ARCHITECTURAL SPECIFICATIONS
Profiler
®
Series 2000
-
IDS Isolation Door System
®
,
1
4242 Baldwin Boulevard Corpus Christi, Texas USA 78405-3399 Tel: 800-531-3111, 361-888-5591 Fax: 800-531-3108, 361-888-6510
The Automatic Choice
AUTOMATIC SLIDE DOORS – ICU/CCU AIRBORNE INFECTION CONTROL
Smoke Rated Automatic Isolation Door System Linear or Belt Drive, Trackless Guide
Page 1 of 5
A23.1
Mar 13
DIVISION 08 - OPENINGS SECTION 08 42 43 – INTERMEDIATE / INTENSIVE / CRITICAL CARE UNIT ENTRANCES
Specifier Note: Coordinate and edit articles and paragraphs below to suit project requirements. Add section numbers and titles per CSI "MasterFormat" and specifier's practice. Consult with manufacturer regarding performance requirements for units applicable to project, as well as, related equipment and accessories required.
PART I – GENERAL
1.01 SUMMARY
A. WORK INCLUDED: Furnish complete automatic airborne infection isolation room door system, as specified, that
has been manufactured, fabricated and installed to maintain performance criteria stated by manufacturer without defects, damage or failure.
B. RELATED WORK:
1. Concrete: Division 03, applicable sections.
2. Masonry: Division 04, applicable sections.
3. Thermal and Moisture Protection: Division 07, applicable sections.
4. Openings: Division 08, applicable sections.
5. Electrical: Division 26, applicable sections.
1.02 REFERENCES
A. 2010 FACILITIES GUIDELINES INSTITUTE (FGI) FOR DESIGN AND CONSTRUCTION OF AIRBORNE
INFECTION ISOLATION ROOMS (AIIR) IN HEALTHCARE FACILITIES
B. THE ALUMINUM ASSOCIATION (AA) Aluminum Finishes Manual.
C. AMERICAN ASSOCIATION OF AUTOMATIC DOOR MANUFACTURERS (AAADM).
D. AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA) 101: Dissimilar Materials.
E. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI): ANSI Z97.1: Safety Glazing Materials Used in
Buildings - Methods of Test.
F. AMERICAN SOCIETY FOR TESTING AND MATERIALS
1. ASTM B221: Aluminum-Alloy Extruded Bars, Rods, Shapes and Tubes.
2. ASTM E283-04: (Air Infiltration) Standard Test Method for Determining Rate of Air Leakage Through Exterior Windows, Curtain Walls, and Doors Under Specified Pressure Differences Across the Specimen
G. NATIONAL FIRE PROTECTION ASSOCIATION:
1. NFPA 101: Code for Safety to Life from Fire in Buildings & Structures.
2. NFPA 105: Standard for the Installation of Smoke Door Assemblies and Other Opening Protectives.
H. UNDERWRITERS LABORATORIES (UL): 1784 Air Leakage Test of Door Assemblies
I. UNDERWRITERS LABORATORY, INC. (USA & CANADA) UL 325: Electrical Door, Drapery, Gate, Louver, and
Window Operators and Systems.
1.03 SUBMITTALS
A. PRODUCT DATA: Submit manufacturer's complete product and installation data.
ARCHITECTURAL SPECIFICATIONS
Profiler
®
Series 2000
-
IDS Isolation Door System
®
,
2
4242 Baldwin Boulevard Corpus Christi, Texas USA 78405-3399 Tel: 800-531-3111, 361-888-5591 Fax: 800-531-3108, 361-888-6510
The Automatic Choice
AUTOMATIC SLIDE DOORS – ICU/CCU AIRBORNE INFECTION CONTROL
Smoke Rated Automatic Isolation Door System Linear or Belt Drive, Trackless Guide
Page 2 of 5
A23.2
Mar 13
B. SHOP DRAWINGS: Submit drawings showing layout, profiles, product components including anchorage,
accessories, finish and glazing details (where required).
C. QUALITY ASSURANCE AND CLOSEOUT SUBMITTALS: Submit the following:
1. Manufacturer's Operation and Maintenance Data.
2. Warranty document as specified herein.
1.04 QUALITY ASSURANCE
A. INSTALLERS QUALIFICATIONS: Installer experienced (as determined by contractor) to perform work of this
section who has specialized in the installation of work similar to that required for this project and who is acceptable to product manufacturer.
