Horner APG XLt, HEXT240C015 User Manual

MAN0873-06-EN Specifications / Installation
1 Specifications
Inputs per Module 12 including 4 configurable HSC inputs Outputs per Module 12 including 2 configurable PWM outputs
Commons per Module 1 Commons per Module 1
Input Voltage Range 12 VDC / 24 VDC Output Type Sourcing / 10 K Pull-Down
Absolute Max. Voltage 35 VDC Max. Absolute Max. Voltage 28 VDC Max.
Input Impedance
Input Current Positive Logic Negative Logic Max. Output Current per point 0.5 A Upper Threshold 0.8 mA -1.6 mA Max. Total Current 4 A Continuous Lower Threshold 0.3 mA -2.1 mA Max. Output Supply Voltage 30 VDC
Max Upper Threshold 8 VDC Minimum Output Supply Voltage 10 VDC
Min Lower Threshold 3 VDC Max. Voltage Drop at Rated Current 0.25 VDC
OFF to ON Response 1 ms Max. Inrush Current 650 mA per channel ON to OFF Response 1 ms Min. Load None
HSC Max. Switching Rate
Number of Channels 2 Thermocouple Temperature Range
Input Ranges
(Selectable)
Safe input voltage range
Nominal Resolution
Input Impedance
(Clamped @ -0.5 VDC to
%AI full scale
Max. Over-Current 35 mA Conversion Time per Channel
Open Thermocouple
Detect Current
XLT OCS Model: HE-XT105 / HEXT240C115 / HEXT240C015
12 Digital DC Inputs / 12 Digital DC Outputs
2 Analog Inputs (High Resolution) / 2 Analog Outputs
Output Protection Short Circuit
OFF to ON Response 1 ms ON to OFF Response 1 ms
Output Characteristics Current Sourcing (Positive Logic)
B / R / S
E T
J
K / N
Thermocouple Common Mode Range ±10V
Converter Type Delta Sigma
Max. Error at 25°C
(*excluding zero)
Max Thermocouple Error
(After Warm Up Time of One Hour) Conversion Speed, Both Channels
Converted
2912°F to 32.0°F (1600°C to 0°C)
1652°F to -328°F (900°C to -200°C)
752.0°F to -400.0°F (400°C to -240°C)
1382.0°F to -346.0°F (750°C to -210°C)
2498.0°F to -400°F (1370°C to -240°C)
*4-20 mA ±0.10%* *0-20 mA ±0.10%* *0-10 VDC ±0.10%*
RTD (PT100) ±1.0 °C
0-100 mV ±0.05%
±0.2% (±0.3% below -100°C)
10V, 20mA, 100mV: 30 Times/Second
RTD, Thermocouple: 7.5 Times/Second
10V, 20mA, 100mV: 16.7mS
RTD, Thermocouple: 66.7mS
12 VDC)
10 kΩ
10 kHz Totalizer/Pulse, Edges 5 kHz Frequency/Pulse, Width
2.5 kHz Quadrature Analog Inputs, High Resolution
0 - 10 VDC
0 – 20 mA 4 – 20 mA
100mV
PT100 RTD,
and J, K, N, T, E, R, S, B Thermocouples
10 VDC: -0.5 V to +15 V
20 mA: -0.5 V to +6 V
RTD / T/C: ±24 VDC
10V, 20mA, 100mV: 14 Bits
RTD, Thermocouple: 16 Bits
Current Mode:
100 Ω, 35mA Max. Continuous
Voltage Mode:
