DIVISION 08 - OPENINGS SECTION 08 42 43 – INTERMEDIATE / INTENSIVE / CRITICAL CARE UNIT ENTRANCES
Specifier Note: Coordinate and edit articles and paragraphs below to suit project requirements. Add section numbers and titles per CSI "MasterFormat" and specifier's practice. Consult with manufacturer regarding performance requirements for units applicable to project, as well as, related equipment and accessories required.
PART I – GENERAL
1.01 SUMMARY
A. WORK INCLUDED: Furnish complete manual airborne infection isolation room door system, as specified, that
has been manufactured, fabricated and installed to maintain performance criteria stated by manufacturer without defects, damage or failure.
B. RELATED WORK:
1. Concrete: Division 03, applicable sections.
2. Masonry: Division 04, applicable sections.
3. Thermal and Moisture Protection: Division 07, applicable sections.
4. Openings: Division 08, applicable sections.
1.02 REFERENCES
A. 2010 FACILITIES GUIDELINES INSTITUTE (FGI) FOR DESIGN AND CONSTRUCTION OF AIRBORNE
INFECTION ISOLATION ROOMS (AIIR) IN HEALTHCARE FACILITIES
B. THE ALUMINUM ASSOCIATION (AA) Aluminum Finishes Manual.
C. AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA) 101: Dissimilar Materials.
D. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI): ANSI Z97.1: Safety Glazing Materials Used in
Buildings - Methods of Test.
E. AMERICAN SOCIETY FOR TESTING AND MATERIALS
1. ASTM B221: Aluminum-Alloy Extruded Bars, Rods, Shapes and Tubes.
2. ASTM E283-04: (Air Infiltration) Standard Test Method for Determining Rate of Air Leakage Through Exterior Windows, Curtain Walls, and Doors Under Specified Pressure Differences Across the Specimen.
F. NATIONAL FIRE PROTECTION ASSOCIATION:
1. NFPA 101: Code for Safety to Life from Fire in Buildings & Structures.
2. NFPA 105: Standard for the Installation of Smoke Door Assemblies and Other Opening Protectives.
G. UNDERWRITERS LABORATORIES (UL): 1784 Air Leakage Test of Door Assemblies
H. UNDERWRITERS LABORATORY, INC. (USA & CANADA) UL 325: Electrical Door, Drapery, Gate, Louver, and
Window Operators and Systems.
1.03 SUBMITTALS
A. PRODUCT DATA: Submit manufacturer's complete product and installation data.
B. SHOP DRAWINGS: Submit drawings showing layout, profiles, product components including anchorage,
accessories, finish and glazing details (where required).
C. QUALITY ASSURANCE AND CLOSEOUT SUBMITTALS: Submit the following:
1. Manufacturer's Operation and Maintenance Data.
ARCHITECTURAL SPECIFICATIONS
Profiler
®
Self
-
Closing IDS Isolation Door System
®
,
2
4242 Baldwin Boulevard Corpus Christi, Texas USA 78405-3399 Tel: 800-531-3111, 361-888-5591 Fax: 800-531-3108, 361-888-6510
The Automatic Choice
MANUAL SLIDE DOORS – ICU/CCU AIRBORNE INFECTION CONTROL
Manual Sliding Isolation Door with Trackless Guide System
Page 2 of 4
A22.2
Aug 14
2. Warranty document as specified herein.
1.04 QUALITY ASSURANCE
A. INSTALLERS QUALIFICATIONS: Installer experienced (as determined by contractor) to perform work of this
section who has specialized in the installation of work similar to that required for this project and who is acceptable to product manufacturer.
B. MANUFACTURER’S QUALIFICATIONS: Manufacturer to have minimum (5) five years successful experience in
the fabrication of intermediate/intensive/critical care doors of the type required for this project. Manufacturer capable of providing field service representation during installation, approving acceptable installer and approving application method.
1.05 WARRANTIES
A. MANUFACTURER'S WARRANTY: Units to be warranted against defect in material and workmanship for a
period of one year from the Date of Substantial Completion. Manufacturer's warranty is in addition to, and not a limitation of, other rights owner may have under Contract Documents.
B. DISTRIBUTOR'S WARRANTY: 1 year warranty: Labor & transportation charges for defective parts replacement.
1.06 PROJECT CONDITIONS
FIELD MEASUREMENTS: Verify actual dimensions/openings by field measurements before fabrication and record on shop drawings. Coordinate with fabrication and construction schedule to avoid construction delays.
1.07 DELIVERY, STORAGE AND HANDLING
A. ORDERING AND DELIVERY: Comply with factory's ordering instructions and lead time requirements. Delivery
shall be in factory's original, unopened, undamaged containers with identification labels intact.
B. STORAGE AND PROTECTION: Provide protection from exposure to harmful weather conditions and vandalism.
PART II – PRODUCTS
2.01 MANUFACTURER
HORTON AUTOMATICS, a division of Overhead Door Corporation, shall manufacture airborne infection isolation room door(s) of type(s) and size(s) specified on plans and door schedule.
2.02 EQUIPMENT
A. MANUFACTURED DOOR UNITS: Shall include header with roller track, carrier assemblies, framing jambs,
sliding door panel, sidelite and accessories required for complete installation.
1. Configuration: Single Slide
2. Mounting Type: Perimeter mounted within rough opening with sliding panel(s) sliding along sidelite.
3. Door Type 310 Trackless: Slide-swing panel ‘SX’ shall slide along interior side of swing-out sidelite ‘SO’ (door must be in full open position) utilizing trackless floor system with no floor track/guide or recess required.
4. Units to provide minimum of 44" (1118mm) of clear slide opening width in compliance with 2010 FGI Guidelines for Airborne Infection Isolation Rooms (AIIR).
B. AIR INFILTRATION RATING: Units tested and certified to be in compliance with ASTM E283. Testing to be
done by nationally recognized laboratory. Maximum leakage rate at ambient temperature shall be less than 1 CFM/ft2 of opening at 0.3 in. of water.