and capacitor. Check for proper
voltage. If water does not pump out, remove the drain valve and check/clean the valve
assembly.
7) Normal Harvest Cycle – same as the initial harvest cycle – Return to step 4.
Note: Unit continues to cycle until bin control is satisfied or power is switched OFF. (The
pump out cycle can be adjusted to occur every cycle, or every 2, 5, or 10 cycles.
The factory default is every 10 cycles.) The unit always restarts at the 1 minute fill
cycle.
B. Diagnostic Charts
1. Ice Making
a) No Ice Production
ProblemPossible CauseRemedy
[1] The icemaker will not
start.
a) Power Supply1. OFF position.1. Move to ON position.
2. Loose connection.2. Tighten.
3. Bad contacts.3. Check for continuity and
replace.
4. Voltage too high.4. Check and get
recommended voltage.
b) Fuse (Inside fused
disconnect, if any)
c) Control Switch1. OFF position.1. Move to ICE position.
d) Bin Control
See the information
to the right and also
see "II.C.4. Bin Control
Troubleshooting."
1. Blown.1. Check for short circuit and
replace.
2. Bad contacts.2. Check for continuity and
replace.
1. Tripped with bin filled
with ice.
2. Bad contacts (stuck
open).
3. Resistor wire harness. 3. Check resistance. Should
1. Remove ice.
2. Check for continuity and
replace.
be approximately 7.9 KΩ
when calling for ice
(proximity switch closed).
e) High Pressure Control1. Bad contacts.1. Check for continuity and
replace.
2. Dirty air filter or
condenser.
3. Ambient temperature
too warm.
2. Clean.
3. Reduce temperature.
25
Page 26
ProblemPossible CauseRemedy
4. Refrigerant
overcharged.
5. Fan not operating. 5. See chart 1. a) [6]
4. Recharge.
[2] Water continues to
be supplied, and the
icemaker will not
start.
[3] Compressor will
not start or stops
operating.
6. Refrigerant line or
components plugged.
f) Transformer1. Coil winding opened
or shorted.
g) Wiring to Control Board 1. Loose connections or
open.
h) Thermistor1. Leads shorted or
opened and high
temperature or harvest
backup timer safety
operates. (1 beep or 2
beep alarm)
i) Hot Gas Valve1. Continues to open
in freeze cycle and
freeze timer safety
operates. (3 beep
alarm)
j) Water Supply Line1. Water supply off and
water supply cycle
does not finish.
k) Inlet Water Valve1. Mesh filter or orifice
gets clogged and
water supply cycle
does not finish.
2. Coil winding opened.2. Replace.
3. Wiring to water valve. 3. Check for loose
l) Control Board1. Defective or in alarm. 1. See "II.C.5. Control Board
m)Control Switch1. SERVICE position.1. Move to ICE position.
2. Bad contacts.2. Check and replace.
a) Float Switch1. Connector
disconnected.
2. Leads opened or
defective switch.
3. Float does not move
freely.
b) Control Board1. Defective.1. See "II.C.5. Control Board
a) Magnetic Contactor1. Bad contacts.1. Check for continuity and
2. Coil winding opened.2. Replace.
b) Start Capacitor or Run
Capacitor
1. Defective.1. Replace.
6. Clean and replace drier.
1. Replace.
1. Check for continuity and
replace.
1. See "II.C.3. Controls and
Adjustments, b) Harvest
Control."
1. Check for hot gas valve
stuck open and replace.
1. Check and get
recommended pressure.
1. Clean.
connection or open, and
replace.
Check Procedure."
1. Place in position.
2. Check and replace.
3. Clean or replace.
Check Procedure."
replace.
26
Page 27
ProblemPossible CauseRemedy
[4] Water continues to
be supplied in freeze
cycle.
[5] No water comes from
spray tubes. Water
pump will not start, or
freeze cycle time is
too short.
c) Internal Overload
Protector Open (check
1 through 3 to the right
and d through f below)
d) Starter1. Bad contacts.1. Check and replace.
e) Compressor1. Wiring to compressor. 1. Check for loose
f) Control Board1. No power to contactor. 1. See "II.C.5. Control Board
a) Inlet Water Valve1. Diaphragm does not
b) Control Board1. Defective.1. See "II.C.5. Control Board
a) Water Supply Line1. Water pressure too
b) Inlet Water Valve1. Dirty mesh filter or
c) Water System1. Water leaks.1. Check connections for
d) Pump Motor1. Motor winding opened. 1. Replace.
1. Loose terminal.1. Tighten or replace.
2. Voltage.2. Check and correct.
3. Dirty condenser.3. Clean.
2. Coil winding opened.2. Replace.
connection or open, and
replace.