500 kΩ, 35mA Max. Continuous
10 V, 20 mA, 100 mV: 32,000 counts full scale.
RTD / T/C: 20 counts / °C
50 nA RTD Excitation Current
250 μA
Analog Outputs General Specifications
Number of Channels 2
Output Ranges
Nominal Resolution 12 Bits Primary Power Range 10 - 30 VDC
Update rate Once per PLC scan Operating Temperature
Minimum 10 V load
Maximum 20 mA load
Analog Outputs;
Output Points Required
Maximum Error at 25°C (excluding
zero)
Additional error for temperatures
other than 25°C
Clock Accuracy +/- Seven Minutes/Month at 20C
__________________________________________________________________________________________________________________________________________________________________ 12/18/2008 Page 1 of 4 ECN # 947
0-10 VDC,
0-20 mA
1 kΩ
500 Ω
2 Filtering
0.1%
0.01% / °C
Note: Highest usable frequency for PWM output is 65 KHz
Required Power
(Steady State)
Required Power (Inrush) 30 A for 1 ms @ 24 VDC
Storage Temperature 14 to 140°F (-10 to 60°C)
Relative Humidity 5 to 95% Non-condensing
1-128 scan digital running average filter
Terminal Type Screw Type,5 mm Removable
Weight 12.5 oz. (354.36)
CE UL
http://www.heapg.com/Pages/TechSupport/ProductCert.html
130 mA @ 24 VDC
-10° to 60° Celsius
15Hz hash (noise) filter
See Compliance Table at
MAN0873-06-EN Specifications / Installation
A
g
2 Panel Cut-Out and Dimensions
Note: Max. panel thickness: 5 mm.
Refer to XLe/XLt User Manual for panel box information and a handy checklist of requirements.
Note: The tolerance to meet NEMA standards is ± 0.005” (0.1 mm).
3.622 [92mm]
3.622 [92mm]
001XLE002
Note – Your keypad overlay
appearance may differ.
Standard US/EU overlays
pictured here for example.
3 Ports / Connectors / Cables Note: The case of the XLt is black, but for clarity, it is shown in a lighter gray color.
RS-232 / RS-485)(
(RS-232 / RS-485)
To Remove Back Cover:
Unscrew 4 screws located on
I/O Jumpers (Not Shown): I/O Jumpers (JP) are located
Wiring Connectors (J1 – J3), I/O Jumpers (JP1 – JP4), and External Jumpers (RS-485) are described in the Wiring and
Jumpers section of this document.
001ACC009
DIP
Memory Slot
Switch
MJ2
MJ1
J1
I/O
Jumper
Power
CAUTION:
the back of the unit.
Remove Cover.
Do not over tighten screws
when replacing the back cover.
internally. To access, remove back cover of unit.
Jumper
NET 1
sCAN)(C
001XLE029-R2
Uses Removable Memory for data logging, screen captures,
J2
program loading and recipes.
I/O
Horner Part No.: HE-MC1
Serial Communications:
MJ1: (RS-232 / RS-485) Use for
Cscape programming and
MJ2: (RS-232 / RS-485) Use for
8
Power Connector
Connect to Earth Ground.
Torque rating 4.5 – 7 Lb-In
Power Up:
Apply 10 - 30 VDC.
Screen lights up.
(0.50 – 0.78 N-m)
CAN Connector
Use the CAN Connector when
using CsCAN network.
Torque Rating 4.5 – 7 Lb-In
(0.50 – 0.78 N-m)
1
Serial
Communications:
MJ1 and MJ2
(RS-232 / RS-485)
4 Wiring and Jumpers
Wire according to the type of inputs / outputs used and select the appropriate jumper option. Use Copper Conductors in Field Wirin
Wiring Specifications
For I/O wiring (discrete), use the following wire type or
equivalent: Belden 9918, 18 AWG (0.8 mm
For shielded Analog I/O wiring, use the following wire
type or equivalent: Belden 8441, 18 AWG (0.8 mm
For CAN wiring, use the following wire type or
equivalent: Belden 3084, 24 AWG (0.2 mm
12-24VDC
Memory Slot:
Application-Defined
Communications.
Application-Defined
Communications.
Pin MJ1 Pins MJ2 Pins
Signal Direction Signal Direction
TXD OUT TXD OUT
8
RXD IN RXD IN
7
0 V Ground 0 V Ground
6
+5 60mA OUT +5 60mA OUT
5*
RTS OUT TX- OUT
4
CTS IN TX+ OUT
3
RX- / TX- IN / OUT TX-/RX- IN
2
RX+ / TX+ IN / OUT TX+/RX+ IN
1
Only, 60/75° C
larger.
