Horner APG HE359THM200 User Manual

Page 1
MAN0841-03-EN Specifications / Installation

1 Specifications

THM100 THM200 THM100 THM200
Channels
Input
Ranges
Resolution 0.1C or 0.001mV
Input
Impedance
Accuracy +/-0.1% F.S.
External
Power
Supply
Voltage
Required
Power
(Steady
State)
Required
Power
(Inrush)
Isolation
CE & UL
Compliance
4 8
J, K, R, S,B,E, T,N,
+/-50mV, +/-
100mV, +/-500mV,
+/-1V
>10MOhm
10-30Vdc
30mA @ 24Vdc,
typical
Negligible
2000Vac for 60
seconds
(Input/Power &
Input/Comms)
See Compliance Table at
http://www.heapg.com/Pages/TechSupport/ProductCert.html
Thermocouple Input Module
Conversion
Time (PLC
Update Rate)
Terminal
Type
Storage
Temp.
Operating
Temp.
Relative
Humidity
Dimensions
WxHxD
Weight 150g (6 oz.)
Communicati-
ons
Factory Default
Communicati-
ons
Parameters
Supported
Modbus
Commands

2 Wiring I/O

HE359THM100 / HE359THM200
0.1C or 0.001mV Resolution
Determined by
Communications
w/OCS
Screw Type,
Removable
-40° to 85° Celsius
-10° to 60° Celsius
5 to 95% Non-
condensing
17.5mm x 100mm x
120mm
0.69” x 3.94” x
4.72”
Modbus/RTU
(binary)
RS-485 half duplex
38400 baud, N, 8,
1, no h/s
Default Modbus ID
1
1,2,3,4,5,6,8,15,16
SmartMod
Note: Number of I/O terminal connections vary from model to model
Dimensions in inches are 0.69”W x 3.95”H x 4.72”D
RS-485
I/O
DC IN
+
-
+
­+
-
+
-
+
-
+
-
+
-
+
-
__________________________________________________________________________________________________________________________________________________________________
5/8/2009 Page 1 of 2 ECN # 950
10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9
V+ GNA V+ GNA V+ GNA V+ GNA
V+ GNA V+ GNA V+ GNA V+ GNA
IN
IN
IN
IN
IN
IN
IN
IN
0
1
2
3
4
5
6
7
Pin # ADC107 ADC207 Pin # ADC107 ADC207
1 INPUT 0+ INPUT 0+ 9 INPUT 4+ 2 3 INPUT 1+ INPUT 1+ 11 INPUT 5+ 4 5 INPUT 2+ INPUT 2+ 13 INPUT 6+ 6 7 INPUT 3+ INPUT 3+ 15 INPUT 7+ 8
Notes:
Both ends of the RS-485 network should be terminated with a 100ohm, 1/4W, 1% resistor. Many OCS controllers feature dip switches or jumpers which enable appropriate termination if the OCS is located on a network end.
ANALOG
COMMON
ANALOG
COMMON
ANALOG
COMMON
ANALOG
COMMON
D­D+ GND INIT
Wiring RS-485
A B C D
ANALOG
COMMON
ANALOG
COMMON
ANALOG
COMMON
ANALOG
COMMON
10
12
14
16
Wiring DC IN
Only Terminals 1
through 8 are
present on the
ADC107 model
I
V-
J
V+
10-30Vdc
ANALOG
COMMON
ANALOG
COMMON
ANALOG
COMMON
ANALOG
COMMON
Page 2
MAN0841-03-EN Specifications / Installation

3 Init Default Setup

Communication parameters will be set to INIT default after performing the procedure:
1. Install jumper between INIT and GND terminals of the RS-485 port.
2. Apply power to Smartmod unit.
3. Read parameter words to see current parameters.
4. Write changes if necessary.
The INIT Default RS485 Settings Are:
Modbus ID = 1 Baud rate = 9600 Parity = None Stop Bits = 1 Data Bits = 8 No handshake
Note: There are 2 types of default settings possible:
1. Factory default as described in section 1 (Specifications)
2. Default after INIT as described in section 3 (INIT Default Setup)

