Inputs per Module 16 Input Characteristics Bidirectional
Isolated Commons
per Module
Input Voltage Range 12-24VDC Minimum ON Current 1mA
Peak Voltage
Isolation
(Between isolated
commons and
Ground)
ON Voltage Level 9VDC
OFF Voltage Level 3VDC
ANALOG OUTPUT
Number of Channels
Output Ranges
Load limits
Output Compliance
Voltage for ±20mA
DIGITAL OUTPUT
Outputs per Module
Load Power Circuits
per Module
Operating Voltage 10 - 30VDC OFF to ON Response 1ms.
Output Type Sourcing / 10K Pull-Down ON to OFF Response 1ms.
Peak Voltage 30VDC Max. Output Characteristics Current Sourcing
Maximum Load
Current per Output
±20 mA 100Ω , Clamped
@ 12VDC, 35mA Max.
±20mA Sourcing
Clamped @ 12VDC
±10V: 2000Ω MIN
±20mA: 470Ω MAX
Analog Inputs
Input Points Required
±10 VDC
±20 mA
Continuous
0.3%
3
35VDC Max.
500VDC
2
±10VDC
±10VDC
16
2
0.5A Max.
Conversion Time
(PLC Update Rate)
Converter Type
Additional error for
temperatures other than
25°C
Maximum Over-Current 35mA
Input Impedance 10K Ohms
Maximum OFF Current
OFF to ON Response 1ms.
ON to OFF Response 1ms.
Analog Outputs;
Output Points Required
Resolution 12 Bit
Additional error for
temperatures other than
25°C
Maximum Error at 25°C
Maximum Inrush Current
per channel
Minimum Load Current None
Output Protection Short Circuit
4
Set by PLC Scan Time
Successive
Approximation
0.01% / °C
200µA
2
0.01% / °C
0.3%
650mA
MAN0504-02
Information is subject to change without notice. Cscape is a trademark of Horner APG, LLC.
Page 2
PAGE 2 23 MAR 2003 MAN0504-02
OCX404
General Specifications
Required Power
(Steady State)
Required Power (Inrush)
Relative Humidity 5 to 95% Non-condensing Weight 21.5 oz. (610 g)
4.8W (200mA @24VDC)
30A @ 24VDC for 250µs.
Operating
Temperature
Terminal Type Spring Clamp, Removable
Information is subject to change without notice. Cscape is a trademark of Horner APG, LLC.
Page 4
PAGE 4 23 MAR 2003 MAN0504-02
y
t
OCX404
2.3 Analog Input / Output
LOOP POWERED TRANSMITTER
20mA LOOP POWER
+
+
±20mA SELF POWERED TRANSMITTER
±10V SOURCE
±10V SOURCE
±20mA LOAD/RECEIVER
±10V LOAD
Note: The Voltage/Current mode switch is located directl
above each input. Moving a switch towards Pin 1* selects
±20mA for the corresponding channel. Moving the switch
towards Pin 12 selects ±10VDC. Each channel must be se
up in Cscape for the desired mode in addition to the physical
switch settings for proper signal scaling in the PLC registers.
*
I1
C
I2
C
I3
C
I4
C
Q1
C
Q2
C
001OCX005
OCX Back View Connector – Shows
*
corresponding I/O pin location
Pin
OCX404 Analog In / Out
I1 Input 1
C Common
I2 Input 2
C Common
I3 Input 3
C Common
I4 Input 4
C Common
I5 Input 5
C Common
I6 Input 6
C Common
Signal
3 INTERNAL SCHEMATIC
I/O Connector
Mini Digital Input
Field
Side
iI1
C
I/O Connector
V+
Mini Digital Output
Field
Side
Q
VC
Specification for transient voltage suppressors used on digital output circuitry is 33V, 300W.
VCC
To
Controller
From
Controller
Information is subject to change without notice. Cscape is a trademark of Horner APG, LLC.
Page 5
MAN0504-02 23 MAY 2003 PAGE 5
OCX404
I/O Connector
I1
Field
Side
12V
100
C
Mini Analog Input
806K
200K
3
2
1 6
+
-
1nF
4
±10V
5
±20mA
To
Controller
Field
Side
I/O Connector
Q1
12V
100
3
2
1 6
4
5
-
+
±10V
±20mA
Mini Analog Output
+
-
From
Controller
C
Specification for transient voltage suppressors (transorbs) used on output circuitry is 12VDC, 600 watts.
4 CONFIGURATION
Note: The status of the I/O can be monitored in Cscape Software.
Module Setup Tab
The Module Setup is used to configure the Analog
Inputs and Analog Outputs ±10V and ±20mA modes
and for applications where it is necessary to change the
default states or values of the outputs when the
controller (e.g., OCS100) enters idle/stop mode.
