Horner APG XLt, HE-XT102-14 User Manual

Page 1
MAN0867-01-EN Specifications / Installation

1 Specifications 1 Specifications

HE-XT102-14 Specifications
Inputs per Module
Commons per Module 1
Input Voltage Range 12 VDC / 24 VDC
Absolute Max. Voltage 35 VDC Max.
Input Impedance
Input Current Positive Logic Negative Logic
Upper Threshold 0.8 mA -1.6 mA Lower Threshold 0.3 mA -2.1 mA
Max Upper Threshold 8 VDC
Min Lower Threshold 3 VDC
OFF to ON Response 1 ms ON to OFF Response 1 ms
HSC Max. Switching Rate
Digital Relay Outputs
Outputs per Module 6 relay
Commons per Module 6
Max. Output Current per Relay 3 A at 250 VAC, resistive
Max. Total Output Current 5 A continuous
Max. Output Voltage 275 VAC , 30 VDC
Max. Switched Power 1250 VA, 150 W
Contact Isolation to XLE
ground
Max. Voltage Drop at Rated
Current
Expected Life
(See Derating section for
chart.)
Max. Switching Rate
Type Mechanical Contact
Response Time
Thermistor Inputs, Medium Resolution
Number of Channels 4
Input Ranges
Input Impedance
(Clamped @ -0.5 VDC to 12
VDC)
Nominal Resolution
%AI at 10K Ohm
Conversion Speed
Max. Error at 25°C reading /
ambient
Filtering
General Specifications
Required Power
(Steady State)
Required Power (Inrush) 30 A for 1 ms @ 24 VDC
Primary Power Range 10 – 30 VDC
Relative Humidity 5 to 95% Non-condensing
Operating Temperature
Terminal Type Screw Type, 5 mm Removable
Weight 12 oz. (340.19 g)
12 including 4 configurable
HSC inputs
10 kΩ
10 kHz Totalizer/Pulse,
Edges
5 kHz Frequency/Pulse,
Width
2.5 kHz Quadrature
1000 VAC
0.5 V
No load: 5,000,000
Rated load: 100,000
300 CPM at no load
20 CPM at rated load
One update per ladder scan
plus 10 ms
10K OHMThermistor
Half Bridge
9.59K ohm pulled up to
4.8 VDC
10 Bits
15,008 counts
All channels converted once
per ladder scan
±0.5°F or ±0.3°C
Using specified linearization
in ladder program
160 Hz hash (noise) filter
1-128 scan digital running
average filter
150 mA @ 24 VDC
-10°C to +60°C
XLT OCS Model: HE-XT102-14
12 Digital DC Inputs
4 10k Thermistors
6 Digital Relay Outputs
CE UL
See Compliance Table at http://www.heapg.com/Pages/TechSupport/ProductCert.html
Note: The highest usable frequency is 65 KHz for the PWM output
General Specifications

2 Panel Cut-Out and Dimensions

Note: Max. panel thickness: 5 mm.
Refer to XLT User Manual (MAN0863) for panel box information and a handy checklist of requirements. Note: The tolerance to meet NEMA standards is ± 0.005” (0.1 mm).
3.622 [92mm]
3.622 [92mm]
001XLE002

3 Ports / Connectors / Cables

Note: The case of the XLT is black, but for clarity, it is shown in a lighter gray color.
To Remove Back Cover:
Unscrew 4 screws located on the back of the unit. Lift lid.
CAUTION: Do not
overtighten screws when screwing the lid back on.
I/O Jumpers: (Not Shown):
I/O Jumpers (JP) are located internally. To access, remove back cover of unit.
Wiring Connectors (J1 / J2): I/O Jumpers (JP1), and DIP Switches (RS-485) are described in the DIP Switches, Wiring and
Jumpers section of this document.
Memory Slot:
Uses Removable Memory for data logging, screen captures, program loading and recipes.
Horner Part No.: HE-MC1 Serial Communications:
MJ1: (RS-232 / RS-485) Use
for Cscape programming and Application-Defined Communications.
MJ2: (RS-232 / RS-485) Use for Application-Defined Communications.
(RS-232 / RS-485)
(RS-232 / RS-485)
DIP
Memory Slot
Switch
MJ2
MJ1
J1
I/O
Jumper
Power Connector
Power Up:
Connect to Earth Ground.
Apply 10 - 30 VDC.
Screen lights up.
Torque rating
4.5-7Lb-in
(0.50-0.78n-m)
Power
CAN Connector
Use the CAN Connector when using CsCAN network.
001XLE029-R2
NET 1
(CsCAN)
Jumper
__________________________________________________________________________________________________________________________________________________________________
3/26/2009 Page 1 of 4 ECN # 956
J2
I/O
Page 2
MAN0867-01-EN Specifications / Installation
A
r
A
r
A
4 Serial Communications:
Serial Communications: MJ1: (RS-232 / RS-485) Use for Cscape programming and
pplication-Defined Communications.
MJ2: (RS-232 / RS-485) Use for Application-Defined Communications.
8
1

