This datasheet also covers products starting with IC300.
16 / 32 Channels
Positive or Negative Logic
* HE- denotes plastic case.
1 SPECIFICATIONS
DIM
310
Inputs per Module 16 32 Minimum ON Current 1 mA.
Commons per Module 3 6 Input Characteristics Bi-Directional
Input Voltage Range 12–24 VDC Maximum OFF Current
Peak Voltage 35 VDC Max. OFF to ON Response 1 ms.
Isolation Voltage
(Common to Common
and Common to
Channel)
Required Power
(Steady State)
Required Power
(Inrush)
ON Voltage Level 9 VDC Min.
OFF Voltage Level 3 VDC Max.
Input Impedance 10 K Ohms
CE
UL
500 VDC
(10 mA@24 VDC)
Same as Steady
See Compliance Table at http://www.heapg.com/Support/compliance.htm
DIM
410
24 W
State
ON to OFF Response 1 ms.
Terminal Type Spring Clamp, Removable
Relative Humidity 5–95% Non-condensing
Operating Temperature
DIM
310
200 µA
0°–60° Celsius
DIM
410
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.
Page 4
PAGE 4 10 NOV 2006 MAN0369-05
DIM310/410
3 INTERNAL WIRING
I/O Connector
Field Side
I1
SmartStack
VCC
C
To
Controller
4 CONFIGURATION
Preliminary configuration procedures that apply to SmartStack™ Modules are contained in the hardware
manual of the controller you are using. Refer to the Additional References section in this data sheet for a
listing of hardware manuals. Although the module has no user defined parameters, the I/O Map describes
which I/O registers are assigned to a specific SmartStack™ Module and where the module is located in
the point map. The I/O Map is determined by the model number and location within the SmartStack™.
The I/O Map is not
edited by the user.
5 INPUT CHARACTERISTICS
0 .125(±15%) V-A
0
Digital Input Chart
35VDC
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.
Page 5
MAN0369-05 10 NOV 2006 PAGE 5
DIM310/410
6 INSTALLATION / SAFETY
Warning: Remove power from the OCS controller, CAN port, and any peripheral equipment
connected to this local system before adding or replacing this or any module.
Use the following wire type or equivalent:
• Belden 8917
• 16 AWG or larger
For detailed installation and a handy checklist
that covers panel box layout requirements and minimum
clearances, refer to the hardware manual of the controller you are using. (See the Additional References
section in this document.).
When found on the product, the following symbols specify:
Warning: Consult user documentation.
Warning: Electrical Shock Hazard.
WARNING: To avoid the risk of electric shock or burns, always connect the safety (or earth)
ground before making any other connections.
WARNING: To reduce the risk of fire, electrical shock, or physical injury it is strongly
recommended to fuse the voltage measurement inputs. Be sure to locate fuses as close to the
source as possible.
WARNING: Replace fuse with the same type and rating to provide protection against risk of fire
and shock hazards.
WARNING: In the event of repeated failure, do not replace the fuse again as a repeated failure
indicates a defective condition that will not clear by replacing the fuse.
WARNING: Only qualified electrical personnel familiar with the construction and operation of
this equipment and the hazards involved should install, adjust, operate, or service this
equipment. Read and understand this manual and other applicable manuals in th eir entirety
before proceeding. Failure to observe this precaution could result in severe bodily injury or loss
of life.
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.
Page 6
PAGE 6 10 NOV 2006 MAN0369-05
DIM310/410
For detailed installation and a handy checklist
that covers panel box layout requirements and minimum
clearances, refer to the hardware manual of the controller you are using. (See the Additional References
section in this document.):
• All applicable codes and standards need to be followed in the installation of this product.
• For I/O wiring (discrete), use the following wire type or equivalent: Belden 9918, 18 AWG or
larger.
Adhere to the following safety precautions whenever any type of connection is made to the module.
• Connect the green safety (earth) ground first before making any other connections.
• When connecting to electric circuits or pulse-initiating equipment, open their related breakers.
make connections to live power lines.
Do not
• Make connections to the module first; then connect to the circuit to be monitored.
• Route power wires in a safe manner in accordance with good practice and local codes.
• Wear proper personal protective equipment including safety glasses an d insulated gloves
when making connections to power circuits.
• Ensure hands, shoes, and floor are dry before making any connection to a power line.
• Make sure the unit is turned OFF before making connection to terminals. Make sure all
circuits are de-energized before making connections.
•Before each use, inspect all cables for breaks or cra cks in the in sulation. Replace
immediately if defective.
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.
Page 7
MAN0369-05 10 NOV 2006 PAGE 7
DIM310/410
7 ADDITIONAL REFERENCES
The following information serves as a general listing of Horner controller products and other references of
interest and their corresponding manual numbers. Visit our website listed in the Technical Support section
to obtain user documentation and updates.
Note: This list is not intended for users to determine which products are appropriate for their
application; controller products differ in the features that they support. If assistance is required,
see the Technical Support section in this document.
Controller Manual Number
XLE Series (e.g., HE-XExxx) MAN0805
QX Series (e.g., HE-QXxxx) MAN0798
NX Series (e.g., HE-NXxxx) MAN0781
LX Series (e.g., LX-xxx; also covers RCS116) MAN0755
Color Touch OCS (e.g., OCSxxx) MAN0465
OCS (Operator Control Station) (e.g., OCS1xx / 2xx; Graphic
OCS250)
Remote Control Station (e.g., RCS2x0)
MiniOCS (e.g., HE500OCSxxx, HE500RCSxxx) MAN0305
Other Useful References
CAN Networks MAN0799
Cscape Programming and Reference MAN0313
Wiring Accessories and Spare Parts Manual MAN0347
DeviceNet™ Implementation SUP0326
Wiring Accessories and Spare Parts Manual MAN0347
MAN0227
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.
Page 8
PAGE 8 10 NOV 2006 MAN0369-05
DIM310/410
8 TECHNICAL SUPPORT
For assistance and manual up-dates, contact Technical Support at the following locations:
North America:+
(317) 916-4274
www.heapg.com
Europe:
(+) 353-21-4321-266
www.horner-apg.com
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.