2
) or larger.
2
) or larger.
Location of I/O jumpers (JP)
and wiring connectors
2
) or
J1 J2
Positive Logic vs. Negative Logic Wiring
The XLe can be wired for Positive Logic inputs or
Negative Logic inputs.
I1
0V
Positive Logic In Negative Logic In
I1
0V
001XLE036
4.1 I/O Jumpers Settings (JP1 – JP4) Note: The Cscape Module Setup configuration must match
the selected I/O (JP) jumper settings.
CURRENT
(20mA)
JP4
ANALOG OUTPUT SETTING
VOLTAGE OR CURRENT
VOLTAGE
(10V)
AQ2 AQ1 AQ2 AQ1
Default
Note: When using JP4 (output) or JP2 / JP3 (inputs), each channel can be independently configured. For example, JP2 can be configured for 10 V and JP3 can be configured as an RTD.
JP1 Digital DC Inputs
Positive Logic
Default
Negative Logic
* +5Vdc 60mA Max
(J1 – J3).
JP1
JP2
JP3
JP4
J3
nalog In Settings
AI1 AI2
T/C/100mV
JP2
T1 T2
RTD (PT100)
JP2 JP3
T1 T2
10V/20mA
JP2 JP3
Default
MA1/V1 MA2/V2
001XLE030
JP3
__________________________________________________________________________________________________________________________________________________________________ 12/18/2008 Page 2 of 4 ECN # 947
MAN0873-06-EN Specifications / Installation
8
j
A
4.2 External DIP Switch Settings (or Jumpers Settings)
The External DIP Switches are used for termination of the RS-485 ports. The XLt is shipped un-terminated.
To terminate, select one of the
umpers shipped with the product and insert it based upon the option that is desired or, select the switch and configure based upon the option that is desired.
s seen when looking at the top of the XLt unit: Refer to
Section 3 for the location of the External Jumpers.
DIPSW3: FACTORY USE ONLY (tiny bootloader firmware downloading). NOT TO BE USED FOR NORMAL OCS OPERATION.
DIPSW2: MJ2 Termination (default – none)
DIPSW1: MJ1 Termination (default – none)
001XLE037-R1
4.3 Wiring Examples Note: The wiring examples show Positive Logic input wiring.
J1
Orange
I1 IN1 I2 IN2 I3 IN3 I4 IN4 I5 IN5 I6 IN6 I7 IN7 I8 IN8
H1 H2 H3
H4 NC NC
0V Ground
J3
Orange
T1+
T1-
T2+
T2­AQ1 AQ2
0V Ground
MA1 20 mA IN1
V1 10 V IN1 0V Ground
MA2 20 mA IN2
V2 10 V IN2 0V Ground
________________________________________________________________ ___________________________________________________________________
Name
12-24
VDC
HSC1 /
IN9
HSC2 /
IN10
HSC3 /
IN11
HSC4 /
IN12
No
Connect
No
Connect
Name
T/C / RTD IN1+ /
100 mV+
T/C / RTD IN1- /
100 mV-
T/C / RTD IN2+ /
100 mV+
T/C / RTD IN2- /
100 mV-
10 V / 20 mA
OUT1
0 V / 20 mA
OUT2
J1 Orange
Positive Logic
Digital In
I1 I2 I3 I4 I5 I6 I7
I8 H1 H2 H3 H4 NC NC 0V
001XLE007
J2
Black
Name
0V Ground
V+* V+*
NC
No
Connect Q12 OUT12 Q11 OUT11 Q10 OUT10
Q9 OUT9 Q8 OUT8 Q7 OUT7 Q6 OUT6 Q5 OUT5 Q4 OUT4 Q3 OUT3
Q2 Q1
OUT2 /
PWM2
OUT1 /
PWM1
V+* Supply for
Sourcing Outputs
J3 Orange
Analog In / Analog Out
Note: A total of 2 Analog Inputs can be used (T/C, RTD, mV, mA, and V).
Thermocouple In
RTD In
mV In
100mV+
100mV-
Note: Loop Power (LOOP PWR) requirements are determined by the transmitter specificatio n.
