Horstmann Z322XL Installation And Commissioning Instructions

COMMISSIONING
To check whether the valve is operating correctly, carry out the following checks after the system is filled and vented. Ensure that the override lever is back in the Auto position and the insert guide is removed.
HOTWATERONLY. Set the room thermostat to minimum or turn the CH off at the programmer. Set the cylinder thermostat to maximum and turn the HW on at the programmer. The valve should close Port A. The boiler should fire, pump run and the pipe on the Port B side should get hot.
CENTRALHEATINGONLY. Set the cylinder thermostat to minimum or turn the HW off at the programmer. Set the room thermostat to maximum and turn the CH on at the programmer. The valve should close Port B. The boiler should fire, pump run and the pipe on the Port A side should get hot.
APPLICATION
The Z322XL mid-position valve has been designed to control the water circulation in fully pumped systems, which employs a single pump for both Hot water and Central heating circuits, by diverting the flow to either circuit or both simultaneously using a single valve.
HOTWATERANDCENTRALHEATING. Set the room and cylinder thermostat to maximum and turn the HW and CH on at the programmer. The valve should be in the mid-position. The boiler should fire, pump run and the pipes on both Port A side and Port B should get hot.
Reset both thermostats and the programmer to their normal settings. Please notethe above assumes that both programmer and thermostats are being used. If this is not the case, ignore the action described for the item not fitted.
SPARES The actuator and body for the Z322XL mid-position valve can be purchased separately as spares or as replacement parts(see page 1).
Email: sales@horstmann.co.uk
Website: www.horstmann.co.uk
Page 4
Horstmann Controls Limited
Bristol
BS4 1UP
t:0117 9788 773 - f:0117 9788 701
LEAFLET No P80955
ISSUE 2
INSTALLATION AND CONNECTION SHOULD ONLY BE CARRIED OUT BY A SUITABLY QUALIFIED PERSON AND IN ACCORDANCE WITH THE CURRENT EDITION OF THE IEE WIRING REGULATIONS. A CLASS ‘A’ SWITCH (HAVING CONTACT SEPARATION OF AT LEAST 3MM IN ALL POLES) MUST BE INCORPORATED IN THE FIXED WIRING AS A MEANS OF DISCONNECTING THE SUPPLY, NORMALLY AT THE CONSUMER UNIT. THE SYSTEM MUST BE APPROPRIATELY FUSED.
WARNING:ISOLATE MAINS SUPPLY BEFORE COMMENCING INSTALLATION
SPECIFICATION
Motor supply voltage: 230V AC, 50Hz Power consumption:<6W Lead supplied:1 meter 4 core cable. Industry standard colours used No earth connection required as unit is double insulated Operating flow temperature:-5 Switch rating:3Amps Maximum ambient temperature:50
Maximum static pressure:8.6 Bar Maximum differential pressure: 0.5 Bar Pipe fitting size:22mm compression Actuator:Maximum time to power
open - 20 seconds
Maximum time to spring
close - 10 seconds Override lever:For manual operating to mid-position for system draining or filling. During normal operation, the lever must be in the auto position. (See diagram opposite).
The Z322XL consists of a 3 port valve body (Ref.B322XL) to which a self-contained actuator (Ref.A322XL) is attached.
o
C to 88oC
o
C
A322XL - ACTUATOR
B322XL - BODY
Page 1
Valve position - In the event that mains power is disconnected the valve automatically spring-returns to the Hot water only position.
Position of valve during the various operation:
HW only - Port A closed
OPERATION
FIT ACTUATOR TO VALVE BODY
Position the actuator on the valve body lining up the valve spindle with the ‘D’ shape slot. A yellow guide strip has been inserted behind the Override lever to assist installation,please remove the guide once the actuator installation is complete and before the system is used.
The actuator guide holes should line up with the spigots on the valve body.
HW & CH - Valve in position AB (Middle) CH only - Port B closed The Valve operates both boiler and
pump when either Heating or Hot water is required.
INSTALLATION
POSITIONING OF VALVE
On new installations ensure that the Z322XL valve is fitted on the flow from the boiler only. Also check that the actuator head is NOTbelow the horizontal level of the pipework and that neither the open vent nor the cold feed are isolated. This will ensure system and product safety at all times. Remember to make allowances for working, maintenance and replacement.
FITTING OF VALVE BODY TO PIPEWORK
Fit the valve body using the 22mm compression fittings provided with the flow from the boiler to AB, the radiator circuit to Port A, and the Hot water cylinder to Port B. Tighten the compression nuts sufficiently to make a watertight seal, only gripping the valve by its body. Take care not to over tighten.
Fix with the screws provided and tighten lightly. The override lever should now be on the Port B side.
Set the override lever to manual. Fill, test and thoroughly flush the system (see diagram and instruction under the Specification section located on page 4 of this guide).
WIRING CONNECTIONS- STANDARD INSTALLATION
The 4 core cable fitted to the actuator can now be connected to the system following the simple colour-coded guide below.
Wire Colour System Connection Blue Any Neutral supply. Orange ‘Call’ terminal of Cylinder Stat if fitted, otherwise the ‘HW ON’ terminal of
the programmer - Also link to Pump/Boiler live.
White ‘Call’ terminal of room Stat if fitted, otherwise the ‘CHON’ terminal of
programmer.
Grey ‘Stat’ terminal of Cylinder Stat if fitted, otherwise the ‘HW OFF’ terminal of
the programmer.
No earth connection is required. Ensure all connections are good and the screw secure. A torque of
0.75Nm is recommended for fixing the wires in place.
USING A ZONEPLUS Z322XL AS A DIVERTER VALVE
The following connections will enable the Z322XL to act as a diverter valve, giving priority to the Central heating.
Wire Colour System Connection Blue Any Neutral supply. Orange ‘Call’ terminal of Cylinder Stat if fitted, otherwise the ‘HW ON’ terminal of
the programmer - Also link to Pump/Boiler live.
Page 2
White+Grey ‘Call’ terminal of room Stat if fitted, otherwise the ‘CHON’ terminal of
programmer.
Page 3
Loading...