Horstmann C-Stat ZW Installation Guide

C-Stat 11-ZW | C-Stat 17-ZW
Installation Instructions
Room Thermostat and ASR-ZW Receiver
Wireless Programmable
Programmable room thermostats are widely recognised as one of the best ways in which to control central heating. Horstmann C-Stat programmable room thermostats have a large display and intuitive user interface, making them easy to set up and use. C-Stat uses a sophisticated time proportional integral (TPI) algorithm for accurate temperature control and energy efficiency. The C-Stat ZW is a wireless electronic battery powe re d pr og rammabl e ro om the rmostat tha t us es interoperable two-way RF mesh networking technology which avoids the need for additional wiring or unsightly cable runs.
Installation and connection should only be carried out by a suitable qualified person and in accordance with the current edition of the IEE wiring regulations.
Warning: Isolate mains supply before commencing installation.
1
Installing the ASR-ZW receiver
The ASR-ZW receiver should be located as near as is practical to the boiler or zone valve to be controlled, as well as a convenient mains electricity supply. To remove the wall plate from the ASR-ZW undo the two retaining screws located in the underside, the wall plate should now be easily removed. Once the wall plate has been removed from the packaging please ensure the ASR­ZW is resealed to prevent damage from dust, debris etc.
The wall plate should be fitted with the retaining screws located at the bottom and in a position which allows a total clearance of at least 50mm around the ASR-ZW receiver.
Direct Wall Mounting
Offer the plate to the wall in position where the ASR-ZW is to be mounted and mark the fixing positions through the slots in the wall plate. Drill and plug the wall, then secure the plate into position. The slots in the wall plate will compensate for any misalignment of the fixings.
Wall Box Mounting
The wall plate may be fitted directly on to a single gang flush wiring box complying with BS4662, using two M3.5 screws. The receiver is suitable for mounting on a flat surface only; it is not suitable for mounting on an unearthed metal surface.
2
Electrical Connections
WARNING: ISOLATE THE MAINS SUPPLY BEFORE COMMENCING INSTALLATION
As the C-Stat is a wireless product with no electrical connections all electrical wiring will be made to the ASR-ZW receiver.
All necessary electrical connections should now be made. Flush wiring can enter from the rear through the aperture in the backplate.
The mains supply terminals are intended to be connected to the supply by means of fixed wiring.
The receiver is mains powered and requires a 3 Amp fused spur.
The recommended cable size is 1.0mm².
The receiver is double insulated and does not require an earth connection, an earth connection block is provided on the backplate for terminating any cable earth conductors. Earth continuity must be maintained and all bare earth conductors must be sleeved. Ensure that no conductors are left protruding outside the central space enclosed by the backplate.
ASR-ZW Receiver internal wiring diagram
Internal Electronics
1 2 3 4LN
230V 50Hz COMM OFF ON
The receiver has Voltage Free contacts. A link between Live and terminal 2 is required for mains Voltage applications.
3
Example circuit diagrams for typical boiler installations are shown below. These diagrams are schematic and should be used for guidance only.
Please ensure that all installations comply with the current IEE regulations and the boil er manufactu rer 's installat ion instructions.
For reasons of space and clarity not every connection has been included and the diagrams have been simplified, for instance some earth connections have been omitted.
Cylinder and Room Thermostat Key:
C= Common CALL= Call for heat or break on rise
SAT= Satisfied on rise N= Neutral
ASR Receiver
3
1 2
L
Mains
N
Supply
E
E
L
N
COMBINATION BOILER
TERMINALS
C-Stat ASR Receiver controlling typical combination boiler installation. For precise termination connection information please refer to the boiler manufactures instructions
4
4
Remove link if Fitted
Programmer
HOT
CENTRAL
WATER
HEATING
OFF
ON
N L
N
MAINS
L
SUPPLY
E
C-Stat ASR Receiver controlling a secondary heating zone on a fully pumped system with existing programmer and two spring return valves with auxiliary switches
C CN
CALL
SAT
OFF
ON
ASR Receiver
MAINS SUPPLY
N L E
1 2 3 4
PUMP
N
&
BOILER
L
ROOM
CYL
STAT
STAT
CALL
SAT
Programmer
HOT
CENTRAL
WATER
HEATING
OFF
CYL STAT
CALLSAT
OFF
ON
ASR Receiver
2
3
4
SAT
L
N
PUMP
&
BOILER
ON
N L
N
MAINS
L
SUPPLY
E
W
BL
0
GR
C-Stat ASR Receiver replacing a conventional room thermostat on a fully pumped system with an existing programmer and 3 port mid-position valve.