5 DIP Switches, Wiring and Jumpers

Wire according to the type of inputs / outputs used, and select the appropriate jumper option.
Wiring Specifications
For I/O wiring (discrete), use the following wire type or equivalent: Belden 9918, 18 AWG or larger.
For shielded Analog I/O wiring, use the following wire type o equivalent: Belden 8441, 18
WG or larger.
For CAN wiring, use the following wire type or equivalent: Belden 3084, 24 AWG or larger.
12-24VDC
5.1. Wiring Examples
J1 Orange Terminal Connector
I1 IN1 I2 IN2 I3 IN3 I4 IN4 I5 IN5 I6 IN6 I7 IN7
I8 IN8 H1 HSC1 /IN9 0V Ground A1 Thermistor 1 A2 Thermistor 2 A3 Thermistor 3 A4 Thermistor 4 0V Ground
__________________________________________________________________________________________________________________________________________________________________
Pin MJ1 Pins MJ2 Pins
Signal Direction Signal Direction
TXD OUT TXD OUT
8
RXD IN RXD IN
7
0 V Ground 0 V Ground
6
5
4
3
2
1
+5
(60mA)
RTS OUT TX- OUT
CTS IN TX+ OUT
RX- /
TX-
RX+ /
TX+
OUT
IN / OUT RX- IN
IN / OUT RX+ IN
+5
(60mA)
Location of I/O jumpers (JP)
and wiring connectors
(J1 and J2).
J1
JP2
Positive Logic vs. Negative Logic Wiring
The XLT can be wired for Positive Logic inputs or
Negative Logic inputs.
I1
0V
I1
0V
001XLE036
Positive Logic In Negative Logic In
XT102
Name
12-24VDC
T
T
XT102 J1 Orange
Positive Logic In
Digital In /
Analog In
OUT
JP1
001XLE062
T
T
001XLE067
J2 Black Terminal Connector
C6 Relay 6 COM R6 Relay 6 NO C5 Relay 5 COM R5 Relay 5 NO C4 Relay 4 COM R4 Relay 4 NO C3 Relay 3 COM R3 Relay 3 NO C2 Relay 2 COM R2 Relay 2 NO C1 Relay 1 COM R1 Relay 1 NO H4 HSC4 / IN12 H3 HSC3 / IN11 H2 HSC2 / IN10
5.2 I/O Jumpers Settings (JP1)
Note: The Cscape Module Setup configuration must match the selected I/O (JP) jumper settings.
J2
5.3 DIP Switch Settings
The DIP Switches are used fo termination of the RS-485 ports. The XLE is shipped un-terminated.
To terminate, select one of the DIP switches and configure it based upon the option that is desired.

6 Derating

I1 I2 I3 I4 I5 I6 I7
I8 H1 0V A1
A2 A3
A4 0V
THE SEALING PROPERTIES OF MATERIALS USED IN THE Tyco relay PCJ
XT102-10 J2 Black
XT102-10
Name
0V ON J1
Positive Logic
Digital In / Relay Out
230VAC
25VDC
230VAC
25VDC
230VAC
25VDC
230VAC
25VDC
230VAC
25VDC
230VAC
25VDC
12-24VDC
N
OR
L
LOAD
N
OR
L
LOAD
N
OR
L
LOAD
N
OR
L
LOAD
N
OR
L
LOAD
N
OR
L
LOAD
C6 R6 C5 R5 C4 R4 C3 R3 C2 R2 C1 R1 H4 H3 H2
001XLE015
JP1 Digital DC In / HSC
Positive Negative
Logic Logic
Default
001XLE026
s seen when looking at the top of the XLT unit:
Factory Use
(default – none)
MJ2 Termination
(default – none)
MJ1 Termination
(default – none)
XLT102 Relay Life Expectancy
40
)
30
4
20 10
(x10
0
Operation
1234
Contact Current (A)
WARNING: EXPOSURE TO SOME CHEMICALS MAY DEGRADE
Cover / case & base: Mitsubishi engineering Plastics Corp.
5010GN6-30 or 5010GN6-30 M8 (PBT)
Sealing Material: Kishimoto 4616-50K (I part epoxy resin)
It is recommended to periodically inspect the relay for any
degradation of properties and replace if degradation is found
001XLE037-R1
3/26/2009 Page 2 of 4 ECN # 956
Page 3
MAN0867-01-EN Specifications / Installation