2. Defective.2. Replace.
3. Protector tripped.3. Reduce temperature.
Check Procedure."
1. Check for water leaks with
close.
low and water level in
water tank too low.
orifice and water level
in water tank too low.
2. Clogged.2. Clean.
icemaker off.
Check Procedure."
1. Check and get
recommended pressure.
1. Clean.
water leaks, and replace.
[6] Fan motor will
not start, or is not
operating.
2. Bearing worn out.2. Replace.
3. Wiring to pump motor. 3. Check for loose
connection or open, and
replace.
4. Defective capacitor.4. Replace.
5. Defective or bound
impeller.
e) Control Board1. Defective.1. See "II.C.5. Control Board
a) Fan Motor1. Motor winding opened. 1. Replace.
2. Bearing worn out.2. Replace.
3. Wiring to fan motor.3. Check for loose
4. Defective capacitor.4. Replace.
5. Fan blade bound.5. Check and replace.
5. Replace and clean.
Check Procedure."
connection or open, and
replace.
27
Page 28
ProblemPossible CauseRemedy
b) Control Board1. Defective.1. See "II.C.5. Control Board
Check Procedure."
[7] All components
run, but no ice is
produced.
a) Refrigerant1. Undercharged.1. Check for leaks and
recharge.
2. Air or moisture
trapped.
b) Compressor1. Defective valve.1. Replace.
c) Hot Gas Valve1. Continues to open in
freeze cycle.
d) Inlet Water Valve1. Water valve is wide
open during freeze.
2. Replace drier and
recharge.
1. Check and replace.
1. Check for water leaks with
icemaker off.
b) Evaporator is Frozen Up
ProblemPossible CauseRemedy
[1]Freeze cycle time is
too long.
[2]All ice formed on
evaporator does not
fall into bin in harvest
cycle.
[3]Othera)Spray Tubes1. Clogged.1. Clean
a)Float Switch1. Leads short-circuit or
defective switch.
2. Float does not move
freely.
b)Inlet Water Valve1. Diaphragm does not
close.
c) Control Board1. Defective.1. See "II.C.5. Control Board
a)Evaporator1. Scaled up.1. Clean.
b)Water Supply Line1. Water pressure too
low.
c) Water Filter System1. Dirty/Restricted1. Replace filter.
d)Inlet Water Valve1. Dirty mesh filter or
orifice.
2. Diaphragm does not
close.
e) Ambient and/or water
temperature.
f) Thermistor1. Out of position or
g)Control Board1. Harvest timer is set
b)Water System1. Dirty.1. Clean.
c) Refrigerant1. Undercharged.1. Check for leaks and
1. Too cool.1. Increase temperature.
loose attachment.
too short.
2. Defective.2. See "II.C.5. Control Board
2. Out of position.2. Place in position.
1. Check and replace.
2. Clean or replace.
1. Check for water leaks with
icemaker off.
Check Procedure."
1. Check and get
recommended pressure.
1. Clean.
2. Check for water leaks with
icemaker off.
1. See "V.H. Removal
and Replacement of
Thermistor."
1. Adjust longer, referring
to "II.C.3. Controls and
Adjustments, c) Harvest
Timer."
Check Procedure."
recharge.
28
Page 29
ProblemPossible CauseRemedy
d)Expansion Valve1. Bulb out of position or
loose attachment.
2. Defective.2. Replace.
e)Hot Gas Valve1. Coil winding opened.1. Replace.
2. Plunger does not
move.
3. Wiring to hot gas
valve.
f) Ice Cube Guide1. Out of position and ice
trapped.
1. Place in position.
2. Replace.
3. Check for loose
connection or open, and
replace.
1. Place in position.
g)Water Supply Line1. Too small; requires
3/8" OD line dedicated
per machine.
h)Water Filter 1. Flow rate too small.1. Replace with filter that has
1. Increase water line size.
larger flow rate.
c) Low Ice Production
ProblemPossible CauseRemedy
[1] Freeze cycle time is
long.
[2] Harvest cycle time is
long.
a) See chart 1. a) [3] and check dirty air filter or condenser, ambient or water
temperature, water pressure, and refrigerant charge.
b) See chart 1. b) [1] and check float switch, inlet water valve and control board.
c) Check pump, hot gas valve, expansion valve, refrigeration check valve, and
compressor.
a) See chart 1. b) [2] and check control board, thermistor, evaporator, ambient
and/or water temperature, water supply line, inlet water valve, and hot gas
valve.
d) Abnormal Ice
ProblemPossible CauseRemedy
[1] Small cubes.a) Ice Cube Guide1. Out of position.
Circulated water falls
into bin.
b) See chart 1. a) [5] and check water supply line, inlet water valve, water system,
pump motor, and control board.
c) Drain Valve1. Dirty.1. Clean.
