1 SPECIFICATIONS
ADC920 ADC920
Input Ranges (including over-range)
Thermistor
(1/10° resolution)
Current Voltage
Resolution 12-Bit Terminal Type Spring Clamp, Removable Maximum Error at 25°C Conversion Time (PLC Update Rate) Additional error for temperatures other than 25°C Required Power (Steady State) Required Power (Inrush) Maximum Over­Current External Power Supply CE UL
Set by PLC Scan Time
0.19 W (8 mA @ 24 VDC)
See Compliance Table at http://www.heapg.com/Support/compliance.htm
12
-37–115°C
-35–240°F
0–20.47 mA
0–5.11 VDC
0.1% Full Scale
0.01% / C°
Negligible
35 mA
None
Converter Type
Input Impedance
Thermistor
Current Voltage
Operating Temperature
Analog Inputs Input Points Required
Relative Humidity 5–95% Non-condensing
Weight 9 oz. (256 g)
Successive Approximation
< 12 VDC, Clamped @
12 VDC, 35 mA Max.
Continuous
10 K
250
1 Mega
0° – 60° Celsius
12
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.
PAGE 2 10 NOV 2006 MAN0317-09
2
ADC920
2 WIRING
V
20
ma
20
ma
5 V
5 V
T
T
20
ma
20
ma
5 V
5 V
T
T
I1 I2 I3
I4 I5 I6 I7 I8 I9
I10
I11
I12
C1 C1
*
C2 C2 C3 C3
C3
001ADC003-R2
The jumper block indicates the correct jumper positions for the wiring shown.
For more information, refer to
Section 4.2 (b), Hardware
Configuration in this document.
CH 1
CH 2
CH 3
CH 4
CH 5
CH 6
CH 7
CH 8
CH 9
CH 10
CH 11
CH 12
OCS Bottom View – Shows
*
Corresponding I/O Pin
Pin ADC920
I1*
I2 Input 2 I3 Input 3 I4 Input 4 I5 Input 5 I6 Input 6 I7 Input 7 I8 Input 8
I9 Input 9 I10 Input 10 I11 Input 11 I12 Input 12 C1 C1 C2 C2 C3 C3 C3
Input 1
Thermistor
Common
0 – 5VDC
Common
20mA
Common
3 INTERNAL CIRCUIT SCHEMATIC
50Ω
SmartStack
10K
V Ref
To Controller
Field Side
I/O Connector
Com
1+
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.
MAN0317-09 10 NOV 2006 PAGE 3 ADC920
4 CONFIGURATION
Note: The status of the I/O can be monitored in Cscape Software.
4.1 Software Configuration
Preliminary configuration procedures that apply to SmartStack Modules are contained in the hardware
manual of the controller you are using. Refer to the Additional References section in this data sheet for
a listing of hardware manuals.
I/O Map Tab
The I/O Map describes which I/O registers are assigned to a specific SmartStack Module and where the module is located in the point map. The I/O Map is determined by the model number and location within the SmartStack. The I/O Map is not
Module Setup Tab
edited by the user.
a) Input range for each channel may be selected independently. b) Filter Constant sets the level of digital filtering according to the following chart. c) In addition to configuring the module setup, the hardware must be jumpered to select the
appropriate range for each channel.
1
2 3 4 5 60 7
Filter Constant
%Complete [ ]
100
90 80 70 60 50 40 30 20 10
0
60
10040 8020
Scans0
Digital Filtering: The illustration above demonstrates the effect of digital filtering (set with Filter Constant)
on module response to a temperature change.
4.2 Hardware Configuration
The inputs are referenced to the bus common. Each of the inputs can be jumper-selected for one of the three input types. Behind each of the input pins is a corresponding group of four jumper pins with a programming plug.
a) To select 5V input: Connect the two pins nearest the connector. b) To select thermistor input: Connect the two pins nearest input 1. c) To select 20mA input: Connect the two pins nearest input 12.
Note: It is also necessary to specify the input channel type in Cscape along with the
temperature format.
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.
PAGE 4 10 NOV 2006 MAN0317-09
ADC920
The ADC920 supports Kele Engineering Precon Type III, 10 K thermistors. It also directly supports the following 10 K (Beta=3574) thermistors from Yellow Springs Instruments (YSI).
44006 46006 44106 46031
44406 46041 44031 44907 45006 44908
Thermistor Curve for PreCon TYPE III (Model 3)
Temperature
°F
-35
-30
-25
-20
-15
-10
-5 0 5
10 15 20 25 30 35 40 45 50 55
Resistance Temperature
°F
203.6 K
173.6 K
148.3 K
127.1 K
109.2 K
94.07 K
81.23 K
70.32 K
61.02 K
53.07 K
46.27 K
40.42 K
35.39 K
31.06 K
27.31 K
24.06 K
21.24 K
18.79 K
16.65 K
60 65 70 75 80 85 90
95 100 105 110 115 120 125 130 135 140 145 150
Resistance Temperature
°F
14.78 K
13.15 K
11.72 K
10.46 K
9.354 K
8.378 K
7.516 K
6.754 K
6.078 K
5.479 K
4.947 K
4.472 K
4.049 K
3.671 K
3.333 K
3.031 K
2.759 K
2.515 K
2.296 K
155 160 165 170 175 180 185 190 195 200 205 210 215 220 225 230 235 240
Resistance
2.098 K
1.920 K
1.759 K
1.614 K
1.482 K
1.362 K
1.254 K
1.156 K
1.066 K
984.0
909.8
841.9
779.8
723.0
671.0
623.3
579.5
539.4
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.
