2 Analog Inputs (High Resolution) / 2 Analog Outputs
1 Specifications
Inputs per Module 12 including 4 configurable HSC inputs Outputs per Module 12 including 2 configurable PWM outputs
Commons per Module 1 Commons per Module 1
Input Voltage Range 12 VDC / 24 VDC Output Type Sourcing / 10 K Pull-Down
Absolute Max. Voltage 35 VDC Max. Absolute Max. Voltage 28 VDC Max.
Input Impedance
Input Current Positive Logic Negative Logic Max. Output Current per point 0.5 A
Upper Threshold 0.8 mA -1.6 mA Max. Total Current 4 A Continuous
Lower Threshold 0.3 mA -2.1 mA Max. Output Supply Voltage 30 VDC
Max Upper Threshold 8 VDC Minimum Output Supply Voltage 10 VDC
Min Lower Threshold 3 VDC Max. Voltage Drop at Rated Current 0.25 VDC
OFF to ON Response 1 ms Max. Inrush Current 650 mA per channel
ON to OFF Response 1 ms Min. Load None
HSC Max. Switching Rate
Number of Channels 2 Thermocouple Temperature Range
Input Ranges
(Selectable)
Safe input voltage range
Nominal Resolution
Input Impedance
(Clamped @ -0.5 VDC to 12
VDC)
%AI full scale
Max. Over-Current 35 mA Conversion Time per Channel
Open Thermocouple Detect
Current
Number of Channels 2
Output Ranges
Nominal Resolution 12 Bits Primary Power Range 10 - 30 VDC
Update rate Once per PLC scan Operating Temperature
Minimum 10 V load
Maximum 20 mA load
Analog Outputs;
Output Points Required
Maximum Error at 25°C (excluding
zero)
Additional error for temperatures
other than 25°C
Display Life
User Keys
Screens supported 1023 Display Screen Dimension 320 x 240
100 BaseTx Fast Ethernet (100-Mbps)
Modes Half or Full Duplex
Auto-Negotiation Both 10/100-Mbps and Half/Full Duplex
Connector Type Shielded RJ-45
Cable Type
(Recommended)
CAT5 (or better) UTP
Port Auto MDI/MDI-X
4.5 Power Port and Wiring
Power Connector
Power Up:
Connect to Earth Ground.
Apply 10 - 30 VDC.
Screen lights up.
Torque rating 4.5 – 7 Lb-In
(0.50 – 0.78 N-m)
5 Wiring and Jumpers
• Wire according to the type of inputs / outputs used and select the appropriate jumper option.
• Use Copper Conductors in Field Wiring Only, 60/75° C
5.1 I/O Jumpers Settings (JP1 – JP4)
Note: The Cscape Module Setup configuration must match the selected I/O (JP) jumper settings.
Note: When using JP4 (output) orJP2 / JP3
(inputs), each channel can be independently
configured. For example, JP2 can be configured
for 10 V and JP3 can be configured as an RTD.
Wiring Specifications
Fo
Belden 9918, 18 AWG (0.8 mm
or larger.
For shielded Analog I/O wiring,
use the following wire type or
equivalent: Belden 8441, 18
AWG (0.8 mm2) or larger.
For CAN wiring, use the
f
Belden 3084, 24 AWG (0.2 mm
or larger.
Positive Logic vs. Negative Logic Wiring
The XL6 can be wired for Positive Logic inputs or
12-24VDC
Positive Logic In Negative Logic In
ANALOG OUTPUT SETTING
VOLTAGE OR CURRENT
CURRENT
(20mA)
AQ2 AQ1
Default
JP1 Digital DC Inputs
Positive Logic
Default
VOLTAGE
(10V)
AQ2 AQ1
Negative Logic
2
J1
2
Negative Logic inputs.
I1
0V
and wiring connectors
(J1 – J3).
JP3
I1
0V
JP2 and JP3
AI1 AI2
T/C/100mV
JP2
T1
RTD (PT100)
JP2
T1
JP2
Default
JP3
JP3
Primary Power Port Pins
Pin Signal Description
1 Ground Frame Ground
2 V- Input Power Supply Ground
3 V+ Input Power Supply Voltage
Note: Not all XL6 units contain the I/O listed in this table.