1. Place in position.
[2] Cloudy or irregular
cubes.
a) See chart 1. b) [1] and 1. b) [3], and check float switch, inlet water valve, control
board, spray tubes, water system, refrigerant charge, and expansion valve.
a) Bin ControlSee "II.C.4. Bin Control Troubleshooting."
b) Control Board1. Defective.1. See "II.C.5. Control Board
Check Procedure."
b) Fan Motor1. Bearings worn out.1. Replace
2. Fan blade deformed.2. Replace fan blade.
3. Fan blade does not
move freely.
c) Compressor1. Bearings worn out or
cylinder valve broken.
2. Mounting pad out of
position.
d) Refrigerant Lines1. Rub or touch other
lines or surfaces.
a) Drain Line(s)1. Plugged.1. Clean.
b) Icemaker and Bin1. Drains not run
separately.
c) Ice Cube Guide1. Out of position.
Circulated water falls
into bin.
3. Replace.
1. Replace.
2. Reinstall.
1. Replace.
1. Separate the drain lines.
1. Place in position.
2. Dispensing
ProblemPossible CauseRemedy
[1] No ice dispensed.a) Power Supply1. OFF position.1. Move to ON position.
2. Loose connection.2. Tighten.
3. Bad contacts.3. Check for continuity and
replace.
4. Voltage too high.4. Check and get
recommended voltage.
b) Fuse (Inside Fused
Disconnect, if any)
c) Dispense Switch1. Connector from front
d) Gear Motor1. Thermal protector is
1. Blown.1. Check for short circuit
and replace.
1. Connect.
panel not connected
to control box.
2. Bad contacts.2. Check for continuity and
replace.
3. Loose connection.3. Tighten.
1. Allow to cool.
tripped.
2. Gear motor winding
opened.
3. Bearing worn out.3. Replace.
2. Replace.
30
Page 31
ProblemPossible CauseRemedy
4. Wiring to gear motor.4. Check for loose
connection or open
circuit, and replace wiring
as needed.
5. Defective capacitor.5. Replace.
6. Agitator rotates in
reverse direction.
e) Solenoid1. Solenoid winding
open.
2. Wiring to solenoid.2. Check for loose
3. Overload due to
loosening screws.
f) Mechanism1. Chain out of position
or loose.
2. Corrosion.2. Apply oil.
3. Key of sprocket is not
in position.
4. Bad alignment of
sprocket.
6. Check leads and reverse
the connections.
1. Replace
connection or open
circuit, and replace wiring
as needed.
3. After tightening, apply
thread sealant to the
parts.
1. Place in position or
tighten.
3. Place in position.
4. Readjust.
g) Ice Storage1. No ice or little ice in
[2] Abnormal noise.a) Gear Motor or Gear
Head
b) Mechanism1. Bad setting.1. Apply oil and readjust.
c) Solenoid1. Overload due to
5. Foreign matter
interrupting agitator.
storage bin.
2. Ice bridge or block
formed.
1. Bearing worn out.1. Replace.
2. Grease leaks.2. Supply grease and
2. Bad alignment of
sprocket.
3. Foreign matter
interrupting agitator.
loosening screws.
2. Foreign matter on
plunger.
5. Remove foreign matter.
1. Make ice.
2. Break with a poker.
replace O-ring.
2. Readjust.
3. Remove foreign matter.
1. After tightening, apply
thread sealant to the
parts.
2. Clean.
31
Page 32
V. Removal and Replacement of Components
IMPORTANT
Ensure all components, fasteners and thumbscrews are securely in place after
the equipment is serviced.
IMPORTANT
1. The Polyol Ester (POE) oils used in R-404A units can absorb moisture
quickly. Therefore it is important to prevent moisture from entering the system
when replacing or servicing parts.
2. Always install a new filter drier every time the sealed refrigeration system is
opened.
3. Do not leave the system open for longer than 15 minutes when replacing or
servicing parts.
A. Service for Refrigerant Lines
1. Refrigerant Recovery
The icemaker unit is provided with two refrigerant access valves–one on the low-side
and one on the high-side line. Using proper refrigerant practices recover the refrigerant
from the access valves and store it in an approved container. Do not discharge the
refrigerant into the atmosphere.
2. Evacuation and Recharge (R-404A)
1) Attach charging hoses, a service manifold and a vacuum pump to the system. Be sure
to connect charging hoses to both high and low-side access valves.
IMPORTANT
The vacuum level and vacuum pump may be the same as those for current
refrigerants. However, the rubber hose and gauge manifold to be used for
evacuation and refrigerant charge should be exclusively for POE oils.
2) Turn on the vacuum pump. Never allow the oil in the vacuum pump to flow backward.