1. For Digital Outputs: The default turns the outputs
OFF when the controller enters idle/stop mode. By
selecting the Module Setup tab, each output can be set
to either turn ON, turn OFF or to hold the last state.
Generally, most applications use the default settings.
Warning: The default turns the digital outputs OFF
when the controller enters idle/stop mode. To avoid
injury of personnel or damages to equipment,
exercise extreme caution when changing the default
settings.
2. For Analog Outputs:
Mode: ±10V or ±20mA must be set for each channel. The
associated slide switch on the back of the module must
match the Cscape setting for each channel.
Idle: The default sets the output values to zero when the
controller enters idle/stop mode. By selecting the Module
Setup tab, each output can be set to a specific value or hold
the last value. Generally, most applications use the default
settings.
Warning: The default sets the output values to zero
when the controller enters idle/stop mode. To avoid
injury of personnel or damages to equipment, exercise
extreme caution when changing the default setting using
the Module Setup tab.
3. For Analog Inputs: :
Mode: ±10V or ±20mA must be set for each channel. The
associated slide switch on the back of the module must
match the Cscape setting for each channel.
Filter Constant: Sets the level of digital filtering according to
the following chart.
I/O Map Tab
The I/O Map describes which I/O registers are assigned.
The I/O Map is not
edited by the user.
Information is subject to change without notice. Cscape is a trademark of Horner APG, LLC.
Page 6
PAGE 6 23 MAR 2003 MAN0504-02
OCX404
1
2345607
Filter
Constant
%Complete [ ]
100
90
80
70
60
50
40
30
20
10
0
60
100408020
Scans0
Digital Filtering. The illustration above demonstrates the effect of digital filtering (set with Fillter
Constant) on module response to a temperature change.
5 ANALOG INPUT CONVERSION FACTOR
The following table describes how real-world inputs are scaled into the controller. Given a known input
current, the data value is configured by using the conversion factor from the table. The following formula
is used: Data = Input Current (mA) / Conversion Factor
Example:The user selects a current range of ±20mA:
1. The known input current is 14mA.
2. Using the table, the conversion factor for the current range of ±20mA is 0.000625.
3. To determine the data value, the formula is used:
Data = Input Current (mA) / Conversion Factor
22400 = 14mA / 0.000625
Conversion of Real-World Inputs into Controller
Selected Range Input Register Data Conversion Factor
+20.00 32000
±20mA
0.00 0
-20.00 -32000
+10.00 32000
±10 V
0.00 0
-10.00 -32000
0.000625
0.0003125
Information is subject to change without notice. Cscape is a trademark of Horner APG, LLC.
Page 7
MAN0504-02 23 MAY 2003 PAGE 7
OCX404
6 ANALOG CONVERSION OUTPUT FACTOR
The following table describes how program data values are scaled to real-world analog voltage outputs by
the module. Given a desired output current, the data value is converted by using the conversion factor
from the table. The following formula is used: Data = Output Current (mA) / Conversion Factor
Example:The user selects a current range of ±20mA:
1. The desired output current is 12mA.
2. Using the table, the conversion factor for the current range of ±20 mA is 0.000625.
3. To determine the data value, the formula is used:
Data = Output Current (mA) / Conversion Factor
19200 = 12mA / 0.000625
Conversion of Real-World Outputs into Controller
Selected Range Output Register Data Conversion Factor
+20.00 3200
0 to +20mA
0.00 0
0.000625
-20.00 -32000
+10.00 32000
±10 V
0.00 0
0.0003125
-10.00 -32000
7 DIGITAL INPUT / OUTPUT CHARACTERISTICS
7.1 Digital Input
.125(±15%) V-A
0
7.2 Digital Output
AMPS / CHANNEL
.5
.4
.3
.2
.1
0
Digital Input Chart
35VDC
Derating Chart
0 10 20 30 40 50 60 °C
32 50 68 86 104 122 140 °F
Information is subject to change without notice. Cscape is a trademark of Horner APG, LLC.
Page 8
PAGE 8 23 MAR 2003 MAN0504-02
OCX404
7 INSTALLATION / SAFETY
a. All applicable codes and standards should be followed in the installation of this product.
b. Shielded, twisted-pair wiring should be used for best performance (Analog I/O).
c. Shields may be terminated at the module terminal strip.
d. In severe applications, shields should be tied directly to the ground block within the panel.
e. Use the following wire type or equivalent: Belden 8917, 16 AWG or larger for Digital I/O and Belden
8441 for Analog I/O.
For detailed installation information, refer to Mini Hardware Manual. A handy checklist
covers panel box layout requirements and minimum clearances.
is provided that
8 TECHNICAL ASSISTANCE
For assistance, contact Technical Support at the following locations:
North America:
(317) 916-4274
www.heapg.com
Europe:
(+) 353-21-4321-266
www.horner-apg.com
Information is subject to change without notice. Cscape is a trademark of Horner APG, LLC.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.