Horner APG HE599MIX116 User Manual

Page 1
MAN0936-02-EN Specifications / Installation
__________________________________________________________________________________________________________________________________________________________________
1/3/2011 Page 1 of 1
1 Specifications
Number of Channels
2
Input Ranges
4-20mA, 0-20mA, 0-5V, 0-10V
Absolute Max. Inputs
±15V, ±25mA
Resolution
12-Bit (4uA,5uA,1.25mV, 2.5mV
Input Impedance
1MΩ (voltage), 250Ω (current)
Accuracy
< ±0.5%
Conversion Time
1mS/ch
Number of Channels
2
Output Ranges
0-10V, 4-20mA, 0-20mA
Absolute Max. Outputs
±15V, ±25mA
Resolution
12-Bit (2.5mV, 4uA, 5uA)
Maximum Load
>2kΩ (voltage), <510Ω (current)
Accuracy
< ±0.5%
Conversion Time
1mS/ch
Isolation
Photocoupler (Input/Power)
Backplane Power Consumed
50mA @ 5V
External Power Required
62mA @ 24V (+/-10%)
Terminal Type
Screw Type, Removable 11-posn
Optional Spring-clamp Plug
HE599TRM011
Storage Temp.
-25° to 70° Celsius
Operating Temp.
-0° to 55° Celsius
Relative Humidity
5 to 95% Non-condensing
Dimensions WxHxD
20mm x 90mm x 60mm
0.79” x 3.54” x 2.36” Weight
73g (2.6 oz.)
CE & UL Compliance
CE, UL & C-UL
2 Wiring – I/O
3 Configuration DATA
The SmartRail MIX116 features a dip switch on the front of the unit for selecting voltage (0-10V) or current (4-20mA or 0-20mA) on a per channel basis. In addition to the physical dip switch, Cscape (9.1 or later) must be used for software configuration as well. The following parameters are configurable in Cscape for the MIX116:
Cscape Configuration Data – Selectable per channel
Parameter
Selections
4-20mA 0-20mA
0-5V
Input/Output Range
0-10V Hold Last State Go to Minimum
Go to Mid-range
Hold Last State (Outputs)
Go to Maximum
4 Installation / safety
a. All applicable codes and standards should be followed in the installation of this product. b. Shielded, twisted-pair wiring should be used for best performance. c. Shields should be grounded at one end only, preferably at the end providing the best noise shunting. d. Use the following wire type or equivalent: Belden 8441.
For detailed installation and a handy checklist that covers panel box layout requirements and minimum clearances, refer to the hardware manual of the controller you are using.
When found on the product, the following symbols specify:
7 Technical Support
Technical Support at the following locations:
North America:
Tel: 317 916-4274 Fax: 317 639-4279 Web: http://www.heapg.com Email: techsppt@heapg.com
Europe:
Tel: +353-21-4321266 Fax: +353-21-4321826 Web: http://www.horner-apg.com Email: tech.support@horner-apg.com
MIX116 LED Status Indication
LED 1
LED 2
Meaning (same for both LEDs) ON = Normal Operation FLASH = I/O Error
IN OK
OUT OK
OFF = No Power or I/O Error
SmartRail
0-10V, 4-20mA Analog Input/Output Module
HE599MIX116
12-Bit Resolution
No part of this publication may be reproduced without the prior agreement and written permission of Horner APG, Inc. Information in this document is subject to change without notice.
Warning: Remove power from the OCS controller and any peripheral equipment connected to this local system before adding or replacing this or any module.
Warning: Consult user documentation.
Warning: Electrical Shock Hazard.
+
-
24VDC
N.C.
-
CH2
+
-
CH1
+
-
CH2
+
-
CH1
+
CH1
CH2
CH1
CH2
OUTPUT
INPUT
INPUT
OUTPUT
VI
24VDC @ 130mA External Power
SHIELD GROUNDED AT
ONE END ONLY
+
-
LOOP PWR
+
-
+
-
4-20mA TRANSMITTER
0-20mA <510 OHM LOAD
0-10V >2k OHM LOAD
+
-
0-10VDC
+
-
LOAD
+
-
LOAD
Prefer Spring-clamps?
Optional Spring-clamp style plugs are available as economical wiring accessories. See specification table for part number(s). Representative 10-position plug shown.