Horner APG HE599ADC170 User Manual

MAN0931-02-EN Specifications / Installation
__________________________________________________________________________________________________________________________________________________________________
1/3/2011 Page 1 of 1
1 Specifications
ADC170
Number of Channels
4
Input Ranges
0-10V, 4-20mA, 0-20mA
Absolute Max. Inputs
+/-15V, +/-30mA Resolution
12-Bit (2.5mV, 4uA, 5uA)
Input Impedance
1MΩ (voltage), 250Ω (current)
Accuracy
< +/-0.5%
Isolation
Photocoupler (Input/Power)
Conversion Time
1.5mS/ch
Backplane Power Consumed
50mA @ 5V
External Power Required
62mA @ 24V (+/-10%)
Terminal Type
Screw Type, Removable 11-posn
Optional Spring-clamp Plug
HE599TRM011
Storage Temp.
-25° to 70° Celsius
Operating Temp.
-0° to 55° Celsius
Relative Humidity
5 to 95% Non-condensing
Dimensions WxHxD
20mm x 90mm x 60mm
0.79” x 3.54” x 2.36” Weight
67g (2.4 oz.)
CE & UL Compliance
CE, UL & C-UL
2 Wiring – I/O
3 Configuration DATA
The SmartRail ADC170 features a dip switch on the front of the unit for selecting voltage (0-10V) or current (4-20mA or 0-20mA) on a per channel basis. In addition to the physical dip switch, Cscape (9.1 or later) must be used for software configuration as well. The following parameters are configurable in Cscape for the ADC170:
Cscape Configuration Data – Selectable per channel
Parameter
Selections
Enable
Channel Enable
Disable 4-20mA 0-20mA
Data Type
0-10V
0-4000
-2000 to +2000
0 to 1000 (for 4-20mA type)
Data Range
0 to 1000 (0-20mA or 0-10V type)
4 Installation / safety
a. All applicable codes and standards should be followed in the installation of this product. b. Shielded, twisted-pair wiring should be used for best performance. c. Shields should be grounded at one end only, preferably at the end providing the best noise shunting. d. Use the following wire type or equivalent: Belden 8441.
For detailed installation and a handy checklist that covers panel box layout requirements and minimum clearances, refer to the hardware manual of the controller you are using.
When found on the product, the following symbols specify:
7 Technical Support
Technical Support at the following locations:
North America:
Tel: 317 916-4274 Fax: 317 639-4279 Web: http://www.heapg.com Email: techsppt@heapg.com
Europe:
Tel: +353-21-4321266 Fax: +353-21-4321826 Web: http://www.horner-apg.com Email: tech.support@horner-apg.com
ADC170 LED Status Indication
LED
Meaning ON = Normal Operation FLASH = I/O Error
RUN
OFF = No Power or I/O Error
SmartRail
0-10V, 4-20mA Analog Input Module
HE599ADC170
12-Bit Resolution
No part of this publication may be reproduced without the prior agreement and written permission of Horner APG, Inc. Information in this document is subject to change without notice.
Warning: Remove power from the OCS controller and any peripheral equipment connected to this local system before adding or replacing this or any module.
Warning: Consult user documentation.
Warning: Electrical Shock Hazard.
+
-
24VDC
N.C.
-
CH4
+
-
CH3
+
-
CH2
+
-
CH1
+
CH1
CH2
CH3
CH4
VI
24VDC @ 62mA External Power
SHIELD GROUNDED AT ONE E ND ON LY
0-10V
0-10V
+
+
+
-
-
-
LOOP POWER
4-20ma
+
-
+
-
LOOP POWER
4-20ma
+
-
+
-
Prefer Spring-clamps?