Horner APG RCS SmartStix User Manual

User Manual for
MiniOCS, MiniRCS,
and SmartStix
Mini Hardware
Fourth Edition 15 March 2003
MAN0305-04
PREFACE 15 MAR 2003 PAGE 3 MAN0305-04
PREFACE
This manual explains how to use MiniOCS / MiniRCS / SmartStix. Copyright (C) 2003 Hor ner APG, LLC., 640 North Sherman Drive Indianapolis, Indiana 46201. All rights
reserved. No part of this publication may be reproduced, transmitted, transcribed, stored in a retrieval system, or translated into any language or computer language, in any form by any means, electronic, mechanical, magnetic, optical, chemical, manual or otherwise, without the prior agreement and written permission of Horner APG, Inc.
All software described in this document or media is also copyrighted material subject to the terms and conditions of the Horner Software License Agreement.
Information in this document is subject to change without notice and does not represent a commitment on the part of Horner APG.
Cscape, SmartStix, and CsCAN are trademarks of Horner APG.
DeviceNet is a trademark of the Open DeviceNet Vendor Association (OVDA), Inc.
Ethernet is a trademark of the Xerox Corporation.
For user manual updates, contact Horner APG Technical Support Division, at (317) 916- 4274 or visit our website at www.heapg.com.
PAGE 4 15 MAR 2003 PREFACE MAN0305-04
LIMITED WARRANTY AND LIMITATION OF LIABILITY
Horner APG,LLC. ("HE-APG") warrants to the original purchaser that the MiniOCS/RCS/SmartStix manufactured by HE-APG is free from defects in material and workmanship under normal use and service. The obligation of HE-APG under this warranty shall be limited to the repair or exchange of any part or parts which may prove defective under normal use and service within two (2) years from the date of manufacture or eighteen (18) months from the date of installation by the original purchaser whichever occurs first, such defect to be disclosed to the satisfaction of HE-APG after examination by HE-APG of the allegedly defective part or parts. THIS WARRANTY IS EXPRESSLY IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR IMPLIED INCLUDING THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR USE AND OF ALL OTHER OBLIGATIONS OR LIABILITIES AND HE­APG NEITHER ASSUMES, NOR AUTHORIZES ANY OTHER PERSON TO ASSUME FOR HE-APG, ANY OTHER LIABILITY IN CONNECTION WITH THE SALE OF THIS MiniOCS/RCS/SmartStix. THIS WARRANTY SHALL NOT APPLY TO THIS MiniOCS/RCS/SmartStix OR ANY PART THEREOF WHICH HAS BEEN SUBJECT TO ACCIDENT, NEGLIGENCE, ALTERATION, ABUSE, OR MISUSE. HE-APG MAKES NO WARRANTY WHATSOEVER IN RESPECT TO ACCESSORIES OR PARTS NOT SUPPLIED BY HE-APG. THE TERM "ORIGINAL PURCHASER", AS USED IN THIS WARRANTY, SHALL BE DEEMED TO MEAN THAT PERSON FOR WHOM THE MiniOCS/RCS/SmartStix IS ORIGINALLY INSTALLED. THIS WARRANTY SHALL APPLY ONLY WITHIN THE BOUNDARIES OF THE CONTINENTAL UNITED STATES.
In no event, whether as a result of breach of contract, warranty, tort (including negligence) or otherwise, shall HE­APG or its suppliers be liable of any special, consequential, incidental or penal damages including, but not limited to, loss of profit or revenues, loss of use of the products or any associated equipment, damage to associated equipment, cost of capital, cost of substitute products, facilities, services or replacement power, down time costs, or claims of original purchaser's customers for such damages.
To obtain warranty service, return the product to your distributor with a description of the problem, proof of purchase, post paid, insured and in a suitable package.
ABOUT PROGRAMMING EXAMPLES
Any example programs and program segments in this manual or provided on accompanying diskettes are included solely for illustrative purposes. Due to the many variables and requirements associated with any particular installation, Horner APG cannot assume responsibility or liability for actual use based on the examples and diagrams. It is the sole responsibility of the system designer utilizing the MiniOCS/RCS/SmartStix to appropriately design the end system, to appropriately integrate the MiniOCS/RCS/SmartStix and to make safety provisions for the end equipment as is usual and customary in industrial applications as defined in any codes or standards which apply.
Note: The programming examples shown in this manual are for illustrative
purposes only. Proper machine operation is the sole responsibility of the system integrator.
PREFACE 15 MAR 2003 PAGE 5 MAN0305-04
REVISIONS TO THIS MANUAL
This version (MAN0305 -04) of the Mini Hardware Manual contains the following revisions, additions, and deletions:
1. Removed Mini data sheets from the back of this manual and moved them into a new manual. Revised Section 1.5: Additional References.
2. Revised Section 1.1. to include the SmartStix product line.
3. Added Chapter 6: SmartStix.
PAGE 6 15 MAR 2003 PREFACE MAN0305-04
PREFACE 15 MAR 2003 PAGE 7 MAN0305-04
Table of Contents
CHAPTER 1 : INTRODU CTION..........................................................................................................9
1.1 Scope...................................................................................................................................9
1.2 MiniOCS and MiniRCS Product Description ............................................................................9
1.2.1 Functions and Features...................................................................................................9
1.2.2 Cscape Software.......................................................................................................... 10
1.2.3 MiniOCS / MiniRCS Specifications ................................................................................. 11
1.3 MiniOCS / MiniRCS Resources ............................................................................................ 12
1.3.1 Overview...................................................................................................................... 12
1.3.2 Resource Definitions ..................................................................................................... 13
1.4 MiniOCS / MiniRCS Models ................................................................................................. 17
1.5 Additional References.......................................................................................................... 18
1.6 Technical Support ............................................................................................................... 18
CHAPTER 2 : INSTALLATION .........................................................................................................19
2.1 MiniOCS Mounting Requirements .........................................................................................19
2.1.1 MiniOCS Mounting Procedures (Installed in a Panel Door).............................................. 19
2.1.2 MiniOCS Dimensions and Panel Cut -outs......................................................................19
2.1.3 MiniOCS Mounting Orientation ...................................................................................... 21
2.2 MiniRCS Mounting Requirements ......................................................................................... 22
2.2.1 MiniRCS Mounting Procedures (Installed in a Panel Box) ................................................22
2.2.2 MiniRCS Dimensions and Panel Cut -outs......................................................................22
2.2.3 MiniRCS Mounting Orientation .......................................................................................23
2.3 Factors Affecting Panel Layout Design and Clearances ......................................................... 23
2.3.1 Panel Layout Design and Clearance Checklist:............................................................... 25
2.4 Ports, Connectors, and Wiring.............................................................................................. 26
2.4.1 Power, Network, and Programming Ports....................................................................... 26
2.4.2 Primary Power Port....................................................................................................... 26
2.3.3 CAN Network / DeviceNet Network Port and Wiring........................................................ 27
2.3.4 RS-232 Programming Port and Wiring ........................................................................... 30
2.3.5 Modem Setup............................................................................................................... 31
2.5 Selecting DeviceNet Network (Firmware Update Wizard)....................................................... 33
2.6 MiniOCS / MiniRCS LEDs .................................................................................................... 33
2.7 Mini Battery Replacement .................................................................................................... 35
CHAPTER 3 : SYSTEM MENU.........................................................................................................37
3.1 General............................................................................................................................... 37
3.2 Navigating Through the System Menu .................................................................................. 37
3.3 Editing System Menu Screen Fields ......................................................................................37
3.4 Remote Screen / Keypad (Using Remote Text Terminal and Status Bar) .................................38
3.5 Initial System Menu Screens and Self-Test ........................................................................... 38
3.6 Entering the System Menu ................................................................................................... 38
CHAPTER 4 : KEYPAD AND SCREEN............................................................................................. 45
4.1 Remote Screen and Keypad Capability .................................................................................45
4.1.1 Remote Text Terminal ................................................................................................... 45
4.1.2 Cscape Status Bar........................................................................................................ 45
4.1.3 Establishing Communications using the Remote Text Terminal........................................ 46
4.2 Keypad Description ............................................................................................................. 46
4.3 Operation............................................................................................................................ 47
4.4 User Screens ...................................................................................................................... 48
4.4.1 Cursor Types ................................................................................................................48
CHAPTER 5 : MINI CONFIGURATION .............................................................................................49
5.1 General............................................................................................................................... 49
5.2 Preliminary Configuration Procedures ................................................................................... 49
PAGE 8 15 MAR 2003 PREFACE MAN0305-04
CHAPTER 6 : SMARTSTIX..............................................................................................................53
6.1 General............................................................................................................................... 53
6.2 SmartStix I/O Introduction .................................................................................................... 53
6.3 SmartStix I/O Modules ......................................................................................................... 53
BASIC SMARTSTIX PROGRAMMING ........................................................................................... 54
6.4 Using GET and PUT ............................................................................................................54
6.4.1 Get Remote I/O Function Block ..................................................................................... 54
6.4.2 Get Remote Parameter Description:............................................................................... 54
6.4.3 Put Remote I/O Function Block ......................................................................................55
6.4.4 Put Remote Parameter Description: ............................................................................... 56
6.5 SmartStix I/O Default Operation ........................................................................................... 56
ADVANCED SMARTSTIX PROGRAMMING ...................................................................................57
6.6 SmartStix I/O Module Device Classes................................................................................... 57
6.7 SmartStix I/O Module Consumed (Received) Directed Data ................................................... 58
6.8 Consumed Directed Data Power -Up Initialization...................................................................59
6.9 SmartStix I/O Module Produced (Transmitted) Global Data.................................................... 60
6.10 Produced Global Data Power-Up Initialization ....................................................................60
6.11 SmartStix I/O Module LED Indicators ................................................................................ 61
6.11.1 Diagnostic LED Indicators ............................................................................................. 61
6.11.2 Status LED Indicators ................................................................................................... 61
6.12 SmartStix I/O Module Network ID...................................................................................... 61
CH.1 15 MAR 2003 PAGE 9 MAN0305-04
CHAPTER 1: INTRODUCTION
1.1 Scope
The Mini Hardware User Manual provides information about the following products:
a. MiniOCS (HE500OCSxxx)
MiniRCS (HE500RCSxxx)
The specifications, installation, and configuration procedures of the Operator Control Station (OCS) and the Remote Control Station (RCS) are covered in detail in this user manual. Information is also provided for the use of the products in CsCAN and DeviceNet Networks.
Note: Mini data sheets are now located in their own manual. (Refer to Additional References on page
18).
b. SmartStix Modules for CsCAN Networks (HE550xxxxxx). SmartStix is a family of remote products for the OCS. This manual covers programming information for
SmartStix used in CsCAN networks.
Figure 1.1 - Front View of MiniOCS (Shown on Door in Panel Box)
1.2 MiniOCS and MiniRCS Product Description
1.2.1 Functions and Features
The MiniOCS provides controller, I/O, operator interface, and optional networking capabilities in one unit. The MiniRCS has the same functionality as the MiniOCS except that it does not have local operator interface capabilities. Both the MiniRCS and the MiniOCS support a remote operator interface through a PC connected to the Mini unit’s built-in network or serial port. The remote operator interface (Remote Text Terminal) is particularly useful when using the MiniRCS, which does not have a physical front panel screen or keypad.
The MiniOCS is mounted in a panel door; the MiniRCS is designed for backplate mounting. Both the MiniOCS and the MiniRCS can be used in CsCAN or DeviceNet networks. To use the MiniRCS in a DeviceNet network, a DeviceNet file can be downloaded from Cscape’s Firmware Update Wizard.
PAGE 10 15 MAR 2003 CH.1 MAN305-04
A variety of MiniOCS / MiniRCS models are available. Each model comes equipped with one factory installed I/O board. Models of the MiniOCS / MiniRCS, which vary according to the type of I/O board installed, are available in non-network and network versions. Network versions contain an additional connector allowing connectivity to networks.
MiniOCS / MiniRCS devices have Serial and CAN (Controller Area Network) communication abilities. The units contain a standard 9-pin RS -232 port for programming/debugging, monitoring and network administration from an IBM -compatible PC. MiniOCS / MiniRCS models, which have built-in networking capabilities, use CsCAN (pronouned “Sea-scan”) protocol and standard CAN network hardware. CAN­based network hardware is used in the controllers because of CAN’s automatic error detection, ease of configuration, low-cost of design and implementation and ability to operate in harsh environments. The MiniOCS / MiniRCS can also be used in DeviceNet networks. Networking abilities are built-in to the MiniOCS / MiniRCS and require no external or additional modules. When several MiniOCS / MiniRCS units are networked together to ac hieve a specific purpose, the system acts like a large parallel­processing controller.