B. MANUFACTURER’S QUALIFICATIONS: Manufacturer to have minimum (5) five years successful experience in
the fabrication of intermediate/intensive/critical care doors of the type required for this project. Manufacturer capable of providing field service representation during installation, approving acceptable installer and approving application method.
1.05 WARRANTIES
A. MANUFACTURER'S WARRANTY: Units to be warranted against defect in material and workmanship for a
period of one year from the Date of Substantial Completion. Manufacturer's warranty is in addition to, and not a limitation of, other rights owner may have under Contract Documents.
B. DISTRIBUTOR'S WARRANTY: 1 year warranty: Labor & transportation charges for defective parts replacement.
1.06 PROJECT CONDITIONS
FIELD MEASUREMENTS: Verify actual dimensions/openings by field measurements before fabrication and record on shop drawings. Coordinate with fabrication and construction schedule to avoid construction delays.
1.07 DELIVERY, STORAGE AND HANDLING
A. ORDERING AND DELIVERY: Comply with factory's ordering instructions and lead time requirements. Delivery
shall be in factory's original, unopened, undamaged containers with identification labels intact.
B. STORAGE AND PROTECTION: Provide protection from exposure to harmful weather conditions and vandalism.
PART II – PRODUCTS
2.01 MANUFACTURER
HORTON AUTOMATICS, a division of Overhead Door Corporation, shall manufacture airborne infection isolation room door(s) of type(s) and size(s) specified on plans and door schedule.
2.02 EQUIPMENT
A. MANUFACTURED DOOR UNITS: Shall include operator, header with roller track, carrier assemblies, framing
jambs, sliding door panel, sidelite, activation, safety devices and accessories required for complete installation.
1. Configuration: Single Slide
2. Mounting Type: Perimeter mounted within rough opening with sliding panel(s) sliding along sidelite.
3. Door Type 310 Trackless: Slide-swing panel ‘SX’ shall slide along interior side of swing-out sidelite ‘SO’ (door must be in full open position) utilizing trackless floor system with no floor track/guide or recess required.
4. Units to provide minimum of 44" (1118mm) of clear slide opening width in compliance with 2010 FGI Guidelines for Airborne Infection Isolation Rooms (AIIR).
ARCHITECTURAL SPECIFICATIONS
Profiler
®
Series 2000
-
IDS Isolation Door System
®
,
3
B. AIR INFILTRATION RATING: Units tested and certified to be in compliance with ASTM E283-04 and UL 1784.
Testing to be done by nationally recognized laboratory. Maximum leakage rate at ambient temperature shall be less than 1 CFM/ft2 of opening at 0.3 in. of water.
C. FGI GUIDELINES COMPLIANCE: Units tested for air leakage and are in compliance with the 2010 FGI
Guidelines for Airborne Infection Isolation Room (AIIR) systems.
D. OPERATOR: The Electric Operating Mechanism shall be Profiler® Series 2000 Linear Drive or 2000B Belt Drive.
The operator shall be mounted and concealed within the header.
1. Series 2000 Linear Drive: Operation shall be accomplished through a 1/8 HP DC permanent magnet working with a threadless, induction hardened stainless steel 1/2" (13mm) diameter linear drive shaft. Maximum current draw shall not exceed 3.15 amps. A linear travel block describes a helical path along the rotating shaft utilizing six aircraft quality ball bearings acting as an integral clutch. Linear drive shaft shall be self lubricating by means of integral oiler located in the travel block.
2. Series 2000B Belt Drive: Operating force shall be accomplished through a 1/8 HP DC permanent magnet motor with worm gear transmission and 1800 RPM working with drive belt, attached door hangers, and idler pulley. Drive belt to be steel reinforced nylon, 1/2" (13 mm) wide. Idler pulley to be reinforced, metallic material.
3. Master Control shall be 16 bit microprocessor controller with dual on-board seven-segment alphanumeric diagnostic display and position encoder. The encoder shall monitor revolutions of the operator shaft and send signals to microprocessor controller to define door position and speed. The control shall have minimum of 28 programmable parameters including the following functions as required by ANSI A156.10:
a. Adjustable opening and closing speeds. b. Adjustable back-check and latching. c. Adjustable braking. d. Adjustable hold-open time between 1 to 30 seconds. e. Adjustable Reversing Circuit will reopen door unit if closing path is obstructed. f. Separate day and night modes of operation with security over-ride.
4. Finger Safety: When unit slides open, strike rail of sliding panel will stop short of adjacent sidelite; resulting opening is net slide.
5. On/Off Switch shall be supplied. When switched OFF, unit reverts to free manual operation (likewise during electrical power failure).
