Horner APG HE-DIQ716 User Manual

Page 1
MAN0268-09 10 NOV 2006 PAGE 1 DIQ716
Mixed DC I/O Module
HE800DIQ716 / HE-DIQ716*
12/24 Vdc In, Positive/Negative Logic
This datasheet also covers products starting with IC300.
(16 Input Channels)
10–28 Vdc Out, Positive Logic
(12 Output Channels)
* HE- denotes plastic case.
1 SPECIFICATIONS
INPUT DIQ716 DIQ716
Inputs per Module 16 Input Characteristics Bidirectional Commons per Module Input Voltage Range 12–24 VDC
Peak Voltage Isolation
(Channel to Ground) ON Voltage Level 9 VDC /1 mA minimum ON to OFF Response 1 ms. OFF Voltage Level 3 VDC
3
35 VDC Max.
500 VDC
Input Impedance 10 K Ohms
Minimum ON Current 1 mA
Maximum OFF Current
OFF to ON Response 1 ms.
200 µA
OUTPUT DIQ716 DIQ716
Outputs per Module 12 Maximum Inrush Current 650 mA Commons per Module 1 Minimum Load None
Operating Voltage 10–28 VDC OFF to ON Response 1 ms. Output Type Sourcing / 10 K Pull-Down ON to OFF Response 1 ms. Peak Voltage 28 VDC Max. Output Characteristics Current Sourcing Maximum Load Current per channel
0.5 A Max.
Output Protection Short Circuit
General Specifications
Required Power (Steady State) Required Power (Inrush) Negligible Terminal Type Spring Clamp, Removable Relative Humidity 5–95% Non-condensing Weight 9 oz. (256 g) CE See Compliance Table at http://www.heapg.com/Support/compliance.htm
0.13 W (5.5 mA @ 24 VDC)
Operating Temperature
0°–60° Celsius
UL Operating Temperature Code T4;
See Compliance Table at http://www.heapg.com/Support/compliance.htm
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.
Page 2
PAGE 2 10 NOV 2006 MAN0268-09 DIQ716
2 WIRING
2.1 Input Wiring
12-24VDC
12-24VDC
12-24VDC
12-24VDC
12-24VDC
12-24VDC
I1
I1
I2
I2
I3
I3
I4
I4
I5
I5
I6
I6
I7
I7
I8
I8
C1
C1
19
19
I10
I10
I11
I11
I12
I12
C2
C2
I13
I13
I14
I14
I15
I15
I16
I16
C3
C3
001DIQ012
*
Pin
*
OCS Top View – Shows
Corresponding I/O Pin
Signal
DIQ716 INPUT
I1 Input 1 I2 Input 2 I3 Input 3 I4 Input 4 I5 Input 5 I6 Input 6 I7 Input 7 I8 Input 8
C1 Common 1 (Isolated)
I9 Input 9 I10 Input 10 I11 Input 11 I12 Input 12 C2 Common 2 (Isolated) I13 Input 13 I14 Input 14 I15 Input 15 I16 Input 16 C3 Common 3 (Isolated)
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.
Page 3
MAN0268-09 10 NOV 2006 PAGE 3 DIQ716
2.2 Output Wiring
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
C4
Q1
Q2
Q3
Q4
V1
C4
Q5
Q6
Q7
Q8
V2
C4
Q9
Q10
Q11
Q12
V3
NC
001DIQ011-R1
*
*
OCS Bottom View – Shows
Corresponding I/O Pin
Pin
Signal
DIQ716 OUTPUT
C4 Common Q1 Output 1 Q2 Output 2 Q3 Output 3 Q4 Output 4 V1 Load Power 1 C4 Common Q5 Output 5 Q6 Output 6 Q7 Output 7 Q8 Output 8 V2 Load Power 2 C4 Common
Q9 Output 9 Q10 Output 10 Q11 Output 11 Q12 Output 12
V3 Load Power
NC
No Connection
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.
Page 4
PAGE 4 10 NOV 2006 MAN0268-09 DIQ716
3 INTERNAL SCHEMATIC DRAWING
Field Side
I/O Connector
I1
SmartStack
C
VCC
To
Controller
I/O Connector
V+
SmartStack
From Controller
Field Side
Q
VC
Specification for transient voltage suppressors (transorbs) used on output circuitry is 33 VDC, 600 W.
4 CONFIGURATION
Note: The status of the I/O can be monitored in Cscape Software.
Preliminary configuration procedures that apply to SmartStack™ Modules are contained in the hardware manual of the controller you are using. Refer to the Additional References section in this data sheet for a listing of hardware manuals.
Selecting the I/O Map tab provides information about the I/O registers, which are assigned to a specific
SmartStack™ Module and where the module is located in the point map. The I/O Map is determined by the model number and location within the SmartStack™. The I/O Map is not
The Module Setup is used in applications where it is necessary to change the default states of the
outputs when the controller (e.g., OCS100) enters idle/stop mode. The default turns the outputs OFF when the controller enters idle/stop mode. By selecting the Module Setup tab, each output can be set to either turn ON, turn OFF or to hold the last state. Generally, most applications use the default settings.