The MiniOCS / MiniRCS have standard features consisting of the following:
24 VDC powered Integrated Bezel
One Internal I/O Module Real-Time Clock
RS-232 Programming Port Flash Memory for easy field upgrades
1.2.2 Cscape Software
Cscape Software (pronounced “Sea -scape”) is used with the MiniOCS / MiniRCS, OCS, and RCS products. (The part number for Cscape is HE500OSW232.) Cscape stands for Control Station Central Application Programming Environment. The Windows -based software package is easy to use and aids in the integration of a CAN-based Distributed Control System. The program is used for configuring controllers and I/O Modules. Cscape is also used for programming MiniOCS / MiniRCS ladder logic, programming user displays for the MiniOCS, configuring the network for global digital and analog data, setting system-wide security and monitoring controllers in the system. Provided there is one serial connection to one node on the network (i.e., CsCAN Network), the operator has control over the entire system. The operator can upload, download, monitor and debug to any node on the network.
CH.1 15 MAR 2003 PAGE 11 MAN0305-04
1.2.3 MiniOCS / MiniRCS Specifications
TBD = To Be Determined
Table 1.1 – Physical Specifications
MiniOCS and MiniRCS
Operating Temperature*
Humidity 5% to 95% non-condensing NEMA Rating NEMA 4X Primary Power Range 10-30VDC Mini OCS Mini RCS Maxim um Power Draw (Non-network Version) Maximum Power Draw (Network Version) Maximum Inrush Current ((Non­network Version) Maximum Inrush Current (Network Version) Ladder Execution Typical Execution Speed CAN Power Range 12 – 25 VDC CAN Power Current 75mA maximum Serial Standard 9 pin RS-232 for programming, monitoring, and network
CAN CsCAN Network / DeviceNet Input / Output One factory -installed I/O board per model Keypad 10 user-programmable keys + , Esc, Enter and 4 direction keys
UL CE
MiniOCS
Height 4.4” (111.76mm) Width 7” (177.80) Mounting Depth 2.25” (57.15)
User Keys (MiniOCS Only) 17 Display (MiniOCS only) 2x20 LCD w/backlight; 3.2mm w x 5.55mm h characters
MiniRCS
Height 4.13” (104.78mm) Width 5.83” (147.98mm) Mounting Depth 1.83” (46.48mm)
(* Although the MiniOCS / MiniRCS withstands the temperature range of 0°C
to +60°C, such temperatures can decrease the life of the display. The recommended rating is 0°C to +50°C.)
200mA max. @ 24VDC 200mA max. @ 24VDC 900mA max. @ 24VDC for 1mS 900mA max. @ 24VDC for 1mS
2.0ms. per 1K of Boolean logic.
administration from a IBM compatible PC
Faceplate made of Marnot XL Polyester by Tekra.
Please refer to Compliance Table located at
http://www.heapg.com/Support/compliance.htm
(approximately 2.75” [69.85] including Ground Screw extension)
(approximately 2.33” [59.18] including Ground Screw extension)
0°C to +50°C*
To Be Determined To Be Determined To Be Determined To Be Determined
PAGE 12 15 MAR 2003 CH.1 MAN305-04
1.3 MiniOCS / MiniRCS Resources
1.3.1 Overview
This section defines the resource limits that a programmer needs to know when writing a program using the MiniOCS / MiniRCS.
A MiniOCS / MiniRCS combine local I/O (analog and digital), networking, and controller, into a single product. The MiniOCS also provides an operator interface (display and keypad). The controller portion of the MiniOCS / MiniRCS is programmed in ladder logic via the Windows -based Cscape (Control Station Central Application Programming Environment) package. Each MiniOCS / MiniRCS provide a set of resources for use by the ladder logic control program as indicated in Table 1.2. The table shows the resources available in MiniOCS / MiniRCS products. Note that although each register type inherently consists of either 1-bit or 16-bit registers, all registers can be accessed via User Screens and/or Ladder Code as 1, 8, 16 or 32-bit values or as ASCII character strings.
Table 1.2 - MiniOCS/MiniRCS Resource Limits
%S Registers 8 %SR Registers 192 %T Registers 2048 %M Registers 2048 %R Registers 2048 %K Registers 10 %D Registers 200 %I Registers 2048 %Q Registers 2048 %AI Registers 512 %AQ Registers 512 %IG Registers 0 / 64 / 0 %QG Registers 0 / 64 / 0 %AIG Registers 0 / 32 / 16 %AQG Regi sters 0 / 32 / 16 Network Port Controllers Per Network 0 / 253 / 64 SmartStack I/O Modules 1 Slot
The faceplate is made of Marnot XL Polyester by Tekra. The material is
Keypad
Local MiniOCS Display / Remote Text Terminal for MiniRCS and MiniOCS
Display Screen Memory 64K Items Per Text Table 20
User Screens 200 Data Fields Per User Screen
resistant to most corrosive substances found in industrial environments. The material also holds up well in most industrial conditions. If used outdoors, the materials can yellow or crack.
2x20 Characters
(Text LCD)
10
None / CsCAN / DeviceNet
16 Keys (Membrane)
Text Tables 200
Ladder Code 64K
CH.1 15 MAR 2003 PAGE 13 MAN0305-04
1.3.2 Resource Definitions
This section defines the resources listed in Table 1.2.
System Registers
System Registers (%S and %SR) are used to store general OCS or RCS status information. This information is used internally, and is also available to the operator via the System Menu, using the Control Station’s display and keypad. The System Registers are also available for User Screens and can be accessed by Ladder Code.
a. %S Registers %S Registers are 1-bit memory loc ations, containing system status information, implemented as shown in
Table 1.3:
Table 1.3 - %S Registers
Register Name Description
%S1 FST_SCN On during first scan after entering RUN mode %S2 NET_OK On if Network is functioning properly %S3 T_10MS On for 5 mS; Off for 5 mS %S4 T_100MS On for 50 mS; Off for 50 mS %S5 T_SEC On for 500 mS; Off for 500 mS %S6 IO_OK On if SmartStack I/O is configured properly %S7 ALW_ON Always On %S8 ALW_OFF Always Off
b. %SR Registers %SR Registers are 16-bit memory locations, containing system status information, implemented as
shown in Table 3. Note: Where 2 %SRs are combined to make a 32-bit value, the lower numbered %SR is the low word, while the higher numbered %SR is the high word.
Table 1.4 - % SR Registers
Register Name Description Min Max %SR1 USER_SCR Current User Screen Number (0=none) 0 200 %SR2 ALRM_SCR Current Alarm Screen Number (0=none) 0 200 %SR3 SYS_SCR Current System Screen Number (0=none) 0 11 %SR4 SELF_TEST Bit-Mapped Self -Test Result 0 65535
%SR5 CS_MODE %SR6 SCAN_RATE Average Scan Rate (in tenths of mS) - 1000
%SR7 MIN_RATE Minimum Scan Rate (in tenths of mS) - 1000 %SR8 MAX_RATE Maximum Scan Rate (in tenths of mS) - 1000 %SR9-10 EDIT_BUF Data Field Edit Buffer 0 232-1 %SR11-12 LADDER_SIZE Ladder Code Size 2 64K %SR13-14 UTXT_SIZE User Text Screen Table Size 4 64K %SR15-16 Reserved - - ­%SR17-18 IO_SIZE I/O Configuration Table Size 16 64K %SR19-20 NET_SIZE Network Configuration Table Size 34 32K %SR21-22 SD_SIZE Security Data Table Size - ­%SR23 LADDER_CRC Ladder Code CRC 0 65535 %SR24 UTXT_CRC User Text Screen Table CRC 0 65535 %SR25 Reserved - - ­%SR26 IO_CRC I/O Configuration Table CRC 0 65535 %SR27 NET_CRC Network Configuration Table CRC 0 65535
Control Station Mode (0=Idle, 1=Do I/O, 2=Run)
0 2
PAGE 14 15 MAR 2003 CH.1 MAN305-04
Table 1.4 - % SR Registers
Register Name Description Min Max %SR28 SD_CRC Security Data Table CRC 0 65535
%SR29 NET_ID
%SR30 NET_BAUD
%SR31 NET_MODE %SR32 LCD_CONT LCD Display Contrast Setting 0 255
%SR33 FKEY_MODE Function Key Mode (0=Momentary; 1=Toggle) 0 1
%SR34 SERIAL_PROT
%SR35-36 SERIAL_NUM This Station’s 32-bit Serial Number 0 232-1 %SR37 MODEL_NUM This Station’s Binary Model Number 0 65535 %SR38 ENG_REV Main CPU Engine Firmware Rev Number x 100 0000 9999 %SR39 BIOS_REV Main CPU BIOS Firmware Rev Number x 100 0000 9999 %SR40 FPGA_REV FPGA Image Rev Number x 10 000 255
%SR41 LCD_COLS
%SR42 LCD_ROWS %SR43 KEY_TYPE
%SR44 RTC_SEC Real-Time-Clock Second 0 59 %SR45 RTC_MIN Real-Time-Clock Minute 0 59 %SR46 RTC_HOUR Real-Time-Clock Hour 0 23 %SR47 RTC_DATE Real-Time-Clock Date 1 31 %SR48 RTC_MON Real-Time-Clock Month 1 12 %SR49 RTC_YEAR Real-Time-Clock Year 1996 2095 %SR50 RTC_DAY Real-Time-Clock Day (1=Sunday) 1 7 %SR51 NET_CNT Network Error Count 0 65535 %SR52 WDOG_CNT Watchdog-Tripped Error Count 0 65535 %SR53-54 BAD_LADDER Bad Ladder Code Error Index 0 65534 %SR55 F_SELF_TEST Filtered Bit -Mapped Self-Test Result 0 65535 %SR56 LAST_KEY Key Code of Last Key Press or Release 0 255 %SR57 BAK_LITE LCD Backlight On/Off Switch (0=Off; 1=On) 0 1 %SR58 USER_LEDS User LED Control / Status 0 65535 %SR59 S_ENG_REV Slave CPU Engine Firmware Rev Number x 100 0000 9999 %SR60 S_BIOS_REV Slave CPU BIOS Firmware Rev Number x 100 0000 9999 %SR61 NUM_IDS This Station’s Number of Network IDs (CsCAN) 1 253 This Station’s Number of Network IDs (DeviceNet) 1 1 %SR62-192 Reserved - - -
This Station’s Primary Network ID (CsCAN) 1 253 This Station’s Primary Network ID (DeviceNet) 0 63 Network Baud Rate (CsCAN)
(0=125KB; 1=250KB; 2=500KB; 3=1MB) Network Baud Rate (DeviceNet) (0=125KB; 1=250KB; 2=500KB) Network Mode (0=Network Not Required; 1=Network Required;
2=Reserved; 3=Network Required and Optimized)
RS232 Serial Protocol Mode (0=Firmware Update (RISM); 1=CsCAN; 2=Generic (Ladder- Controlled); 3=Modbus RTU; 4=Modbus ASCII)
LCD Text Display Number of Columns 20 20 LCD Graphics Display Number of Columns 240 240 LCD Text Display Number of Rows 2 4 LCD Graphics Display Number of Rows 128 128 Keypad Type (0=16 Keys; 1=17 Keys; 2=32 Keys; 3=36 Keys)
0 3 0 2
0 3
0 4
0 3
CH.1 15 MAR 2003 PAGE 15 MAN0305-04
User Registers
User Registers (%T, %M and %R) are used to store application-specific Mini data. This data can be accessed via User Screens and/or by Ladder Code.
a. %T Register A %T Register is a non -retentive 1-bit memory location, used to store application-specific state
information. b. %M Registers A %M Register is a retentive 1-bit memory location, used to store application-specific state information. c. %R Registers A %R Register is a retentive 16 -bit memory location, used to store application-specific values.
HMI Registers
HMI Registers (%K and %D) give the user access to the OCS or RCS keypad and display. The MiniOCS has a membrane keypad and text-based LCD display, allowing the operator to enter and
display general and application -specific information. This same information can be entered and displayed for the MiniRCS (and MiniOCS if desired) via a remote PC using Cscape’s Remote Display Terminal function.
a. %K Registers A %K Register is a non -retentive 1-bit memory location (contact), used to store the state of a function key
on the Control Station’s keypad. If the function keys are set for momentary mode, a function key’s associated %K register will be ON as long as the function key is pressed. If the function keys are set for toggle mode, a function key’s associated %K register will toggle each time the function key is pressed.
b. %D Registers A %D Register is a non-retentive 1-bit memory location (coil), which can be turned ON by Ladder Code to
cause the corresponding User or Alarm Screen to be displayed. c. User Screens A User Screen is a combination of fixed text or graphics, along with variable Data Fields (called Graphics
Objects in the MINIOCS), which together fill the LCD display screen. These screens are defined via Cscape di alogs and are then downloaded and stored into the Control Station’s Flash memory. User Screens can be selected for display by operator entries on the keypad, or by Ladder Code.
d. Data Fields A Data Field is an area on a User Screen where variable data is displayed and edited. The source data
for a Data Field can be any of the Control Station’s Register resources as defined above. The field size and display format is programmable via Cscape dialogs.
PAGE 16 15 MAR 2003 CH.1 MAN305-04
e. Text Tables A Text Table is a list of Text Items, which can be used in a Data Field, to display descriptive words and
phrases to describe the value of a Register, instead of displaying numeric values. A simple example of this, would allow the strings “OFF” and “ON” to be displayed, instead of 0 and 1, to describe the state of the %I4 digital input. The maximum number of Text Tables and Text Items per Text Table is shown in Table 1, but the number can be further limited by overall User Screen memory usage.