4 Configuration DATA

SmartMod Configuration settings are mapped into Modbus Register space. This configuration data may be modified with any Modbus/RTU Master device. For convenience, Horner APG has developed a variety of Cscape application files which allow an OCS (Xle, NX, LX, QX) to act as a SmartMod configurator. Initial configuration of SmartMod module should be done on an individual basis, since all modules come from the factory with a default Modbus ID of 1. Once each module on the network has its own unique Modbus ID, further configuration adjustments can be made with the entire network powered.
All configuration parameters listed below (except 40012 Channel Enable) are stored in EPROM. That means they should not be constantly rewritten.
Configuration Parameters – Registers 40001 through 40013
Modbus
Register
40001­40005
40006 40007 Modbus ID 1 255 1
40008 40009 40010 Modbus Coil Data
40011 Input Type See Table 1 (+/- 50 mV) 40012 Channel Enable See Table 40013 Reserved
Register 40006 (Communications Parameters) Bit Definition
Bits 7-15 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Unused Mode Parity
Value Input Type Value Input T ype
1 +/-50mV 14 Type J T/C 2 +/-100mV 15 Type K T/C 3 +/-250mV 16 Type T T/C 4 +/-1000mV 17 Type E T/C
5-13 Not Used 18 Type R T/C
A
D-
B
D+
C
GND
INIT
D
Description Min Max Default
Reserved
Communications
Parameters
Rx/Tx Dela y (in 2mS
steps)
Watchdog Timer (in 0.5s
steps)
See Table
0 255 0mS 0 255 10 (5s)
Not Configuration Dat a – See
Data
Bits
Value Meaning Value Meaning
0 = ASCII Mode
1 =
RTU
Mode
0 Mark 0 1200 baud 1 Even 2 Odd 2 4800 baud 3 Space 3 9600 baud
0 = 7 Data
Bits
1 = 8 Data
Bits
5-7 38400 baud
Register 40011 (Input Type) Value Definition
19 Type S T/C 20 Type B T/C 21 Type N T/C
38.4kbaud,
N, 8, 1, RTU
Mode
I/O Data
255
(Channels
1-8 enabled)
Baud Rate
1 2400 baud
4 19200 baud
Register 40012 (Channel Enable) Bit Definition
Bit 8-15 Bit 7 Bit 6 Bit 4 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Unused Input 7 Input 6 Input 5 Input 4 Input 3 Input 2 Input 1 Input 0
0 = Disable Input
1 = Enable Input

5 Input/Output DATA

SmartMod Analog I/O utilizes both Modbus Registers (40001-40030) and Coils (1-11). It is possible to access all data using Registers only, because the Coils can be accessed through Register 40010.
The following tables lists all Modbus I/O data available.
I/O Register Data (Registers 40014-40022) Modbus Register
40010 40014
Description Access Minimum Maximum Units
Mirror of Coil
Data
Cold Junction
Temperature
Read/Write n/a n/a n/a
Read-only -1000 6000 0.01 degrees C
40015 Input 0 Read-only 0.1C or 0.001mV 40016 Input 1 Read-only 0.1C or 0.001mV 40017 Input 2 Read-only 0.1C or 0.001mV 40018 Input 3 Read-only 0.1C or 0.001mV 40019 Input 4 Read-only 0.1C or 0.001mV 40020 Input 5 Read-only 0.1C or 0.001mV
Depends
on Input
Type
Depends
on Input
Type
40021 Input 6 Read-only 0.1C or 0.001mV 40022 Input 7 Read-only
Modbus
Coil
Description Access
00001 Open Detect Input 0 Read/Write 00002 Open Detect Input 1 Read/Write 00003 Open Detect Input 2 Read/Write 00004 Open Detect Input 3 Read/Write 00005 Open Detect Input 4 Read/Write 00006 Open Detect Input 5 Read/Write 00007 Open Detect Input 6 Read/Write 00008 Open Detect Input 7 Read/Write 00009 Watchdog Enabled Read/Write 00010 Watchdog Event Read/Write
00011 Power-up Event Read/Write
Watchdog Event & Power-up
Event Operation
If Coil 9 (Watchdog Enabled) is set, Coil 10 (Watchdog Event) will set if the Watchdog Timeout value is exceeded. The Watchdog Timeout value is set in Register 40009. When set, Coil 10 can be reset by the controller when normal communications resumes.
The Power-up Event (Coil 11) is set every time the power is applied. It can be cleared by the controller if desired.
0.1C or 0.001mV

6 Installation / safety

Warning: Remove power from the OCS controller, CAN port, and any peripheral equipment
connected to this local system before adding or replacing this or any module.
a. All applicable codes and standards should be followed in the installation of this product. b. Shielded, twisted-pair wiring should be used for best performance. c. Shields may be terminated at the module terminal strip. d. In severe applications, shields should be tied directly to the ground block within the panel. e. Use the following wire type or equivalent: Belden 8441.
For detailed installation and a minimum clearances, refer to the hardware manual of the controller you are using.
When found on the product, the following symbols specify:
handy checklist that covers panel box layout requirements and
Warning: Electrical Shock Hazard.
Warning: Consult user documentation.

7 Technical Support

Technical Support at the following locations:
North America:
Tel: 317 916-4274 Fax: 317 639-4279 Web: http://www.heapg.com
techsppt@heapg.com
Email: No part of this publication may be reproduced without the prior agreement and written
permission of Horner APG, Inc. Information in this document is subject to change without notice.
Europe:
Tel: +353-21-4321266 Fax: +353-21-4321826 Web: http://www.horner-apg.com Email: tech.support@horner-apg.com
__________________________________________________________________________________________________________________________________________________________________
5/8/2009 Page 2 of 2 ECN # 950
Loading...