Only qualied service technicians should install and service the appliance. To
obtain the name and phone number of your local Hoshizaki Certied Service
Representative, visit www.hoshizaki.com. No service should be undertaken until
the technician has thoroughly read this Service Manual. Failure to service and
maintain the appliance in accordance with this manual will adversely affect safety,
performance, component life, and warranty coverage. Proper installation is the
responsibility of the installer. Product failure or property damage due to improper
installation is not covered under warranty.
Hoshizaki provides this manual primarily to assist qualied service technicians in the
service and maintenance of the appliance.
Should the reader have any questions or concerns which have not been satisfactorily
addressed, please call, send an e-mail message, or write to the Hoshizaki Technical
Support Department for assistance.
HOSHIZAKI AMERICA, INC.
618 Highway 74 South
Peachtree City, GA 30269
Attn: Hoshizaki Technical Support Department
Web Site: www.hoshizaki.com
NOTE: To expedite assistance, all correspondence/communication MUST include the
following information:
• Model Number
• Serial Number
• Complete and detailed explanation of the problem.
2
Page 3
IMPORTANT
This manual should be read carefully before the appliance is serviced. Read
the warnings and guidelines contained in this manual carefully as they provide
essential information for the continued safe use, service, and maintenance of the
appliance. Retain this manual for any further reference that may be necessary.
CONTENTS
Important Safety Information ................................................................................................. 4
I. General Information ............................................................................................................ 7
A. Construction .................................................................................................................. 7
B. Refrigeration Flow Chart ............................................................................................... 8
II. Sequence of Operation and Service Diagnosis ................................................................. 9
A. Sequence of Operation Flow Charts ............................................................................. 9
2. Temperature Setpoint ............................................................................................ 25
3. Changing the Temperature Display Scale (°F or °C) ............................................. 25
C. Defrost ........................................................................................................................ 26
D. Alarm Safeties ............................................................................................................. 26
E. Safety Devices ............................................................................................................ 27
F. Mullion/Perimeter Heater ............................................................................................. 27
IV. Replacement of Components ......................................................................................... 28
A. Service for Refrigerant Lines ....................................................................................... 28
B. Important Notes for Component Replacement ............................................................ 31
C. Door Reversal ............................................................................................................. 31
V. Maintenance .................................................................................................................... 32
VI. Preparing the Appliance for Periods of Non-Use ............................................................ 33
VII. Disposal ......................................................................................................................... 34
VIII. Technical Information .................................................................................................... 35
A. Electrical and Refrigerant Data ................................................................................... 35
B. Wiring Diagrams .......................................................................................................... 36
3
Page 4
Important Safety Information
Throughout this manual, notices appear to bring your attention to situations which could
result in death, serious injury, or damage to the appliance or damage to property.
WARNING Indicates a hazardous situation which could result in death or
serious injury.
NOTICEIndicates a situation which could result in damage to the
appliance or property.
IMPORTANTIndicates important information about the use and care of the
appliance.
WARNING
The appliance should be destined only to the use for which it has been expressly
conceived. Any other use should be considered improper and therefore dangerous.
The manufacturer cannot be held responsible for injury or damage resulting from
improper, incorrect, and unreasonable use. Failure to service and maintain the
appliance in accordance with this manual will adversely affect safety, performance,
component life, and warranty coverage.
To reduce the risk of death, electric shock, serious injury, or re, follow basic
precautions including the following:
• Only qualied service technicians should install and service the appliance.
• The appliance must be installed in accordance with applicable national, state, and
local codes and regulations.
• The appliance requires an independent power supply of proper capacity. Seethe
nameplate for electrical specications. Failure to use an independent power
supply of proper capacity can result in a tripped breaker, blown fuse, or damage
to existing wiring. This could lead to heat generation or re.
• To reduce the risk of electric shock, do not touch the plug or power switch with
damp hands.
• Make sure the power switch is in the "OFF" position before plugging in or
unplugging the appliance to reduce the risk of electric shock.
• Before servicing, move the power switch to the "OFF" position. Unplug the
appliance from the electrical outlet.
For 115VAC Models
• THE APPLIANCE MUST BE GROUNDED:The appliance is equipped with a
NEMA5-15 three-prong grounding plug to reduce the risk of potential shock
hazards. It must be plugged into a properly grounded, independent 3-prong wall
outlet. If the outlet is a 2-prong outlet, it is your personal responsibility to have a
qualied electrician replace it with a properly grounded, independent 3-prong wall
outlet. Do not remove the ground prong from the plug and do not use an adapter
plug. Failure to follow these instructions may result in death, electric shock, or re.
4
Page 5
WARNING, continued
For 208-230VAC Models
• THE APPLIANCE MUST BE GROUNDED:The appliance is equipped with a
NEMA L14-20 four-prong locking, grounding plug to reduce the risk of potential
shock hazards. It must be plugged into a properly grounded, independent 4-prong
wall outlet. If the outlet is a 3-prong outlet or a 4-prong non-locking outlet, it is your
personal responsibility to have a qualied electrician replace it with a properly
grounded, independent 4-prong locking wall outlet. Do not remove the ground
prong from the plug and do not use an adapter plug. After plugging in, twist the plug
clockwise to lock it into place. Failure to follow these instructions may result in death,
electric shock, or re.
For All Models
• The GREEN ground wire in the factory-installed power cord is connected to the
appliance. If it becomes necessary to remove or replace the power cord, be sure to
connect the power cord's ground wire.
• Do not use an extension cord.
• Do not use an appliance with a damaged power cord. The power cord should not
be altered, jerked, bundled, weighed down, pinched, or tangled. Such actions could
result in electric shock or re. To unplug the appliance, be sure to pull the plug, not
the cord, and do not jerk the cord. Before unplugging a 4-prong plug, rotate the plug
counter-clockwise to unlock it.
• Do not splash, pour, or spray water directly onto or into the appliance. This might
cause short circuit, electric shock, corrosion, or failure.
• Do not make any alterations to the appliance. Alterations could result in electric
shock, injury, re, or damage to the appliance.
• The appliance is not intended for use by persons (including children) with reduced
physical, sensory, or mental capabilities, or lack of experience and knowledge,
unless they have been given supervision or instruction concerning use of the
appliance by a person responsible for their safety.
• Children should be properly supervised around the appliance.
• Do not climb, stand, or hang on the appliance or door or allow children or animals to
do so. Do not climb into the appliance or allow children or animals to do so. Death or
serious injury could occur or the appliance could be damaged.
• Be careful not to pinch ngers when opening and closing the door. Be careful when
opening and closing the door when children are in the area.
• Open and close the doors with care. Doors opened too quickly or forcefully may
cause injury or damage to the appliance or surrounding equipment.
• Do not use combustible spray or place volatile or ammable substances near the
appliance. They might catch re.
• Keep the area around the appliance clean. Dirt, dust, or insects in the appliance
could cause harm to individuals or damage to the appliance.
• Do not throw anything onto the shelves or load any single shelf with more than
120lb. (54.5 kg) of product. They might fall off and cause injury.
5
Page 6
WARNING, continued
• Do not place anything on top of the appliance. Foreign objects or moisture could
enter the appliance and result in electric shock or re.
• The appliance is designed only for temporary storage of food. Employ sanitary
methods. Use for any other purposes (for example, storage of chemicals or medical
supplies such as vaccine and serum) could cause deterioration of stored items.
• Do not block air inlets or outlets, otherwise cooling performance may be reduced.
• Do not tightly pack the cabinet. Allow some space between items to ensure good air
ow. Also allow space between items and interior surfaces.
• Do not put warm or hot foods in the cabinet. Let them cool rst, or they will raise the
cabinet temperature and could deteriorate other foods in the cabinet or overload the
appliance.
• All foods should be wrapped in plastic lm or stored in sealed containers. Otherwise
foods may dry up, pass their smells onto other foods, cause frost to develop, result
in poor appliance performance, or increase the likelihood of cross-contamination.
Certain dressings and food ingredients, if not stored in sealed containers, may
accelerate corrosion of the evaporator, resulting in failure.
• Do not store items near the air outlet. They might freeze up and crack or break
causing a risk of injury or contamination of other food.
NOTICE
• Protect the oor when moving the appliance to prevent damage to the oor.
• Keep ventilation openings, in the appliance enclosure or in the built-in structure,
clear of obstruction. Do not place anything on top of the appliance. Blockage of
airow could negatively affect performance and damage the appliance.