C
CALL
5
Programmer
HOT
CENTRAL
WATER
HEATING
OFF
ON
N L
N
MAINS
L
SUPPLY
E
C-Stat ASR Receiver replacing a conventional room thermostat on a fully pumped system with existing programmer and two spring return valves with auxiliary switches
N
PUMP
BOILER
C
CALL
L
&
OFF
ON
ASR Receiver
CYL
2
STAT
4
3
CALLSAT
SAT
6
TPI Temperature control software
Thermostats using TPI (Time Proportional Integral) control algorithms will reduce the temperature swing that normally occurs when using traditional bellows or thermally operated thermostats. As a consequence, a TPI regulating thermostat will maintain the comfort level far more efficiently than any traditional thermostat.
When used with a condensing boiler, the TPI thermostat will help to save energy as the control algorithm allows the boiler to operate in condensing mode more consistently compared to older types of thermostat.
Ÿ For Gas boilers set the TPI setting to 6 cycles per hour (default
setting)
Ÿ For Oil boilers set the TPI setting to 3 cycles per hour Ÿ For Electric heating set the TPI setting to 12 cycles per hour
To adjust this setting go to the SET UP MENU and select TPI CYCLES
7
Fitting the C-Stat Programmable Room Thermostat
Before final installation it is advisable to commission the product and e nsure t hat t he Th ermosta t and R ec eiver a re communicating satisfactorily. First install the 2 x AA batteries provided making sure that they are fitted correctly as indicated by the markings in the battery compartment on the front of the C­Stat. Once the thermostat and receiver are successfully 'paired' the thermostat can be installed in its correct location. Please see Z-Wave pairing instructions on page 9.
1.5m
8
Before fixing the wall plate in position check to see that the thermostat and receiver are still able to communicate satisfactorily by turning the thermostat temperature up and down to switch the ASR-ZW receiver on and off.
Offer the plate to the wall in the position where the C-Stat is to be mounted and mark the fixing positions through the slots in the wall plate. Drill and plug the wall, then secure the plate into position. The slots in the wall plate will compensate for any misalignment of the fixings.
Complete installation by swinging the C-Stat into position by engaging with the lugs at the top of the wall plate before pushing it carefully home into its plug-in terminal block.
Tighten the 2 captive screws on the underside of the unit.
Now ensure that the heating system is responding to the ON/OFF commands from the C-Stat and explain its operation to the householder before handing over the User Instructions.
9
Pairing the C-Stat ZW programmable room thermostat with ASR-ZW receiver
The C-Stat uses the latest Z-Wave wireless communication technology to give a reliable wireless link that should not suffer from interference from other nearby devices. The device comprises of a thermostat (C-Stat ZW) and its receiver (ASR­ZW). Pa ir in g th e de vi ce s on s it e ensures reliable communication.
Follow these steps to ensure that the C-Stat programmable stat will communicate satisfactorily with its receiver; this is best carried out with the C-Stat held nearby the (powered) ASR-ZW receiver.
The ASR-ZW receiver should be powered up with the network button flashing red before following Procedure A on page 11.
If the red network button light does not flash red then please go to Procedure B on page 12 before returning to Procedure A on page 11.
