![](/html/5b/5be7/5be7acf14a8dcc87c9b82a02fd758d4e272aa73efc23e6d50070a5fc46fdceac/bg1.png)
MAN0453-04 10 NOV 2006 PAGE 1
DAC106
4–20 mA Sourcing
Analog Output Module
HE800DAC106 /
This datasheet also covers products starting with IC300.
HE-DAC106*
14-Bit Resolution
* HE- denotes plastic case.
1 SPECIFICATIONS
Number of
Channels
Output Ranges
(including overrange)
Resolution
Peak Output
Voltage
PLC Update Rate Set by PLC Scan
Current Output
Resolution
Required Power
(Steady State)
Required Power
(Inrush)
Maximum Error at
25°C
DAC106
0–20.47 mA;
10 VDC Compliance
14-Bits
10 VDC Max.
Rate
14-Bits
3.3 W
(139 mA @24 VDC)
Negligible
0.05% Full Scale
4
Maximum Loop Resistance
Additional error for
temperatures other than
25°C
Analog Outputs;
Output Points Required
Operating Temperature
External Power Supply None
Terminal Type
Weight 9.5 oz. (270 g)
CE
UL
See Compliance Table at
http://www.heapg.com/Support/compliance.
htm
DAC106
500 Ω
0.005% / °C
4
0°–60° Celsius
Spring Clamp,
Removable
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.
![](/html/5b/5be7/5be7acf14a8dcc87c9b82a02fd758d4e272aa73efc23e6d50070a5fc46fdceac/bg2.png)
PAGE 2 10 NOV 2006 MAN0453-04
DAC106
2 WIRING
*
OCS Bottom View – Shows
Corresponding I/O Pin
Signal Pin
DAC106
Channel 1+ 1+
Common 1-
Shield
Channel 2+ 2+
Common 2-
Shield
Channel 3+ 3+
Common 3-
Shield
Channel 4+ 4+
Common 4-
Shield
LOADLOAD
1+
1-
*
LOAD
LOAD
LOAD
2+
2-
3+
3-
4+
4-
001DAC004
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.
![](/html/5b/5be7/5be7acf14a8dcc87c9b82a02fd758d4e272aa73efc23e6d50070a5fc46fdceac/bg3.png)
MAN0453-04 10 NOV 2006 PAGE 3
DAC106
3 INTERNAL CIRCUIT SCHEMATIC
Field
Side
I/O Connector
1+
SmartStack
Analog Out
+
-
From
Controller
1-
Specification for transient voltage suppressors (transorbs) used on output circuitry is 15 V, 300 W.
4 CONFIGURATION
Note: The status of the I/O can be monitored in Cscape Software.
Preliminary configuration procedures that apply to SmartStack™ Modules are contained in the hardware
manual of the controller you are using. Refer to the Additional References section in this data sheet for a
listing of hardware manuals.
Selecting the I/O Map tab provides information about the I/O registers, which are assigned to a specific
SmartStack™ Module and where the module is located in the point map. The I/O Map is determined by
the model number and location within the SmartStack™. The I/O Map is not
edited by the user.
The Module Setup is used in applications where it is necessary to change the default values of the
outputs when the controller (e.g., OCS100) enters idle/stop mode. The default sets the output values to
zero when the controller enters idle/stop mode. By selecting the Module Setup tab, each output can be
set to a specific value or hold the last value. Generally, most applications use the default settings.
Module Setup Tab
a) Output range for each channel may be selected independently.
b) Filter Constant sets the level of digital filtering according to the following chart.
Warning: The default sets the output values to zero when the controller enters idle/stop mode.
To avoid injury of personnel or damages to equipment, exercise extreme caution when
changing the default setting using the Module Setup tab.
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.