Horner APG HE-RTD100 User Manual

Page 1
MAN0236-09 10 NOV 2006 PAGE 1 RTD000/100
RTD Input Module
HE800RTD000 / HE800RTD100
HE-RTD000 / HE-RTD100*
This datasheet also covers products starting with IC300.
* HE- denotes plastic case.
1 SPECIFICATIONS
RTD000 RTD100 RTD000 RTD100 Number of Channels
RTD Types
Input Range Input Impedance
RTD Excitation Current RTD Short Indefinite
Channel-to-Channel Tracking Update Time 16 channels/second Input Transient Protection
Notch Filter CE
UL
2 4
100, 200, 500, 1000 Ohms at 0°C, Platinum, Alpha
0.00385, DIN43760
-200°C to +850°C
>100Meg Ohm 0-4VDC
Clamped @ 0 and 4VDC
2.2, 1.1, 0.44, 0.22mA, 25% duty cycle
0.1°C
Zener/Capacitor
50-60 Hz. Software
Selectable
See Compliance Table at http://www.heapg.com/Support/compliance.htm
Required Power
(Steady State)
Required Power
(Inrush) Average RTD Current
I/O Points Required
Converter Type Integrating Types Supported DIN43760
Accuracy
Resolution Operating Temperature Relative Humidity
Terminal Type Spring Clamp, Removable Weight 9.5 oz. (270 g)
0.10W (4.2mA @ 24VDC) Negligible
0.44mA (100 Ohm Range) 2 4
± 0.5°C
0.05°C
0° to 60° Celsius
5 to 95% Non-condensing
This Data Sheet is published individually & also as a part of the SmartStack Supplement (SUP0246-05).
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.
Page 2
PAGE 2 10 NOV 2006 MAN0236-09 RTD000/100
2 WIRING
1E 1S 1C
2E 2S 2C
3E 3S 3C
4E 4S 4C
*
OCS Bottom View – Shows
Corresponding I/O Pin
*
Pin
RTD100 RTD000
1E RTD1 Excitation RTD1 Excitation 1S RTD1 Sense RTD1 Sense 1C RTD1 Common RTD1 Common
Shield Shield 2E RTD2 Excitation RTD2 Excitation 2S RTD2 Sense RTD2 Sense 2C RTD2 Common RTD2 Common
Shield Shield 3E RTD3 Excitation 3S RTD3 Sense 3C RTD3 Common
Shield 4E RTD4 Excitation 4S RTD4 Sense 4C RTD4 Common
Shield
Signal
001RTD001
3 CONFIGURATION
Note: The status of the I/O can be monitored in Cscape Software.
Preliminary configuration procedures that apply to SmartStack Modules are contained in the hardware manual of the controller you are using. Refer to the Additional References section in this data sheet for a listing of hardware manuals.
Module Setup Tab
a) Sensor T ype for each chann el may be selected independently. b) Temperature format may be set for various C° or F° ranges. c) Filter Constant sets the level of digital filtering according to the chart below. d) Reject Rates sets the frequency level for noise rejection at 50 or 60HZ.
I/O Map Tab
The I/O Map describes which I/O registers are assigned to a specific SmartStack Module and where the module is located in the point map. The I/O Map is determined by the model number and location within the SmartStack. The I/O Map is not
edited by the user.
This Data Sheet is published individually & also as a part of the SmartStack Supplement (SUP0246-05).
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.
Page 3
MAN0236-09 10 NOV 2006 PAGE 3 RTD000/100
1
2 3 4 5 6 70
Filter Constant
Digital Filtering. The illustration above demonstrates the effect of digital filtering (set with Filter Constant) on module response to a temperature change.
%Complet e [ ]
100
90 80 70 60 50 40 30 20 10
0
750ms
1250ms500ms 1000ms250ms0
Scans
4 TEMPERATURE CONVERSION
For a given module configuration, use the appropriate formula in the table to obtain the actual temperature (°C or °F) that is represented by the value in the %AI register.
Temperature Conversion Module
Configuration
0.05° °C = %AI / 20 °F = %AI / 20
0.1° °C = %AI / 10 °F = %AI / 10
0.5° °C = %AI / 2 °F = %AI / 2
Celsius Fahrenheit
This Data Sheet is published individually & also as a part of the SmartStack Supplement (SUP0246-05).
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.
