MAN0937-02-EN Specifications / Installation
__________________________________________________________________________________________________________________________________________________________________
1/3/2011 Page 1 of 1
1 Specifications
4
American (α=0.00392)
Japanese Std (α=0.003916)
Screw Type, Removable 15-posn
Optional Spring-clamp Plug
20mm x 90mm x 60mm
0.79” x 3.54” x 2.36”
Weight
CE, UL & C-UL
*requires a user defined function block for Cscape
(available for free download)
2 Wiring – I/O
3 Reported Data & Configuration Data
Data is reported to the OCS in signed integer format, with a single implied decimal place. For a
temperature of +457.4°C, with a data range configured for °C, the reported data value is 4574
decimal. For a temperature of -12.1°F, with a data range configured for °F, the reported data value
is -121 decimal.
The SmartRail RTD100 is configured using Cscape (9.1 or later). The following parameters are
configurable for the RTD100:
Cscape Configuration Data – Selectable per channel
Disable
American Std (α=0.00392)
Japanese Std (α=0.003916)
°C
If you are using the common European (DIN) standard RTDs, configure the module for the American
Standard type. An extra calculation is then required in logic to convert the value reported by the
RTD100 into an accurate value. This calculation may be performed using a user defined function
block inserted into the Cscape logic program. This function block (DIN_RTD_FUN) is available for
download from the Horner APG web site. This function block performs the following calculation.
Y = 4.70573965141697e-06(x2) + 1.01922059169856e+00(x) + 1.28999644570005e-02
where Y = DIN temperature value and
x = American Standard temperature value
4 Installation / safety
a. All applicable codes and standards should be followed in the installation of this product.
b. Shielded, twisted pair wiring of the proper type should be used for best performance.
Maximum lead-wire resistance should be less than 10Ω.
c. Shields should be terminated at one end only, at the end providing the best noise shunting.
For detailed installation and a handy checklist that covers panel box layout requirements and
minimum clearances, refer to the hardware manual of the controller you are using.
When found on the product, the following symbols specify:
5 Technical Support
Technical Support at the following locations:
North America:
Tel: 317 916-4274
Fax: 317 639-4279
Web: http://www.heapg.com
Email: techsppt@heapg.com
Europe:
Tel: +353-21-4321266
Fax: +353-21-4321826
Web: http://www.horner-apg.com
Email: tech.support@horner-apg.com
RTD100 LED Status Indication
Meaning
ON = Normal Operation
FLASH = I/O Error
OFF = No Power or I/O Error
ON = Normal Operation
FLASH = Open Circuit Detected
SmartRail
RTD Input Module (Pt-100)
HE599RTD100
0.1°C Resolution, typical
No part of this publication may be reproduced without the prior agreement and written
permission of Horner APG, Inc. Information in this document is subject to change without
notice.
Warning: Remove power from the OCS controller and any peripheral equipment connected
to this local system before adding or replacing this or any module.
Warning: Consult
user documentation.
Warning: Electrical
Shock Hazard.
+
-
24VDC
C
S
E
N.C.
C
H
4
C
H
3
C
S
E
C
S
E
C
S
E
C
H
2
C
H
1
+
_
24VDC @ 100mA
External Power
SHIELD GROUNDED
AT O NE EN D O NLY
E
S
C
E
S
C
E
S
C
E
S
C
Prefer Spring-clamps?
Optional Spring-clamp style plugs are
available as economical wiring accessories.
See specification table for part number(s).
Representative 10-position plug shown.