• To prevent deformation or cracks, do not spray insecticide onto the plastic parts or
let them come into contact with oil.
• To avoid damage to the gasket, use only the door handle when opening and closing.
6
Page 7
I. General Information
A. Construction
Control Box
Power Switch
Compressor
Thermostatic Expansion Valve
Condenser Fan Motor
Condenser
Front Panel
Power Cord
Control Module
Light Switch
(glass door
models only)
Light
Door Switch
Door Lock
Door
Door
Gasket
Condensate Tube and Spring
Condensate Pan
Pressure Relief Valve
Model Shown: CR1S-FS
7
• Evaporator
• Cabinet Thermistor
• Defrost Thermistor
• Evaporator Fan Shroud
Page 8
B. Refrigeration Flow Chart
Condenser
High-Pressure Switch
Thermostatic
Expansion Valve
Defrost Heater and
Defrost Thermostat
(freezer only)
Condenser Fan
Evaporator Fans
(quantity depends on model)
Drier
Compressor
Defrost
Thermistor
Evaporator
Cabinet Thermistor
Condensate Pan
8
Page 9
II. Sequence of Operation and Service Diagnosis
A. Sequence of Operation Flow Charts
1. Refrigerator
DTh warms to
40°F (4.4°C) or
1-Hr Maximum
Defrost Timer
5. Defrost Termination
Terminates
Comp energized
ConFM energized
EvapFM energized
DTh in control
20-min.
Minimum
Defrost
36°F (2°C)
2-min. Comp off
timer starts
EvapFM energized
EvapFM energized
Comp de-energized
Comp de-energized
ConFM de-energized
ConFM de-energized
a) EvapFM de-energizes when door is opened on -FS models and
when upper door is opened on -HS models.
b) 2-min. minimum Comp on timer starts when Comp energizes.
c) 2-min. minimum Comp off timer starts when Comp de-energizes.
d) 20-min. minimum defrost time.
e) 1-hr. maximum defrost time.
Note:
f) Temperature displayed during defrost.
4. Defrost
2. Cool Down Achieved
2-Hr Comp
Cumulative Run
Timer Terminates
CTh warms
to 3°F (1.7°C)
above
setpoint
CTh cools
to 3°F (1.7°C)
below setpoint.
Factory default
Refrigerator Sequence Flow Chart
3. Cool Down Restart
CTh in control
2-min. Comp on
timer starts
Legend:
Comp-compressor
ConFM-condenser fan motor
CTh-cabinet thermistor
DTh-defrost thermistor
Comp energized
ConFM energized
EvapFM energized
EvapFM-evaporator fan motor
1. Startup/Cool Down
Cycle Steps
Slight
Delay at
Startup
EvapFM energized
Power On
9
Page 10
2. Freezer
DTh warms to 59°F (15°C)
5. Defrost Termination
MH energized
PH energized
DH de-energized
DrH de-energized
Comp energized (after delay)
ConFM energized (after delay)
EvapFM energized (after delay)
DTh in control
DTh is at or below 32°F (0°C)
and 4-hr. cumulative Comp
4. Defrost
run timer terminates
CTh warms
to 3°F (1.7°C)
above setpoint
DH energized
DrH energized
MH energized
PH energized
Comp de-energized
ConFM de-energized
EvapFM de-energized
Freezer Sequence Flow Chart
CTh cools to
3°F (1.7°C)
below setpoint.
Factory default
-4°F (-20°C)
2-min. Comp off
CTh in control
2-min. Comp on
timer starts
timer starts
EvapFM energized
MH energized
PH energized
Comp de-energized
ConFM de-energized
a) EvapFM de-energizes when door is opened on -FS models and when upper door is opened on -HS models.
b) 2-min. minimum Comp on timer starts when Comp energizes.
c) 2-min. minimum Comp off timer starts when Comp de-energizes.
d) 5-min. minimum defrost time.
e) 1-hr. maximum defrost time.
f) 3-min. Comp/ConFM delay timer starts when defrost termination temperature is met.
g) 7-minute EvapFM delay timer starts when defrost termination temperature is met (3-minute delay timer when defrost initiated manually)
h) 18-minute temperature display delay timer starts when defrost termination temperature is met (15-minute delay timer when defrost
initiated manually).
Comp energized
ConFM energized
EvapFM energized
MH energized
Note:
PH energized
2. Cool Down Achieved
1. Startup/Cool Down
3. Cool Down Restart
DTh reaches 32°F (0°C),
then 4-hr. cumulative
Comp run timer starts
Slight
Delay at
Startup
Power on
MH energized
PH energized
10
Legend:
Comp-compressor
ConFM-condenser fan motor
CTh-cabinet thermistor
DH-defrost heater
DrH-drain heater
DTh-defrost thermistor
EvapFM-evaporator fan motor
MH-mullion heater
PH-perimeter heater
Page 11
B. Service Diagnosis
WARNING
• The appliance should be diagnosed and repaired only by qualied service
personnel to reduce the risk of death, electric shock, serious injury, or re.
• Risk of electric shock. Use extreme caution and exercise safe electrical practices.
• Moving parts (e.g., fan blade) can crush and cut. Keep hands clear.
• Make sure all food zones are clean after the appliance is serviced.
NOTICE
• This appliance is not intended for outdoor use.
• Normal operating ambient temperature:
– Refrigerators and Solid Door Freezers 45°F to 100°F (7°C to 38°C)
– Glass Door Freezers 45°F to 80°F (7°C to 27°C)
Operation of the appliance, for extended periods, outside of this normal
temperature range may affect appliance performance.
• The appliance must not be located next to ovens, grills, or other high heat
producing equipment.
• The appliance must not be located in a corrosive environment.
• Minimum Clearance:
SideTopRear
3" (8 cm)12" (31 cm)1" (3 cm)
The diagnostic procedure is a sequence check that allows you to diagnose the electrical
system and components. Before proceeding, check for correct installation and proper
voltage per nameplate. Always choose a neutral (W) to establish a good neutral
connection when checking high voltages. If the display is in alarm, see "III.D. Alarm
Safeties."
IMPORTANT
The maximum allowable voltage variation is ±10 percent of the nameplate rating.
115VAC is used as a reference voltage when checking voltage to components.
Voltage may vary depending on power supply.
1. Factory Default Settings:
a) Temperature Settings: Refrigerator: 36°F (2°C); Freezer: -4°F (-20°C).
b) Temperature Display Scale: °F.
For further details, see "II.C. Control Module Check" or "III. Controls and Adjustments."
• There is a minimum 2-min. Comp on time and 2-min. Comp off time.
1) Move the power switch to the "OFF" position.
2) Unplug the appliance from the electrical outlet.
11
Page 12
3) Remove the control box cover.
4) Plug the appliance back into the electrical outlet.
5) Move the power switch to the "ON" position.
6) Conrm 115VAC at the power switch. On 3-section models, also conrm proper supply
voltage at the receptacle box (115VAC for refrigerator/208-230VAC for freezer).
1. Refrigerator
7) Startup/Cool Down–There is a slight delay, cabinet temperature appears on display.
Comp, ConFM, EvapFM, and MH energize.
a) EvapFMDiagnosis: Conrm EvapFM energizes. If not, conrm doors are closed
and DS engaged. Next, check for 115VAC at DSR #8 (LBU or GY) to #7(W).
If115VAC is not present, check DS continuity. If DS is engaged and contacts are
open, replace DS. If 15VAC is present, check for 115VAC at DSR #4(DBU) to
neutral (W). If115VAC is not present, check for 115VAC at DSR #6(BK or W/BU) to
neutral(W). If 115VAC is present at DSR #6 (BK or W/BU) to neutral (W) and not at
DSR#4(DBU) to neutral (W), replace DSR. If 115VAC is present at DSR #4 (DBU)
to neutral (W), check EvapFM blades for binding and EvapFM continuity.
b) Cabinet Light: FGY CL: Diagnosis: Open the door conrm CLS is in the ON position.
If not, move CLS to the ON position. CLS turns on. If CLS does not turn on, check
for 115VAC at both CLS (BK) wires to neutral(W). If 115VAC is present one 1
CLS(BK) wire and not the other, conrm power supply and continuity of CLS switch.
