Horner APG XLe, HEXE220C000 User Manual

MAN0877-03-EN Specifications / Installation
r
1 Specifications
HE-XE100 / HEXE220C100 / HEXE220C000
Specifications
UL
2 Panel Cut-Out and Dimensions
General Specifications
130 mA @ 24 VDC 30A for 1 ms @ 24 VDC 10 – 30 VDC
0°C to +50°C
See Compliance Table at :
http://www.heapg.com/Support/compli ance.htm
Note: Max. panel thickness: 5 mm. Refer to the User Manual for panel box information and a handy
checklist of requirements. Note: The tolerance to meet NEMA standards is ± 0.005” (0.1 mm).
3.622 [92mm]
3.622 [92mm]
001XLE002
XLE OCS Model:
3 Ports / Connectors / Cables
Note: The case of the XLe is black, but for clarity, it is shown in a lighter gray color.
To Remove Back Cover:
Unscrew 4 screws located on
the back of the unit and remove
CAUTION: Do notover tighten
back cover.
screws when replacing back
cover.
Memory Slot:
Uses Removable Memory for
data logging, screen captures,
program loading and recipes.
Horner Part No.: HE-MC1
Serial Communications:
MJ1: (RS-232 / RS-485) Use for
Cscape programming and
Application-Defined
Communications.
MJ2: (RS-232 / RS-485) Use for
Application-Defined
Communications.
(RS-232 / RS-485)
(RS-232 / RS-485)
DIP
Switch
MJ2
MJ1
Power Connector
Power Up:
Connect to Earth Ground.
Apply 10 - 30 VDC.
Screen lights up.
Torque rating 4.5 – 7 Lb-In
(0.50 – 0.78 N-m)
Memory Slot
Use the CAN Connector when
using CsCAN network.
Torque rating 4.5 – 7 Lb-In
Powe
CAN Connector
(0.50 – 0.78 N-m)
NET 1
(CsCAN)
Note – Your keypad overlay
appearance may differ. Standard
US/EU overlays pictured here for
__________________________________________________________________________________________________________________________________________________________________ 12/18/2008 Page 1 of 3 ECN # 947
example.
MAN0877-03-EN Specifications / Installation
g
A
A
8
4 Serial Communications: MJ1: (RS-232 / RS-485) Use for Cscape programming and
pplication-Defined Communications.
MJ2: (RS-232 / RS-485) Use for Application-Defined Communications.
8
1
Pin MJ1 Pins MJ2 Pins
Signal Direction Signal Direction
TXD OUT TXD OUT
8
RXD IN RXD IN
7
0 V Ground 0 V Ground
6
+5 60mA OUT +5 60mA OUT
5*
RTS OUT TX- OUT
4
CTS IN TX+ OUT
3
RX- / TX- IN / OUT RX- IN
2
RX+ / TX+ IN / OUT RX+ IN
1
* +5Vdc 60mA Max on XLe Rev E and later
5 Wiring and Jumpers
Wire according to the type of inputs / outputs used, and select the appropriate jumper option.
Use Only Copper Conductors in Field Wiring, 60/75° C
Wiring Specifications
For CAN wiring, use the following wire type or equivalent: Belden 3084, 24 AWG (0.2 mm or lar
er.
2
)
6 MJ2 Pinouts in Half and Full Duplex Modes
Pin MJ2 Pins
Signal Direction
TXD OUT
8
RXD IN
1
7
0 V Ground
6
+5 60mA OUT
5*
TX- OUT
4
TX+ OUT
3
TX-/RX- IN/OUT
2
TX+/RX+ IN/OUT
1
MJ2 Half Duplex Mode
* +5Vdc 60mA Max on XLe
8
1
Pin MJ2 Pins
Signal Direction
TXD OUT
8
RXD IN
7
0 V Ground
6
+5 60mA OUT
5*
TX- OUT
4
TX+ OUT
3
RX- IN
2
RX+ IN
1
Rev E and later
MJ2 Full Duplex Mode
5.1 External DIP Switch Settings (or Jumpers Settings)
The DIP Switches or jumpers are used for termination of the RS-485 ports. The XLe is shipped un­terminated.
To terminate, select one of the DIP Switches and configure it based upon the option that is desired.
s seen when looking at the top of the XLe unit :
DIPSW3: FACTORY USE ONLY (tiny bootloader firmware downloading). NOT TO BE USED FOR NORMAL OCS OPERATION.
DIPSW2: MJ2 Termination (default – none)
DIPSW1: MJ1 Termination (default – none)
DIPSW3: FACTORY USE ONLY (tiny bootloader firmware downloading). NOT TO BE USED FOR NORMAL OCS OPERATION.
DIPSW2: MJ2 Termination (default – none)
DIPSW1: MJ1 Termination (default – none)
001XLE037
001XLE037-R1