Warning: The default turns the outputs OFF when the controller enters idle/stop mode. To
avoid injury of personnel or damages to equipment, exercise extreme caution when changing
the default setting using the Module Setup tab.
edited by the user.
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.
Page 5
MAN0268-09 10 NOV 2006 PAGE 5 DIQ716
5 INPUT / OUTPUT CHARACTERISTICS
Digital Input Chart
0.125(±15%) V-A
0
35VDC
Derating Chart for DIQ716
AMPS/CHANNELS
.5
.4 .3 .2 .1
0
0 10 20 30 40 50 60 °C 32 50 68 86 104 122 140 °F
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.
Page 6
PAGE 6 10 NOV 2006 MAN0268-09 DIQ716
6 INSTALLATION / SAFETY
Warning: Remove power from the OCS controller, CAN port, and any peripheral equipment
connected to this local system before adding or replacing this or any module.
Use the following wire type or equivalent:
Belden 8917
16 AWG or larger
For detailed installation and a handy checklist
that covers panel box layout requirements and minimum clearances, refer to the hardware manual of the controller you are using. (See the Additional References section in this document.).
When found on the product, the following symbols specify:
Warning: Consult user documentation.
Warning: Electrical Shock Hazard.
WARNING: To avoid the risk of electric shock or burns, always connect the safety (or earth)
ground before making any other connections.
WARNING: To reduce the risk of fire, electrical shock, or physical injury it is strongly
recommended to fuse the voltage measurement inputs. Be sure to locate fuses as close to the source as possible.
WARNING: Replace fuse with the same type and rating to provide protection against risk of fire
and shock hazards.
WARNING: In the event of repeated failure, do not replace the fuse again as a repeated failure
indicates a defective condition that will not clear by replacing the fuse.
WARNING: Only qualified electrical personnel familiar with the construction and operation of
this equipment and the hazards involved should install, adjust, operate, or service this equipment. Read and understand this manual and other applicable manuals in their entirety before proceeding. Failure to observe this precaution could result in severe bodily injury or loss of life.
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.
Page 7
MAN0268-09 10 NOV 2006 PAGE 7 DIQ716
For detailed installation and a handy checklist
that covers panel box layout requirements and minimum clearances, refer to the hardware manual of the controller you are using. (See the Additional References section in this document.):
All applicable codes and standards need to be followed in the installation of this product.
For I/O wiring (discrete), use the following wire type or equivalent: Belden 9918, 18 AWG or
larger.
Adhere to the following safety precautions whenever any type of connection is made to the module.
Connect the green safety (earth) ground first before making any other connections.
When connecting to electric circuits or pulse-initiating equipment, open their related breakers.
make connections to live power lines.
Do not
Make connections to the module first; then connect to the circuit to be monitored.
Route power wires in a safe manner in accordance with good practice and local codes.
Wear proper personal protective equipment including safety glasses and insulated gloves
when making connections to power circuits.
Ensure hands, shoes, and floor are dry before making any connection to a power line.
Make sure the unit is turned OFF before making connection to terminals. Make sure all
circuits are de-energized before making connections.
Before each use, inspect all cables for breaks or cracks in the insulation. Replace immediately if defective.
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.
Page 8
PAGE 8 10 NOV 2006 MAN0268-09 DIQ716
7 ADDITIONAL REFERENCES
The following information serves as a general listing of Horner controller products and other references of
interest and their corresponding manual numbers. Visit our website listed in the Technical Support section to obtain user documentation and updates.
Note: This list is not intended for users to determine which products are appropriate for their
application; controller products differ in the features that they support. If assistance is required,
see the Technical Support section in this document.
Controller Manual Number
XLE Series (e.g., HE-XExxx) MAN0805 QX Series (e.g., HE-QXxxx) MAN0798 NX Series (e.g., HE-NXxxx) MAN0781 LX Series (e.g., LX-xxx; also covers RCS116) MAN0755 Color Touch OCS (e.g., OCSxxx) MAN0465 OCS (Operator Control Station) (e.g., OCS1xx / 2xx; Graphic
OCS250) Remote Control Station (e.g., RCS2x0) MiniOCS (e.g., HE500OCSxxx, HE500RCSxxx) MAN0305
Other Useful References
CAN Networks MAN0799 Cscape Programming and Reference MAN0313 Wiring Accessories and Spare Parts Manual MAN0347 DeviceNet™ Implementation SUP0326 Wiring Accessories and Spare Parts Manual MAN0347
MAN0227
8 TECHNICAL SUPPORT
For assistance and manual up-dates, contact Technical Support at the following locations:
North America:+
(317) 916-4274
www.heapg.com
Europe:
(+) 353-21-4321-266
www.horner-apg.com
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.