Physical I/O Registers Physical I/O Registers (%I, %Q, %AI and %AQ) give the user access to the Physical I/O Module
data. This data can be accessed via User Screens and/or by Ladder Code. a. %I Registers A %I Register is a 1-bit memory location, which is normally used to store the state of one of the digital
inputs associated with a Physical I/O module. When used in this way, %I registers are non -retentive. All extra %I registers, which are not associated with physical inputs, are retentive, and can be used just like %M registers.
b. %Q Registers A %Q Register is a non-retentive 1-bit memory location, which is normally used to store the state of one
of the digital outputs associated with a Physical I/O module. c. %AI Registers A %AI Register is a 16 -bit memory location, which is normally used to store the value of one of analog
inputs associated with a Physical I/O module. When used in this way, %AI registers are non -retentive. All extra %AI registers, which are not associated with physical inputs, are retentive, and can be used just like %R registers.
d. %AQ Registers A %AQ Register is a non-retentive 16-bit memory location, which is normally used to store the value of
one of the analog outputs associated with a Physical I/O module.
Global Data I/O Registers
Global Data I/O Registers (%IG, %QG, %AIG and %AQG) give the user access to the Network Port’s Global I/O data. This data can be accessed via User Screens and/or by Ladder Code.
a. %IG Registers A %IG Register is a retentive 1-bit memory location, which is normally used to store a global digital state
obtained from another Control Station on the network. b. %QG Registers A %QG Register is a retentive 1-bit memory location, which is normally used to store a digital state to be
sent as global data to the other Control Stations on the network.
CH.1 15 MAR 2003 PAGE 17 MAN0305-04
c. %AIG Registers A %AIG Register is a retentive 16-bit memory location, which is normally used to store a global analog
value obtained from another Control Station on the network. d. %AQG Registers A %AQG Register is a retentive 16 -bit memory location, which is normally used to store an analog value
to be sent as global data to the other Control Stations on the network. e. Network Port The CsCAN Network is based on the Bosch Control Area Network (CAN), and implements the CsCAN
Protocol which is designed to take maximum advantage of the global data broadcasting capability of CAN. Using this network protocol, up to 64 Control Stations can be linked without repeaters, and up to 253 Control Stations can be linked by using 3 repeaters. For more information regarding CsCAN Protocol, refer to the CsCAN Protocol Specification document.
DeviceNet is an “open” higher layer protocol, which is supported by products from multiple vendors. In an OCS or RCS, DeviceNet can be loaded as a replacement for the CsCAN Protocol Message Layer, and as a result, the OCS or RCS becomes a DeviceNet Slave device. Note that the Mini still implements the CsCAN Protocol Command Layer with respect to the RS -232 programming port. For more information regarding DeviceNet Protocol, contact the DeviceNet governing body (ODVA).
Ladder Code
The Ladder Code, stores ladder instructions generated by Cscape. This Ladder Code is downloaded and stored into the Control Station’s Flash memory, to be executed each controller scan, when the controller is in RUN mode.
1.4 MiniOCS / MiniRCS Models
Because there are several models of MiniOCS / MiniRCS models available, the MiniOCS / MiniRCS can be used in a wide range of applications. The MiniOCS consists of an Operator Control Station, and the MiniRCS consists of a Remote Control Station. Each model comes equipped with one factory installed I/O board. The models vary according to the type of I/O board installed and are available in non-network and network versions. Network versions contain an additional connector allowin g connectivity to CAN networks. Refer to Additional References on page 18 to locate model-specific information for each Mini.
PAGE 18 15 MAR 2003 CH.1 MAN305-04
1.5 Additional References
For further information regarding products covered in this manual, refer to the following references: a. Mini I/O (MAN0581) – Contains a collection of individual data sheets covering model-specific
information.
b. DeviceNet Implementation Using Control Station Modules (SUP0326) - Covers the
implementation of Control Station products in a DeviceNet network.
c. Cscape Reference Manual (MAN0313) – Contains topics specifically selected to assist you
through the programming process.
1.6 Technical Support
For user manual updates, contact Technical Services at the following locations:
North America:
(317) 916 -4274 www.heapg.com
Europe:
(+) 353-21-4321-266 www.horner-apg.com
CH.2 15 MAR 2003 PAGE 19
3 3/16
MAN0305-04
CHAPTER 2: INSTALLATION
2.1 MiniOCS Mounting Requirements
2.1.1 MiniOCS Mounting Procedures (Installed in a Panel Door)
The MiniOCS is designed for permanent panel mounting. To install the MiniOCS, follow the instructions below.
1. Prior to mounting the MiniOCS, observe requirements for the panel layout design and adequate
clearances. A checklist is provided on page 25.
2. Cut the host panel as described in the Figure 2.1 - Figure 2.6.
Warning: Make sure the power and network connectors are removed from the MiniOCS.
3. Insert the MiniOCS through the panel cutout (from the front). The gasket material needs to lie
between the host panel and the MiniOCS panel.
4. Install and tighten the mounting clips (provided with the MiniOCS) until the gasket material forms a
tight seal. (See Figure 2.7.)
Caution: Do not over-tighten. Over-tightening can potentially damage the case.
5. Connect the communications, programming, and power cables to the MiniOCS ports using the
provided connectors.
6. Begin configuration procedures for the MiniOCS models.
2.1.2 MiniOCS Dimensions and Panel Cut -outs
80.96mm
Programming Port
Figure 2.1 –Right-end View Network Model Figure 2.2 - Left-end View Network Model
Network Port
Power Port
PAGE 20 15 MAR 2003 CH.2
3 3/16
2 1/4 5 13/16
MAN0305-04
Programming Port
80.96mm
Power Port
Figure 2.3 - Right -end View (Non-Network Model) Figure 2.4 - Left-end View (Non-Network Model)
I/O Port
147.64mm
57.15mm
Figure 2.5 – Bottom View
CH.2 15 MAR 2003 PAGE 21
3 11/32
6
MAN0305-04
84.93mm
152.40
Figure 2.6 – Panel Cut-out (MiniOCS)
Figure 2.7 – MiniOCS Mounted in Panel Box using Mounting Clips.
2.1.3 MiniOCS Mounting Orientation
The bases of the MiniOCS model needs to be mounted with the proper orientation.
Figure 2.8 - Orientation of MiniOCS (Shown in Panel Box)
NOTE: There are NO orientation restrictions on the MiniOCS. However, the above orientation provides
for optimum readability of the screen and ease of use of the keypad.
PAGE 22 15 MAR 2003 CH.2
001RCS001
MOUNTING HOLES FOR
MAN0305-04
2.2 MiniRCS Mounting Requirements
2.2.1 MiniRCS Mounting Procedures (Installed in a Panel Box)
The MiniRCS is designed for permanent installation in a panel box. To install the MiniRCS in a panel box, use the instructions that follow:
1. Prior to mounting the MiniRCS, observe requir ements for the panel layout design and adequate
clearances. A checklist is provided on page 25.
2. Drill holes as described in the Figure 2.9.
Warning: Make sure the power and network connectors are removed from the MiniRCS.
3. Install and tighten washers and nuts. Do not over -tighten.
4. Connect the communications and power cables to the MiniRCS ports using the provided connectors.
5. Begin configuration procedures for the MiniRCS models.
2.2.2 MiniRCS Dimensions and Panel Cut -outs
#6 OR M3.5 HARDWARE 4 PLCS.
4.13
(104.78mm)
3.75
(95.25mm)
0.19
[4.78mm]
0.91 [23.19mm] 4.00 [101.60mm]
1.83 [46.48mm]
5.83 [147.98mm]
Figure 2.9 – MiniRCS Dimensions / Mounting Holes and MiniRCS Side View
CH.2 15 MAR 2003 PAGE 23
Note: Consider the length
Ground
Warning: It is important to follow the requirements of the panel manufacturer and to follow
MAN0305-04
2.2.3 MiniRCS Mounting Orientation
There are NO orientation restrictions on the MiniRCS. However, the orientation shown provides for the ease of use of the keypad.
2.3 Factors Affecting Panel Layout Design and Clearances
The designer of a panel layout needs to assess the requirements of a particular system and to consider the following des ign factors . A convenient checklist is provided on page 25.
of the Ground Screw extension when determining clearances.
applicable electrical codes and standards.
strap
Figure 2.10 – Back view of MiniOCS (Shown On Panel Door)
PAGE 24 15 MAR 2003 CH.2
Warning: Be sure to meet the ground requirements of the panel manufacturer and also meet
Warning: To provide maximum noise immunity and to insure minimum EMI radiation, the V-
rth ground at the power supply.
The user must ensure that the power supply selected is compatible with this method
MAN0305-04
a. Clearance / Adequate Space Install devices to allow sufficient clearance to open and close the panel door. Note that the MiniOCS is
mounted on a panel door and the MiniRCS is mounted in a panel box.
Table 2.1 – Minimum Clearance Requirements for Panel Box and Door
Minimum Distance between base of device and sides of cabinet
Minimum Distance between base of device and wiring ducts If more than one device installed in panel box (or on door):
Minimum Distance between bases of each device When door is closed:
Minimum distance between device and closed door (Be sure to allow enough depth for MiniOCS / MiniRCS Model and Ground Screw Extension.)
b. Grounding
Panel box : The panel box needs to be properly connected to earth ground to provide a good common ground reference.
Panel door: Tie a low impedance ground strap between the panel box and the panel door to ensure that they have the same ground reference (Figure 2.10).
Devices in panel box and on the panel box door: Use the mounting hardware provided with the device, which includes mounting clips. c. Temperature / Ventilation Ensure that the panel layout design allows for adequate ventilation and maintains the specified ambient
temperature range. Consider the impact on the design of the panel layout if operating at the extreme ends of the ambient temperature range. For example, if it is determined that a cooling device is required, allow adequate space and clearances for the device in the panel box or on the panel door.
applicable electrical codes and standards.
signal (DC power return) need to be connected to ea
of grounding.
2 inches (50.80mm)
1.5 inches (38.10mm)
4 inches between bases of each
device (101.60mm)
2 inches (50.80mm)
CH.2 15 MAR 2003 PAGE 25
Warning: To provide maximum noise immunity and to insure minimum EMI radiation, the V-
MAN0305-04
d. Orientation Observe guidelines for proper orientation of the bases when mounting the MiniOCS / MiniRCS (page 25).
Proper orientation helps to ensure a good connection when MiniOCS / MiniRCS models are installed into the devices.
e. Noise Consider the impact on the panel layout design and clearance requirements if noise supression devices
are needed. Be sure to maintain an adequate distance between the MiniOCS / MiniRCS and noisy devices such as relays, motor starters, etc.
Note: Do not route power and signal wires in the same conduit.
2.3.1 Panel Layout Design and Clearance Checklist:
The following list provides highlights of panel layout design factors. ____Meets the electrical code and applicable standards for proper grounding, etc.? ____Meets the panel manufacturer’s requirements for grounding, etc.? ____Is the panel box properly connected to earth ground? Is the panel door properly grounded? Has the
appropriate procedure been followed to properly ground the devices in the panel box and on the panel door? (See page 25.)
____Are minimum clearance requirements met? (See Table 2.1.) Can the panel door be easily opened
and closed? Is there adequate space between device bases as well as the sides of the panel and wiring ducts?
____Is the panel box deep enough to accommodate the MiniOCS / MiniRCS. (Be sure to consider the
Ground Screw extension.)
____Are the device bases oriented correctly? (See page 25.) The MiniOCS / MiniRCS devices are
mounted on the door of a panel box.
____Is there adequate ventilation? Is the ambient temperature range maintained? Are cooling or heating
devices required?
____Are noise suppression devices or isolation transformers be required? Is there adequate distance
between the base of the MiniOCS / MiniRCS and noisy devices such as relays or motor starters? Ensure that power and signal wires are not routed in the same conduit.
____Are there other requirements that impact the particular system, which need to be considered?
signal (DC power return) need to be connected to earth ground at the power supply. The user must ensure that the power supply selected is compatible with this method of grounding.
PAGE 26 15 MAR 2003 CH.2
Warning: To provide maximum noise immunity and to insure minimum EMI radiation, the V-signal
DC Power
MINI
Frame
MAN0305-04
2.4 Ports, Connectors, and Wiring
2.4.1 Power, Network, and Programming Ports
The MiniOCS / MiniRCS Power, Network, and Programming Ports are shown in Figure 2.11 - Figure 2.12. for both the network and non-network versions of the MiniOCS / MiniRCS. The MiniOCS / MiniRCS I/O Module receptacle is located on the bottom.
2.4.2 Primary Power Port
Table 2.2 – Primary Power Port Pins
Pin Signal Description
1
Frame Ground
2 V+ Input power supply voltage 3 V- Input power supply ground
PIN 1 PIN 2 PIN 3
PIN 1 PIN 2 PIN 3
Figure 2.11 - Power Connector Figure 2.12 - As viewed looking at
(Primary Power Port) the Mini (Front and Side Views Shown)
Note: Power Supply Voltage Range is from 10 -30 VDC.
