Horner APG XLe, HE-XE102-14 User Manual

Page 1
MAN0855-01-EN Specifications / Installation
3
.
6
2
2
[
9
2
m
m
]
001XLE002
Unscrew 4 screws located
Remove cover
.
Application
Memory Slot
001XLE029-R2
Jumper
NET 1
(CsCAN)
Power
DIP
1 Specifications
XLE OCS Model: HE-XE102-14
HE-XE102-14 Specifications
Digital DC Inputs
Commons per Module 1
Input Voltage Range 12 VDC / 24 VDC
Absolute Max. Voltage 35 VDC Max.
Input Impedance
Input Current Positive Logic Negative Logic Upper Threshold 0.8 mA -1.6 mA Lower Threshold 0.3 mA -2.1 mA
Max Upper Threshold 8 VDC
Min Lower Threshold 3 VDC
OFF to ON Response 1 ms ON to OFF Response 1 ms
HSC Max. Switching Rate
Outputs per Module 6 relay
Commons per Module 6
Max. Output Current per Relay 3 A at 250 VAC, resistive
Max. Total Output Current 5 A continuous
Max. Output Voltage 275 VAC , 30 VDC
Max. Switched Power 1250 VA, 150 W
Contact Isolation to XLE
Max. Voltage Drop at Rated
(Clamped @ -0.5 VDC to 12
Max. Error at 25°C reading /
CE
UL
ground
Current
Expected Life
(See Derating section for
chart.)
Max. Switching Rate
Type Mechanical Contact
Response Time
Number of Channels 4
Input Ranges
Input Impedance
VDC)
Nominal Resolution
%AI at 10K Ohm
Conversion Speed
ambient
Filtering
Required Power
(Steady State)
Required Power (Inrush) 30 A for 1 ms @ 24 VDC
Primary Power Range 10 – 30 VDC
Relative Humidity 5 to 95% Non-condensing
Operating Temperature
Terminal Type Screw Type, 5 mm Removable
Weight 12 oz. (340.19 g)
http://www.heapg.com/Pages/TechSupport/ProductCert.html
Clock Accuracy +/- 7 Minute/Month at 20C
Highest usable frequency for PWM output is 65 KHz.
Digital Relay Outputs
Thermistor Inputs, Medium Resolution
General Specifications
12 including 4 configurable HSC
10 kHz Totalizer/Pulse, Edges 5 kHz Frequency/Pulse, Width
One update per ladder scan plus
All channels converted once per
Using specified linearization
1-128 scan digital running average
See Compliance Table at
inputs
10 k
2.5 kHz Quadrature
1000 VAC
0.5 V
No load: 5,000,000
Rated load: 100,000
300 CPM at no load
20 CPM at rated load
10 ms
10K OHMThermistor
Half Bridge
9.59K ohm pulled up to
4.8 VDC 10 Bits
15,008 counts
ladder scan
±0.5°F or ±0.3°C
in ladder program
160 Hz hash (noise) filter
filter
130 mA @ 24 VDC
0°C to +50°C
12 Digital DC Inputs
4 10k Thermistors
6 Digital Relay Outputs
2 Panel Cut-Out and Dimensions
Note: Max. panel thickness: 5 mm. Refer to the XLe/XLt User Manual for panel box information and a handy checklist of requirements.
Note: The tolerance to meet NEMA standards is ± 0.005” (0.1 mm).
3.622 [92mm]
3 Ports / Connectors / Cables Note: The case of the XLe is black, but for clarity, it is shown in a lighter gray color.
To Remove Back Cover:
on the back of the unit.
CAUTION: Do not over
tighten screws when
replacing the back cover.
I/O Jumpers: (Not Shown):
I/O Jumpers (JP) are located internally. To access, remove back cover of unit.
Wiring Connectors (J1 / J2): I/O Jumpers (JP1), and External Jumpers (RS-
485) are described in the Wiring and Jumpers
section of this document.
Memory Slot:
Uses Removable Memory for data logging, screen captures, program loading and recipes.
Horner Part No.: HE-MC1 Serial Communications:
MJ1: (RS-232 / RS-485)
Use for Cscape programming and
Communications. MJ2: (RS-232 / RS-485)
Use for Application-Defined Communications.
-Defined
(RS-232 / RS-485)
(RS-232 / RS-485)
Switch
MJ2
MJ1
Jumper
Power Connector
Power Up:
Connect to Earth Ground.