If power supply is ok, check CLS continuity. IfCLS is engaged and CLS switch is
open, replace CLS. If CLS is engaged, contacts are closed, and 115VAC is present
at CLS(BK) and CL is not energized, replace CL.
FS/HS CL: Diagnosis: Open the door (upper on HS) and conrm CL is energized.
If not, with the door open, check for 115VAC at DSR #5 (BK) to neutral(W) and DSR
#1 (V or Y) to neutral(W). If115VAC is not present at DSR #5 (BK), conrm power
supply and continuity of power switch. If 115VAC is present at DSR #5 (BK) and not
present at DSR #1 (V or Y), check DS continuity. IfDS is disengaged and contacts
are closed (DSR energized), replace DS. If DSR is de-energized and 115VAC is
present at DSR#5(BK) and not at DSR #1 (V or Y) to neutral (W), replace DSR.
If 115VAC is present at DSR #1 (V or Y) and CL is not energized, replace CL.
c) CM Diagnosis: Cabinet temperature appears on display. If not, check for 115VACat
CM L2 (BK) to CM N3 neutral (W). If 115VAC is not present, check power switch,
power cord connections, and breaker/fuse. Conrm wiring connections are secure
for both CM L2 (BK) (power supply) and CMN3(W) (neutral). If 115VAC is present
and display is off, replace CM.
d) Comp and ConFM Diagnosis: Conrm Comp and ConFM energize. Ifnot, check
for 115VAC at CM C1 (R or V) to neutral(W). If 115VAC is not present, check CTh
status. See "II.D.Thermistor Check." IfCTh ohm reading is in proper range, replace
CM. If 115VAC is present at CM C1 (R or V) to neutral (W), check for 115VAC at
CR #0 (GY or P) to CR#1(W). If 115VAC is not present, check continuity of HPS.
If open, allow time for HPS to reset. If HPS does not reset, see "e) HPS Activation"
below. If HPS is closed and 115VAC is present, check for 115VAC at CR#4(BK)
and CR #6 (R) to neutral (W). If 115VAC is present at CR #4 (BK) and not at
CR#6(R), replace CR. If115VAC is present at CR #6 (R) to neutral (W) and ConFM
12
Page 13
is energized but Comp is not, give time for Comp internal protector to cool and reset.
Next, check Comp start capacitor, start relay, and Comp motor windings. If Comp
does not start, replace Comp. If ConFM is not energized, check ConFM fan blades
for binding and motor winding continuity.
If Comp and ConFM are energized and the cabinet does not cool down, check for a
restriction in the refrigeration circuit, correct TXV operation, and correct refrigerant
charge.
e) HPS Activation: Conrm ConFM is energized and fan blade turns freely.
Conrmcondenser coil is not clogged or restricted. Conrm there are no restrictions
in the refrigeration circuit (TXV and drier). Let refrigeration circuit pressures
equalize. IfHPS does not reset and pressures are equalized, replace HPS.
Ifpressures are not equalized, reclaim refrigerant and diagnose refrigeration circuit
restriction.
8) Cool Down Achieved–CTh cools to 3°F (1.7°C) below setpoint. EvapFM continues.
Comp and ConFM de-energize. Diagnosis: Conrm Comp and ConFM de-energize.
If not, and Comp and ConFM were energized longer than 2 min., check CTh status.
See "II.D. Thermistor Check." If CTh ohm reading is in range and Comp and ConFM
continue longer than 2 min., check for 115VAC at CM C1 (R or V) to neutral(W).
If115VAC is present, replace CM. If 115VAC is not present and Comp and ConFM
continue, check for 115VAC at CR #1 (R or V). If 115VAC is present, replace CR.
9) Defrost–Cabinet temperature is displayed during defrost. There is a 20-min. minimum
defrost time, a 1-hr. maximum defrost time, and a 2-hr. minimum defrost interval.
1a) Time-Initiated: When 2-hr. cumulative Comp run timer terminates, defrost starts (off
cycle). EvapFM continues. Comp and ConFM de-energize.
1b) Manually-Initiated: To initiate a manual defrost, press the manual defrost button
on display. Defrost icon turns on and, if energized, Comp and ConFM de-energize.
Cabinet temperature is displayed during defrost.
2) Defrost Termination: DTh warms to 40°F (4.4°C). EvapFM and MH continue. Comp
and ConFM energize.
Defrost Diagnosis:
a) Defrost Initiation: Has DTh cooled to 8.6°F (-13°C) or lower? Conrm DTh status.
See "II.D. Thermistor Check." If DTh is in proper range or manual defrost initiated,
conrm Comp and ConFM de-energize. If not, check for 115VAC at CM C1 (R orV)
to neutral (W). If 115VAC is present and DTh is within proper range, replace CM.
Ifthere is no voltage at CMC1 (R or V) to neutral (W) and Comp and ConFM do not
de-energize, check for 115VAC at CR #6 (R) to neutral (W). If 115VAC is present at
CR #6 (R) to neutral(W) and DTh is within proper range, replace CR.
b) Defrost Termination: Has DTh warmed to 40°F (4.4°C)? If not yet conrmed,
conrm DTh status. See "II.D. Thermistor Check." If DTh is in proper range, have
Comp and ConFM energized? If not, see "7d) Comp and ConFM Diagnosis"above.
7) Startup/Cool Down– MH and PH energize. There is a slight delay, then Comp, ConFM,
and EvapFM energize. Cabinet temperature appears on display. Once DTh cools to
32°F (0°C), 4-hr.Comp cumulative run timer starts.
a) MH and PH Diagnosis: Conrm MH and PH energize. Check for 115VAC at MH and
PH. If 115VAC is not present, conrm power supply and continuity of power switch.
If 115VAC is present, check amp draw of MH and PH. If an amp reading is not
present, check continuity of MH or PH. If open, replace MH or PH.
b) Cabinet Light: FGY CL: Diagnosis: Open the door conrm CLS is in the ON position.
If not, move CLS to the ON position. CLS turns on. If CLS does not turn on, check
for 115VAC at both CLS (BK) wires to neutral(W). If 115VAC is present one 1
CLS(BK) wire and not the other, conrm power supply and continuity of CLS switch.
If power supply is ok, check CLS continuity. IfCLS is engaged and CLS switch is
open, replace CLS. If CLS is engaged, contacts are closed, and 115VAC is present
at CLS(BK) and CL is not energized, replace CL.
FS/HS CL: Diagnosis: Open the door (upper on HS) and conrm CL is energized.
If not, with the door open, check for 115VAC at DSR #5 (BK) to neutral(W) and DSR
#1 (V or Y) to neutral(W). If115VAC is not present at DSR #5 (BK), conrm power
supply and continuity of power switch. If 115VAC is present at DSR #5 (BK) and not
present at DSR #1 (V or Y), check DS continuity. IfDS is disengaged and contacts
are closed (DSR energized), replace DS. If DSR is de-energized and 115VAC is
present at DSR#5(BK) and not at DSR #1 (V or Y) to neutral (W), replace DSR.
If 115VAC is present at DSR #1 (V or Y) and CL is not energized, replace CL.
c) CM Diagnosis: Cabinet temperature appears on display. If not, check for 115VAC
at CM L2 (BK) to CM N3 neutral (W). If 115VAC is not present, conrm wiring
connections are secure on CM L2 (BK) (power supply) and CM N3 (W) (neutral).
If115VAC is present and display is off, replace CM.
d) EvapFM Diagnosis: Conrm EvapFM energizes. If not, conrm doors are closed and
DS engaged. Next, check for 115VAC at DSR #8 (LBU or GY) to DSR#7neutral
(W). If 115VAC is not present, check DS continuity. If DS is engaged and contacts
are open, replace DS. If 115VAC is present, check for 115VAC at CM F5(Y or W/BU)
to neutral (W). If 115VAC is not present, replace CM. If115VAC is present, check for
115VAC at DSR #4 (DBU) to neutral (W). If115VAC is not present, check for 115VAC
at DSR #6 (Y or W/BU) to neutral (W). If115VAC is present at DSR #6 (Y or W/BU)
to neutral (W) and not at DSR #4 (DBU) to neutral (W), replace DSR. If 115VAC
is present at DSR#4(DBU) to neutral (W), check EvapFM blades for binding and
EvapFM continuity.