7 Analog Conditioning

7.1 Filter
Filter Constant sets the level of digital filtering according to the following chart.
100
90 80 70 60 50 40 30 20
%Complet e [ ]
10
0
2 3 4 5 60 7
1
60
Filter Constant
10040 8020
Scans0
Digital Filtering. The illustration above demonstrates the effect of
digital filtering (set with Filter Constant) on module response to a temperature change.
It is recommended that the filter constant for the HE-XT102-14 be set to a value of 7. This will minimize noise and jitter, improve effective resolution, and provide adequate speed for most temperature monitor and control applications.
7.2 Thermistor Linearization
Thermistors are measured using a half-bridge circuit that exhibits variable resolution and the associated increased measurement range.
Temperature, degrees C Resolution, degrees C
-55 1.05
-35 0.36
-15 0.17 5 0.11
25 0.1 45 0.13 65 0.22
85 0.30 105 0.55 125 0.85 145 1.35
Best resolution is at 25°C, 77°F. With a constant 0.1°C resolution circuit, the measurement range would only extend from –26°C to +76°C.
Linearization must be performed by the user in the ladder application code, using 26 internal %R registers per channel. The example below uses %R1-26 to linearize one channel - %AI1. Linearization consists
7.3 Thermistor types
The HE-XT102-14 with the given example ladder code supports Kele Engineering Precon Type III, 10 K thermistors. It also directly supports the following 10 K (Beta=3574) thermistors from Yellow Springs Instruments (YSI).
44006 46006 44106 46031 44406 46041 44031 44907 45006 44908

8 I/O Register Map

Registers
Description
%I1 to %I12 Digital Inputs
%I32 Output Fault
%I25 to %I31 Reserved
%Q1 to %Q16 Digital Outputs
%Q17 Clear HSC1 accumulator to 0
%Q18
Quadrature 1-2: Accumulator 1 Reset to max – 1
Totalizer: Clear HSC2
%Q19 Clear HSC3 Accumulator to 0
%Q20
Quadrature 3-4: Accumulator 3 Reset to max – 1
Totalizer: Clear HSC4
%Q21 to %Q32 Reserved
%AI1 to %AI4 Analog inputs
%AI5, %AI6 HSC1 Accumulator %AI7, %AI8 HSC2 Accumulator
%AI9, %AI10 HSC3 Accumulator
%AI11, %AI12 HSC4 Accumulator
%AQ9 to %AQ14 Analog outputs
%AQ1, %AQ2 PWM1 Duty Cycle %AQ3, %AQ4 PWM2 Duty Cycle %AQ5, %AQ6 PWM Prescale %AQ7, %AQ8 PWM Period
Note: Not all XLT units contain the I/O listed in this table.