(DC power return) need to be connected to earth ground at the power supply. The user must ensure that the power supply selected is compatible with this method of grounding.
Supply
+ -
(Earth) Ground
Connect DC V - to earth ground at the power supply.
Figure 2.13 - Grounding
CH.2 15 MAR 2003 PAGE 27 MAN0305-04
2.3.3 CAN Network / DeviceNet Network Port and Wiring
Table 2.3 – CAN Port Pins
Pin Signal Description
1 V- Power ­2 CN_L Signal ­3 SHLD Shield 4 CN_H Signal + 5 V+ Power +
Figure 2.14 – Network Connector Figure 2.15 – As viewed looking
(CAN Port) at the Mini
1 2 3 4 5
V+ CN_H SHLD
CN_L
V-
1 2 3 4 5
V-
SHLD
CN_L
V+
CN_H
PAGE 28 15 MAR 2003 CH.2
12-25VDC
MAN0305-04
V-
SHIELD
CN_H
V-
SHIELD
CN_H
V-
SHIELD
CN_H
V-
SHIELD
CN_H
121
121
+
12-25VDC
-
CN_LV-SHIELD121
V+
CN_LV-SHIELD
V+
CN_LV-SHIELD
V+
CN_LV-SHIELD
BLK
WHT
-
+
BLK
BLK
BLU
BLU
WHT
WHT
RED
RED
SHIELD
BLK
BLK
BLU
BLU
WHT
WHT
RED
RED
SHIELD
121
BLK
Figure 2.16 – CAN Wiring
Note: To optimize CAN network reliability in electrically noisy environments, the CAN power
supply needs to be isolated (dedicated) from the primary power.
a. CAN Wiring Rul es (See Figure 2.16.)
1. Wire the CAN network in a daisy-chained fashion such that there are exactly two physical end -
points on the network.
2. The two nodes at the physical end -points need to have 121 ohm 1% terminating resistors
connected across the CN_L and CN_H terminals.
3. Use data conductors (CN_L and CN_H) that are 24 AWG shielded twisted pair for “thin cable” and
22 AWG shielded twisted pair for “thick cable.” They must also have 120-ohm characteristic impedance. In typical industrial environments, use a Belden wire #3084A (“thin”). Use #3082A (“thick”) for network cable lengths greater than 100 meters environments where noise is a concern. Place data conductors (CN_L and CN_H) into a twisted pair together.
4. Use powe r conductors (V- and V+) that are 18 AWG twisted-pair for “thin cable” and 15 AWG
twisted-pair for “thick cable.” Place power conductors (V - and V+) into a twisted pair together.
5. If local codes require the local CAN power supply to be earth grounded, connect the V- power
conductor to a good earth ground at one place only on the network, preferably at a physical endpoint. If multiple power supplies are used, only one power supply must have V- connected to earth ground. The remaining power supplies need to be isolated.
V+
WHT
CH.2 15 MAR 2003 PAGE 29 MAN0305-04
6. For a section of cable between two nodes, the cable shield is connected to the cable shield input at
one end of the cable only.
7. A CAN network (without repeaters) is limited to 64 nodes (with 63 cable segments) with a maximum
combined cable length of 1500 ft. at 125KBaud.
8. Up to four CAN network segments, which adhere to the above rules, may be connected together
using three CAN repeaters. In this manner, a CAN network may be extended to 253 nodes with a total cable distance of 6000 ft. at 125KBaud.
b. CsCAN or DeviceNet Cable The 5-wire, multi-conductor copper cable used in CsCAN or DeviceNet network include:
1. Two wires used as a transmission line for network communications.
2. Two wires used to transmit network power.
3. One conductor used as an electromagnetic shield.
Cabling is available in a variety of current-carrying capacities. On a CsCAN or DeviceNet fieldbus, every device must, at least, power its network transceivers from the network power supply. Some devices draw all of their power from the network supply.
In CsCAN or DeviceNet, thick and thin cable is used as indicated:
1. Thick cable: Use for long distances and more power. Usually used for Trunk cable.
2. Thin cable: Use for shorter distances. Usually used for drop cables or where cable flexibility is
needed.
Table 2.4 - CsCAN / DeviceNet Cable Specifications
Thick Cable – general specifications (e.g., Belden 3082A)
Thin Cable – general specifications (e.g., Belden 3084A)
Network Topology Bus with limited branching (truckline / dropline) Redundancy Not Supported Network Power for Node devices Allowed Nodes (Bridging excluded) Data Packet Size 0-8 bytes with allowance for message fragmentation Duplicate Address Detection Addresses verified at power-up Error Detection / Correction CRC – retransmission of message if validity not acknowledged by
Two twisted shielded pairs –Common axis with drain wire in center. One signal pair (#18), blue/white; One power power pair (#15) black/red. Separate aluminized mylar shields around power pair and signal pair.
Overall foil/braid shield with drain wire (#18), bare*. High Speed (Vp=75% min), low loss, low distortion, data pair (to keep propagation delays to a minimum). 8 amp maximum current capacity. PVC insulation on power pair. Industrial temperature range. High flexibility.
Two twisted shielded pairs –Common axis with drain wire in center. One signal pair (#24), blue/white; One power power pair (#22) black/red. Separate aluminized mylar shields around power pair and signal pair.
Overall foil/braid shield with drain wire (#22), bare*. High Speed (Vp=75% min), low loss, low distortion, data pair (to keep propagation delays to a minimum). 3 amp maximum current capacity. PVC insulation on pow er pair. Industrial
temperature range. High flexibility
Nominal 24 VDC ±4% 64 nodes
recipient.
* The drain wire connects shields within the cable and serves as a means to terminate the shield into the
connector.
PAGE 30 15 MAR 2003 CH.2 MAN0305-04
c. Bus Length Several factors affect the maximum length of the bus including the accumulated length of drop lines,
cable type, transfer rate and the number of drop lines. Although a branch is limited to one network per drop, it can have multiple ports. A branch can not exceed 6 meters.
Table 2.5 - CAN Network Baudrate vs. Total Cable Length
Note: The following values apply to both CsCAN or DeviceNetworks except as indicated.
Thick Cable: Network Data Rate Maximum Total Cable Length
1Mbit / sec. (Does not apply to DeviceNet.) 40m (131 feet)
500Kbit / sec. 100m (328 feet) 250Kbit / sec. 200m (656 feet) 125Kbit / sec. 500m (1,640 feet)
Thin Cable Maximum Total Cable Length
Maximum bus length is independent of network data rate. Maximum bus length is 100m.
Note: Network baud rates above 250Kbit/sec are not recommended for the MiniOCS / MiniRCS . The potential for a high rate of network messages can cause an unacceptable increase in the ladder scan rate.
d. Bus Power and Grounding When using CsCAN or DeviceNet:
1. A power supply of 24VDC (±4%) at 16A maximum is required for use in a CsCAN / DeviceNet network
2. With thick cable, a single network segment can have a maximum of 8A. To do this, the power supply
needs to be located in the center of two network segments.
3. Thin cable has maximum of 3A.
4. To ground the cable shield, connect to pin 3 as shown in Figure 2.16.
5. If local codes require the local CAN power supply to be earth grounded, connect the V- power
conductor to a good earth ground at one place only on the network, preferably at a physical endpoint. If multiple power supplies are used, only one power supply must have V- connected to earth ground. The remaining power supplies need to be isolated.
2.3.4 RS-232 Programming Port and Wiring
Table 2.6 – RS -232 Port Pins
Pin Signal Description Direction
1 DCD Always high Out 2 RXD Received Data Out 3 TXD Transmitted Data In 4 DTR Data Terminal Ready In 5 GND Ground ­6 DSR Data Set Ready Out 7 RTS Request to Send In 8 CTS Clear to Send Out 9 RI Ring Indicate Out
Pin 1
Pin 9
Figure 2.17 – RS -232 Port
CH.2 15 MAR 2003 PAGE 31
15.24 METERS MAX
Telephone
Telephone
MAN0305-04
a. RS-232 Communications Wiring The MiniOCS / MiniRCS features an RS -232 port (Programming/Debug) for connection to a personal
computer. This port is used for the purposes of MiniOCS / MiniRCS programming, configuring, monitoring, and debugging. This port can also be used for general ladder logic controlled serial communications to printers, modems, terminals, etc. When ladder has control of this port, it is not available for programming or debugging. The wiring diagram for the RS -232 ports is shown in Figure
2.18Figure 2.18. For connection between the MiniOCS / MiniRCS and the PC, the use of a shielded,
multiple conductor wire with a maximum length of 15.24 meters (50 feet) enables proper performance. Note: A shorter cable can be required when used for high-speed MiniOCS / MiniRCS firmware updating.
OCS RS -232
DCD 1 RXD 2 TXD 3 DTR 4 GND 5 DSR 6 RTS 7 CTS 8 RI 9
DB9
MALE
SHIELDED MULTI CONDUCTOR
(50 FEET MAX)
9-PIN PC COM
1 DCD 2 RXD 3 TXD 4 DTR 5 GND 6 DSR 7 RTS 8 CTS 9 RI
DB9
FEMALE
Figure 2.18 – MiniOCS / RCS to PC Wiring
2.3.5 Modem Setup
A modem can be used for remote communications between a computer (using Cscape Software) and the MiniOCS / MiniRCS. The modem must operate at 9600 baud or higher.
PC
Modem
Modem
System
System
Figure 2.19 – Modem Setup
Mini
PAGE 32 15 MAR 2003 CH.2
Warning: Damage can result if the CD and RI lines are connected to each other or to any other signal
Warning: To connect a modem to the MiniOCS / MiniRCS the controller to modem cable must be
9-PIN 25- PIN
MAN0305-04
a. Setup
Setup the modems to match the default serial port characteristics of the MiniOCS / MiniRCS. 9600 baud
8 data bits No parity 1 stop bit disable error checking disable compression
b. Cable Wiring
Note: If the mo dem has a DB25 connector, a 9-to-25-pin adapter may need to be supplied. The grayed connections are used only if hardware handshaking between the controller and modem
is required. The wire type used in not overly critical except where the length of the cable must be between 30 and 50
feet (10 to 15 meters). In all cases, the cable must be shielded multi-conductor with conductors of at least 20 gauge. The length of the cable must be as short as possible, and in no case, longer than 50 feet (15 meters).
The modem must be located as close as possible to the OCS, preferably less than one meter. However, EIA-232 specifications allow for cable runs up to 50 feet (15 meters). If cable lengths longer than 30 feet (10 meters) are required, a special low capacitance cable must be used.
on the connector or through the cable to the other unit.
constructed or purchased. Using a Null Modem cable can cause damage to the MiniOCS / MiniRCS, modem or both.
DCD
RXD
TXD
DTR
GND
DSR
RTS
CTS
RI
N/C
N/C
N/C N/C
Figure 2.20 – Modem Wiring
MODEM OCS
DCD
RXD
TXD
DTR
GND
DSR
RTS CTS
RI
CH.2 15 MAR 2003 PAGE 33 MAN0305-04
c. Recommended Modem Selection of a telephone modem for use with the OCS is highly dependent on environment . For a
relatively benign, low-noise environment, an off-the-shelf external modem like a U.S. Robotics Sportster Modem can work well. For a more industrial environment, however, it is appropriate to use a telephone modem designed for that environment. Manufacturers such as Datalinc and Sixnet have models, which have been known to work in more harsh environments, at a higher cost. If a modem is used, which is not appropriate for the environment, there may be little that can be done to correct the situation other than change to a more appropriate model.
For detailed inform ation regarding the use of modems with Control Station Products, contact Technical Support. (See page 18.) You can also find specific application information (cabling, modem commands, etc.) in the Cscape Help file as well.
2.5 Selecting DeviceNet Network (Firmware Update Wizard)
To use the OCS in a DeviceNet network, use Cscape’s Firmware Update Wizard. Select File, Firmware Update Wizard from the pull-down menu. The following screen appears.
Figure 2.21 – Using Firmware Update Wizard
Select the product type (MiniOCS or MiniRCS) using the pull-down menu and click on the circle next to the desired network. Press OK. On the next screen, press Send. Firmware is now updated.
2.6 MiniOCS / MiniRCS LEDs
The following LED information is provided for the MiniOCS / MiniRCS.
Table 2.7 - LEDs
LED MiniOCS / MiniRCS
RUN
OK
OFF indicates OCS is in IDLE/STOP mode.
Flashing indicates DO / IO mode or RUN with no ladder program.
ON indicates ladder code running.
OFF indicates one or more self -tests failed.
ON indicates all self -tests passed.
FLASHING indicates all self -tests passed and one or more I/O points is
currently forced.
PAGE 34 15 MAR 2003 CH.2
001RCS002
MAN0305-04
MiniOCS LED status is indicated on the physical unit as shown in the following figure.