14
Page 15
e) Comp and ConFM Diagnosis: Conrm Comp and ConFM energize. If not, check
for 115VAC at CM C1 (R or V) to neutral (W). If 115VAC is not present, check CTh
status. See "II.D.Thermistor Check." If CTh ohm reading is in proper range, replace
CM. If115VAC is present at CM C1 (R or V) to neutral (W), check for 115VAC at
CR #0 (GY or P) to CR #1 (W). If 115VAC is not present, check continuity of HPS.
Ifopen, allow time for HPS to reset. If HPS does not reset, see "e) HPS Activation"
below. If HPS is closed and 115VAC is present, check for 115VAC at CR #4 (BK)
and CR #6 (R) to neutral (W). If115VAC is present at CR #4 (BK) and not at CR
#6(R), replace CR. If115VAC is present at CR #6 (R) to neutral (W) and ConFM
is energized but Comp is not: On 1-section; Give time for internal protector to cool
and reset. Next, check run capacitor, start capacitor, start relay, and Comp motor
windings. If Comp does not start, replace Comp. On 2-section; Check for 115VAC
at Comp external protector to neutral (W). If 115VAC is not present, give time for
Comp external protector to cool and reset. If Comp external protector does not reset,
replace Comp external protector. If115VAC is present, check run capacitor, start
capacitor, start relay, and Comp motor windings. If ConFM is not energized, check
ConFM fan blades for binding and motor winding continuity.
If Comp and ConFM are energized and the cabinet does not cool down, check for a
restriction in the refrigeration circuit, correct TXV operation, and correct refrigerant
charge.
f) HPS Activation: Conrm ConFM is energized and fan blade turns freely. Conrm
condenser coil is not clogged or restricted. Conrm there are no restrictions in the
refrigeration circuit (TXV and drier). Let refrigeration circuit pressures equalize.
IfHPS does not reset and pressures are equalized, replace HPS. If pressures are
not equalized, reclaim refrigerant and diagnose refrigeration circuit restriction.
8) Cool Down Achieved–CTh cools to 3°F (1.7°C) below setpoint. EvapFM, MH, and
PH continue. Comp and ConFM de-energize. Diagnosis: Conrm Comp and ConFM
de-energize. If not, and Comp and ConFM were energized longer than 2 min., check
CTh status. See "II.D. Thermistor Check." If CTh ohm reading is in proper range and
Comp and ConFM continue longer than 2 min., check for 115VAC at CM C1 (R or V) to
neutral (W). If115VAC is present, replace CM. If 115VAC is not present and Comp and
ConFM continue, check CR#6(R) to neutral (W). If 115VAC is present, replace CR.
9) Defrost–The defrost icon turns on and "dEF" is displayed during defrost. There is a
5-min. minimum defrost time and a 1-hr.maximum defrost time.
1a) Temperature/Time-Initiated: DTh cools to 32°F (0°C), 4-hr. cumulative Comp
run timer starts. Once DTh is at or below 32°F (0°C) with 4-hr. cumulative Comp
run timer satised (Comp energized more than 4 hrs.), defrosticon turns on and
"dEF"is displayed. MHand PH continue. DH and DrH energize. If on, Comp and
EvapFM icons turn off. Comp, ConFM, and EvapFM de-energize.
1b) Manually-Initiated: To initiate a manual defrost, press the manual defrost button
on display. Comp and EvapFM icons turn off. Defrost icon turns on and "dEF" is
displayed. MHand PH continue. DH and DrH energize, Comp and EvapFM icons
turn off, Comp, ConFM, and EvapFM de-energize.
and PH continue. EvapFM icon turns on and EvapFM energizes. Note that the
7-min. EvapFM delay time is a maximum; if the defrost thermistor cools to 25°F
(-3.9°C) before the 7-min. EvapFM delay timer terminates, EvapFM icon turns on
and EvapFM energizes.
(4) 11-min. later, 18-min. temperature display delay timer terminates. "dEF" is
replaced by cabinet temperature.
2b) Manually Initiated Defrost-Termination:
(1) DTh warms to 59°F (15°C). Defrost icon, "dEF," MH, and PH continue. DH and
DrH de-energize. 3-min. Comp, ConFM, and EvapFM delay timer starts, and
15-min. temperature display delay timer starts.
(2) 3-min. Comp, ConFM, and EvapFM delay timer terminates. "dEF," MH, and PH
continue. Defrost icon turns off, Comp and EvapFM icons turn on, and Comp,
ConFM, and EvapFM energize.
(3) 12-min. later, 15 min. temperature display timer terminates. "dEF" is replaced by
cabinet temperature.
Defrost Diagnosis:
1a) Temperature/Time-Initiation: Has DTh cooled to 32°F (0°C) or lower? Before
proceeding, conrm DTh status. See "II.D. Thermistor Check." Has 4-hr. Comp
cumulative run timer satised?
(1) CM Diagnosis: Conrm defrost icon turns on, "dEF" is displayed, and Comp and
EvapFM icons turn off. If not, replaceCM.
(2) DH and DrH Diagnosis: Conrm DH and DrH energize. If not, check for 115VAC
at CM H4 (O) to neutral (W). If 115VAC is not present, replace CM. If115VAC is
present, check DT continuity. If open, let cool and reset. If DT does not close,
replace DT. If DT is closed, check DH and DrH amp draw and continuity.
(3) Comp and ConFM Diagnosis: Conrm Comp and ConFM de-energize.
If not, check for 115VAC at CM C1 (R or V) to neutral (W). If 115VAC is present,
replace CM. If 115VAC is not present and Comp and ConFM continue, check
CR#6(R) to neutral (W). If 115VAC is present, replace CR.
(4) EvapFM Diagnosis: Conrm EvapFM de-energizes. If not, check for 115VAC at
CM F5 (Y or W/BU) to neutral (W). If 115VAC is present, replace CM.
1b) Manual-Initiation: After pressing the manual defrost button, check the following:
(1) CM Diagnosis: Conrm Comp and EvapFM icons turn off, defrost icon turns on,
and "dEF" is displayed. If not, replace CM.
(2) DH and DrH Diagnosis: Conrm DH and DrH energize. If not, check for 115VAC
at CM H4 (O) to neutral (W). If 115VAC is not present, replace CM. If115VAC is
present, check DT continuity. If open, let cool and reset. If DT does not close,
replace DT. If DT is closed, check DH and DrH amp draw and continuity.
16
Page 17
(3) Comp and ConFM Diagnosis: Conrm Comp and ConFM de-energize.
If not, check for 115VAC at CM C1 (R or V) to neutral (W). If 115VAC is present,
replace CM. If 115VAC is not present and Comp and ConFM continue, check
CR#6(R) to neutral (W). If 115VAC is present, replace CR.
(4) EvapFM Diagnosis: Conrm EvapFM de-energizes. If not, check for 115VAC at
CM F5 (Y or W/BU) to neutral (W). If 115VAC is present, replace CM.
2a) Temperature/Time Initiated Defrost-Termination: Has DTh warmed to 59°F
(15°C)? If not yet conrmed, conrm DTh status. See "II.D. Thermistor Check."
IfDTh is in proper range, DHde-energizes and 3 delay timers start. If DTh has not
warmed to 59°F (15°C), check DT and DH continuity. Next, check DH amp draw.
(1) 3-min. Comp delay timer terminates: 3 min. after DH de-energizes, conrm
defrost icon turns off, Comp icon turns on, and Comp and ConFM energize.
If not, conrm cabinet temperature is warm enough for Comp and ConFM
operation. Next, check for 115VAC at CM C1 (R or V) to neutral(W). If 115VAC
is not present, check CTh status. See "II.D.Thermistor Check." If CTh ohm
reading is in proper range, replace CM. If 115VAC is present, check for 115VAC
at CR#4(BK) to neutral (W) and CR#6(R) to neutral (W). If 115VAC is present
at CR #4 (BK) to neutral (W) but not at CR #6(R) to neutral (W), replace CR.
If115VAC is present at CR #6 (R) and Comp or ConFM are not energized, check
Comp start components, Comp protector (internal on 1-section, external on
2-section), and Comp motor winding continuity. If ConFM is not energized, check
ConFM fan blades for binding and motor winding continuity.
(2) 7-min. EvapFM delay timer terminates: (note that the 7-min. EvapFM delay
time is a maximum; if the defrost thermistor cools to 25°F (-3.9°C) before the
7-min. EvapFM delay timer terminates, EvapFM icon turns on and EvapFM
energizes): 4min. after Comp and ConFM energize, conrm EvapFM icon turns
on and EvapFM energizes. If not, conrm doors are closed and DS engaged.