Apply 10 - 30 VDC.
Screen lights up.
Torque rating 4.5 – 7 Lb-In
(0.50 – 0.78 N-m)
J1
I/O
Note – Your keypad overlay
appearance may differ.
Standard US/EU overlays
pictured here for example
.
CAN Connector
Use the CAN Connector when
using CsCAN network.
Torque Rating 4.5 – 7 Lb-In
(0.50 – 0.78 N-m)
J2
I/O
__________________________________________________________________________________________________________________________________________________________________
7/22/2009 Page 1 of 4 ECN # 956
Page 2
MAN0855-01-EN Specifications / Installation
J2
001XLE025
)
001XLE036
For I/O wiring (discrete), use the
following wire type or equivalent:
For shielded Analog I/O wiring,
following wire type or equivalent:
)
1
8
Application
The Cscape Module Setup configuration must match the
001XLE015
12-24VDC
H4
H2
H3
LOAD
230VAC
LOAD
LOAD
LOAD
230VAC
LOAD
230VAC
Some XLes have jumpers to set
485 port termination, though
The External Jumpers or DIP
Switches are used for termination
485 ports. The XLE is
To terminate, select one of the
jumpers shipped with the product
and insert it based upon the option
that is desired or, select the switch
and configure based upon the
MJ2 Termination
MJ1 Termination
001XLE037
As seen when looki
Operation
001XLE037-R1
MJ2 Termination
MJ1 Termination
0V
A3
A4
001XLE067
4 Serial Communications: MJ1: (RS-232 / RS-485) Use for Cscape programming and
MJ2: (RS-232 / RS-485) Use for Application-Defined
Communications.
-Defined Communications.
Pin
MJ1 Pins MJ2 Pins
Signal Direction Signal Direction
TXD OUT TXD OUT
8
RXD IN RXD IN
7
0 V Ground 0 V Ground
6 5*
4 3
2 1
+5
60mA
RTS OUT TX- OUT CTS IN TX+ OUT
RX- /
TX-
RX+ /
TX+
OUT
IN / OUT RX- IN
IN / OUT RX+ IN
* +5 on XLe Rev E and later
+5
60mA
OUT
5 Wiring and Jumpers
Wire according to the type of inputs / outputs used, and select the appropriate jumper option.
Wiring Specifications
Belden 9918, 18 AWG (0.8 mm2)
use the following wire type or
equivalent: Belden 8441, 18
AWG (0.8 mm2) or larger. For CAN wiring, use the
Belden 3084, 24 AWG (0.2 mm
Use copper conductors in field
wiring only, 60/75° C
12-24VDC
or larger.
or larger.
Positive Logic vs. Negative Logic Wiring
The XLe can be wired for Positive Logic inputs or
Negative Logic inputs.
I1
0V
Positive Logic In Negative Logic In
Location of I/O jumpers (JP
and wiring connectors
(J1 and J2).
J1
2
JP2
JP1
I1
0V
5.1. Wiring Examples
J1 Orange Terminal Connector
I1 IN1 I2 IN2
XE102
Name
12-24VDC
I3 IN3 I4 IN4 I5 IN5 I6 IN6 I7 IN7 I8 IN8
H1 HSC1 /IN9
0V Ground A1 Thermistor 1 A2 Thermistor 2 A3 Thermistor 3 A4 Thermistor 4 0V Ground
T
T
T
T
XE102 J1 Orange
Positive Logic In
Digital In /
Analog In
I1 I2 I3 I4 I5 I6 I7 I8
H1
A1 A2
0V
J2 Black Terminal Connector
C6 Relay 6 COM R6 Relay 6 NO C5 Relay 5 COM R5 Relay 5 NO C4 Relay 4 COM R4 Relay 4 NO C3 Relay 3 COM R3 Relay 3 NO C2 Relay 2 COM R2 Relay 2 NO C1 Relay 1 COM R1 Relay 1 NO H4 HSC4 / IN12 H3 HSC3 / IN11 H2 HSC2 / IN10
XE102
Name
XE102 J2 Black
Positive Logic
Digital In / Relay Out
230VAC 25VDC
230VAC 25VDC
230VAC 25VDC
25VDC
25VDC
25VDC
N
OR
L
LOAD
N
OR
L
N
OR
L
N
OR
L
N
OR
L
N
OR
L
0V ON J1
5.2 I/O Jumpers Settings (JP1)
JP1 Digital DC In / HSC
Positive Negative
Logic Logic
Note:
selected I/O (JP) jumper settings.