OK
RUN
Esc
1 2 3 4 5
QZ ABC DEF GHI JKL
F1 F2
6
F6
7
MNO PRS TUV WXY
F7 F8 F9 F 10
F3
8 9 0
F4 F5
+/-
System
Enter
Figure 2.22 – MiniOCS LEDs
The MiniRCS LEDs are also viewed by looking at the physical unit. They are not viewable from a remote screen.
mini
OCS/RCS
OPERATOR CONTROL STATION
COM
PORT
OK
RUN
SHIELD
NETWORK
V+
CAN_H
CAN_L
INPUT
POWER
9-30VDC
Figure 2.23 – MiniRCS L EDs (I/O Connections Not Shown)
CH.2 15 MAR 2003 PAGE 35
Warning: Disposal of lithium batteries must be done in accordance with federal, state, and local Warning: Do not make subs titutions for the battery. Be sure to only use the authorized part number
MAN0305-04
2.7 Mini Battery Replacement
The following instructions apply to the MiniOCS and MiniRCS.
1. Disconnect power from the unit.
2. Remove ground screw (item #1) from back of unit.
3. Remove back cover (item #2) by carefully pressing in on one corner locking tab and lifting back cover to disengage the locking tab. Repeat this for all four corners.
4. Unscrew the grounding spacer (item #3) using a ¼” Hex nut driver.
5. Gently lift up and remove the I/O board (item #4) from the three snap top fasteners on the CPU board.
6. Once the CPU board is exposed locate the battery (item #5, U7). Remove the battery by prying up slightly on each end until it lifts free. Dispose of the battery.
regulations. Be sure to consult with the appropriate regulatory agencies before disposing batteries. In addition, do not re-charge, disassemble, heat or incinerate lithium batteries.
7. Replace the battery with HE500BAT005 noting the polarity tab at one end of the battery. Use
care when replacing the battery that this tab is located in the right direction. Use only the authorized battery part number.
to replace the battery.
8. Reassemble the Mini unit by first replacing the I/O board then replacing the ¼” hex spacer. It is
recommended that Loctite 222MS Threadlocker or an equivalent be applied to the male threads of item #xx before reassembling. Line up the back cover with ground hole over the ground spacer and press back in place. Make sure all four locking tabs of the back cover snap into place. Reconnect the ground wire. Follow the instructions in the units’ manual for powering up the Mini and restoring it to operation.
OR
Figure 2.24 – Battery Replacement
PAGE 36 15 MAR 2003 CH.2 MAN0305-04
NOTES
CH.3 15 MAR 2003 PAGE 37 MAN0305-04
CHAPTER 3: SYSTEM MENU
3.1 General
Chapter Three describes the System Menu for the MiniOCS / MiniRCS. The System Menu is used to access and edit information using the MiniOCS front panel or using the
Remote Text Terminal , which is a feature available in both the MiniOCS and the MiniRCS. The Remote Text Terminal is particularly useful when using the MiniRCS, because the MiniRCS does not have a physical front panel display screen or keypad. For more information, see page 45.
The following list contains examples of parameters that can be set using the System Menu:
Network ID
Network Baud
RS232 Mode
Time/Date
LCD contrast
Fkeys mode
3.2 Navigating Through the System Menu
Prior to configuration, it is important to know how to navigate through the System Menu using the following guidelines.
1. Pressing the and keys scroll up or down through the menu options.
2. Pressing the Enter key selects the system screen that the indicator arrow is pointing to.
3. Once in a system screen, press ESC (if not currently modifying a field) to return to the main System Menu.
3.3 Editing System Menu Screen Fields
Prior to configuration, it is important to know how to edit the System Menu screen fields using the following guidelines.
1. Some fields in the system screens are editable; others are not editable. The MiniOCS / MiniRCS model indicates an editable field with a solid cursor (_) under the first character in the field.
2. To change a value in an editable field, press the Enter key to select edit mode. The MiniOCS / MiniRCS model indicates edit mode by displaying a flashing block curs or.
3. In edit mode, the fields require one of the following methods for modifying the value. Refer to the field description to determine which method to use.
Enumerated entry - use and keys to select appropriate value.
Numeric entry - use Numeric keys or ↑ and ↓ keys on the appropriate digit.
Bar graph entry - use and keys to adjust value.
4. After the value is correctly entered, press the Enter key to accept the value.
5. Should the user not wish to accept the value before the Enter key is pressed, the ESC key may be pressed instead. This action restores the original value to the display. The MiniOCS / MiniRCS model also immediately exits edit mode; however, the Text models remains in edit mode with the original value and requires the Enter key to be pressed to exit.
PAGE 38 15 MAR 2003 CH.3 MAN0305-04
3.4 Remote Screen / Keypad (Using Remote Text Terminal and Status Bar)
The MiniRCS has the same functionality as the MiniOCS except that it does not have a local operator screen and keypad. However, the MiniRCS (as well as the MiniOCS) supports a remote operator screen and keypad through a PC connected to the Mini unit’s built-in network or serial port. If desired, the remote operator interface and keypad can be displayed (using Cscape software) by pressing Screens, Remote Text Terminal . A virtual display screen and keypad appear that are similar to that of the MiniOCS, and the user can navigate through the system menu, make selections, and edit fields using a mouse. In addition, the Cscape Status Bar can be used as a tool to ensure that communications are properly established. For more information on the Remote Test Terminal and the Cscape Status
Bar feature, see page 45.
3.5 Initial System Menu Screens and Self-Test
Note: The examples in this chapter depict the MiniOCS, but the information also applies to the MiniRCS
when using the Remote Text Terminal screen. (Refer to Section 3.4.)
1. After turning on the power to the Mini, the following screen appears which indicates the product
name and the network it is connected to. It also indicates that the Self-Test is running.
(This screen does not appear when using the Remote Text Terminal.)
a. If the Self-Test passes, the following screen appears:
b. If the Self-Test fails, see View OCS(RCS) Diags (page 41.)
3.6 Entering the System Menu
a. To enter the System Menu on the MiniOCS using the local keypad, press both the and keys
at the same time. Notice that the two keys are surrounded by a white outline and the word “System” on the silkscreen of the keypad.
b. If using the MiniRCS, refer to Section 4.1 (starting on page 45) to use the Remote Text Terminal
to create a virtual keypad and screen. Be sure to follow the procedures to establish and verify proper communications (page 46). After doing so, the following menu options can be accessed by clicking the specified key in the display representation using a mouse.
MiniOCS – CsCAN
Self-Test Running
** Self-Test **
**** Passed ****
CH.3 15 MAR 2003 PAGE 39 MAN0305-04
3.7 System Menu Option Screens
In addition to providing access to the MiniOCS / MiniRCS, configuration parameters, the System Menu also provides power-up and runtime status. For brevity, both configuration and status fields are covered in this section
There are up to ten different menu options, which include the following:
Set Network ID
Set Network Baud
Set Contrast
View OCS(RCS) Status
View OCS(RCS) Diags
View I/O LEDs
View OCS(RCS) Model
Set Fkeys Mode
Set RS232 Mode.
Set Time/Date
Set Network ID
This screen contains two fields. The first field cont ains the current network status. The second field contains the current Network ID of the model. The second field is numerically editable and is used to configure the Network ID.
Each unit on the network needs a unique ID number. The correct ID number should be entered here before physically attaching the unit to the network.
Cscan model: [ 1 - 253 ] DeviceNet model: [ 0 - 63 ]
Note: If the Network ID setting is changed, the unit stops executing the ladder code (for up to 1 second) while the network is re-tested. If the “Network OK?” status changes from “Yes” to “No,” the new Network ID is a duplicate, and another ID needs to be selected.
Set Network Baud
This screen contains an editable enumerated field allowing the user to select the current baud rate of the network.
Cscan model: [125K, 250K, 500K, 1M] DeviceNet model: [125K, 250K, 500K]
Note: All devices on the network must be at the same baud rate. A device configured for the wrong baud rate may shut down the network entirely.
Set Contrast
This menu contains an editable bar graph entry allowing the user to set the contrast of the LCD display.
PAGE 40 15 MAR 2003 CH.3 MAN0305-04
View OCS (RCS) Status
This screen contains both a single enumerated editable field that sets the MiniOCS / MiniRCS scan mode and status fields that display information about the internal state of the MiniOCS/ MiniRCS. Pressing the and keys scrolls through the different items. Pressing Esc returns to the System Menu.
Parameter Description OCS Mode Displays the current scanning mode (Idle, Run, DoIO). In Idle mode, the I/O is
not scanned and the OCS ladder program does not execute. The green “RUN” LED is OFF. In Run mode, the ladder program executes and the green “RUN” LED illuminates. DoIO mode is similar to Run mode, except the ladder logic is not solved. When the OCS is in DoIO mode, the user is able to exercise all of the I/O from Cscape, without interference from the ladder program. In this mode the green “RUN” LED flashes. This feature is a valuable troubleshooting tool.
Scan-Rate Shows the number of milliseconds for the scan. The scan-rate is the sum of the
time required to execute the following items: a. Scan inputs
b. Solve logic c. Write outputs d. Handle network communications e. Handle host communications request f. Process data for operator interface
OCS Net Use Shows the percentage of the network used by the Mini. All Net Use Shows the percentage of the network used by all devices on the network.
Ladder Size Shows the number of bytes used by the ladder program. Config Size Shows the number of bytes used by the I/O configuration
Text Size Shows the number of bytes used by the text screens Firmware Rev Shows the execution engine firmware version.
BIOS Rev Shows the BIOS firmware revision. FPGA Rev Shows the FPGA Image version. Self-Test Shows if the power-up self-test passed or failed by displaying Ok or Fault.
CH.3 15 MAR 2003 PAGE 41 MAN0305-04
View OCS(RCS) Diags
This screen displays a list of self-test diagnostics results (no editable fields). Each item describes a test and shows a result of Ok if the test passed or Fault/Warn if an error was found while running the test. Fault indications will prevent the loaded application from running. Warn(ing) indications allow the application to run but inform the user that a condition exists that needs correction.
System BIOS - This test checks for a valid BIOS portion of the controller firmware. Ok The loaded BIOS firmware is valid Fault The loaded BIOS is invalid.
(Engine) Firmware - This test validates the controller firmware. Ok The firmware is valid. Fault The controller firmware is invalid.
User Program - This tests for a valid user program and configuration data. Ok The user program and confi guration is valid. Fault The user program and/or configuration are not valid.
System RAM - This test checks the functionality of the controller RAM at power up. Ok The RAM is functioning correctly. Fault The RAM is not functioning correctly.
Logic Error - This test checks for problems with the user program while running. Ok No errors have been encountered while running a user program.
Fault Indicates the user program contained an instruction that was invalid or unsupported.
W-Dog Trips - This test checks for resets caused by hardware faults, power brownouts or large amounts
of electrical interference. 0 No unintentional resets have occurred. xx Indicates a fault with xx showing the number of occurrences.
Net Errors - This test checks for abnormal network operations while running. (Network models only.) 0 No network errors were counted
xx Indicate serious networking problems exist, xx indicates the number of occurrences.
Network State - This test checks that the network sub-system is powered and operating correctly.
(Network models only.) Ok The network system is receiving power and has determined other devices are
communicating on the network. Warn Power is not being applied to the network or no other devices were found to be
communicating on the network. Network ID - This test checks that the network ID is valid. (Network models only.)
Ok The network ID is valid. Warn The network ID is not valid for the selected protocol.
Dup Net ID - This test checks for duplicate IDs on a network. (Network models only.) Ok This controller's ID was not found to be a duplicate. Warn Another controller on the network was found with the same ID as this controller.
PAGE 42 15 MAR 2003 CH.3 MAN0305-04
DeviceNet In - (DeviceNet model only.) Ok DeviceNet master is maintaining a polled connection and not sending IDLE.
Warn The DeviceNet master is no longer maintaining a polled connection or sending IDLE.
(IDLE is a network state in which ‘some’ masters maintain a polled connection but sends
zero data if an associated PLC controller is in IDLE mode. Refer to Master
documentation for more information.) Clock Error - This test checks that the real time clock contains valid data.
Ok The real time clock contains valid data. Warn Indicates invalid data in the real time clock.
I/O System - This test checks that the configured (downloaded) model number matches the physical
I/O module installed in the controller. Ok The configured model number matches the installed I/O module. Warn Indicates the configured model number does not match the installed I/O module. (See View OCS(RCS) Model system screen for more information.)
View I/O LEDs The View I/O LEDs simulate the LEDs and show the statuses of the first 16 %I and first 16 %Q registers.