Next, check for 115VAC at CMF5 (Y or W/BU) to neutral (W). If 115VAC is not
present, replace CM. If 115VAC is present, checkfor 115VAC at DSR#4(DBU) to
neutral(W). If115VAC is not present, check for 115VAC at DSR#6(Y or W/BU)
to neutral (W). If115VAC is present on DSR #6 (Y or W/BU) to neutral (W) and
not on DSR #4(DBU) to neutral (W), replace DSR. If 115VAC is present on DSR
#4 (DBU) to neutral (W) and EvapFM is not energized, check EvapFM blades for
binding and EvapFM continuity.
(3) 18-min. temperature display delay timer terminates: 11 min. after EvapFM
energizes, "dEF" is replaced by cabinet temperature on display. If not, replace
CM.
17
Page 18
2b) Manually Initiated Defrost-Termination: Has DTh warmed to 59°F (15°C)? If not
yet conrmed, conrm DTh status. See "II.D. Thermistor Check." If DTh is in proper
range, DHde-energizes and 2 delay timers start. If DTh has not warmed to 59°F
(15°C), check DT and DH continuity. Next, check DH amp draw.
(1) 3-min. Comp/ConFM and EvapFM delay timers terminate: 3 min. after DH
de-energizes, conrm defrost icon turns off, Comp and EvapFM icons turn on,
and Comp, ConFM, and EvapFM energize. If not, conrm cabinet temperature is
warm enough for Comp and ConFM operation.
Comp and ConFM: Check for 115VAC at CM C1 (R or V) to neutral(W).
If115VAC is not present, check CTh status. See "II.D.Thermistor Check." If CTh
ohm reading is in proper range, replace CM. If 115VAC is present, check for
115VAC at CR #4(BK) to neutral (W) and CR#6(R) to neutral (W). If 115VAC is
present at CR #4 (BK) to neutral (W) but not at CR #6(R) to neutral (W), replace
CR. If 115VAC is present at CR #6 (R) and Comp or ConFM are not energized,
check Comp start components, Comp protector (internal on 1-section, external
on 2-section), and Comp motor winding continuity. If ConFM is not energized,
check ConFM fan blades for binding and motor winding continuity.
EvapFM: Conrm EvapFM icon turns on and EvapFM energizes. If not, conrm
doors are closed and DS engaged. Next, check for 115VAC at CMF5 (Y or
W/BU) to neutral (W). If 115VAC is not present, replace CM. If 115VAC is present,
checkfor 115VAC at DSR#4(DBU) to neutral(W). If115VAC is not present,
check for 115VAC at DSR#6(Y or W/BU) to neutral (W). If115VAC is present
on DSR #6 (Y or W/BU) to neutral (W) and not on DSR #4(DBU) to neutral (W),
replace DSR. If 115VAC is present on DSR #4 (DBU) to neutral (W) and EvapFM
is not energized, check EvapFM blades for binding and EvapFM continuity.
(2) 15-min. temperature display delay timer terminates: 12 min. after Comp,
ConFM, and EvapFM energize, "dEF" is replaced by cabinet temperature on
display. If not, replace CM.
Legend: CM–control module; Comp–compressor; ConFM–condenser fan motor;
Before replacing CM that does not show a visible defect and that you suspect is
bad, conduct the following check procedure. This procedure will help you verify your
diagnosis. Always choose a neutral (W) to establish a good neutral connection when
checking high voltages. Also, conrm there is a good power supply and neutral
connection to CM: 115VAC at CM L2 (BK) to CM N3 (W).
Alarm Reset: To silence the alarm, press and release the up button with power on.
Foralarm information, see "III.D. Alarm Safeties."
Startup/Cool Down
1) Check all wiring connections. Conrm the CTh and DTh are properly connected.
2) Move the power switch to the "ON" position.
3) Check for 115VAC at CM L2 (BK) to CM N3 neutral (W). If 115VAC is not present, check
power supply, wire connections, and power switch.
4) Check that cabinet temperature is displayed. If not, replace CM.
5) Freezer: Check that EvapFM is energized. Make sure doors are closed and DS
engaged. Next, check for 115VAC at CM F5 (Y or W/BU) to neutral (W). If 115VAC is not
present, replace CM.
6) Check that Comp and ConFM energize. If not, check CTh status. See "II.D.Thermistor
Check." If CTh ohm reading is in proper range, check for 115VAC at CM C1 (R or V) to
neutral (W). If 115VAC is not present, replace CM.
Defrost
7) Manual Defrost Check: Press the manual defrost button briey. If on, Comp and
EvapFM icons turn off. Defrosticon turns on and "dEF" is displayed.
8) Conrm Comp, ConFM, and EvapFM (freezer) de-energize. Check for 115VAC at CM
C1 (R or V) to neutral (W) for Comp and ConFM, then at CM F5 (Y or W/BU) (freezer)
to neutral (W) for EvapFM. If"dEF" is displayed and 115VAC is present, replace CM.
9) Freezer: Conrm DH energizes. Check for 115VAC at CM H4 (O) to neutral (W). If"dEF"
is displayed and 115VAC is not present, replace CM.
10) Check that the components restart after defrost termination.
Refrigerator: DTh reaches 40°F (4.4°C), Comp and ConFM (CM C1 (R or V)) energize.
If not, check DTh status. See "II.D.Thermistor Check." If DTh ohm reading is in proper
range, and Comp and ConFM do not energize, replace CM.
Freezer: DTh reaches 59°F (15°C). 3-min. later, Comp and ConFM (CM C1
(RorV)) and EvapFM (CM F5 (Y or W/BU)) energize. If not, check DTh status. See
"II.D.Thermistor Check." IfDTh ohm reading is in proper range, and Comp, ConFM,
or EvapFM do not energize, replaceCM. 12min. after Comp, ConFM, and EvapFM
energize, cabinet temperature appears on CM. If components fail to start, replace CM.
Legend: CM–control module; Comp–compressor; ConFM–condenser fan motor;
The cabinet thermistor is used for cabinet temperature control and the defrost thermistor
is used for defrost cycle initiation and termination. Thermistor resistance varies
depending on temperature. The control module monitors the thermistors to control
system operation. No adjustment is required.
In the event the cabinet thermistor reading is out of range (E1 alarm), the compressor
operates on a xed time basis of 5-min. on and 5-min. off.
In the event the refrigerator defrost thermistor reading is out of range (E2alarm), defrost
initiation occurs every 4-hr. of cumulative compressor run time and terminates on
20-min. minimum defrost timer.
In the event the freezer defrost thermistor reading is out of range (E2 alarm), defrost
initiation occurs every 4-hr. of cumulative compressor run time and terminates based on
cabinet thermistor temperature.
To check thermistor resistance, follow the steps below.
1) Move the power switch to the "OFF" position, then unplug the appliance.
2) Remove the control box cover.
3) Disconnect and remove the thermistor in question.
4) Immerse the thermistor sensor portion in a glass containing ice and water for 2 to 3 min.
5) Check the resistance between the wires at the thermistor connector. Normal reading is
within 16.0 to 16.7 kΩ. If outside the normal reading, replace the thermistor.
6) Reconnect and replace the thermistor in its correct position. See "IV.B. Important Notes
for Component Replacement."
7) Plug the appliance back in. Move the power switch to the "ON" position.
20
Page 21
E. Diagnostic Tables
Check for correct appliance installation per the instruction manual and proper voltage per
appliance nameplate.
1. Not Cooling
Not Cooling - Possible Cause
Power Supply
1.
Cord and Plug
2.
On three-section model, check
receptacle box cord and plug and
one-section and two-section cords
and plugs.
Power Switch (control box)
3.
Wiring
4.
Control Module
5.
See "III.D. Alarm Safeties" and "II.C.
Control Module Check."
Door Switch
6.
Door Switch Relay
7.
Evaporator Fan Motor
8.
High-Pressure Switch
9.
Compressor Relay
10.
Compressor External Protector
11.
(CF2S-XX only)
Compressor
12.
Condenser
13.
Evaporator
14.
See "2. Evaporator Frozen Up."
Refrigerant/Refrigerant Lines
15.
Unplugged, off, blown fuse, tripped or defective circuit breaker. On
a)
three-section receptacle box, only top receptacles have power.