9 Safety

When found on the product, the following symbols specify:
Warning: Electrical Shock Hazard.
Warning: Consult user documentation.
of the following example steps.
1) Load the desired linearization coefficients into a table on First Scan using a Move Constant Data block.
Registers (Real) Degrees C Degrees F
R0011 -1.94454e-028 -3.50017e-028 R0013 2.40268e-023 4.32483e-023 R0015 -1.24101e-018 -2.23381e-018 R0017 3.46655e-014 6.23979e-014 R0019 -5.69403e-010 -1.02493e-009 R0021 5.62368e-006 1.01226e-005 R0023 -0.0353121 -0.0635617 R0025 163.878 326.981
2) Load %AI0001 into %R0001 as a Real.
3) Perform the Real Math Expression
4) %R3 = (((%R11*%R1+%R13)*%R1+%R15)*%R1+%R17)
5) Perform the Real Math Expression %R5 = (((%R3*%R1+%R19)*%R1+%R21)*%R1+%R23)*%R1+%R25
6) Load %R0005 result into another register such as %R0007 to save the temperature value.
7) Steps 2 though 5 can be on a single rung.
The expression rung may be copied, substituting %AI0002 and %R00011 for %AI0001 and %R0007, and used to linearize the second
This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or Non-hazardous locations only
WARNING – EXPLOSION HAZARD – Substitution of components may impair suitability for Class I, Division 2 AVERTISSEMENT - RISQUE D'EXPLOSION - LA SUBSTITUTION DE COMPOSANTS PEUT RENDRE CE MATERIAL INACCEPTABLE POUR LES EMPLACEMENTS DE CLASSE 1, DIVISION 2
WARNING – EXPLOSION HAZARD – Do not disconnect equipment unless power has been switched off or the area is known to be non-hazardous. AVERTISSEMENT - RISQUE D'EXPLOSION - AVANT DE DECONNECTOR L'EQUIPMENT, COUPER LE COURANT OU S'ASSURER QUE L'EMPLACEMENT EST DESIGNE NON DANGEREUX.
WARNING: To avoid the risk of electric shock or burns, always connect the safety (or earth) ground before making any other connections.
WARNING: To reduce the risk of fire, electrical shock, or physical injury it is strongly recommended to fuse the voltage measurement inputs. Be sure to locate fuses as close to the source as possible.
WARNING: Replace fuse with the same type and rating to provide protection against risk of fire and shock hazards.
WARNING: In the event of repeated failure, do a defective condition that will
not clear by replacing the fuse.
not replace the fuse again as a repeated failure indicates
WARNING: Only qualified electrical personnel familiar with the construction and operation of this equipment and the hazards involved should install, adjust, operate, or service this equipment. Read and understand this manual and other applicable manuals in their entirety before proceeding. Failure to observe this precaution could result in severe bodily injury or loss of life.
channel. Contact Horner APG Technical Support for an example file containing the above program.
__________________________________________________________________________________________________________________________________________________________________
3/26/2009 Page 3 of 4 ECN # 956
Page 4
MAN0867-01-EN Specifications / Installation
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
1. This device may not cause harmful interference.
2. This device must accept any interference received, including interference that may cause undesired operation.
All applicable codes and standards need to be followed in the installation of this product. Adhere to the following safety precautions whenever any type of connection is made to the module: Connect the safety (earth) ground on the power connector first before making any other connections. When connecting to electric circuits or pulse-initiating equipment, open their related breakers. Do
not make connections to live power lines. Make connections to the module first; then connect to the circuit to be monitored. Route power wires in a safe manner in accordance with good practice and local codes. Wear proper personal protective equipment including safety glasses and insulated gloves when making connections to power circuits. Ensure hands, shoes, and floor are dry before making any connection to a power line. Make sure the unit is turned OFF before making connection to terminals.
Make sure all circuits are de-energized before making connections. Before each use, inspect all cables for breaks or cracks in the
insulation. Replace immediately if defective.
Use Copper Conductors in Field Wiring Only, 60/75° C.

10 Technical Support

For assistance and manual updates, contact Technical Support at the following locations:
North America:
Tel: 317 916-4274 Fax: 317 639-4279
http://www.heapg.com
Web:
techsppt@heapg.com
Email:
Europe:
Tel: +353-21-4321266 Fax: +353-21-4321826
http://www.horner-apg.com
Web: Email: tech.support@horner-apg.com
"WARNING: EXPOSURE TO SOME CHEMICALS MAY DEGRADE
THE SEALING PROPERTIES OF MATERIALS USED IN THE Tyco relay PCJ
Cover / case & base: Mitsubishi engineering Plastics Corp.
5010GN6-30 or 5010GN6-30 M8 (PBT)
Sealing Material: Kishimoto 4616-50K (I part epoxy resin)
It is recommended to periodically inspect the relay for any
degradation of properties and replace if degradation is found
No part of this publication may be reproduced without the prior agreement and written permission of Horner APG, Inc. Information in this document is subject to change without notice.
__________________________________________________________________________________________________________________________________________________________________
3/26/2009 Page 4 of 4 ECN # 956
Loading...