HRT4
ASR-ZW
ON
OFF
Network LED
Network Button
Procedure A
1. On the C-Stat programmable stat, Press ENTER twice
2. Press '-' or '+' to select SETUP
3. Press ENTER
4. Press '-' or '+' to select SET UP Z-WAVE
5. Press ENTER
6. This will now show the sub menu available for the Z-Wave wireless communication settings
7. Select INCLUDE NODE / RECEIVER
8. Press ENTER
9. INCLUDING will appear under the INCLUDE NODE heading.
10. Press and hold the network button on the ASR-ZW Receiver until the flashing red light turns to a flashing green light followed quickly by a solid red light
11. RECEIVER INCLUDED will now appear in the display of the C-Stat. Press BACK and the antenna icon on the top left had corner of the display will show it is active with radio waves
12. The C-Stat and ASR-ZW Receiver are now 'paired'. The
Receiver should receive ON/OFF commands from the C­Stat wirelessly.
Check this by turning the temperature on the C-Stat up and down to see that the ASR-ZW receiver responds accordingly with a green light for ON and a red light for OFF.
11
Procedure B
1. On the C-Stat programmable stat, Press ENTER twice
2. Press '-' or '+' to select SETUP
3. Press ENTER
4. Press '-' or '+' to select SET UP Z-WAVE
5. Press ENTER
6. Press '-' or '+' to select NETWORK RESET
7. Press ENTER
8. Press ENTER again to confirm and NETWORK RESET
COMPLETE will appear on the display
9. Press BACK to go back to SET UP Z-WAVE
10. Press ENTER
11. Press '-' or '+' to select EXCLUDE NODE / RECEIVER
12. Press ENTER
13. Go to the Powered ASR-ZW receiver, press and hold the
network button
14. EXCLUDING will appear on the display of the C-Stat
15. When completed NODE / EXCLUDED will appear on the
display.
16. The red network light on the ASR-ZW will start flashing
17. Once the red light is flashing follow Procedure A on page
11
12
Installer Settings
There are a number of 'Installer Settings' that should be set on installation.
These can be found under the 'SET UP MENU' on page 15 of the user instructions.
Clock Format AM/PM or 24 Hour clock display - Default
Daylight saving On or Off - Default setting ON for UK Market
Standby temperature Frost protection setting – Default setting 5°C
Upper and Lower Default settings 30°C and 5°C
Temperature limits
TPI Cycles This setting will change according to the
Optimum Start On or Off – Default setting Off
The TPI Cycles setting and Optimum Start settings should be carefully set on installation as this will affect system performance.
setting AM/PM
type of boiler being used - Default setting 6
For Gas boiler this setting should be 6
cycles per hour
For Oil boilers this setting should be 3
cycles per hour
For Electric panel heaters this should be 12
cycles per hour
13
Resetting the C-Stat
Electronic equipment can in some circumstances be affected by electrical interference.
If the display becomes frozen or scrambled simply press both the BACK and ENTER button simultaneously.
This will cancel all settings made and return to the factory default settings.
BACK
14
ENTER
Specification – C-Stat 11-ZW | C-Stat 17-ZW
Thermostat
Power Supply 2 x AA Batteries Contact type Micro-disconnection Wiring configuration Voltage free c/o contacts (SPDT) Temperature differential 0.5°C Temperature accuracy +/- 0.5°C to 21°C Standards BS EN 60730-2-9 Dimensions (WxHxD) 120mm x 100mm x 26.5mm Weight 0.3kg (approx) Enclosure Flame retardant thermoplastic Ingress protection IP30 Pollution degree Degree 2 Insulation class Class II (Double Insulated) Temperature range 0°C to 40°C Transmitter Frequency 868 MHZ Receiver Category Category 3 Power Class Class B
Receiver
Power Supply 230V AC 50Hz Contact Type Micro-disconnection
Contact Current Rating 3 (1) Amps 230V AC Insulation Class Double Insulated Rated Impulse Voltage Cat 2 – 2500V Pollution Degree Degree 2 Enclosure Protection Flame retardant thermoplastic Dimensions 86 x 86 x 36.25mm
15
Voltage Free
Secure Controls (UK) Limited