Loose connection.
b)
Not within specications.
c)
Loose connection.
a)
Defective.
b)
"OFF" position.
a)
Defective.
b)
Loose connection.
a)
Faulty.
b)
In alarm.
a)
Defective.
b)
Not engaged.
a)
Defective.
b)
Loose connection.
a)
Defective.
b)
Defective.
a)
Dirty condenser.
a)
Ambient temperature too warm.
b)
Condenser fan motor not operating.
c)
Refrigerant overcharge.
d)
Refrigerant lines or components restricted.
e)
Defective.
f)
Defective.
a)
Dirty condenser.
a)
Condenser fan motor not operating.
b)
Compressor capacitor or start relay defective.
c)
Defective.
d)
Defective.
a)
Dirty.
a)
Clogged or frozen.
a)
Refrigerant leak.
a)
Refrigerant lines restricted.
b)
21
Page 22
2. Evaporator Frozen Up
Evaporator Frozen Up - Possible Cause
Evaporator
1.
Evaporator Fan Motor
2.
Defrost Thermistor
3.
Control Module
4.
5. Compressor Relaya) Defective.
Refrigerant Charge/Refrigerant
6.
Lines
Defrost Heater (freezer)
7.
Defrost Thermostat (freezer)
8.
Dirty.
a)
Fan blades binding.
a)
Defective.
b)
Out of position or defective.
a)
Defective.
a)
Low.
a)
Component restriction (TXV, cap tube, drier).
b)
Defective.
a)
Defective.
a)
3. Defrost: Control Module
Refrigerator Defrost Fails to Initiate - Possible Cause
1. Defrost Thermistor (Conrm
DTh status. See "II.D. Thermistor
Check.")
2. Compressor Relaya) Defective.
3. Control Modulea) Defective.
Refrigerator Defrost Fails to Terminate - Possible Cause
1. Defrost Thermistor (Conrm
DTh status. See "II.D. Thermistor
Check.")
2. Compressor Relaya) Defective.
3. Control Modulea) Defrost thermistor connection loose.
a) Defrost initiation temperature 8.6°F (-13°C) not achieved. See "1. Not
Cooling."
b) Out of position or defective.
a) Defrost termination temperature 40°F (4.4°C) not achieved.
b) Defective.
b) Defective.
Freezer Defrost Fails to Initiate - Possible Cause
Defrost Thermistor (Conrm
1.
DTh status. See "II.D. Thermistor
Check.")
Compressor 4-hr. cumulative run
2.
timer not satised.
Control Module
3.
Freezer Defrost Fails to Terminate - Possible Cause
Defrost Thermistor (Conrm
1.
DTh status. See "II.D. Thermistor
Check.")
Defrost Heater
2.
Compressor Relay
3.
Control Module
4.
Defrost initiation temperature 32°F (0°C) not achieved. See "1. Not
a)
Cooling."
Out of position or defective.
b)
Check compressor operation. See "1. Not Cooling."
a)
Defective.
a)
Defrost termination temperature 59°F (15°C) not achieved.
a)
Defrost thermistor connection loose.
b)
Defrost thermostat defective.
a)
Defective.
b)
Defective.
a)
Defective.
a)
22
Page 23
III. Controls and Adjustments
A. Control Module
All models are pretested and factory set. When the power switch is moved to the "ON"
position there is a slight delay, then the current cabinet temperature is displayed. From
the display module, the cabinet setpoint and temperature display scale can be changed.
Note: When exposed to high temperatures, a high-temperature alarm "Hi" may occur at
start-up. To silence the alarm, press and release the upper button. Alarm clears
once temperature is within factory parameters. For details, see"III.D.Alarm
Safeties."
NOTICE
• The control module is fragile, handle very carefully.
• Do not change wiring and connections. Never misconnect terminals.
• Do not short out power supply to test for voltage.
1. Display Icons
Control Module Icons
IconMeaning
Compressor
Compressor running.
Defrost
Appliance is in defrost cycle. See "II.B. Service Diagnosis" for details.
Evaporator Fan Motor (Icon is Applicable to Freezers Only)
Evaporator fan motor is running. Evaporator fan motor de-energizes when door is open and
when appliance is in defrost.
Alarm
Appliance is in alarm. See "III.D. Alarm Safeties" for details.
2. Display Layout
Manual
Defrost
Button
Compressor Icon
SC
ECO
°C
°F
Up
Button
V
V
SC
Button
Defrost
Icon
Evaporator Fan
Motor Icon
Alarm
Icon
Down
Button
23
Front
Panel
Page 24
3. Control Module Connections
Cabinet Thermistor
Defrost Thermistor
Auxiliary Code XX and Earlier
Cabinet
Thermistor
C1 Compressor (R)
L2 Power Supply (BK)
Defrost
Thermistor
N3 Neutral (W)
H4 Defrost Heater (O)
(Freezer)
F5 Evaporator Fan Motor (Y)
(Freezer)
Auxiliary Code XX and Later
Cabinet
Thermistor
C1 Compressor (V)
L2 Power Supply (BK)
Defrost
Thermistor
N3 Neutral (W)
H4 Defrost Heater (O)
(Freezer)
F5 Evaporator Fan Motor (W/BU))
(Freezer)
24
Page 25
B. Temperature
EHE
The temperature default scale is °F, but it can be changed to read °C. To change,
see "III.B.3. Changing the Temperature Display Scale (°F or °C)" below.
1. Default Settings
a) Temperature Setting: Refrigerator: 36°F (2°C).
Freezer: -4°F (-20°C).
b) Temperature Display Scale: °F.
2. Temperature Setpoint
The temperature setpoint is the value for the average cabinet temperature. The
temperature differential for the compressor to turn on and off is ±3°F (±1.7°C) of the
temperature setpoint. For example, for a refrigerator temperature setpoint of 36°F (2°C),
the compressor comes on at 39°F (3.7°C), and the compressor goes off at 33°F (0.3°C).
If necessary, adjust the temperature setpoint as follows:
1) Press and hold the upper or lower button briey, then release. The current temperature
setpoint ashes.
2) Press the upper or lower button until the desired value is displayed. After a few sec.,
the display returns to the current cabinet temperature and the temperature setpoint is
saved.
• For refrigerators, the temperature setpoint is adjustable between 34°F and 52°F
(1°Cand 11°C). Factory default is 36°F (2°C).
• For freezers, the temperature setpoint is adjustable between -15°F and +12°F
(-26°Cand -11°C). Factory default is -4°F (-20°C).
Note: Do not adjust the temperature setpoint outside of the factory-specied range.
Adjustment outside of this range may prevent the appliance from operating
correctly.
3. Changing the Temperature Display Scale (°F or °C)
To change the temperature display scale, follow the steps below.
1) Press and hold both the up and down buttons for 5 sec. "PAS" appears briey in the
display, then "000" appears.
2) Press the up button to change the display to "001".
3) Press the SC button. "
"diS" is displayed.
4) Press the SC button. "CFu" appears in the display. Press the SC button again. The
current temperature display scale setting appears.
5) Press the up or down button to change the temperature display scale.
6) Press the SC button to save the setting. Wait 1 min. or press the manual defrost button
twice to return to the temperature display.
" appears in the display. Press the up or down button until
25
Page 26
C. Defrost
To initiate a manual defrost, press the manual defrost button briey. The defrost icon and
"dEF" appear in the display.
D. Alarm Safeties
Alarm signals are designed to protect the appliance and food product. These alarms
give information or warnings in the event the appliance is operating out of acceptable
parameters. Should one of the alarms occur, follow the instructions in the table below
to address the alarm. The alarm code ashes once every second with audible alarm. To
silence the alarm, press and release the upper button.
Alarm Signals
Alarm Code ProblemCorrective Action/Reset Details
E01
E02
Hi
Lo
Cabinet Thermistor Malfunction Alarm
Cabinet thermistor has failed.
Defrost Thermistor Malfunction Alarm
Defrost thermistor has failed.
High Temperature Alarm
Refrigerator: Cabinet temperature has
remained above 57°F (13.9°C) for more
than 2hr.
Freezer: Cabinet temperature has
remained above 26°F (-3.3°C) for more
than 2hr.
Low Temperature Alarm
Refrigerator: Cabinet temperature has
remained below 26°F (-3.3°C) for more
than 2hr.
Freezer: Cabinet temperature has
remained below -23°F (-30.6°C) for more
than 2hr.