Default
001XLE026
5.3 External DIP Switch Settings (or Jumpers Settings)
RS­most use DIP Switches.
of the RS­shipped un-terminated.
Section 4 for the location of the External Jumpers.
Factory Use
(default – none)
(default – none)
(default – none)
ng at the top of the XLE unit: Refer to
option that is desired.
Factory Use
(default – none)
(default – none)
(default – none)
6 Derating
40
)
30
4
20 10
(x10
0
XLE102 Relay Life Expectancy
1 2 3 4
Contact Current (A)
C6 R6 C5 R5 C4 R4 C3 R3 C2 R2 C1 R1
__________________________________________________________________________________________________________________________________________________
7/22/2009 Page 2 of 4 ECN # 956
Page 3
MAN0855-01-EN Specifications / Installation
Substitution of components may impair suitability for Class
60201004080
20
Scans
0
6
%
C
o
m
p
l
e
t
e
[
]
Constant
7 Analog Conditioning
7.1 Filter
Filter Constant sets the level of digital filtering according to the following chart.
1 2 3 4 5
0 7
Filter
100
90 80 70 60 50 40 30
10
0
Digital Filtering. The illustration above demonstrates the effect of digital
filtering (set with Filter Constant) on module response to a temperature change.
It is recommended that the filter constant for the HE-XE102-14 be set to a value of 7. This will minimize noise and jitter, improve effective resolution, and provide adequate speed for most temperature monitor and control applications.
7.2 Thermistor Linearization
Thermistors are measured using a half-bridge circuit that exhibits variable resolution and the associated increased measurement range.
Temperature, degrees C Resolution, degrees C
-55 1.05
-35 0.36
-15 0.17 5 0.11
25 0.1 45 0.13 65 0.22
85 0.30 105 0.55 125 0.85 145 1.35
Best resolution is at 25°C, 77°F. With a constant 0 .1°C resolution circuit, the measurement range would only extend from –26°C to +76°C.
Linearization must be performed by the user in the ladder application code, using 26 internal %R registers per channel. The example below uses %R1­26 to linearize one channel - %AI1. Linearization consists of the following example steps.
1) Load the desired linearization coefficients into a table on First Scan using a Move Constant Data block.
Registers (Real) Degrees C Degrees F
R0011 -1.94454e-028 -3.50017e-028 R0013 2.40268e-023 4.32483e-023 R0015 -1.24101e-018 -2.23381e-018 R0017 3.46655e-014 6.23979e-014 R0019 -5.69403e-010 -1.02493e-009 R0021 5.62368e-006 1.01226e-005 R0023 -0.0353121 -0.0635617 R0025 163.878 326.981
2) Load %AI0001 into %R0001 as a Real.
3) Perform the Real Math Expression
4) %R3 = (((%R11*%R1+%R13)*%R1+%R15)*%R1+%R17)
5) Perform the Real Math Expression %R5 = (((%R3*%R1+%R19)*%R1+%R21)*%R1+%R23)*%R1+%R25
6) Load %R0005 result into another register such as %R0007 to save the temperature value.
7) Steps 2 though 5 can be on a single rung.
7.3 Thermistor types
The HE-XE102-14 with the given example ladder code supports Kele Engineering Precon Type III, 10 K thermistors. It also directly supports the following 10 K (Beta=3574) thermistors from Yellow Springs Instruments (YSI).
44006 46006 44106 46031 44406 46041 44031 44907 45006 44908
8 I/O Register Map
9 Safety
When found on the product, the following symbols specify:
This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or Non-hazardous locations only
WARNING – EXPLOSION HAZARD – I, Division 2 AVERTISSEMENT - RISQUE D'EXPLOSION - LA SUBSTITUTION DE COMPOSANTS PEUT RENDRE CE MATERIAL INACCEPTABLE POUR LES EMPLACEMENTS DE CLASSE 1, DIVISION 2
WARNING – EXPLOSION HAZARD – Do not disconnect equipment unless power has been switched off or the area is known to be non-hazardous. AVERTISSEMENT - RISQUE D'EXPLOSION - AVANT DE DECONNECTOR L'EQUIPMENT, COUPER LE COURANT OU S'ASSURER QUE L'EMPLACEMENT EST DESIGNE NON DANGEREUX.
