MAN0945-04-EN Specifications / Installation
__________________________________________________________________________________________________________________________________________________________________________
1/24/2011 Page 1 of 4 #1037
1 Specifications
Required
Power
(Steady state)
650 mA @ 24 VDC
1.3A @ 12 VDC
25 A for <1 ms @ 24 VDC – DC Switched
15 A for <1 ms @ 12VDC – DC Switched
2.5 A for 1 ms @ 24 VDC - AC Switched
+/- 35 ppm maximum at 25° C
(+/- 1.53 Minutes per Month)
10.4” VGA TFT (550 nit typical)
Minimum 50000 hours (50% brightness, 25 deg C)
7 user-defined Function keys and a System Key
USA:
http://www.heapg.com/Pages/TechSupport/ProductCert.
html
Europe:
http://www.horner-apg.com/en/support/certification.aspx
2 Serial Ports – Each RS232 & RS485
Mini B for connecting to PC (Programming, Envision…)
Removable Media for upto 2 GB of storage for programs,
data logging or screen capture…
Remote I/O, Peer to Peer, PC, Programming…
SmartStix, SmartBlock, SmartMod or SmartRail
2 Installation
1. Prior to mounting, observe requirements for the panel layout design and
spacing/clearances in the OCS XL10e Series Manual (MAN0883).
2. Cut the host panel.
3. Insert the OCS through the panel cutout (from the front). The gasket
material needs to be between the host panel and the OCS.
4. Install and tighten the mounting clips (provided with the OCS) until the
gasket material forms a tight seal.
5. Connect cables as needed such as communications, programming, power
and CsCAN cables to the ports using the provided connectors.
6. Begin configuration procedures.
3 Panel Cut-Out and Dimensions
Note: Max. panel thickness: 5 mm.
Refer to the User Manual (MAN0883) for panel box information and a checklist of requirements.
There are 10 mounting clip locations on the XL10e.
For minimal mounting use four clips at 1, 2, 3 & 4 or 5, 6, 7 & 8.
For IP67 mounting use eight clips at locations 1 to 8.
For NEMA 4X mounting use ten clips in all locations.
The unit includes 8 clips order HE500ACC604 for additional
XL10e OCS
Base Controller Datasheet
for
HE-XV1E0, HE-XV1E2, HE-XV1E3, HE-XV1E4, HE-XV1E5
HEXT501C100, HEXT501C112, HEXT501C113 HEXT501C114 HEXT501C115
Caution: Do not force the OCS into the panel cutout.
An incorrectly sized panel cutout can damage the
touch screen.
Note: The tolerance to meet NEMA standards is ± 0.005” (0.1 mm).

MAN0945-04-EN Specifications / Installation
__________________________________________________________________________________________________________________________________________________________________________
1/24/2011 Page 2 of 4 #1037
4 Ports and Connectors
Removable
Media
Memory Slot
USB
Mini B USB 5 pin
programming port
Micro SD Memory Slot:
Uses Removable Memory for
data logging, screen captures,
program loading and recipes.
Horner Part No.: HE-MC1
USBA: For flash drive
connectivity
Serial Communications:
MJ1/MJ2: (RS-232 / RS-485)
Used for Cscape programming
and Application-Defined
Communications.
Ethernet: Used for Cscape
programming and ApplicationDefined Communications.
USBB: For network
communication and
programming of OCS

MAN0945-04-EN Specifications / Installation
__________________________________________________________________________________________________________________________________________________________________________
1/24/2011 Page 3 of 4 #1037
4.2 External DIP Switch Settings
MJ2 Pinouts in Half and Full Duplex Modes
4.3 Built-in I/O Details
Table - Ports and Functions
Ladder function
controlled
Serial Downloable
Protocols
12DC in (4HSC), 6 Relay out, 4 Analog In
12 DC in (4HSC), 12 DC out (2 PWM), 2 Analog in
24 DC in (4HSC), 16 DC out (2 PWM), 2 Analog in
12 DC in (4HSC), 12 DC out (2 PWM), 2 Universal
Analog In (T/C, RTD, mV, mA, V) & 2 Analog out (mA, V)
4.1 Serial Communications:
MJ1: (RS-232 / RS-485) Use for Cscape programming and
Application-Defined Communications.
MJ2: (RS-232 / RS-485) Use for Application-Defined
Communications.
As seen when looking at the side of the XL10 unit:
The DIP Switches are used for
termination of the RS-485 ports. The
XL10 is shipped un-terminated.
To terminate, select one of the DIP
Switches and configure it based upon
the option that is desired.
SW1 - ON enables MJ2 RS485 port termination (121 Ohms).
OFF disables MJ2 RS485 port termination.
SW2 & SW3 - ON places MJ2 RS485 port in half-duplex mode.
OFF places MJ2 RS485 port in full-duplex mode.
SW4 - ON enables MJ1 RS485 port termination (121 Ohms).
OFF disables MJ1 RS485 port termination.