View OCS(RCS) Model
The View OCS(RCS) Model screen allows the user to view the MiniOCS / MiniRCS model number. When viewing the model number, the following status screens are possible. Note the term OCSxxx (or
RCSxxx) refers to the MiniOCS (or Mini RCS) model number such as OCS082 (or RCS082). a. If the Mini model number is not configured and no I/O module is installed, the message
" I/O: Empty” is displayed.
b. If the Mini model number is not configured but has an I/O module installed, the message
"+Mini OCSxxx (or RCSxx)" is displayed.
c. If the Mini model number is configured but no I/O module is installed, the message
"-I/O Missing" is displayed.
d. If the configured Mini model number does not match the installed I/O module, the message
"?Mini OCSxxx (or RCSxx)" is displayed.
e. If the installed I/O module is not supported by the Mini firmware, the message
“*Unsupported” is displayed. The module is either defective or an Engine firmware upgrade is required to support the module.
f. If the installed I/O module has erroneous or outdated firmware in it, the message
fMini OCSxxx (or RCSxx)" is displayed. The module is either defective or a Module firmware upgrade is required.
g. If the installed I/O module has a configuration error, the message
"cMini OCSxxx (or RCSxx)" is displayed. The configuration data for that module is incorrect.
h. If the configured Mini model number matches the installed I/O module, the message
" Mini OCSxxx (or RCSxx)" is displayed.
CH.3 15 MAR 2003 PAGE 43 MAN0305-04
Set FKeys Mode
This screen contains an editable enumerated field that allows the Function keys to be configured to operate in one of two modes. When a function key is pressed, it can TOGGLE the point associated with the key or it can MOMENTARILY turn the point ON when the key is pressed.
Set RS232 Mode
This screen contains an editable enumerated field that allows the mode of the serial port to be set to one of two modes. The CsCAN mode allows Csape to connect to the serial port for uploads, downloads, monitoring and control. The Update mode allows a firmware update and factory test utility to be used. When Update mode is selected, the firmware is ready to download when the OK LED flashes. When using Cscape to perform firmware updates, the “Update” mode is not necessary.
Set Time/Date
This screen contains two editable enumerated fields for displaying and modifying the Mini’s time and date. Each field is subdivided and allows the and key to modify the value.
PAGE 44 15 MAR 2003 CH.3 MAN0305-04
NOTES
CH.4 15 MAR 2003 PAGE 45
Equal Indicator – indicates whether the current program in Cscape is equal to the program
, the program in Cscape is the same as the program stored in the Target
the same as the program stored in the Target
there may have been a change since the last time the program in Cscape
Communications Status - indicates the current status of the
Message Line -
messages sent by
Message line can
Current User -
Controller Model - Network (Model Confirmation)
File Modified Indicator - indicates that the fi le in
MAN0305-04
CHAPTER 4: KEYPAD AND SCREEN
4.1 Remote Screen and Keypad Capability
4.1.1 Remote Text Terminal
The MiniRCS has the same functionality as the MiniOCS except that it does not have a local operator screen and keypad. However, the MiniRCS (as well as the MiniOCS) supports a remote operator screen and keypad through a PC connected to the Mini unit’s built-in network or serial port. The remote operator interface and keypad can be displayed using Cscape software by pressing Screens, Remote Text Terminal. A virtual display screen and keypad appear that are similar to the MiniOCS physical front panel, and the user can navigate through various screens, make selections, and edit fields using a mouse.
4.1.2 Cscape Status Bar
When the MiniOCS/ MiniRCS is connected to a PC using Cscape software, and the Remote Text Terminal feature is selected, a Cscape Status Bar appears at the bottom of the screen. The Cscape Status Bar can be used to determine if communications have been established between the Mini and the Cscape program. Components of the Cscape Status Bar are explained in page 45.
contains Cscape the programs.
The contents of these messages are context sensitive. The
be empty.
Ready User: NONE HE500OCS061-CsCAN (Model=) Equal Local :1 Target :2(R) [no forces] MOD
Controller Model indicates the MiniOCS or MiniRCS
for which the program in Cscape is configured.
Network indicates the type of network that the program
in Cscape expects to use (e.g., CsCAN or DeviceNet).
(Model Confirmation) provides the following
indications:
(Model=) - the actual Target Controller matches the
configured Controller Model and Network.
(Model Not=) – the actual Target Controller does not
match the configured Controller Model and Network.
(Model ?) – there may have been a change since the
last time the Target Controller was compared to the configured
Controller Model and Network.
stored in the Target Controller.
If Equal Controller.
If Not Equal , the program in Cscape is not Controller.
If Unknown, was compared to the Target Controller.
indicates who is logged (for security purposes).
“pass through” Connector.
Local: xx – indicates the Network ID of the Mini to which
Target: yy(R) – indicates the Network ID of the Mini with
the selected window has been modified but has not been saved.
the Cscape program is physically connected through its serial port. It can serve as a “pass through” device to other nodes on the network.
which the Cscape program is exchanging data.
Note: The Local unit and Target unit can be the
same unit or they can be separate units. The following are status indicators: (R) – Running
(D) - Do I/o (I) – Idle (?) – Cscape is not communicating with the remote unit.
[no forces] – indicates no I/O has been forced.
PAGE 46 15 MAR 2003 CH.4 MAN0305-04
4.1.3 Establishing Communications using the Remote Text Terminal
1. Start Cscape software. Press Screens, Remote Text Terminal.
2. Establish communications between the Cscape program and Mini by pressing Controller, Set Network Target ID. Set the Target ID.
3. Again, select Controller, Configure I/O. Follow the procedures specified in Chapter Five: Configuration.
4. Download the program from Cscape to the Mini by pressing Program, Download.
5. Check the Cscape Status Bar as described in Section 4.1.2 to ensure that the program in Cscape matches the program downloaded to the Mini model. Be sure to chec k the Status Bar often. Another way to check that the download occurred is to press Program, Verify.
6. Click on the System Key in the display representation and continue the procedures to enter the system menu beginning on page 38.
4.2 Keypad Description
The MiniOCS keypad contains 10 user -programmable keys, Esc, Enter and four direction keys. The user-programmable keys, or function keys, also serve the purpose of numeric and alphabetic character entry. Function keys F1-F10 are available (%K registers). Depending on the configuration of the MiniOCS and the field needing to be edited, the MiniOCS automatically knows what type of digit or alphanumeric character needs to be entered.
The MiniOCS keypad also contains four direction keys. The and keys contain split fields. The key also contains the +/- function. The key also contains the . function. Similar to the operation of the function keys, the MiniOCS automatically knows if a decimal point or a positive or negative indicator is required. The and keys are also used to increment and decrement fields, respectively. The and keys are used to move the cursor from one character to another in an editable field and to switch from one editable fi eld to another editable field.
The MiniOCS features an Esc and an Enter key. The Esc key is used to exit out of a number of different menus and fields or abort an editing operation. The Enter key is used to select a field for editing and for sending data to the MiniOCS. The Enter key can also be used to escape out of some selected fields.
OK
RUN
1 2 3 4 5
QZ ABC DEF GHI JKL
F1 F2
6
F6
7
MNO PRS TUV WXY
F7
F3
8 9 0
F8
F4 F5 F9 F10
Figure 4.1 - MiniOCS Keypad
+/-
System
Esc
Enter
CH.4 15 MAR 2003 PAGE 47 MAN0305-04
The MiniOCS keypad has “OK” and “RUN” indicators. These indicators are green LEDs that are built into the keypad. When there are no errors present in the MiniOCS and the Self-Tests have “passed,” the green “OK” LED illuminates. When the controller is running logic, the RUN LED illuminates. If the controller is in the RUN mode with no logic loaded or if it is in the DO I/O mode, the RUN LED flashes.
4.3 Operation
When the MiniOCS unit first powers -up, it displays “MiniOCS Self-Test In Progress.”Next, the message “MiniOCS Self-Tests In Progress...” appears. After the Mini displays this message, the unit performs tests to examine the current state of the network. Four different scenarios can occur:
Scenario #1: No power is supplied to the CAN port. The message “No Network Power Network Disabled” is displayed. Assuming the controller is configured to require the network, the OCS then displays the message “Self-Tests Failed.” Also, there is a Fault Code of 80 displayed in “View OCS Info” in the System Menu (see Chapter 3). The green “OK” light does not illuminate.
Scenario #2: No other units are on the CAN network (or this is the first device to power -up on the network). The message "Waiting for Net: F1 = Disable Net" is shown. If another device is placed on the CAN network, the message clears and operation continues. The message “Self-Tests Passed” is displayed. The green “OK” light illuminates. If F1 is pressed the message “No Net Response Network Disabled” appears and is followed by the message “Self-Tests Failed”. The green “OK” light does not illuminate.
Scenario #3: If a unit powers -up and finds another unit with the same node number as itself, the display shows "Duplicate ID Network Disabled". The network is disabled, and the unit displays the message “Self-Tests Failed.” The green “OK” light does not illuminate.
Note: The ID checking works when one of two devices with the same ID is powered-up more than 1 second before the other. If both devices are powered-up at the same time, this method of ID checking may not work. In this case, the Mini continues to check for duplicate IDs during operation.
Scenario #4: If a unit powers up and it has network power, and other units are powered up on the network, the message “Self-Tests Passed” is displayed, and the green “OK” light is illuminated.
At any time, the Mini unit can be reset by pressing: + F1 + F2 (press the keys at the same time )
PAGE 48 15 MAR 2003 CH.4 MAN0305-04
4.4 User Screens
In the normal operating mode there are a set of user -defined screens that can be scrolled through using the and keys.
If the ladder program energizes a text coil, the screen associated with this coil is displayed and overrides the "normal" user screens. This is designed to show alarm conditions or to display other ladder -detected events. When the text coil is de-energized, the previous screen that was being viewed before the alarm is returned.
If the screen contains an editable field, the user can press the Enter key to enter the edit mode. When in edit mode, a cursor appears on one digit of the editable field. Use the direction keys (← and → ) to move to the cursor to the desired position. Use the and keys to increment or decrement the digit or
enter the number/data with the alphanumeric keys. If there is more than one field on the screen nee ding to be edited, use the direction keys ( and ) to
move the cursor to the desired location. The value chosen by the user may not exceed the minimum or maximum set by the user program. If the
user tries to exceed the maximum point or enter a value below the minimum point, the value does not change.
Note: If the MiniOCS displays “>>>>>>” in a text field, the value is too big to display in the field or is above the maximum for an editable field. If the MINI displays “<<<<” in a text field, the value is too small to display or is below the minimum for an editable field.
4.4.1 Cursor Types
There are three different cursor types, which may show on the display: a. Solid underline
b. Blinking block c. Blinking underline
A solid underline cursor appears under an editable field which is not being edited yet. The key and the key can be used to move this type of cursor to select a different editable field, if required. Press Enter to start editing the selected field. This causes a blinking block cursor to appear.
A blinking block cursor appears in an editable field when Enter is first pressed to start editing the field. The blinking block cursor indicates that the field will be cleared when a numeric (or alphanumeric for an ASCII field) key is pressed. This allows a new value to be entered for the field just as it would be entered on a PC keyboard or a calculator. If a direction key (←, →,↑,↓) is pressed, the cursor changes from a blinking block to a blinking underline, and single-digit edit mode is entered.
A blinking underline cursor appears under an editable field which is being edited in single digit edit mode. In this mode, the digit (or character) above the cursor can be modified individually. This can be done by pressing or (increments or decrements) or by pressing a numeric (or alphanumeric) key. Pressing or moves the cursor to the previous or next digit (or character).
CH.5 15 MAR 2003 PAGE 49 MAN0305-04
CHAPTER 5: MINI CONFIGURATION
5.1 General
Chapter Five provides preliminary configurat ion procedures that are applicable to all MiniOCS / MiniRCS models.
Remote Screen Usage for the the MiniRCS: The MiniRCS has the same functionality as the MiniOCS except that it does not have a local operator screen and keypad. However, the MiniRCS supports a remote operator screen and keypad. through a PC connected to the Mini unit’s built-in network. If desired, the remote operator interface and keypad can be displayed (using Cscape software) by pressing Screens, Remote Text Terminal. A virtual display screen and keypad appears that is similar to that of the MiniOCS. In addition, a Status Bar can be used as a tool to ensure that communications are properly established. For more information on the Remote Test Terminal and the Status Bar feature, see
page 45.
Note: The examples in this chapter depict the MiniOCS, but the information also applies to the
MiniRCS when using the Remote Text Terminal screen.
The MiniOCS / MiniRCS models use Cscape Software for configur ation. General information is also provided pertaining to the screens that the user encounters when configuring specific modules. In addition, each MiniOCS / MiniRCS model has its own data sheet which covers specifications, wiring and other pertinent information. (See page 18.)
5.2 Preliminary Configuration Procedures
1. The MiniOCS / MiniRCS configuration is accomplished through the Configure Controller Type Dialog.
Note: Th e configuration examples in this chapter depict the MiniOCS, but the procedures also apply to
the MiniRCS as well.
a. Using Auto Configuration
From the Main Menu, select Controller|Configure for the following dialog. If the desired MiniOCS / MiniRCS is physically connected to the PC, press Auto Config. A dialog box appears and indicates that
settings will be deleted from currently configured models. If OK, press Yes. Then press OK. To obtain a description of the MiniOCS / MiniRCS model, double -click on the box (or press the top
Config button) to select the desired controller from the pull -down menu.