3) Allow the vacuum pump to pull down to a 29.9" Hg vacuum. Evacuating period depends
on pump capacity.
4) Close the low-side valve and high-side valve on the service manifold.
5) Disconnect the vacuum pump, and attach a refrigerant service cylinder to the highside line. Remember to loosen the connection, and purge the air from the hose. See
the nameplate for the required refrigerant charge. Hoshizaki recommends only virgin
refrigerant or reclaimed refrigerant which meets ARI Standard No. 700-88 be used.
6) A liquid charge is recommended for charging an R-404A system. Invert the service
cylinder. Open the high-side, service manifold valve.
7) Allow the system to charge with liquid until the pressures balance.
32
Page 33
8) If necessary, add any remaining charge to the system through the low-side. Use a
throttling valve or liquid dispensing device to add the remaining liquid charge through
the low-side access port with the unit running.
9) Close the two refrigerant access valves, and disconnect the hoses and service
manifold.
10) Cap the access valves to prevent a possible leak.
B. Brazing
DANGER
1. Refrigerant R-404A itself is not flammable at atmospheric pressure and
temperatures up to 176°F (80°C).
2. Refrigerant R-404A itself is not explosive or poisonous. However, when
exposed to high temperatures (open flames), R-404A can be decomposed to
form hydrofluoric acid and carbonyl fluoride both of which are hazardous.
3. Always recover the refrigerant and store it in an approved container. Do not
discharge the refrigerant into the atmosphere.
4. Do not use silver alloy or copper alloy containing arsenic.
5. Do not use R-404A as a mixture with pressurized air for leak testing.
Refrigerant leaks can be detected by charging the unit with a little refrigerant,
raising the pressure with nitrogen and using an electronic leak detector.
Note: Because the pipes in the evaporator case are specially coated to resist corrosion,
it is important to make connections outside the evaporator case when possible. If
it is necessary to braze inside the evaporator case, use sandpaper to remove the
coating from the brazing connections before unbrazing the components.
C. Removal and Replacement of Compressor
IMPORTANT
Always install a new drier every time the sealed refrigeration system is opened.
Note: When replacing a compressor with a defective winding, be sure to install the
new start capacitor and start relay supplied with the replacement compressor.
Due to the ability of the POE oil in the compressor to absorb moisture quickly,
the compressor must not be opened more than 15 minutes for replacement or
service. Do not mix lubricants of different compressors even if both are charged
with R-404A, except when they use the same lubricant.
1) Turn off the power supply.
2) Remove the panels. Be sure to disconnect the dispense switch connector from the
control box when removing the front panel.
3) Recover the refrigerant and store it in an approved container.
33
Page 34
4) Remove the terminal cover on the compressor, and disconnect the compressor wiring.
5) Remove the discharge and suction pipes using brazing equipment.
6) Remove the hold-down bolts, washers and rubber grommets.
7) Remove the compressor. Unpack the new compressor package.
8) Attach the rubber grommets of the prior compressor.
9) Place the compressor in position, and secure it using the bolts and washers.
10) Remove the drier, then place the new drier in position.
11) Remove plugs from the suction, discharge and process pipes.
12) Braze all fittings while purging with nitrogen gas flowing at a pressure of 3 to 4 PSIG.
13) Check for leaks using nitrogen gas (140 PSIG) and soap bubbles.
14) Evacuate the system, and charge it with refrigerant. See the nameplate for the required
refrigerant charge.
15) Connect the terminals, and replace the terminal cover in its correct position.
16) Replace the panels in their correct positions.
17) Turn on the power supply.
D. Removal and Replacement of Drier
IMPORTANT
Always install a new drier every time the sealed refrigeration system is opened.
Do not replace the drier until after all other repair or replacement has been
made.
1) Turn off the power supply.
2) Remove the panels. Be sure to disconnect the dispense switch connector from the
control box when removing the front panel.
3) Recover the refrigerant and store it in an approved container.
4) Remove the drier.
5) Install the new drier with the arrow on the drier in the direction of the refrigerant flow.
Use nitrogen gas at a pressure of 3 to 4 PSIG when brazing the tubings.
6) Check for leaks using nitrogen gas (140 PSIG) and soap bubbles.
7) Evacuate the system, and charge it with refrigerant. See the nameplate for the required
refrigerant charge.
8) Replace the panels in their correct positions.
9) Turn on the power supply.
34
Page 35
E. Removal and Replacement of Expansion Valve
IMPORTANT
Sometimes moisture in the refrigeration circuit exceeds the drier capacity and
freezes up at the expansion valve. Always install a new drier every time the
sealed refrigeration system is opened. Do not replace the drier until after all
other repair or replacement has been made.