T1+
T1-
T1+ T1-
0V
T1+
T1­0V
LOOP PWR
Note: Be sure to wire 0 V to V1 as shown for proper operation.
_______________________________
0 -10 V Analog Out
10VDC
4 - 20 mA Analog Out
20mA
0 – 10 V Analog In
0-10VDC
20 mA Analog In
20mA
J2 Black
Positive Logic
Digital Outputs
10 - 30VDC
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
001XLE00
AQ1
0V
AQ1
0V
MA1
NC
V1
0V
MA1
V1
0V
5 I/O Register Map
Registers
Description
%I1 to %I24 Digital Inputs
%I32 Output Fault
%I25 to %I31 Reserved
%Q1 to %Q16 Digital outputs
%Q17 Clear HSC1 accumulator to 0
Totalizer: Clear HSC2
%Q18
Quadrature 1-2: Accumulator 1
Reset to max – 1
%Q19 Clear HSC3 Accumulator to 0
Totalizer: Clear HSC4
%Q20
Quadrature 3-4: Accumulator 3
Reset to max – 1
%Q21 to %Q32 Reserved
%AI1 to %AI4 Analog inputs
%AI5, %AI6 HSC1 Accumulator %AI7, %AI8 HSC2 Accumulator
%AI9, %AI10 HSC3 Accumulator
%AI11, %AI12 HSC4 Accumulator %AQ1, %AQ2 PWM1 Duty Cycle
%AQ3, %AQ4 PWM2 Duty Cycle %AQ5, %AQ6 PWM Prescale
0V V+
NC Q12 Q11 Q10
Q9 Q8 Q7 Q6 Q5 Q4 Q3 Q2 Q1
%AQ7, %AQ8 PWM Period
%AQ9 to %AQ14 Analog outputs
Note: Not all XLe units contain the I/O listed in this table.
Registers PWM HSC Stepper
%AQ1 %AQ2
%AQ3 %AQ4
%AQ5 %AQ6 %AQ7
%AQ8
PWM1 Duty
Cycle
(32 bit)
PWM2 Duty
Cycle
(32 bit)
PWM
Prescale
(32 bit)
PWM Period
(32 bit)
HSC1
Preset
Value HSC2
Preset
Value
%Q1 Run %I30 Ready/Done %I31
6 MJ2 Pinouts in Full and Half Duplex Modes
8
1
8
1
Pin MJ2 Pins
Signal Direction
TXD OUT
8
RXD IN
7
0 V Ground
6
+5 60mA OUT
5*
TX- OUT
4
TX+ OUT
3
RX- IN
2
RX+ IN
1
* +5Vdc 60mA Max
Pin MJ2 Pins
Signal Direction
TXD OUT
8
RXD IN
7
0 V Ground
6
+5 60mA OUT
5*
TX- OUT
4
TX+ OUT
3
TX-/RX- IN/OUT
2
TX+/RX+ IN/OUT
1
Full Duplex
Half Duplex
Start
Frequency
Run
Frequency
Accel Count
(32 bit)
Run Count
(32 bit)
Decel Count
(32 bit)
Error
12/18/2008 Page 3 of 4 ECN # 947
MAN0873-06-EN Specifications / Installation
g
y
r
7 Digital Filtering for Analog Inputs 9 Safety
The digital filter is updated once per conversion. It is an “IIR” running average filter that emulates a simple RC filter. The equivalent time constant is determined by the Filter Constant and the sum of the conversion times for the two channels. The Filter two input mode selections. This filter delay is in addition to the PLC scan delay. Constant determines the weight given to the most recent conversion. The following table lists the equivalent time constant for the three possible total conversion times, which are dependent upon the
Equivalent RC Time Constant in Seconds
(Nominal time to reach 63% of final value.)