E. SECURITY AND SAFETY POWER FAIL OPTIONS:
1. Automatic lock: Automatically locks slide function of door when in closed position. Additional power supply for autolock not acceptable.
a. Autolock Fail Secure: If power fails the lock engages. b. Autolock Fail Safe: If power fails the lock disengages.
2. Monitored Power Fail Options (battery back-up): a. Software Selectable Power Fail Open: If power fails the door slides open. b. Software Selectable Power Fail Close: If power fails the door slides closed.
3. Recommended that isolation door system be powered by facility provided UPS (Uninterrupted Power Source).
F. PROFILER® HEADER: Shall be slim 4" (102mm) deep by 6" (152mm) high aluminum construction with extruded
z-profile reinforcement for dead load and lateral strength. Header shall have removable face plate for service and adjustment of operator and controls. Header mounts flush to 4" framing jambs.
G. CARRIER ASSEMBLIES AND HEADER ROLLER TRACK: Carrier assemblies shall support door panels with
minimum four rollers per panel. Rollers will be steel, high quality ball bearing wheels 1-1/4" (32 mm) diameter.
4242 Baldwin Boulevard Corpus Christi, Texas USA 78405-3399 Tel: 800-531-3111, 361-888-5591 Fax: 800-531-3108, 361-888-6510
The Automatic Choice
AUTOMATIC SLIDE DOORS – ICU/CCU AIRBORNE INFECTION CONTROL
Smoke Rated Automatic Isolation Door System Linear or Belt Drive, Trackless Guide
Page 3 of 5
A23.3
Mar 13
ARCHITECTURAL SPECIFICATIONS
Profiler
®
Series 2000
-
IDS Isolation Door System
®
,
4
Anti-Derailing shall be accomplished by means of a continuous aluminum extrusion full length of slide panel travel. Overhead header roller track shall be continuous aluminum, nylon covered, and replaceable.
H. SLIDE-SWING PANEL AND SWING-OUT SIDELITE: Shall be aluminum, 1-3/4" (44 mm) deep with narrow stile
construction and with perimeter seals. Floor seal to allow between an 1/8" to 1/2" (3mm to 13mm) gap to finished floor. An intermediate, horizontal rail (muntin bar), 2 1/4" (57 mm) wide, shall be furnished for safety and division of glass. Standard bottom rail shall be 4" (102mm) tall with custom bottom rails up to 10" (254mm) tall. Standard glazing prep to be for 1/4" (6 mm) tempered glass. Total weight limit per panel shall be 156 lbs (70.7 kg) for UL listed slide-swing panel.
1. Locking Hardware: Flush Bolt shall be provided for swing-out sidelite. Swing-out sidelite will thus be locked in place under normal conditions.
2. Swing-out Feature: In full slide-open position, after ‘SO’ flush bolt has been released, panels can swing out 90° with maximum 50 lbs. of force applied at the strike rail. Breakout mechanism shall provide support across full width of the door, in normal operating mode. In breakout mode, torsion assembly shall support weight of the door to minimize drop.
I. JAMBS/FRAME: Shall be aluminum, 1 3/4" (44 mm) deep by 4" (102 mm) wide.
2.03 RELATED EQUIPMENT
4242 Baldwin Boulevard Corpus Christi, Texas USA 78405-3399 Tel: 800-531-3111, 361-888-5591 Fax: 800-531-3108, 361-888-6510
The Automatic Choice
AUTOMATIC SLIDE DOORS – ICU/CCU AIRBORNE INFECTION CONTROL
Smoke Rated Automatic Isolation Door System Linear or Belt Drive, Trackless Guide
Page 4 of 5
A23.4
Mar 13
A. ACTIVATING DEVICE: Shall actuate door open; door closes after time delay expires. Optional latch relay action
(push-to-open/push-to-close). Activating device shall be jamb mounted on each side of the opening.
1. Push plate: shall be jamb mounted with 1 1/2" (38 mm) wide x 4 3/4" (121 mm) tall stainless steel face plate with momentary contact microswitch assembly. Face plate to have “Press To Open” engraving. Optional plain face plate with no engraving.
2. Optional touchless sensor: active infrared device shall provide hands free operation with detection range of 6" to 30" (152 mm to 762 mm). Jamb mounted stainless steel face plate shall be 1 11/16" (43 mm) wide x 4 1/2" (114 mm) tall.