1) Turn off the power.
2) Remove the panels. Be sure to disconnect the dispense switch connector from the
control box when removing the front panel.
3) Recover the refrigerant and store it in an approved container.
4) Remove the insulation and the expansion valve bulb on the suction line.
5) Remove the expansion valve cover, and disconnect the expansion valve using brazing
equipment.
6) Braze the new expansion valve with nitrogen gas flowing at the pressure of 3 to 4 PSIG.
WARNING
Always protect the valve body by using a damp cloth to prevent the valve from
overheating. Do not braze with the valve body exceeding 250°F (121°C).
7) Install the new drier.
8) Check for leaks using nitrogen gas (140 PSIG) and soap bubbles.
9) Evacuate the system, and charge it with refrigerant. See the nameplate for the required
refrigerant charge.
10) Attach the expansion valve bulb to the suction line in the same location as the previous
bulb. The bulb should be at the 12 o'clock position on the tube. Be sure to secure the
bulb with the clamp and holder and to insulate it.
11) Place the new set of expansion valve covers in position.
12) Replace the panels in their correct positions.
13) Turn on the power supply.
F. Removal and Replacement of Hot Gas Valve
IMPORTANT
1. Always use a copper tube of the same diameter and length when replacing
the hot gas lines; otherwise the performance may be reduced.
2. Always install a new drier every time the sealed refrigeration system is
opened. Do not replace the drier until after all other repair or replacement
has been made.
3. Always replace the strainer when replacing the hot gas valve.
35
Page 36
1) Turn off the power supply.
2) Remove the panels. Be sure to disconnect the dispense switch connector from the
control box when removing the front panel.
3) Recover the refrigerant and store it in an approved container.
4) Remove the screw and the solenoid.
5) Disconnect the hot gas valve using brazing equipment.
6) Install the new valve.
CAUTION
Always protect the valve body by using a damp cloth to prevent the valve from
overheating. Do not braze with the valve body exceeding 250°F (121°C).
7) Install the new drier.
8) Check for leaks using nitrogen gas (140 PSIG) and soap bubbles.
9) Evacuate the system, and charge it with refrigerant. See the nameplate for the required
refrigerant charge.
10) Cut the leads of the solenoid allowing enough lead length to reconnect using closed
end connectors.
11) Connect the new solenoid leads.
12) Attach the solenoid to the valve body, and secure it with a screw.
13) Replace the panels in their correct positions.
14) Turn on the power supply.
G. Removal and Replacement of Evaporator
IMPORTANT
1. Always install a new drier every time the sealed refrigeration system is
opened. Do not replace the drier until after all other repairs or replacement
have been made.
2. Because the pipes in the evaporator section are specially coated to resist
corrosion, it is important to make the new evaporator inlet and outlet piping
connections outside the evaporator section as described below.
1) Turn off the power supply.
2) Remove the outer panels and the evaporator insulation panels. Be sure to disconnect
the dispense switch connector from the control box when removing the front panel.
3) Recover the refrigerant and store it in an approved container.
4) Remove the spray tubes and the insulations at the "U" shaped notch where the
refrigeration tubings go through the molded chassis.
5) Remove the insulation tube, and disconnect the evaporator inlet piping at the tee before
the expansion valve. Disconnect the evaporator outlet piping before the heat exchanger.
36
Page 37
6) Remove the pop rivets securing the evaporator, then lift out the evaporator.
7) Install the new evaporator.
8) Install the new drier.
9) Check for leaks using nitrogen gas (140 PSIG) and soap bubbles.
10) Evacuate the system, and charge it with refrigerant. See the nameplate for the required
refrigerant charge.
11) Replace the removed parts in the reverse order of which they were removed.
12) Replace the evaporator insulation panels and the outer panels in their correct positions.
13) Turn on the power supply.
H. Removal and Replacement of Condenser
1) Turn off the power supply.
2) Remove the panels, including the rear panel next to the condenser. Be sure to
disconnect the dispense switch connector from the control box when removing the front
panel.
3) Recover the refrigerant and store it in an approved container.
4) Disconnect the fan motor wiring harness from the back of the control box. Remove the
four bolts securing the fan motor assembly to the floor of the machine, then remove the
assembly.
5) Disconnect the condenser inlet and outlet piping.
6) Remove the screws securing the condenser assembly, then remove the assembly.
7) Remove the shroud from the old condenser and attach it to the new condenser.
8) Install the new condenser.
9) Install the new drier.
10) Check for leaks using nitrogen gas (140 PSIG) and soap bubbles.
11) Evacuate the system, and charge it with refrigerant. See the nameplate for the required
refrigerant charge.
12) Replace the removed parts in the reverse order of which they were removed.