MAN0945-04-EN Specifications / Installation
__________________________________________________________________________________________________________________________________________________________________________
1/24/2011 Page 2 of 4 #1037
4.4 CAN Network Port and Wiring
NET1 Port Pin Assignments
10 BaseT Ethernet (10-Mbps)
100 BaseTx Fast Ethernet (100-Mbps)
Both 10/100-Mbps and Half/Full Duplex
Shielded RJ-45
Cable Type
(Recommended)
4.6 Power Port and Wiring
6 Technical Support
For assistance and manual updates, contact Technical Support at the
following locations:
North America:
Tel: 317 916-4274
Fax: 317 639-4279
Web: http://www.heapg.com
Email: techsppt@heapg.com
Europe:
Tel: +353-21-4321266
Fax: +353-21-4321826
Web: http://www.horner-apg.com
Email: tech.support@horner-apg.com
5 Safety
No part of this publication may be reproduced without the prior agreement and written permission of
Horner APG, Inc. Information in this document is subject to change without notice.
Input Power Supply Ground
Input Power Supply Voltage
CAN Connector
Use the CAN Connector when
using CsCAN network.
Torque rating 4.5 – 7 Lb-In
(0.50 – 0.78 N-m)
Power Connector
Power Up:
Connect to Earth Ground.
Apply 10 - 30 VDC.
Screen lights up with slight delay.
Torque rating 4.5 – 7 Lb-In
(0.50 – 0.78 N-m)
This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or Non-hazardous
locations only.
WARNING – EXPLOSION HAZARD – Do not disconnect equipment unless power has been switched
off or the area is known to be non-hazardous.
AVERTISSEMENT - RISQUE D'EXPLOSION - AVANT DE DECONNECTOR L'EQUIPMENT,
COUPER LE COURANT OU S'ASSURER QUE L'EMPLACEMENT EST DESIGNE NON
DANGEREUX.
WARNING: To avoid the risk of electric shock or burns, always connect the safety (or earth) ground
before making any other connections.
WARNING: To reduce the risk of fire, electrical shock, or physical injury it is strongly recommended to
fuse the voltage measurement inputs. Be sure to locate fuses as close to the source as possible.
WARNING: Replace fuse with the same type and rating to provide protection against risk of fire and
shock hazards.
WARNING: In the event of repeated failure, do not replace the fuse again as a repeated failure
indicates a defective condition that will not clear by replacing the fuse.
WARNING – EXPLOSION HAZARD – Substitution of components may impair suitability for Class I,
Division 2
AVERTISSEMENT - RISQUE D'EXPLOSION - LA SUBSTITUTION DE COMPOSANTS PEUT
RENDRE CE MATERIAL INACCEPTABLE POUR LES EMPLACEMENTS DE CLASSE 1, DIVISION 2.
WARNING - The USB parts are for operational maintenance only. Do not leave permanently connected
unless area is known to be non-hazardous.
WARNING – EXPLOSION HAZARD - BATTERIES MUST ONLY BE CHANGED IN AN AREA
KNOWN TO BE NON-HAZARDOUS.
AVERTISSEMENT - RISQUE D'EXPLOSION - AFIN D'EVITER TOUT RISQUE D'EXPLOSION,
S'ASSURER QUE L'EMPLACEMENT EST DESIGNE NON DANGEREUX AVANT DE CHANGER LA
BATTERIE.
WARNING - Battery May Explode If Mistreated. Do Not Recharge, Disassemble or Dispose Of In Fire
WARNING: Only qualified electrical personnel familiar with the construction and operation of this
equipment and the hazards involved should install, adjust, operate, or service this equipment. Read
and understand this manual and other applicable manuals in their entirety before proceeding. Failure to
observe this precaution could result in severe bodily injury or loss of life.
" All applicable codes and standards need to be followed in the installation of this product.
" Adhere to the following safety precautions whenever any type of connection is made to the module:
# Connect the safety (earth) ground on the power connector first before making any other connections.
# When connecting to electric circuits or pulse-initiating equipment, open their related breakers.
# Do not make connections to live power lines.
# Make connections to the module first; then connect to the circuit to be monitored.
# Route power wires in a safe manner in accordance with good practice and local codes.
# Wear proper personal protective equipment including safety glasses and insulated gloves when
making connections to power circuits.
# Ensure hands, shoes, and floor are dry before making any connection to a power line.
# Make sure the unit is turned OFF before making connection to terminals.
# Make sure all circuits are de-energized before making connections.
# Before each use, inspect all cables for breaks or cracks in the insulation. Replace immediately
if defective.
Warning: Consult
user documentation.
Warning: Electrical
Shock Hazard.
When found on the product, the following symbols specify:
This device complies with part 15 of the FCC Rules. Operation is subject to the following two
conditions:
1. This device may not cause harmful interference.
2. This device must accept any interference received, including interference that may cause
undesired operation.
Radiated Emission Compliance: For compliance requirement, a ferrite (Horner P/N FBD006 supplied
with the unit) needs to be placed on the AC/DC line with one loop.