PAGE 50 15 MAR 2003 CH.5 MAN0305-04
Figure 5.1
Note: The configuration examples in this chapter depict the MiniOCS, but the procedures also apply to
the MiniRCS.
b. Manual Selection of MiniOCS / MiniRCS Model and Obtaining a Description of the Model
Figure 5.2
CH.5 15 MAR 2003 PAGE 51
MAN0305-04
If a different controller is installed, select the MiniOCS / MiniRCS by double-clicking on the box (or press the top Config button) and select the desired controller from the pull-down menu.
Figure 5.3
Note: The configuration examples in this chapter depict the MiniOCS, but the procedures also apply to
the MiniRCS.
Using pull-down menus, select either a network version of the MiniOCS / MiniRCS (MiniOCS / MiniRCS – CsCAN) or a non -network version (MiniOCS / MiniRCS – No net). Then, select the MiniOCS / MiniRCS model that is going to be configured. A description of the selected model is provided on this screen. Press OK.
2. The following screen appears.
Figure 5.4
PAGE 52 15 MAR 2003 CH.5
Warning: The default turns the outputs OFF when the controller enters idle/stop mode. To avoid injury
MAN0305-04
3. To view the registers associated with the MiniOCS / MiniRCS model, press the lower Config button.
a. A screen appears showing the I/O Map for the MiniOCS / MiniRCS model selected. The user (i.e., programmer) needs to view the I/O Map to determine which registers are assigned to the model.
Figure 5.5
Model number: Provides the I/O part number. Description: Describes the number of input and output channels and other key
characteristics of the module. Type: Displays the register types assigned to the module. Starting/Ending : Denotes the starting and ending locations of the register type. Number: Indicates the quantity for a particular register type.
Note: Do not confuse the described number of input and output channels with the numbers found in the Type column (i.e., %I and %Q). The numbers do not necessarily match.
b. Selecting the I/O Map tab provides information about the I/O registers, which are assigned to a specific MiniOCS / MiniRCS Module. The I/O Map is determined by the model number. The I/O Map is not edited by the user.
The Module Setup is used in applications where it is necessary to change the default states of the outputs when the controller (e.g., OCS100) enters idle/stop mode. The default turns the outputs OFF when the controller enters idle/stop mode. By selecting the Module Setup tab, each output can be set to either turn ON, turn OFF or to hold the last state. Generally, most applications use the default settings.
of personnel or damages to equipment, exercise extreme caution when changing the default setting using the Module Setup tab.
4. There is no further configuration required for most MiniOCS / MiniRCS models. The exceptions are the High Speed Counter MiniOCS / MiniRCS Models which include 033/063 and 034/064. Refer to the SmartStack High Speed Counter Supplement for further information.
CH.6 15 MAR 2003 PAGE 53 MAN0305-04
CHAPTER 6: SMARTSTIX
6.1 General
Chapter Six covers SmartStix I/O programming and configuration parameters.
6.2 SmartStix I/O Introduction SmartStix I/O is a family of low -cost Remote I/O devices that are designed to extend the I/O capabilities
of Control Station products, such as MiniOCS, OCS and RCS. SmartStix I/O Modules connect to Control Station devices via the CsCAN Network and communicate using CsCAN Protocol.
Devices with CsCAN Network ports that are connected to each other for peer-to-peer communication are called CsCAN Nodes. A device that is connected to a CsCAN Node’s programming port for master-slave supervisory communication is called a CsCAN Host. For example, SmartStix I/O Modules and OCS Control Stations are CsCAN Nodes while a PC running Cscape is a CsCAN Host.
6.3 SmartStix I/O Modules SmartStix I/O Modules are devices that exchange data with Control Stations over the CsCAN Network
and control and monitor physical I/O points. To control physical outputs, data is sent by a Control Station to the SmartStix I/O Module using CsCAN
Directed Data Messages. To monitor physical inputs, a Control Station receives data from the SmartStix I/O Module using CsCAN Global Data Messages.
In addition to I/O control and monitoring, configuration and status data can be exchanged between a Control Station and a SmartStix I/O Module.
For example, a Control Station can send configuration data to a SmartStix I/O Module to tell it how often to expect output control data, and what to do if the Control Station stops sending output control data. Also, a Control Stat ion can receive status data from a SmartStix I/O Module indicating if it needs configuration or if a fault has been detected.
All this is accomplished by using the PC-based Cscape programming tool to program the Control Station. Since the Control Station dynamically configures the SmartStix I/O Module, SmartStix I/O Modules can be readily deployed without having to configure them first.
PAGE 54 15 MAR 2003 CH.6 MAN0305-02
BASIC SMARTSTIX PROGRAMMING
6.4 Using GET and PUT
6.4.1 Get Remote I/O Function Block
This function handles receiving data from a remote I/O device and places the received data in a set of registers specified by the user. This function passes power flow if the function is actively receiving data / heartbeat messages from the remote I/O device. This function stops passing power flow if it has not received data / heartbeat messages from the remote I/O device for 2000 milliseconds.
A remote I/O device consists of a CsCAN device such as a SmartStix Module that transmits global data and receives directed network data.
Figure 6.1 – Get Remote I/O Function Block and Parameter Screen
6.4.2 Get Remote Parameter Description:
ID – This is the network ID of the remote I/O from which to receive data. This can be a constant from 1 to 253 or a 16 -bit register.
Digital / Analog – These radio buttons allow choosing digital or analog network data. Remote I/O devices with discrete inputs/out puts normally require digital data. Remote I/O devices such as voltage, current or thermocouple would require analog data.
Destination Data Address – This is the location to start placing data received from the remote I/O device. The number of registers used is defined by the Num Words parameter in this section. Any valid read/write OCS reference types can be used (%R, %AI, %I, %M, etc.).
Status – This 16 -bit register is used internally. It must not written by any other function block. Use the power flow from this function for the pass/fail status.
CH.6 15 MAR 2003 PAGE 55 MAN0305-04
Num Words – This is the number of words to receive from the remote I/O device. Up to four words can be received from the remote I/O device. The function of these words are described in Table 6.1.
Table 6.1 - Consumed / Produced Parameter Descriptions
Consumed Directed Digital Data Words
Word 1 (bits 1 to 16) Controls on/off state of digital outputs 1-16. Relay or Digital output SmartStix Word 2 (bits 17 to 32) Controls on/off state of digital outputs 17-32. Relay or Digital output SmartStix Word 3 (bits 33 to 48) Specifies whether SmartStix uses default
configuration or values from Word 4.
Word 4 (bits 49 to 64) Sets digital inputs / heartbeat and life
expectancy time data. Word 5 (bits 65 to 80) Sets the default state of outputs 1-16. Relay and Digital output Word 6 (bits 81 to 96) Sets the default state of outputs 17-32. Relay and Digital output Word 7 (bits 97 to 112) Determines if default state is on or off for
outputs 1-16. Word 8 (bits 113 to 128) Determines if default state is on or off for
outputs 17-32.
Produced Global Digital Data Words
Word 1 (bits 1 to 16) On/off state of inputs 1-16. Digital input SmartStix Word 2 (bits 17 to 32) On/off state of inputs 17-32. Digital input SmartStix Word 3 (bits 33 to 48) Status bits and diagnostic data Relay or Digital input and output Word 4 (bits 49 to 64) Device class number and firmware identifier
sent by SmartStix module.
Function
Function
Affects
Relay and Digital input and output Relay and Digital input and output
Relay and Digital output Relay and Digital output
Affects
Relay or Digital input and output
Note: Table 6.1 summarizes SmartStix I/O module consumed and produced data words. For advanced
users, refer to pages 58 and 60 for sections describing the Consumed and Produced words in detail.
6.4.3 Put Remote I/O Function Block
This function handles sending data to a remote I/O device block obtained from a set of registers specified by the user. This function passes power flow if the remote I/O device is behavi ng normally. This function does not pass power flow if the remote I/O device has not sent a heartbeat in 2000 milliseconds. This function sends heartbeat messages to the output device every 1000 milliseconds. The default remote I/O operation is to expec t heartbeat messages at least every 2000 milliseconds; otherwise the outputs are turned off (or their configured default state). Data is normally transmitted on change of state or if the remote I/O device is power-cycled.
A remote I/O device consists of a CsCAN device such as SmartStix Modules that transmit global data and receive directed network data.
Figure 6.2 - Put Remote I/O Function Block and Parameter Screen
PAGE 56 15 MAR 2003 CH.6 MAN0305-02
6.4.4 Put Remote Parameter Description:
ID – This is the network ID of the remote I/O to direct the sent data. This can be a constant from 1 to 253 or can be a 16 -bit register.
Digital / Analog – These radio buttons allow choosing digital or analog network data. Remote I/O devices with discrete inputs/outputs normally require digital data. Remote I/O devices such as voltage, current or thermocouple require analog data.
Source Data Address – This is the starting location to get data to send to the remote I/O device. When this data changes state, it is sent to the remote I/O device. The number of registers used is defined by the Num Words parameter in this section. Any valid OCS reference types can be used (%R, %AQ, %Q, %M, etc.).
Status – this 16-bit register is used internally. It must not be written by any other function block. Bit 1-12 – reserved or internal use only
Bit 13 – Remote I/O OK and in sync with supplied data Bit 14 – the Remote I/O detected a heartbeat error Bit 15 – the Remote I/O has just powered up Bit 16 – the function is forcing a send (unit just power cycled or first scan)
Num Words – This is the number of words to send to the remote I/O device. Up to 8 words can be sent to the remote I/O device. The function of these words are described in Table 6.1.
6.5 SmartStix I/O Default Operation
SmartStix I/O has been designed so that its default operation satisfies the most common applications. This keeps the user interface simple and makes the product easy to use. The default operation is summarized in Table 6.2. To change the default operator, see Advanced SmartStix Programming (page
57).
Table 6.2 – SmartStix I/O Default Operation
Digital Input Devices
Data Reporting Method Change of State Heartbeat Generation Interval 1000msec.
Digital Output Devices
Update Method (using NETPUT Remote I/O Function block) Heartbeat Generation Interval 1000msec. (LET) Life Expectance Time (Receipt of Heartbeat) (LET) Action Upon Expiration Turn all outputs OFF
Change of State
2000msec.
CH.6 15 MAR 2003 PAGE 57 MAN0305-04
ADVANCED SMARTSTIX PROGRAMMING
6.6 SmartStix I/O Module Device Classes
There are currently five SmartStix I/O Module device classes (0, 1, 2, 3 and 7) that control and monitor Digital I/O points and exchange Directed and Global Data words with a Control Station via the CsCAN Network.
Table 6. 3 shows the five device classes along with the number of Digital I/O points they contain and the number of Directed and Global Data words they exchange.
Example: Determining the class of a SmartStix module:
1. Select the number of digital output points and the number of digital input points using Table 6.3.
2. Upon doing so, the device class is located in the same row as the digital outputs and inputs; the words consumed and produced are also shown for that device class.
Table 6.3 – SmartStix I/O Module Device Classes
Device
Class
Digital
Output Points
Digital
Input Points
Directed Data
Words Consumed
Global Data
Words Produced
0 16 0 8 4 1 0 16 8 4 2 16 16 8 4 3 0 32 8 4 7 32 0 8 4
All other device classes are reserved for future products.
Note that although all of the above device classes can consume eight Directed Data Words and can
produce four Global Data words, each device class uses a specific subset of this data. The following terms are defined:
Consumed Data: Directed Data received by a SmartStix I/O Module from a Control Station Produced Data: Global Data transmitted by a SmartStix I/O Module to a Control Station
Table 6.4 summarizes SmartStix I/O module consumed and produced data words. For advanced users,
the following sections describe the consumed and produced words in det ail.
PAGE 58 15 MAR 2003 CH.6 MAN0305-02
6.7 SmartStix I/O Module Consumed (Received) Directed Data
Table 6.4 – Consumed Directed Data Word 1
16-bit Word
8-bit High Byte 8-bit Low Byte
Digital Output Control Data – Low Word
Q16 Q15 Q14 Q13 Q12 Q11 Q10 Q9 Q8 Q7 Q6 Q5 Q4 Q3 Q2 Q1
Q16…Q1 Controls the Off / On state of the SmartStix I/O Module’s 1st 16 Digital Outputs, if any.
Table 6.5 – Consumed Directed Data Word 2
16-bit Word
8-bit High Byte 8-bit Low Byte
Digital Output Control Data - High Word
Q32 Q31 Q30 Q29 Q28 Q27 Q26 Q25 Q24 Q23 Q22 Q21 Q20 Q19 Q18 Q17
Q32…Q17 Controls the Off / On state of the SmartStix I/O Module’s 2nd 16 Digital Outputs, if any.
Table 6.6 – Consumed Directed Data Word 3
16-bit Word
8-bit High Byte 8-bit Low Byte
Diagnostic Command Data Configuration Command Data
Reserved for Future Products CIT
CHT CL
T
CLT = 0 Command the SmartStix I/O Module to set its Life Expectancy Time to 2.0 seconds, as the maximum
time to wait between Control Station to SmartStix I/O Module output control data messages, before setting all Digital Outputs to their default states.
CLT = 1 Command the SmartStix I/O Module to use Word 4’s Life Expectancy Time. In this case, a value of 0.0
disables the Life Expectancy feature.