13) Replace the panels in their correct positions.
14) Turn on the power supply.
37
Page 38
I. Removal and Replacement of Thermistor
IMPORTANT
1. Fragile, handle very carefully.
2. Always use a recommended sealant (High Thermal Conductive Type), Model
KE4560RTV manufactured by SHINETSU SILICONE, Part Code 60Y000-11,
or Part Code 4A0683-01 or equivalent.
3. Always use a recommended foam insulation (non-absorbent type) or
equivalent.
4. Do not shorten or cut the thermistor leads when installing it.
1) Turn off the power supply.
2) Remove the panels. Be sure to disconnect
the dispense switch connector from the
control box when removing the front panel.
3) Remove the control box cover.
4) Disconnect the thermistor leads from the
K3 connector on the control board.
Thermistor Lead Cable Tie
5) Remove the plastic cable ties, foam
insulation, thermistor holder and thermistor.
6) Scrape away the old sealant on the
thermistor holder and the suction pipe.
7) Wipe off moisture or condensation on the
suction pipe.
8) Smoothly apply recommended sealant (KE4560RTV, Part Code 60Y000-11 or
4A0683-01) to the thermistor holder concave.
9) Attach the new thermistor to the suction pipe in the same position as the previous
thermistor. Be very careful to prevent damage to the leads. Secure it using the
thermistor holder and recommended foam insulation.
10) Secure the insulation using the plastic cable ties.
11) Connect the thermistor leads through the bushing of the control box to the K3
connector on the control board.
Note: Do not cut the leads of the thermistor while installing it.
12) Replace the control box cover and the panels in their correct positions.
13) Turn on the power supply.
Foam Insulation Thermistor Holder
J. Removal and Replacement of Fan Motor
Note: When replacing a fan motor with defective winding, it is recommended that a new
capacitor be installed.
1) Turn off the power supply.
2) Remove the panels. Be sure to disconnect the dispense switch connector from the
control box when removing the front panel.
38
Page 39
3) Disconnect the fan motor wiring harness from the back of the control box. Remove the
four bolts securing the fan motor assembly to the floor of the machine, then remove the
assembly.
4) Remove the fan motor from the fan motor bracket.
5) Remove the fan blade from the old fan motor and attach it to the new fan motor.
6) Install the new fan motor, and replace the removed parts in the reverse order of which
they were removed.
7) Replace the panels in their correct positions.
8) Turn on the power supply.
K. Removal and Replacement of Inlet Water Valve
1) Turn off the power supply.
2) Close the water supply line shut-off valve.
3) Remove the panels. Be sure to disconnect the dispense switch connector from the
control box when removing the front panel.
4) Loosen the fitting nut. Be careful not to lose the washer.
5) Remove the screws securing the valve to the bracket.
6) Remove the screws attaching the bracket to the machine wall, then remove the bracket
from the unit.
7) Remove the valve outlet tubing by releasing the clamp.
8) Disconnect the terminals from the water valve.
9) Install the new water valve, and replace the removed parts in the reverse order of which
they were removed. Make sure the washer is in place in the fitting nut.
10) Open the water supply line shut-off valve.
11) Turn on the power supply.
12) Check for leaks.
13) Replace the panels in their correct positions.
L. Removal and Replacement of Pump Motor
1) Turn off the power supply.
2) Remove the panels. Be sure to disconnect the dispense switch connector from the
control box when removing the front panel.
3) Remove the three screws securing the float switch assembly, then remove the
assembly.
4) Remove the two screws securing the barrier directly over the pump, then remove the
barrier.
5) Remove the wiring connectors from the pump motor leads.
6) Remove the four screws securing the pump motor, disconnect the hoses, then remove
the pump motor.
39
Page 40
7) Install the new pump, and replace the removed parts in the reverse order of which they
were removed.
8) Turn on the power supply, and check for leaks.
9) Replace the panels in their correct positions.
M. Removal and Replacement of Spray Tubes
1) Turn off the power supply.
2) Remove the outer panels and the evaporator insulation panels. Be sure to disconnect
the dispense switch connector from the control box when removing the front panel.
3) Remove the rubber hoses from the spray tubes (water supply pipe).
4) Release the clamps, and disconnect the rubber hoses.
5) Remove the spray tubes.
6) Install the new spray tubes, and replace the removed parts in the reverse order of which
they were removed.
7) Replace the evaporator insulation panels and the outer panels in their correct positions.
8) Turn on the power supply.
N. Removal and Replacement of Gear Motor
1) Turn off the power supply.
2) Remove the panels. Be sure to disconnect
the dispense switch connector from the
control box when removing the front panel.
3) Disconnect the gear motor wiring harness
from the back of the control box.