B. SAFETY DEVICE: Hold-open beams: Two pulsed infrared photoelectric beams to be mounted in vertical rail of
sidelite and in jamb. Sender/receiver arrangement parallels door opening and shall prevent door from closing while door way is occupied.
2.04 RELATED WORK REQUIREMENTS
A. ELECTRICAL: 120 VAC, 50/60 cycle, single phase, dedicated 20 amp circuit per operator. Non-North American
voltages can be 240 VAC 50/60 cycle (operator must have 240 volt power supply).
B. GLASS AND GLAZING: Glass stops, glazing vinyl and setting blocks for field glazing as per Safety Glazing
standard ANSI Z97.1.2.
2.05 MATERIALS, FINISHES AND FABRICATION
A. EXTRUDED ALUMINUM: ASTM B221, 6063-T5 alloy and temper, anodized:
1. Structural Header Sections: Minimum 3/16" (5 mm) thickness.
2. Structural Frame Sections: Minimum 1/8" (3 mm) thickness.
3. Structural Panel Sections: Commercial grade.
B. FINISHES (for all exposed aluminum surfaces): Shall be one of the following with optional antimicrobial coating:
1. 204-R1 Clear: Arch. Class 2 Clear Anodized Coating, AA-MI2C22A31.
2. 313-R1 Dark Bronze: Arch. Class 1 Anodized Coating, AA-MI2C22A44.
3. 312-R1 Light Bronze: Arch. Class 1 Anodized Coating, AA-MI2C22A44.
ARCHITECTURAL SPECIFICATIONS
Profiler
®
Series 2000
-
IDS Isolation Door System
®
,
5
4242 Baldwin Boulevard Corpus Christi, Texas USA 78405-3399 Tel: 800-531-3111, 361-888-5591 Fax: 800-531-3108, 361-888-6510
The Automatic Choice
AUTOMATIC SLIDE DOORS – ICU/CCU AIRBORNE INFECTION CONTROL
Smoke Rated Automatic Isolation Door System Linear or Belt Drive, Trackless Guide
Page 5 of 5
A23.5
Mar 13
4. 315-R1 Black: Arch. Class 1 Anodized Coating, AA-MI2C22A44.
5. Special Paint Coating: Color as selected.
6. Clad with stainless steel or muntz metal (brass alloy): #7 or #4 brushed finish.
C. PANEL CONSTRUCTION:
1. Corner block type with 3/16" steel backup plate construction, mechanically secured with minimum of four hardened steel screws. Sash consists of snap-in glass stops, snap-in glazing beads and vinyl gaskets. Gasketing material to be captured in extruded aluminum door panel. Floor seal is brush material. Perimeter and floor seals to be factory installed to maintain ASTM E283-04 and UL 1784 rating.
2. Slide-swing doors to be supplied with adjustable glass setting block to allow for adjusting of door to meet site conditions eliminating the need for additional shims.
D. FRAME CONSTRUCTION: Butt joints, mechanically secured by means of screws & formed aluminum brackets.
PART III - EXECUTION
3.01 EXAMINATION
SITE VERIFICATION OF CONDITIONS: Installer must verify that base conditions previously installed under other sections are acceptable for product installation according to with manufacturer's instructions. Notify the Contractor in writing of conditions detrimental to the proper and timely completion of work. Do not start work until all negative conditions are corrected in a manner acceptable to the installer and manufacturer.
3.02 INSTALLATION
A. GENERAL: Install door units plumb, level and true to line, without warp or rack of frames or sash with
manufacturer's prescribed tolerances. Provide support and anchor in place.
B. DISSIMILAR MATERIALS: Comply with AAMA 101, Appendix Dissimilar Materials by separating aluminum
materials and other corrodible surfaces from sources of corrosion or electrolytic action contact points.
C. SMOKE CONTAINMENT BARRIER CONSTRUCTION: Install header and framing members in a bed of neutral
cure silicone sealant to maintain compliance with NFPA 105. Coordinate installation with wall flashings and other components of construction.
3.03 CLEANING, ADJUSTMENT AND PROTECTION
A. CLEANING: After installation, installer to take following steps:
1. Remove temporary coverings and protection of adjacent work areas.
2. Remove construction debris from construction site and legally dispose of debris.
3. Repair or replace damaged installed products.
4. Clean product surfaces and lubricate operating equipment for optimum condition and safety.
B. ADVISE CONTRACTOR: Of precautions required through the remainder of the construction period, to ensure
that doors will be without damage or deterioration (other than normal weathering) at the time of acceptance.
Horton Automatics reserves the right to make product improvements and change specifications without notice.
END OF SECTION