Beeps for 10 sec., then silent for 50 sec.. To silence
the alarm, press and release the up button.
Appliance cycles 5 min. on, 5 min. off.
Beeps for 10 sec., then silent for 50 sec. To silence
the alarm, press and release the up button.
Appliance cycles on and off with cabinet thermistor.
Beeps for 10 sec., then silent for 50 sec. To silence
the alarm and clear "Hi" from the display, press and
release the up button. The alarm icon stays on.
Automatically resets when temperature returns to
normal.
Beeps for 10 sec., then silent for 50 sec. To silence
the alarm and clear "Lo" from the display, press and
release the up button. The alarm icon stays on.
Automatically resets when temperature returns to
normal.
26
Page 27
E. Safety Devices
1. Compressor External or Internal Protector
If combined temperature/amperage value is above the limit specied by the compressor
manufacturer, the compressor external or internal protector operates independently to
turn off the compressor. The compressor external or internal protector de-energizes the
compressor until the temperature/amperage value returns to an acceptable level.
• If the condenser fan motor is operating and the compressor is off, it is most likely that
the compressor external or internal protector opened. If both the compressor and
condenser fan motor are off, it is most likely the appliance is off or the high-pressure
switch has opened. For further details, see "II.B. Service Diagnosis."
• On refrigerators and 1-section freezers, the compressor protector is an internal
protector. On 2-section freezers, the compressor protector is an external protector.
2. Short-Cycle Protection
There is a 2-min. minimum off-time and on-time for the compressor.
Note: Time may vary with compressor protector or high-pressure switch activation.
3. High-Pressure Switch
If pressure on the high-side of the appliance exceeds Hoshizaki specications, the
high-pressure switch activates and interrupts the compressor circuit, de-energizing the
compressor until the pressure returns to an acceptable level.
F. Mullion/Perimeter Heater
Freezers are equipped with perimeter and mullion heaters. The heaters are energized as
soon as the power switch is turned on.
27
Page 28
IV. Replacement of Components
WARNING
• The appliance should be diagnosed and repaired only by qualied service
personnel to reduce the risk of death, electric shock, serious injury, or re.
• Move the power switch to the "OFF" position, then unplug the appliance from the
electrical outlet before servicing.
• Make sure all food zones in the appliance are clean after the appliance is
serviced.
A. Service for Refrigerant Lines
WARNING
• Repairs requiring the refrigeration circuit to be opened must be performed by
properly trained and EPA-certied service personnel.
• Always recover the refrigerant and store it in an approved container. Do not
discharge the refrigerant into the atmosphere.
• Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of
refrigerant to the system (if using an electronic leak detector), and then raise the
pressure using nitrogen gas (140 PSIG). DO NOT use R-134a or R-404A as a
mixture with pressurized air for leak testing.
NOTICE
• Do not leave the system open for longer than 15 min. when replacing or servicing
parts. The Polyol Ester (POE) oils used in R-134a and R-404A appliances
can absorb moisture quickly. Therefore it is important to prevent moisture from
entering the system when replacing or servicing parts.
• Always install a new drier every time the sealed refrigeration system is opened.
• Do not replace the drier until after all other repair or replacement has been made.
Install the new drier with the arrow on the drier in the direction of the refrigerant
ow.
• When brazing, protect the drier by using a wet cloth to prevent the drier from
overheating. Do not allow the drier to exceed 250°F (121°C).
1. Refrigerant Recovery
The appliance is provided with refrigerant access valves. Using proper refrigerant
practices recover the refrigerant from the access valves and store it in an approved
container. Do not discharge the refrigerant into the atmosphere.
28
Page 29
2. Brazing
WARNING
• R-134a and R-404A themselves are not ammable at atmospheric pressure and
temperatures up to 176°F (80°C).
• R-134a and R-404A themselves are not explosive or poisonous. However,
when exposed to high temperatures (open ames), R-134a and R-404A can be
decomposed to form hydrouoric acid and carbonyl uoride both of which are
hazardous.
• Do not use silver alloy or copper alloy containing arsenic.
• Use an electronic leak detector or soap bubbles to check for leaks. Add a trace
of refrigerant to the system (if using an electronic leak detector), and then raise
the pressure using nitrogen gas (140PSIG). Do not use R-134a or R-404A as a
mixture with pressurized air for leak testing.
1) Braze all ttings while purging with nitrogen gas owing at a pressure of 3 to 4 PSIG.
NOTICE
• Always install a new drier every time the sealed refrigeration system is opened.
• Do not replace the drier until after all other repair or replacement has been made.
Install the new drier with the arrow on the drier in the direction of the refrigerant
ow.
• When brazing, protect the drier by using a wet cloth to prevent the drier from
overheating. Do not allow the drier to exceed 250°F (121°C).
2) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of
refrigerant to the system (if using an electronic leak detector), and then raise the
pressure using nitrogen gas (140 PSIG). Do not use R-134a or R-404A as a mixture
with pressurized air for leak testing.
3. Evacuation and Recharge
1) Attach a vacuum pump to the system. Be sure the charging hoses are connected to both
high and low-side access valves.
IMPORTANT
The vacuum level and vacuum pump may be the same as those for current
refrigerants. However, the rubber hose and gauge manifold to be used for
evacuation and refrigerant charge should be exclusively for POE oils.
2) Turn on the vacuum pump. Open the gauge manifold valves. Never allow the oil in the
vacuum pump to ow backwards.
3) Allow the vacuum pump to pull down to a 29.9" Hg vacuum. Evacuating period depends
on pump capacity.
4) Close the low-side valve and high-side valve on the gauge manifold.
29
Page 30
5) Disconnect the gauge manifold hose from the vacuum pump and attach it to a
refrigerant service cylinder. Remember to loosen the connection and purge the air from
the hose. See the nameplate for the required refrigerant charge. Hoshizaki recommends
only virgin refrigerant or reclaimed refrigerant which meets ARI Standard 700 (latest
edition) be used.
6) A liquid charge is required when charging an R-404A system (to prevent fractionation)
and optional when charging an R-134a system. Place the service cylinder on the
scales; if the service cylinder is not equipped with a dip tube, invert the service cylinder,
then place it on the scales. Open the high-side valve on the gauge manifold.
7) Allow the system to charge with liquid until the proper charge weight is met.
8) If necessary, add any remaining charge to the system through the low-side.
NOTICE!To prevent compressor damage, use a throttling valve or liquid
dispensing device to add the remaining liquid charge through the low-side
access valve with the appliance running.
9) Close gauge manifold valves and disconnect the hoses.
10) Cap the access valves to prevent a possible leak.
30
Page 31
B. Important Notes for Component Replacement
NOTICE
• When replacing a component listed below, see the notes to help ensure proper
operation.
ComponentNotes
CompressorInstall a new start relay, start capacitor, and external protector (on 2-section freezers only).
Compressor,
Evaporator
Fan Motor,
Condenser Fan
Motor
Thermostatic
Expansion Valve
Defrost
Thermistor
WARNING! To reduce the risk of electric shock, be sure to reconnect the
component's ground wire.
• Attach the thermostatic expansion valve bulb to the suction line in the same location as
the previous bulb.
• Secure the bulb with the clamp and holder, then insulate it.
After working with or around the defrost thermistor on a freezer, make sure the defrost
thermistor wire is not touching the defrost heater.
C. Door Reversal
The appliance is provided with a cabinet design which, after being delivered to the
installation location, permits changing of the door swing from left to right or right to left.
To change the door swing, an HS kit from your local Hoshizaki distributor is required. See
the table below. NOTICE! Improper installation of the HS kit may result in the doors not closing completely and/or the gaskets not sealing correctly. For further details,
contact your local Hoshizaki distributor or Hoshizaki Technical Support at
1-800-233-1940.
Door TypeConvertHS Kit Number
Full Glass
Full Solid
Half Solid
Right Hinge to Left HingeHS-5177
Left Hinge to Right HingeHS-5176
Right Hinge to Left Hinge
Left Hinge to Right Hinge
Right Hinge to Left Hinge
Left Hinge to Right Hinge
HS-3726
HS-3725
HS-3725
HS-3726
31
Page 32
V. Maintenance
WARNING
• Move the power switch to the "OFF" position and unplug the appliance before
performing maintenance to prevent electric shock or injury by moving parts. To
reduce the risk of electric shock, do not touch the power switch or plug with damp
hands.