Total Conversion Time in Seconds
Filter Constant 0.03 0.09 0.13
0* 0.03* 0.09* 0.13*
1 0.07 0.18 0.27 2 0.13 0.35 0.53 3 0.27 0.71 1.07 4 0.53 1.41 2.13 5 1.07 2.83 4.27 6 2.14 5.65 8.54 7 4.28 11.30 17.08
* No filter delay, reading is unfiltered conversion value
8 Thermocouple Grounding Schemes
Ungrounded Thermocouples
Alternate Shield Connection for
Ungrounded Thermocouples.
Ungrounded Thermocouples
Preferred Shield Connection for
Un
rounded Thermocouples.
Grounded Thermocouples
Field Ground Potential Less
Than Seven Volts AC
Typical Shield Connection for
Grounded Thermocouples
Field Ground Potential Less Than Seven Volts AC
Shields Connected at One End Only May be Used to
Grounded Thermocouples May Use the Ungrounded Thermocouple Shield Connections if the Shield is not
Note: The examples for thermocouple grounding schemes above are generic illustrations.
The XT105 has two thermocouple inputs.
Grounded Thermocouples
Reduce Noise
Grounded at the Field End
10 Technical Support
For assistance and manual updates, contact Technical Support at the following locations:
North America:
(317) 916-4274 www.heapg.com email:
__________________________________________________________________________________________________________________________________________________________________ 12/18/2008 Page 4 of 4 ECN # 947
techsppt@heapg.com
Europe:
(+) 353-21-4321-266 www.horner-apg.com email:
techsupport@hornerirl.ie
When found on the product, the following symbols specify:
Warning: Electrical Shock Hazard.
This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or Non-hazardous locations only
WARNING – EXPLOSION HAZARD – Substitution of components may impair suitability for Class I, Division 2 AVERTISSEMENT - RISQUE D'EXPLOSION - LA SUBSTITUTION DE COMPOSANTS PEUT RENDRE CE MATERIAL INACCEPTABLE POUR LES EMPLACEMENTS DE CLASSE 1, DIVISION 2
WARNING – EXPLOSION HAZARD – Do not disconnect equipment unless power has been switched off or the area is known to be non-hazardous. AVERTISSEMENT - RISQUE D'EXPLOSION - AVANT DE DECONNECTOR L'EQUIPMENT, COUPER LE COURANT OU S'ASSURER QUE L'EMPLACEMENT EST DESIGNE NON DANGEREUX.
WARNING: To avoid the risk of electric shock or burns, always connect the safety (or earth) ground before making any other connections.
WARNING: To reduce the risk of fire, electrical shock, or physical injury it is strongly recommended to fuse the voltage measurement inputs. Be sure to locate fuses as close to the source as possible.
WARNING: Replace fuse with the same type and rating to provide protection against risk of fire and shock hazards.
WARNING: In the event of repeated failure, do repeated failure indicates a defective condition that will fuse.
WARNING: Only qualified electrical personnel familiar with the construction and operation of this equipment and the hazards involved should install, adjust, operate, or service this equipment. Read and understand this manual and other applicable manuals in their entirety before proceeding. Failure to observe this precaution could result in severe bodily injury or loss of life.
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
1. This device may not cause harmful interference.
2. This device must accept any interference received, including interference that may cause undesired operation.
All applicable codes and standards need to be followed in the installation of this product. Adhere to the following safety precautions whenever any type of connection is made to the module: Connect the safety (earth) ground on the power connector first before making an other connections. When connecting to electric circuits or pulse-initiating equipment, open their related breakers. Do
not make connections to live power lines.
Make connections to the module first; then connect to the circuit to be monitored. Route power wires in a safe manner in accordance with good practice and local
codes. Wear proper personal protective equipment including safety glasses and insulated gloves when making connections to power circuits. Ensure hands, shoes, and floor are dry before making any connection to a powe line.
Make sure the unit is turned OFF before making connection to terminals. Make sure all circuits are de-energized before making connections. Before each use, inspect all cables for breaks or cracks in the insulation. Replace
immediately if defective.
Use Copper Conductors in Field Wiring Only, 60/75° C
No part of this publication may be reproduced without the prior agreement and written permission of Horner APG, Inc. Information in this document is subject to change without notice.
Warning: Consult user documentation.
not
replace the fuse again as a
not clear by replacing the
Loading...