Registers PWM HSC Stepper
%AQ1 Start Frequency
%AQ2
%AQ3
%AQ4
%AQ5
%AQ6
%AQ7
%AQ8
%Q1 Run
%I30 Ready/Done
%I31
PWM1 Duty Cycle
PWM2 Duty Cycle
Quadrature 1-2: Accumulator 1 Reset to
Quadrature 3-4: Accumulator 3 Reset to
(32 bit)
(32 bit)
PWM Prescale
(32 bit)
PWM Period
(32 bit)
Description
Totalizer: Clear HSC2
max – 1
Totalizer: Clear HSC4
max – 1
HSC1
Preset
Value
HSC2
Preset
Value
Run Frequency
Accel Count (32
Run Count (32
Decel Count (32
bit)
bit)
bit)
Error
7 Digital Filtering for Analog Inputs
The digital filter is updated once per conversion. It is an “IIR” running average filter that emulates a simple
RC filter. The equivalent time constant is determined by the Filter Constant and the sum of the conversion
times for the two channels. The Filter Constant determines the weight given to the most recent
conversion. The following table lists the equivalent time constant for the three possible total conversion
times, which are dependent upon the two input mode selections. This filter delay is in addition to the PLC
scan delay.
When found on the product, the following symbols specify:
Warning: Electrical
Shock Hazard.
This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or Non-hazardous locations only.
WARNING – EXPLOSION HAZARD – Do not disconnect equipment unless power has been switched off or the area is known to be non-hazardous.
AVERTISSEMENT - RISQUE D'EXPLOSION - AVANT DE DECONNECTOR L'EQUIPMENT, COUPER LE COURANT OU S'ASSURER QUE L'EMPLACEMENT EST DESIGNE
NON DANGEREUX.
WARNING: To avoid the risk of electric shock or burns, always connect the safety (or earth) ground before making any other connections.
WARNING: To reduce the risk of fire, electrical shock, or physical injury it is strongly recommended to fuse the voltage measurement inputs. Be sure to locate fuses as close to
the source as possible.
WARNING: Replace fuse with the same type and rating to provide protection against risk of fire and shock hazards.
WARNING: In the event of repeated failure, do not replace the fuse again as a repeated failure indicates a defective condition that will not clear by replacing the fuse.
WARNING – EXPLOSION HAZARD – Substitution of components may impair suitability for Class I, Division 2.
AVERTISSEMENT - RISQUE D'EXPLOSION - LA SUBSTITUTION DE COMPOSANTS PEUT RENDRE CE MATERIAL INACCEPTABLE POUR LES EMPLACEMENTS DE
CLASSE 1, DIVISION 2.
WARNING - The USB parts are for operational maintenance only. Do not leave permanently connected unless area is known to be non-hazardous.
WARNING – EXPLOSION HAZARD - BATTERIES MUST ONLY BE CHANGED IN AN AREA KNOWN TO BE NON-HAZARDOUS
AVERTISSEMENT - RISQUE D'EXPLOSION - AFIN D'EVITER TOUT RISQUE D'EXPLOSION, S'ASSURER QUE L'EMPLACEMENT EST DESIGNE NON DANGEREUX
AVANT DE CHANGER LA BATTERIE.
WARNING - Battery May Explode If Mistreated. Do Not Recharge, Disassemble or Dispose Of In Fire.
WARNING: Only qualified electrical personnel familiar with the construction and operation of this equipment and the hazards involved should install, adjust, operate, or service
this equipment. Read and understand this manual and other applicable manuals in their entirety before proceeding. Failure to observe this precaution could result in severe
bodily injury or loss of life.
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
1. This device may not cause harmful interference.
2. This device must accept any interference received, including interference that may cause undesired operation.
Radiated Emission Compliance: For compliance requirement, a ferrite (Horner P/N FBD006 supplied with the unit) needs to be placed on the AC/DC line with one loop.
All applicable codes and standards need to be followed in the installation of this product.
Adhere to the following safety precautions whenever any type of connection is made to the module:
Connect the safety (earth) ground on the power connector first before making any other connections.
When connecting to electric circuits or pulse-initiating equipment, open their related breakers.
Do not make connections to live power lines.
Make connections to the module first; then connect to the circuit to be monitored.
Route power wires in a safe manner in accordance with good practice and local codes.
Wear proper personal protective equipment including safety glasses and insulated gloves when making connections to power circuits.
Ensure hands, shoes, and floor are dry before making any connection to a power line.
Make sure the unit is turned OFF before making connection to terminals.
Make sure all circuits are de-energized before making connections.
Before each use, inspect all cables for breaks or cracks in the insulation. Replace immediately if defective.
• Use Copper Conductors in Field Wiring Only, 60/75° C
10 Technical Support
Warning: Consult
user documentation.
For assistance and manual updates, contact Technical Support at the following locations:
No part of this publication may be reproduced without the prior agreement and written permission of Horner APG, Inc. Information in this document is subject to change without
notice.