MAN0317-09 10 NOV 2006 PAGE 5 ADC920
5 INPUT CONVERSION FACTOR
The following table describes how real-world inputs are scaled into the controller. Given a known input voltage, the data value is configured by using the conversion factor from the table. The following formula is used:
Data = Voltage In (Vin) / Conversion Factor
Example: The user selects avoltage range of 0 to +5 VDC:
1) The known input voltage is 3 VDC.
2) Using the table, the conversion factor for the voltage range of 0 to +5 VDC is 0.00015625.
3) To determine the data value, the formula is used: Data = Vin / Conversion Factor 19200 = 3 VDC / 0.00015625
Conversion of Real-World Inputs into Controller
Selected Voltage
0 to +5.00 VDC
Range
0 to +20 mA
°C
°F
Voltage In (Vin) VDC Data Out Conversion Factor
+5.11 32704 +5.00 32000
0 0 NA NA NA NA
+20.47 32736 +20.00 32000
0 0 NA NA NA NA
+115 1150
0 0
-37 -370
+240 2400
0 0
-35 -350
0.00015625
0.000625
0.1
0.1
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.
PAGE 6 10 NOV 2006 MAN0317-09 ADC920
6 INSTALLATION / SAFETY
Warning: Remove power from the OCS controller, CAN port, and any peripheral equipment
connected to this local system before adding or replacing this or any module.
a) All applicable codes and standards should be followed in the installation of this product. b) Shielded, twisted-pair wiring should be used for best performance. c) Shields should be tied directly to the ground block within the panel. d) Use the following wire type or equivalent:
Belden 8441
For detailed installation and a handy checklist clearances, refer to the hardware manual of the controller you are using. (See the Additional References section in this document.).
When found on the product, the following symbols specify:
that covers panel box layout requirements and minimum
Warning: Consult user documentation.
Warning: Electrical Shock Hazard.
WARNING: To avoid the risk of electric shock or burns, always connect the safety (or earth)
ground before making any other connections.
WARNING: To reduce the risk of fire, electrical shock, or physical injury it is strongly
recommended to fuse the voltage measurement inputs. Be sure to locate fuses as close to the source as possible.
WARNING: Replace fuse with the same type and rating to provide protection against risk of fire
and shock hazards.
WARNING: In the event of repeated failure, do not replace the fuse again as a repeated failure
indicates a defective condition that will not clear by replacing the fuse.
WARNING: Only qualified electrical personnel familiar with the construction and operation of
this equipment and the hazards involved should install, adjust, operate, or service this equipment. Read and understand this manual and other applicable manuals in their entirety before proceeding. Failure to observe this precaution could result in severe bodily injury or loss of life.
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.
MAN0317-09 10 NOV 2006 PAGE 7 ADC920
For detailed installation and a handy checklist
that covers panel box layout requirements and minimum clearances, refer to the hardware manual of the controller you are using. (See the Additional References section in this document.):
All applicable codes and standards need to be followed in the installation of this product.
For I/O wiring (discrete), use the following wire type or equivalent: Belden 9918, 18 AWG or
larger.
Adhere to the following safety precautions whenever any type of connection is made to the module.
Connect the green safety (earth) ground first before making any other connections.
When connecting to electric circuits or pulse-initiating equipment, open their related breakers.
make connections to live power lines.
Do not
Make connections to the module first; then connect to the circuit to be monitored.
Route power wires in a safe manner in accordance with good practice and local codes.
Wear proper personal protective equipment including safety glasses and insulated gloves
when making connections to power circuits.
Ensure hands, shoes, and floor are dry before making any connection to a power line.
Make sure the unit is turned OFF before making connection to terminals. Make sure all
circuits are de-energized before making connections.
Before each use, inspect all cables for breaks or cracks in the insulation. Replace immediately if defective.
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.
PAGE 8 10 NOV 2006 MAN0317-09 ADC920
7 ADDITIONAL REFERENCES
The following information serves as a general listing of Horner controller products and other references of
interest and their corresponding manual numbers. Visit our website listed in the Technical Support section to obtain user documentation and updates.
Note: This list is not intended for users to determine which products are appropriate for their
application; controller products differ in the features that they support. If assistance is required,
see the Technical Support section in this document.
Controller Manual Number
XLE Series (e.g., HE-XExxx) MAN0805 QX Series (e.g., HE-QXxxx) MAN0798 NX Series (e.g., HE-NXxxx) MAN0781 LX Series (e.g., LX-xxx; also covers RCS116) MAN0755 Color Touch OCS (e.g., OCSxxx) MAN0465 OCS (Operator Control Station) (e.g., OCS1xx / 2xx; Graphic OCS250) Remote Control Station (e.g., RCS2x0) MiniOCS (e.g., HE500OCSxxx, HE500RCSxxx) MAN0305
Other Useful References
CAN Networks MAN0799 Cscape Programming and Reference MAN0313 Wiring Accessories and Spare Parts Manual MAN0347 DeviceNet™ Implementation SUP0326 Wiring Accessories and Spare Parts Manual MAN0347