4) Loosen the adjustment bolt, then loosen
the four bolts securing Gear Motor Bracket
(B).
5) Slide Gear Motor Bracket (B) up to its
highest position and retighten.
6) Remove the chain.
7) Loosen the socket set screw securing the
sprocket, then use a gear puller to remove
the sprocket.
8) Remove the bushing from the barrier and
slide the gear motor wires free of the
barrier. Release the wires from the wire tie
on the barrier.
9) While supporting the gear motor and
barrier, remove the four bolts securing
them to Gear Motor Bracket (B). Carefully
remove the motor and barrier.
Lower sprocket
takes a 2.5 mm
allen wrench.
Bushing
Sprocket
40
Adjustment Bolt
Bolts
Chain
Bolts
Gear Motor
Bracket (B)
Sprocket
Gear Motor
Barrier
Gear Motor
Bracket (B)
Bolt
Page 41
10) Install the new gear motor, assembling the removed parts in the reverse order of the
above procedure.
Note:
• When weight (2.2 Ib) is applied to the chain at the center, the displacement must be
0.31 to 0.51".
• Lubricant (Class SAE 20) must be applied to the chain using a cloth.
11) Replace the panels in their correct positions.
12) Turn on the power supply.
O. Removal and Replacement of Dispense Switch
1) Turn off the power supply.
2) Remove the front panel. Be sure to disconnect the dispense switch connector from the
control box when removing the front panel.
3) Remove the dispense switch assembly.
4) Install a new dispense switch.
5) Replace the front panel in its correct position.
6) Turn on the power supply.
P. Removal and Replacement of Solenoid
1) Turn off the power supply.
2) Remove the panels. Be sure to disconnect the dispense switch connector from the
control box when removing the front panel.
3) Disconnect the connectors from the solenoid leads.
4) Remove the solenoid, and install a new solenoid.
5) Connect the connectors to the solenoid leads.
6) Replace the panels in their correct positions.
7) Turn on the power supply.
41
Page 42
VI. Cleaning and Maintenance Instructions
IMPORTANT
Ensure all components, fasteners and thumbscrews are securely in place after
any maintenance or cleaning is done to the equipment.
A. Cleaning Instructions
To clean the machine, perform the cleaning and sanitizing procedures for the icemaker
and bin in the order in which they appear below.
WARNING
1. Hoshizaki recommends cleaning this unit at least once a year. More frequent
cleaning, however, may be required in some existing water conditions.
2. To prevent injury to individuals and damage to the icemaker, do not use
ammonia type cleaners.
3. Always wear liquid-proof gloves to prevent the cleaning and sanitizing
solutions from coming into contact with skin.
1. Cleaning Procedure – Icemaker
1) Dilute approximately 10.5 fl. oz. of recommended cleaner Hoshizaki "Scale Away" or
"LIME-A-WAY," (Economics Laboratory, Inc.) with 2 gallons of warm water.
2) Remove all ice from the evaporator and the bin.
Note: To remove cubes on the evaporator, turn off the power supply and turn it on
after 3 minutes. The defrost cycle starts and the cubes will be removed from the
evaporator.
3) Turn off the power supply.
4) Remove the front panel and disconnect the connector from the control box.
5) Move the control switch on the control box
Bin Control
Connector
to the SERVICE position. Then move the
service switch to the DRAIN position.
Thumbscrew
6) Replace the front panel in its correct position.
7) Turn on the power supply for 2 minutes.
8) Turn off the power supply.
Bin Cover
9) Remove the front panel.
10) Disconnect the bin control connector.
Remove the three thumbscrews securing
the bin cover, and remove the bin cover
Connector
with the bin control attached.
11) Pour the cleaning solution into the water tank.
Control
Box
12) Move the service switch to the WASH position.
13) Replace the front panel in its correct position.
Front
Panel
14) Turn on the power supply, and start the
washing process.
42
Bin
Page 43
15) Turn off the power supply after 30 minutes.
16) Remove the front panel.
17) Move the service switch to the DRAIN position.
18) Replace the front panel in its correct position.
19) Turn on the power supply for 2 minutes.
20) Turn off the power supply.
21) Remove the front panel.
22) Move the control switch to the ICE position.
23) Replace the front panel in its correct position.
24) Turn on the power supply to fill the water tank with water.
25) Turn off the power supply after 3 minutes.
26) Remove the front panel.
27) Move the control switch to the SERVICE position. Then move the service switch to the
WASH position.
28) Replace the front panel in its correct position.
29) Turn on the power supply to rinse off the cleaning solution.
30) Turn off the power supply after 5 minutes.
31) Remove the front panel.
32) Move the service switch to the DRAIN position.
33) Replace the front panel in its correct position.
34) Turn on the power supply for 2 minutes.