• Before performing maintenance, move all foods into another clean refrigerator or
freezer.
1. Condenser
Check the condenser once a year and use a brush or vacuum cleaner to clean the
condenser as required.
2. Power Supply Connection
If a plug, power cord, or receptacle (three-section models) is damaged, replace it. Be
sure to connect the ground wire.
32
Page 33
VI. Preparing the Appliance for Periods of Non-Use
WARNING
• When preparing the appliance for long storage, prevent the doors from closing to
reduce the risk of children getting trapped.
• To reduce the risk of electric shock, do not touch the attachment plug or power
switch with damp hands.
• When shutting down the appliance for more than one week, move the power
switch to the "OFF" position and unplug the appliance.
• Do not plug in/unplug the appliance to start/stop operation. Make sure the power
switch is in the "OFF" position before plugging in or unplugging the appliance to
reduce the risk of electric shock.
1) Before shutting down the appliance, move the stored food into another refrigerator or
freezer.
2) Reach over the front panel and move the power switch to the "OFF" position. The
appliance will shut down.
3) Unplug the appliance.
IMPORTANT
When preparing the appliance for long storage, clean the cabinet interior, door
gaskets, and shelves.
33
Page 34
VII. Disposal
WARNING
When preparing the appliance for disposal, remove the door to reduce the risk of
children getting trapped. Leave the shelves in place so that children may not easily
climb inside.
The appliance contains refrigerant and must be disposed of in accordance with
applicable national, state, and local codes and regulations. Refrigerant must be
recovered by properly certied service personnel.
See the nameplate for electrical and refrigerant data. The nameplate is located inside the
cabinet.
We reserve the right to make changes in specications and design without prior notice.
(PSIG)Refrigerant (oz.)
HIGHLOW134a404A
240120
450250-17
12-
1-Section
11
2-Section
12
-
1-Section
8
2-Section
17
35
Page 36
B. Wiring Diagrams
1. CR1S-FS(-FSL)(-HS)(-HSL) Auxiliary Code E-5 and Earlier
CR1S-FS(-FSL)
115/60/1
L
(BK)
POWER
SWITCH
BK
GND
N
GR
(W)
W
CABINET
THERM
(BR)
WIRE COLOR CODE
BK BLACK
BR BROWN
BU BLUE
DBU DARK BLUE
GR GREEN
GY GRAY
LBU LIGHT BLUE
O ORANGE
P PINK
R RED
V VIOLET
W WHITE
Y YELLOW
(BU)
BK
DEFROST
THERM
(BR)
C
CONTROL
MODULE
R
BK
R
HIGH - PRESSURE
*
SWITCH
BK
(BU)
(L)2(C)1(N)
BK
BK
W
BK
BD
4
3
W
W
W
GY
A
6(F)5(H)
0
BK
4
COMPRESSOR RELAY
BK
BK
DOOR SWITCH
BK
BK
1
6
(DOOR OPEN)
BK
DBU
DBU
(BK)
(BK)
R
R
LBU
DBU
EVAPORATOR
FAN
EVAPORATOR
FAN
W
W
INTERNAL
PROTECTOR
14
(BK)
CONDENSER
FAN
(BK)(BK)
(BK)
BK
GND
GND
LBU
8
2
(BK)
GR
GR
6
4
DOOR SWITCH
RELAY
W
W
START CAP.
280 MFD
AT 120VAC
BK
13
12
GND
GR
7
5
3
1
BK
11
START
RELAY
GND
BK
BK
W
BK
CABINET
LIGHT
V
10
W
GR
(BK)
W
COMPRESSOR
W
W
W
W
W
W
W
W
* High-Pressure Switch
Cut-out300±10 PSIG
Cut-in190±20 PSIG
3A8726-012
36
Page 37
2. CR2S-FS(-HS) Auxiliary Code E-5 and Earlier
L
BK
POWER
SWITCH
115/60/1
GND
N
W
GR
(BR)
CABINET
THERM
(BU)
BK
DEFROST
THERM
(BR)
CONTROL
MODULE
R
BK
R
HIGH PRESSURE
*
BK
C
R
(BU)
(L)2(C)1(N)
BK
SWITCH
3
W
W
BD
4
W
GY
BK
COMPRESSOR RELAY
BK
BK
V
V
10
LBU
CABINET
LIGHT
CABINET
LIGHT
BK
BK
BK
COMPRESSOR
BK
DOOR SWITCH
(DOOR OPEN)
W
W
START CAP.
280 MFD
AT 120VAC
BK
BK
13
12
START
RELAY
LBU
W
7
BK
5
3
V
1
11
LBU
BK
DBU
(BK)
(BK)
(BK)
BK
8
6
4
2
DOOR SWITCH
RELAY
GND
GR
GND
GR
GND
GR
DBU
(BK)
(BK)
(BK)
R
BK
DOOR SWITCH
(DOOR OPEN)
EVAPORATOR
FAN
EVAPORATOR
FAN
EVAPORATOR
FAN
W
INTERNAL
PROTECTOR
14
(BK)
BK
A
6(F)5(H)
0
4
BK
BK
DBU
BK
DBU
W
1
R
6
W
W
W
W
W
W
W
W
W
W
W
W
WIRE COLOR CODE
BK BLACK
BR BROWN
BU BLUE
DBU DARK BLUE
GR GREEN
GY GRAY
LBU LIGHT BLUE
O ORANGE
P PINK
R RED
V VIOLET
W WHITE
Y YELLOW
37
CONDENSER
FAN
(BK)(BK)
GND
(BK)
GND
GR
GR
* High-Pressure Switch
Cut-out300±10 PSIG
Cut-in190±20 PSIG
Page 38
3. CR1S-FGY(-FS)(-FSL)(-HS)(-HSL), CR2S-FGY(-FS)(-HS), and CR3S-FS(-HS)
Auxiliary Code E-6 and Later
CR1S-FGYCR1S-FSCR1S-HSCR2S-FGYCR2S-FSCR2S-HS
CR_S-FGY
CR2S-FGY
CR2S-FGY(-FS)(-HS)
CR_S-FS(-HS)
CR2S-FS(-HS)
CR2S-FGY(-FS)(-HS)
*
INTERNAL
PROTECTOR
38
* High-Pressure Switch
Cut-out300±10 PSIG
Cut-in190±20 PSIG
Page 39
4. CF1S-FS(-FSL)(-HS)(-HSL) Auxiliary Code E-5 and Earlier
**
*
* High-Pressure Switch
Cut-out490±10 PSIG
Cut-in370±20 PSIG
** Defrost Thermostat
Cut-out
Cut-in
120°F±5°F (49°C±3°C)
70°F±5°F (21°C±3°C)
39
Page 40
5. CF1S-FS(-FSL)(-HS)(-HSL) Auxiliary Code E-6 and Later
CF1S-HS
CF1S-FGY
CF1S-FS(-HS)
**
*
INTERNAL
PROTECTOR
* High-Pressure Switch
Cut-out490±10 PSIG
Cut-in370±20 PSIG
40
** Defrost Thermostat
Cut-out
Cut-in
120°F±5°F (49°C±3°C)
70°F±5°F (21°C±3°C)
Page 41
6. CF2S-FS(-HS) Auxiliary Code E-5 and Earlier
*
**
* High-Pressure Switch
Cut-out490±10 PSIG
Cut-in370±20 PSIG
** Defrost Thermostat
Cut-out
Cut-in
120°F±5°F (49°C±3°C)
70°F±5°F (21°C±3°C)
41
Page 42
7. CF2S-FS(-FSL)(-HS)(-HSL) Auxiliary Code E-6 and Later
CF2S-HS
CF2S-FGY
CF2S-FS(-HS)
**
*
EXTERNAL
PROTECTOR
* High-Pressure Switch
Cut-out490±10 PSIG
Cut-in370±20 PSIG
42
** Defrost Thermostat
Cut-out
Cut-in
120°F±5°F (49°C±3°C)
70°F±5°F (21°C±3°C)
Page 43
8. CR3S-FS/HS Receptacle Box Connection
Power Cord Receptacle Box
Top Receptacle
To 2-Section System
Note: Only the top receptacles have power.
Power Cord Receptacle Box
Top Receptacle
To 1-Section System
To 2-Section System
Note: Only the top receptacles have power.
43
Top ReceptacleTop Receptacle
To 1-Section System
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.