Page 4
PAGE 4 10 NOV 2006 MAN0236-09 RTD000/100
5 INSTALLATION / SAFETY
Warning: Remove power from the OCS controller, CAN port, and any peripheral equipment connected to this local system before adding or replacing this or any module.
a) All applicable codes and standards should be followed in the installation of this product. b) Shielded wiring should be used for best performance such as Omega EXTT-3CU-26S or
equivalent. c) Shields may be terminated at the module terminal strip. d) In severe applications, shields should be tied directly to the ground block within the panel. e) Interposing electrical devices (such as relays) in the signal path can cause errors due to
resistive imbalance.
For detailed installation and a handy checklist clearances, refer to the hardware manual of the controller you are using. (See the Additional References section in this document.)
When found on the product, the following symbols specify:
that covers panel box layout requirements and minimum
Warning: Consult user documentation.
Warning: Electrical Shock Hazard.
WARNING: To avoid the risk of electric shock or burns, always connect the safety (or earth) ground before making any other connections.
WARNING: To reduce the risk of fire, electrical shock, or physical injury it is strongly recommended to fuse the voltage measurement inputs. Be sure to locate fuses as close to the source as possible.
WARNING: Replace fuse with the same type and rating to provide protection against risk of fire and shock hazards.
WARNING: In the event of repeated failure, do not
replace the fuse again as a repeated failure
indicates a defective condition that will not clear by replacing the fuse.
WARNING: Only qualified electrical personnel familiar with the construction and operation of this equipment and the hazards involved should install, adjust, operate, or service this equipment. Read and understand this manual and other applicable manuals in their entirety before proceeding. Failure to observe this precaution could result in severe bodily injury or loss of life.
This Data Sheet is published individually & also as a part of the SmartStack Supplement (SUP0246-05).
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.
Page 5
MAN0236-09 10 NOV 2006 PAGE 5 RTD000/100
For detailed installation and a handy checklist
that covers panel box layout requirements and minimum clearances, refer to the hardware manual of the controller you are using. (See the Additional References section in this document.)
All applicable codes and standards need to be followed in the installation of this product.
For I/O wiring (discrete), use the following wire type or equivalent: Belden 9918, 18 AWG or
larger.
Adhere to the following safety precautions whenever any type of connection is made to the module.
Connect the green safety (earth) ground first before making any other connections.
When connecting to electric circuits or pulse-initiating equipment, open their related breakers.
make connections to live power lines.
Do not
Make connections to the module first; then connect to the circuit to be monitored.
Route power wires in a safe manner in accordance with good practice and local codes.
Wear proper personal protective equipment including safety glasses and insulated gloves
when making connections to power circuits.
Ensure hands, shoes, and floor are dry before making any connection to a power line.
Make sure the unit is turned OFF before making connection to terminals. Make sure all
circuits are de-energized before making connections.
Before each use, inspect all cables for breaks or cracks in the insulation. Replace immediately if defective.
This Data Sheet is published individually & also as a part of the SmartStack Supplement (SUP0246-05).
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.
Page 6
PAGE 6 10 NOV 2006 MAN0236-09 RTD000/100
6 ADDITIONAL REFERENCES
The following information serves as a general listing of Horner controller products and other references of interest and their corresponding manuals numbers. Visit our website listed in the Technical Support section to obtain user documentation and updates.
Note: This list is not intended for users to determine which products are appropriate for their application; controller products differ in the features that they support. If assistance is required, see the Technical Support section in this document.
Controller Manual Number
XLE Series (e.g., HE-XExxx) MAN0805 QX Series (e.g., HE-QXxxx) MAN0798 NX Series (e.g., HE-NXxxx) MAN0781 LX Series (e.g., LX-xxx; also covers RCS116) MAN0755 Color Touch OCS (e.g., OCSxxx) MAN0465 OCS (Operator Control Station) (e.g., OCS1xx / 2xx; Graphic
OCS250) Remote Control Station (e.g., RCS2x0) MiniOCS (e.g., HE500OCSxxx, HE500RCSxxx) MAN0305
Other Useful References
CAN Networks MAN0799 Cscape Programming and Reference MAN0313 Wiring Accessories and Spare Parts Manual MAN0347 DeviceNet Implementation Wiring Accessories and Spare Parts Manual MAN0347
MAN0227
SUP0326
7 TECHNICAL SUPPORT
For assistance and manual up-dates, contact Technical Support at the following locations:
North America:
(317) 916-4274 www.heapg.com
Europe:
(+) 353-21-4321-266 www.horner-apg.com
This Data Sheet is published individually & also as a part of the SmartStack Supplement (SUP0246-05).
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.
Loading...