35) Turn off the power supply.
36) Remove the front panel.
37) Repeat the above steps 22 through 36 three more times to rinse thoroughly, then
proceed to "2. Sanitizing Procedure – Icemaker".
2. Sanitizing Procedure – Icemaker
1) Dilute approximately 1.0 fl. oz. of a 5.25% sodium hypochlorite solution (chlorine
bleach) with 2 gallons of warm water.
2) Pour the sanitizing solution into the water tank.
3) Move the service switch to the WASH position.
4) Replace the front panel in its correct position.
5) Turn on the power supply, and start the sanitizing process.
6) Turn off the power supply after 15 minutes.
7) Remove the front panel.
8) Move the service switch to the DRAIN position.
9) Replace the front panel in its correct position.
43
Page 44
10) Turn on the power supply for 2 minutes.
11) Turn off the power supply.
12) Remove the front panel.
13) Repeat steps 22 through 36 in "Cleaning Procedure – Icemaker" two times to rinse
thoroughly.
14) Move the control switch to the ICE position, then proceed to "3. Cleaning Procedure
– Bin".
3. Cleaning Procedure – Bin
1) Dilute approximately 5 fl. oz. of recommended cleaner Hoshizaki "Scale Away" or
"LIME-A-WAY," (Economics Laboratory, Inc.) with 1 gallon of warm water.
2) Make sure that the power supply is off.
3) Remove the grill and chute from the front panel.
4) Remove the shutter and spout extension as follows:
a. Remove the snap pin fitted to the shutter shaft. Shift the shaft to the left, pull out the
right side and slide out.
b. Remove the four thumbscrews securing the spout extension and remove the spout
extension.
5) Remove the two thumbscrews securing the bin control assembly to the bin cover. Note
the orientation of the stainless steel bracket, then remove the bin control and bracket
from the bin cover. Carefully remove the bin control paddle from the bin control body.
6) Scrub the inside of the bin, the agitator, the bin spout, the spout extension, the shutter,
the front panel spout, the grill, the chute, the bin cover, and the bin control assembly
using a nylon scouring pad, brushes and cleaning solution.
7) Rinse all parts thoroughly with clean water, then proceed to "4. Sanitizing Procedure
– Bin".
4. Sanitizing Procedure – Bin
Bin Control
Connector
Thumbscrew
Bin
1) Dilute approximately .5 fl. oz. of
a 5.25% sodium hypochlorite
solution (chlorine bleach) with
1 gallon of warm water.
2) Wash all parts from step 6 of
"Cleaning Procedure – Bin"
with the sanitizing solution.
3) Rinse all parts thoroughly
with clean water.
Bin Cover
Chute
Snap Pin
Connector
Agitator
Shutter
4) Reassemble all parts in the
reverse order of the removal
procedure.
5) Turn on the power supply.
6) Check for proper operation.
44
Front
Panel
Spout
Grill
Control
Box
Thumbscrew
Bin Spout
Spout
Extension
Page 45
B. Maintenance Instructions
1. Exterior Panels
To keep the exterior clean, wipe occasionally with a clean and soft cloth. Use a damp
cloth containing a neutral cleaner to wipe off oil or dirt buildup.
2. Air Filters
The plastic mesh air filters (located behind the louvers on either side of the unit)
remove dirt and dust from the air, and keep the condenser from getting clogged. As
the filters get clogged, the icemaker's performance will be reduced. Check the filters at
least twice a month. When they are clogged, use warm water and a neutral cleaner to
wash the filters.
3. Condenser
Check the condenser once a year and clean if required by using a brush or vacuum
cleaner. More frequent cleaning may be required depending on the location of the
icemaker.
C. Preparing the Icemaker for Long Storage
IMPORTANT
When shutting off the icemaker for an extended time, drain the water tank
and remove the ice from the bin. The bin should be cleaned and dried. Drain
the icemaker to prevent damage to the water supply line at sub-freezing
temperatures, using a foot or hand pump. Shut off the icemaker until proper air
temperature is resumed.
1) Turn off the power supply.
2) Remove the front panel and disconnect the connector from the control box.
3) Move the control switch on the control box to the SERVICE position. Then move the
service switch to the DRAIN position.
4) Replace the front panel in its correct position.
5) Turn on the power supply for 2 minutes to allow the machine to drain.
6) Turn off the power supply.
7) Remove the front panel.
8) Move the control switch to the OFF position.
9) Close the water supply line shut-off valve.
10) Remove ice from the bin, then clean and dry the bin.
11) Reconnect the connector from the front panel to the control box and replace the front
panel in its correct position.
IMPORTANT
When the icemaker is not used for two or three days, move only the control
switch to the OFF position.
45
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.