CHT = 0 Command the SmartStix I/O Module to set its Heartbeat Send Time to 1.0 second, as the minimum time
between SmartStix I/O Module to Control Station Heartbeat messages.
CHT = 1 Command the SmartStix I/O Module to use Word 4’s Heartbeat Send Time. In this case, a value of 0.0
CIT = 0 Command the SmartStix I/O Module to send its Digital Input data to the Control Station, only when the
CIT = 1 Command the SmartStix I/O Module to use Word 4’s Digital Input Send Time, to determine how often to
Note: Regardless of the CIT setting, Digital Inputs are always sent to the Control Station when the
disables the Heartbeat Send feature.
Digital Inputs change state.
periodically send its Digital Input data to the Control Station. In this case, a value of 0.0 disables automatic sending of Digital Input data.
SmartStix I/O Module powers-up, and when specifically requested by the Control Station.
Table 6.7 – Consumed Directed Data Word 4
16-bit Word
8-bit High Byte 8-bit Low Byte
Digital Input / Heartbeat Send Time Data Life Expectancy Time Data
0.0 to 25.5 seconds = Minimum Send Interval 0.0 to 25.5 seconds = Maximum Receive Interval
See Directed Data Word 3’s CLT, CHT and CIT command descriptions above.
CH.6 15 MAR 2003 PAGE 59 MAN0305-04
Table 6.8 – Consumed Directed Data Word 5
16-bit Word
8-bit High Byte 8-bit Low Byte
0 = Force Off / On 1 = Hold-Last-State Default Digital Output Data - Low Word
H16 H15 H14 H13 H12 H11 H10 H9 H8 H7 H6 H5 H4 H3 H2 H1
H16…H1 Determines default state of the SmartStix I/O Module’s 1st 16 Digital Outputs, if any, when
the configured Life Expectancy Time expires. If an H bit is 1, its corresponding Digital Output, by default, holds its last state. If an H bit is 0, its corresponding Digital Output is forced Off or On, depending on the corresponding F bit in Word 7 (Table 6.10).
Table 6.9 – Consumed Directed Data Word 6
16-bit Word
8-bit High Byte 8-bit Low Byte
0 = Force Off / On 1 = Hold-Last-State Default Digital Output Data - High Word
H32 H31 H30 H29 H28 H27 H26 H25 H24 H23 H22 H21 H20 H19 H18 H17
H32…H17 Determines default state of the SmartStix I/O Module’s 2nd 16 Digital Outputs, if any, when
the configured Life Expectancy Time expires. If an H bit is 1, its corresponding Digital Output, by default, holds its last state. If an H bit is 0, its corresponding Digital Output is forced Off or On, depending on the corresponding F bit in Word 8 (Table 6.11).
Table 6.10 – Consumed Directed Data Word 7
16-bit Word
8-bit High Byte 8-bit Low Byte
0 = Force Off 1 = Force On Default Digital Output Data - Low Word
F16 F15 F14 F13 F12 F11 F10 F9 F8 F7 F6 F5 F4 F3 F2 F1
F16…F1 Determines default Off or On state of each of the SmartStix I/O Module’s 1st 16 Digital
Outputs, if any, when the configured Life Expectancy Time expires, and when the corresponding H bit in Word 5 (Table 6.8) is 0.
Table 6.11 – Consumed Directed Data Word 8
16-bit Word
8-bit High Byte 8-bit Low Byte
0 = Force Off 1 = Force On Default Digital Output Data - High Word
F32 F31 F30 F29 F28 F27 F26 F25 F24 F23 F22 F21 F20 F19 F18 F17
F32…F17 Determines default Off or On state of each of the SmartStix I/O Module’s 2nd 16 Digital
Outputs, if any, when the configured Life Expectancy Time expires, and when the corresponding H bit in Word 6 (Table 6.9) is 0.
6.8 Consumed Directed Data Power-Up Initialization
At power-up, the SmartStix I/O Module’s eight Consumed Directed Data words are all cleared to 0. Until Directed Data is actually received from a Control Station, the SmartStix I/O Module will exhibit the following behavior:
1. All Digital Outputs are Off, until Q data is received from a Control Station.
2. The device expects to receive Q data at least every two seconds.
3. The device transmits a Heartbeat every second.
4. The device transmits its Digital Input data, only when the Digital Inputs change state.
5. If Q data is received, and then not received for 2 seconds, the outputs go Off again.
6. At power-up, a request for Directed Data is transmitted to the CsCAN Network.
PAGE 60 15 MAR 2003 CH.6 MAN0305-02
6.9 SmartStix I/O Module Produced (Transmitted) Global Data
Table 6.12 – Produced Global Data Word 1
16-bit Word
8-bit High Byte 8-bit Low Byte
Digital Input Status Data - Low Word
I16 I15 I14 I13 I12 I11 I10 I9 I8 I7 I6 I5 I4 I3 I2 I1
I16…I1 Monitors the Off / On state of the SmartStix I/O Module’s 1st 16 Digital Inputs, if any.
Table 6.13 – Produced Global Data Word 2
16-bit Word
8-bit High Byte 8-bit Low Byte
Digital Input Status Data - High Word
I32 I31 I30 I29 I28 I27 I26 I25 I24 I23 I22 I21 I20 I19 I18 I17
I32…I17 Monitors the Off / On state of the SmartStix I/O Module’s 2nd 16 Digital Inputs, if any.
Table 6.14 – Produced Global Data Word 3
16-bit Word
8-bit High Byte 8-bit Low Byte
Module Fault Data Network Fault Data Configuration Status Data
PUP I/O ROM RAM LIFE ID DUP NAK SIT SHT SLT
SLT CLT command status; matches CLT when command is complete SHT CHT command status; matches CHT when command is complete SIT CIT command status; matches CIT when command is complete
NAK Network Acknowledge test failed; found no other Network devices DUP Network Duplicate ID test failed; found another Network device with our Network ID ID Network ID test failed; Network ID rotary switches illegally set to 00, FE or FF LIFE Network Life Expectancy Time has expired; outputs are in default state
RAM Module RAM test failed; found a RAM memory fault during power-up-self-test ROM Module ROM test failed; found a ROM memory fault during power-up-self-test I/O Module I/O test failed; found an I/O fault during power-up-self-test PUP Module just powered up; using default configuration; outputs are Off
Table 6.15 – Produced Global Data Word 4
16-bit Word
8-bit High Byte 8-bit Low Byte
Firmware Revision Status Data Device Identification Status Data
0.00 to 2.55 = Version Number 0 to 255 = Device Class Number
Device Class Number SmartStix I/O Module’s numeric product identifier (see Table 6.3). Version Number SmartStix I/O Module’s numeric firmware identifier
6.10 Produced Global Data Power-Up Initialization
At power-up, a SmartStix I/O Module’s four Produced Global Data words are initialized as follows:
1. Digital Inputs are read and loaded into Words 1 and 2.
2. Power-up-self-test result is loaded into Word 3; if tests passed, only PUP bit is On.
3. Module’s Device Class Number and Version Number are loaded into Word 4.
4. All four Produced Global Data words are transmitted to the CsCAN Network.
CH.6 15 MAR 2003 PAGE 61 MAN0305-04
6.11 SmartStix I/O Module LED Indicators
SmartStix I/O Modules provide diagnostic and status LED indicators
6.11.1 Diagnostic LED Indicators
The MS an NS diagnostic LEDs indicate the fault status of the module and the network, respective ly. Note that the diagnostic LEDs correspond directly to the Module Fault and Network Fault bits as shown in
Table 6.14.
The following table shows the possible LED states and their meanings:
Table 6.16 – SmartStix I/O Module Diagnostic LED Indicators
Diagnostic
LED
MS
(Module
Status)
NS
(Network
Status)
State Meaning
Solid Red RAM or ROM test failed (RAM or ROM bit On)
Blinking Red I/O test failed (I/O bit On)
Blinking Green Module is in power-up state (PUP bit On)
Solid Green Module is running normally (all Module Fault bits Off)
Solid Red Network Ack or Dup ID test failed (NAK or DUP bit On)
Blinking Red Network ID test failed (ID bit On)
Blinking Green Module is in Life Expectancy default state (LIFE bit On)
Solid Green Network is running normally (all Network Fault bits Off)
6.11.2 Status LED Indicators
In addition to the MS and NS diagnostic LED indicators described above, Sma rtStix I/O Modules also provide a Power Status LED, which illuminates Red when power is applied to the module.
Also, there are I/O Status LED indicators for each of the Digital I/O points, which illuminate Red when the I/O point is On.
6.12 SmartStix I/O Module Network ID
Each SmartStix I/O Module (as well as all other CsCAN Nodes on the CsCAN Network) must be assigned a unique Network ID number, to arbitrate network data exchanges.
Since a Network ID is a number in the range 1 to 253, up to 253 CsCAN Nodes can be logically connected to a CsCAN Network. However, the use of standard CAN transceiver chips, limits the number of physically attached devices to 64. Thus, to reach the logical limit of 253 devices, up to three smart CAN repeaters (HE200CGM100) are used, to connect groups of devices together.
Assigning a SmartStix I/O Module’s Network ID is accomplished by setting its two hexadecimal (base 16) Network ID rotary switches, which are labeled HI and LO. Each rotary switch has 16 positions, labeled 0, 1, 2, 3, 4, 5, 6, 7, 8, 9, A, B, C, D, E and F, where A through F represent the decimal values 10 through
15. The Network ID rotary switches are set as follows: Network ID = (Network IDHI x 16) + Network IDLO
This allows the Network ID to be set to any number from 0 to 255. However, since Network IDs 0, 254 and 255 (00, FE and FF) are reserved for other purposes, they are illegal settings for a SmartStix I/O Module. If a SmartStix I/O Module’s rotary switches are set for an illegal Network ID, a default Network ID of 253 will be used, the ID Network Fault bit will be On, and the NS LED will blink Red.
PAGE 62 15 MAR 2003 CH.6 MAN0305-02
NOTES
INDEX 15 MAR 2003 PAGE 63 MAN0305-04
INDEX
Auto Configuration, 49
Battery Replacement, 35 Bus Length
CsCAN, 30 DeviceNet, 30
Bus Power
CsCAN, 30 DeviceNet, 30
Cable
CsCAN or DeviceNet, 29 CsCAN/DeviceNet
Bus Length, 30
Bus Power and Grounding, 30 CAN Wiring Rules, 28 Checklist, 25 Configuration
Preliminary Procedures, 49
Connectors / Ports
CAN, 27 DeviceNet, 27 Primary Power, 26
CsCAN
cable, 29 Cscape Software, 10 Cursor Types, 48 DeviceNet
cable, 29 DeviceNet Network
Selecting, 33 Dimensions and Panel Cut -outs, 19 Features, 9 Firmware Update Wizard, 33 GET, 54 Grounding, 26
CsCAN, 30
DeviceNet, 30 Initial System Menu Screens, 38 Keypad, 46 Ladder Control, 17 LEDs, 33
Diagnostic, 61
Status, 61 LEDs, MiniOCS and MiniRCS, 33 Mini
Functions/Features, 9
Specifications, 11 Modem Cable Wiring, 32
Modem Setup, 31 Modem, Recommended, 33 Mounting Orientation, 21 Mounting Requirements, 19 Operation, 47 Panel Box
Clearances, 24 Design Checklist, 25 Grounding, 24 Noise, 25 Orientation, 25
Temperature, 24 Panel Box Design, 23 Primary Power Port, 26 PUT, 55 References, Additional, 18 Registers
Global I/O, 16
HMI, 15
Physical I/O, 16
System, 13
User, 15 Remote Screen and Keypad, 45
Using Remote Text Terminal, 38 Remote Text Terminal, 45
Establishing Communications, 46 Resources, 12
Definitions, 13
Global Data I/O Registers, 16
HMI Registers, 15
Ladder Code, 17
Physical I/O Registers, 16
System Registers, 13
User Registers, 15 RS-232 Communications Wiring, 31 RS-232 Programming Port and Wiring, 30 Scope, 9 Self-Test, System Menu, 38
Set Contrast , 39 Set FKeys Mode , 43 Set Network Baud, 39 Set Network ID, 39 Set RS232 Mode , 43 Set Time/Date, 43
SmartStix, 53
Consumed Data, 58
Consumed Data, Power-Up, 59
PAGE 64 15 MAR 2003 INDEX MAN0305-04
CsCAN, 9 Default Operation, 56 Device Classes, 57 GET, 54 Introduction, 53 LED Indicators, 61 Module Network ID, 61 Modules, 53 Modules, Functions of, 53 Produced Data, 60 Produced Dat a Power-Up, 60 Programming, Advanced, 57 Programming, Basic, 54 PUT, 55
Specifications, 11 Status Bar, 45 System Menu
Entering, 38
Option Screens, 39
System Menu (Navigating through ), 37 System Menu Screen Fields (Editing), 37
Technical Support, 18 User Screens, 48
View I/O LEDs, 42 View OCS (RCS) Status, 40 View OCS(RCS) Diags, 41 View OCS(RCS) Model, 42
Loading...