MAN0938-02-EN Specifications / Installation
__________________________________________________________________________________________________________________________________________________________________
1/3/2011 Page 1 of 1
1 Specifications
Accuracy
Temp. Coefficient
Screw Type, Removable 11-posn
Optional Spring-clamp Plug
20mm x 90mm x 60mm
0.79” x 3.54” x 2.36”
Weight
2 Wiring – I/O
3 Reported Data & Configuration Data
Data is reported to the OCS in signed integer format, with a single implied decimal place. For a
temperature of +762.4°C, with a data range configured for °C, the reported data value is 7624
decimal. For a temperature of -12.1°F, with a data range configured for °F, the reported data value
is -121 decimal.
The SmartRail THM100 is configured using Cscape (9.1 or later). The following parameters are
configurable for the THM100:
Cscape Configuration Data – Selectable per channel
4 Installation / safety
a. All applicable codes and standards should be followed in the installation of this product.
b. Shielded, thermocouple extension wiring of the proper type should be used for best
performance.
c. Shields should be terminated at one end only, at the end providing the best noise shunting.
For detailed installation and a handy checklist that covers panel box layout requirements and
minimum clearances, refer to the hardware manual of the controller you are using.
When found on the product, the following symbols specify:
7 Technical Support
Technical Support at the following locations:
North America:
Tel: 317 916-4274
Fax: 317 639-4279
Web: http://www.heapg.com
Email: techsppt@heapg.com
Europe:
Tel: +353-21-4321266
Fax: +353-21-4321826
Web: http://www.horner-apg.com
Email: tech.support@horner-apg.com
THM100 LED Status Indication
Meaning
ON = Normal Operation
FLASH = I/O Error
OFF = No Power or I/O Error
OFF = Normal Operation
ALARM
FLASH = Open Circuit Detected
SmartRail
Thermocouple Input Module (Type J, K, T, R)
HE599THM100
0.1°C Resolution, typical
No part of this publication may be reproduced without the prior agreement and written
permission of Horner APG, Inc. Information in this document is subject to change without
notice.
Warning: Remove power from the OCS controller and any peripheral equipment connected
to this local system before adding or replacing this or any module.
Warning: Consult
user documentation.
Warning: Electrical
Shock Hazard.
+
-
24VDC
N.C.
-
+
-
+
-
+
-
+
1
2
3
4
CH
+
_
24VDC @ 100mA
External Power
SHIELD GROUNDED
AT O NE EN D O NLY
+
_
+
_
+
_
+
_
Prefer Spring-clamps?
Optional Spring-clamp style plugs are
available as economical wiring accessories.
See specification table for part number(s).
Representative 10-position plug shown.