WARNING: To avoid the risk of electric shock or burns, always connect the safety (or earth) ground before making any other connections.
WARNING: To reduce the risk of fire, electrical shock, or physical injury it is strongly recommended to fuse the voltage measurement inputs. Be sure to locate fuses as close to the source as possible.
WARNING: Replace fuse with the same type and rating to provide protection against risk of fire and shock hazards.
WARNING: In the event of repeated failure, do not replace the fuse again as a repeated failure indicates a defective condition that will not clear by replacing the fuse.
WARNING: Only qualified electrical personnel familiar with the construction and operation of this equipment and the hazards involved should install, adjust, operate, or service this equipment. Read and understand this manual and other applicable manuals in their entirety before proceeding. Failure to observe this precaution could result in severe bodily injury or loss of life.
Registers
Description
%I1 to %I24 Digital Inputs
%I32 Output Fault
%I25 to %I31 Reserved
%Q1 to %Q16 Digital outputs
%Q17 Clear HSC1 accumulator to 0 %Q18
Quadrature 1-2: Accumulator 1 Reset to max – 1
Totalizer: Clear HSC2
%Q19 Clear HSC3 Accumulator to 0 %Q20
Quadrature 3-4: Accumulator 3 Reset to max – 1
Totalizer: Clear HSC4
%Q21 to %Q32 Reserved
%AI1 to %AI4 Analog inputs
%AI5, %AI6 HSC1 Accumulator %AI7, %AI8 HSC2 Accumulator
%AI9, %AI10 HSC3 Accumulator
%AI11, %AI12 HSC4 Accumulator
%AQ1, %AQ2 PWM1 Duty Cycle %AQ3, %AQ4 PWM2 Duty Cycle %AQ5, %AQ6 PWM Prescale %AQ7, %AQ8 PWM Period
%AQ9 to %AQ14 Analog outputs
Note: Not all XLe units contain the I/O listed in this table.
Warning: Electrical
Shock Hazard.
Warning: Consult user documentation.
The expression rung may be copied, substituting %AI0002 and %R00011 for %AI0001 and %R0007, and used to linearize the second channel. Contact Horner APG Technical Support for an example file containing the above program.
__________________________________________________________________________________________________________________________________________________________________
7/22/2009 Page 3 of 4 ECN # 956
Page 4
MAN0855-01-EN Specifications / Installation
All applicable codes and standards need to be followed in the
Adhere to the following safety precautions whenever any type of
ety (earth) ground on the power connector first before
initiating equipment, open
to the module first; then connect to the circuit to be
Route power wires in a safe manner in accordance with good practice
Wear proper personal protective equipment including safety glasses
dry before making any connection
Make sure the unit is turned OFF before making connection to
Before each use, inspect all cables for breaks or cracks in the
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
1. This device may not cause harmful interference.
2. This device must accept any interference received, including interference that may cause undesired operation.
installation of this product. connection is made to the module:
Connect the saf making any other connections. When connecting to electric circuits or pulse­their related breakers.
Do not make connections to live power lines. Make connections
monitored. and local codes. and insulated gloves when making connections to power circuits. Ensure hands, shoes, and floors are to a power line. terminals.
Make sure all circuits are de-energized before making connections.
insulation. Replace immediately if defective.
Use Copper Conductors in Field Wiring Only, 60/75° C.
10 Technical Support
For assistance and manual updates, contact Technical Support at the following locations:
North America:
Tel: 317 916-4274 Fax: 317 639-4279 Web: http://www.heapg.com Email: techsppt@heapg.com
"WARNING: EXPOSURE TO SOME CHEMICALS MAY DEGRADE
THE SEALING PROPERTIES OF MATERIALS USED IN THE Tyco relay PCJ
Cover / case & base: Mitsubishi engineering Plastics Corp.
Sealing Material: Kishimoto 4616-50K (I part epoxy resin)
It is recommended to periodically inspect the relay for any
degradation of properties and replace if degradation is found
No part of this publication may be reproduced without the prior agreement and written permission
of Horner APG, Inc. Information in this document is subject to change without notice.
Europe:
Tel: +353-21-4321266 Fax: +353-21-4321826 Web: http://www.horner-apg.com Email: tech.support@horner-apg.com
5010GN6-30 or 5010GN6-30 M8 (PBT)
__________________________________________________________________________________________________________________________________________________
7/22/2009 Page 4 of 4 ECN # 956
Loading...