Horner APG HE-ADC120 User Manual

MAN0235-09 10 NOV 2006 PAGE 1 ADC020/120
4-20 mA Analog Input
Module
HE800ADC020 / HE800ADC120
HE-ADC020* / HE-ADC120*
This datasheet also covers products starting with IC300.
12-Bit Resolution
* HE-denotes plastic case.
1 SPECIFICATIONS
Input Impedance
Required Power (Steady State) Required Power (Inrush) Maximum Over­Current External Power Supply CE UL
ADC020 ADC120 ADC020 ADC120
2 4
Nominal: 0-20.47 mA,
±20.47 mA,
0.05% Full Scale
100 < 12 VDC, Clamped @
12 VDC, 35 mA Max. Continuous
0.09 W (4.1 mA @ 24 VDC)
Negligible
35 mA
None
See Compliance Table at http://www.heapg.com/Support/compliance.htm
Converter Type
Conversion Time (PLC Update Rate)
Additional error for
temperatures other than 25°C
Analog Inputs
Input Points Required
Operating
Temperature
Relative Humidity 5–95% Non-condensing
Weight 9 oz. (256 g)
Successive Approximation
Set by PLC Scan Time
0.005% / °C
2 4
0° to 60° Celsius
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.
PAGE 2 10 NOV 2006 MAN0235-09
1
ADC020/120
2 WIRING
4-20mA
TRANSMITTER
4-20mA
TRANSMITTER
4-20mA
TRANSMITTER
4-20mA
TRANSMITTER
LOOP
POWER
LOOP
POWER
LOOP
POWER
LOOP
POWER
1+
1-
2+
2-
3+
3-
4+
4-
001ADC002
3 INTERNAL CIRCUIT SCHEMATIC
*
*
OCS Bottom View – Shows
Corresponding I/O Pin
Pin # ADC120 ADC020
1+ Channel 1+ Channel 1+
1- Common Common
Shield Shield
2+ Channel 2+ Channel 2+
2- Common Common
Shield Shield
3+ Channel 3+
3- Common
Shield
4+ Channel 4+
4- Common
Shield
Field Side
I/O Connector
1+
Gnd
1- Shield
SmartStack
00Ω
To Controller
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.
MAN0235-09 10 NOV 2006 PAGE 3 ADC020/120
4 CONFIGURATION
Note: The status of the I/O can be monitored in Cscape Software.
Preliminary configuration procedures that apply to SmartStack Modules are contained in the hardware manual of the controller you are using. Refer to the Additional References section in this data sheet for a listing of hardware manuals.
Selecting the I/O Map tab provides information about the I/O registers, which are assigned to a specific
SmartStack™ Module and where the module is located in the point map. The I/O Map is determined by the model number and location within the SmartStack™. The I/O Map is not
edited by the user.
Module Setup Tab
a) Input range for each channel may be selected independently. b) Filter Constant sets the level of digital filtering according to the following chart.
1
2 3 4 5 60 7
Filter Constant
100
90 80 70 60 50 40 30 20
%Complete [ ]
10
0
60
10040 8020
Scans0
Digital Filtering: The illustration above demonstrates the effect of digital filtering (set with Filter Constant)
on module response to a temperature change.
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.
Loading...
+ 5 hidden pages