Horner APG HE359RTD100 User Manual

Page 1
MAN0840-04-EN Specifications / Installation
100,
SmartMod
Many OCS
CS is located on
1 Specifications
Number of
Channels
Input Ranges
Resolution 0.1C or 0.1ohm Storage Temp.
RTD
Excitation
Current
Accuracy +/-0.1% F.S.
External
Power Supply
Voltage
Required
Power
(Steady State)
Required
Power
(Inrush)
Isolation
CE & UL
Compliance
4
RTD Pt-100, Ni-
Pt-1000, & Ni-1000,
0-2000ohm,
0-500ohm
(PT, .00385)
350microamp,
typical
10-30Vdc Weight 150g (6 oz.)
30mA @ 24Vdc,
typical
Negligible
2000Vac for 60
seconds
(Input/Power &
Input/Comms)
http://www.heapg.com/Pages/TechSupport/ProductCert.html
Conversion Time
(PLC Update
Rate)
Terminal Type
Operating Temp.
Relative Humidity
Dimensions
WxHxD
Communications
Factory Default
Communications
Parameters
Supported
Modbus
Commands
See Compliance Table at
2 Wiring – I/O
RTD Input Module
0.1C or 0.1ohm Resolution
Determined
by
Communicat-
ions w/OCS
Screw Type,
Removable
-40° to 85° Celsius
-10° to 60° Celsius
5 to 95%
Non-
condensing
17.5mm x 100mm x
120mm
0.69” x 3.94” x 4.72”
Modbus/RTU
(binary)
RS-485 half
duplex
38400 baud,
N, 8, 1, no
h/s
Default
Modbus ID 1
1,2,3,4,5,6,8,
15,16
HE359RTD100
Note: Number of I/O terminal connections vary from model to model
Dimensions in inches are 0.69”W x 3.95”H x 4.72”D
RS-485
I/O
DC IN
1
GEN
IN
2
IN REF GEN IN REF GEN IN REF GEN IN REF
IN
IN
IN
0
1
2
3
Notes:
Both ends of the RS-485 network should be terminated with a 100ohm, 1/4W, 1% resistor. controllers feature dip switches or jumpers which enable appropriate termination if the O a network end.
3 4 5 6 7 8
9 10 11 12
__________________________________________________________________________________________________________________________________________________________________
5/11/2009 Page 1 of 2 ECN # 950
Pin # RTD100 Pin # RTD100
1 GEN 7 GEN 2 IN 8 IN 3 REF 4 GEN 10 GEN 5 IN 11 IN 6 REF
A
D-
B
D+
C
GND INIT
D
Wiring RS-485
IN 0
IN 1
12 REF
9 REF
V­V+
Wiring DC IN
IN 2
IN 3
I
J
10-30Vdc
Page 2
MAN0840-04-EN Specifications / Installation
Coil 10 (Watchdog Event) will set if the
Watchdog Timeout value is exceeded.
every time the power is applied. It can
INIT
3 Init Default Setup
Communication parameters will be set to INIT default after performing the procedure:
1. Install jumper between INIT and GND terminals of the RS-485 port.
2. Apply power to Smartmod unit.
3. Read parameter words to see current parameters.
4. Write changes if necessary.
The INIT Default RS485 Settings Are:
D­D+ GND
A B C D
Modbus ID = 1 Baud rate = 9600 Parity = None Stop Bits = 1 Data Bits = 8 No handshake
Note: There are 2 types of default settings possible:
1. Factory default as described in section 1 (Specifications)
2. Default after INIT as described in section 3 (INIT Default Setup)
4 Configuration DATA
SmartMod Configuration settings are mapped into Modbus Register space. This configuration data may be modified with any Modbus/RTU Master device. For convenience, Horner APG has developed a variety of Cscape application files which allow an OCS (Xle, NX, LX, QX) to act as a SmartMod configurator. Initial configuration of SmartMod module should be done on an individual basis, since all modules come from the factory with a default Modbus ID of 1. Once each module on the network has its own unique Modbus ID, further configuration adjustments can be made with the entire network powered.
All configuration parameters listed below (except 40012 Channel Enable) are stored in EPROM. That means they should not be constantly rewritten.
Configuration Parameters – Registers 40001 through 40013
Modbus
Register
40001-
40005 40006
Description Min Max Default
Reserved
Communications
Parameters
See Table
38.4kbaud,
N, 8, 1, RTU
Mode
40007 Modbus ID 1 255 1 40008
40009 40010 Modbus Coil Data 40011 Input Type See Table
Rx/Tx Delay (in 2mS
steps)
Watchdog Timer (in 0.5s
steps)
0 255 0mS 0 255 10 (5s)
Not Configuration Data – See
I/O Data
23 (RTD Pt-
100 Type)
255 (All
40012 Channel Enable See Table
Channels
enabled)
40013 Reserved
Register 40006 (Communications Parameters) Bit Definition
Bits 7-15 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Unused Mode Parity
Value Meaning Value Meaning
0 = ASCII Mode
1 =
RTU
Mode
0 Mark 0 1200 baud 1 Even 2 Odd 2 4800 baud 3 Space 3 9600 baud
Data
Bits
Baud Rate
0 = 7
Data
Bits
1 2400 baud
1 = 8
Data
Bits
4 19200 baud
5-7 38400 baud
Register 40011 (Input Type) Value Definition
Value Input Type
7 0-2000ohm Resistance
8 0-500ohm Resistance 23 RTD Pt-100 Type 24 RTD Ni-100 Type 25 RTD Pt-1000 Type 26 RTD Ni-1000 Type
Register 40012 (Channel Enable) Bit Definition
Bit 4-15 Bit 3 Bit 2 Bit 1 Bit 0
Unused Input 3 Input 2 Input 1 Input 0
0 = Disable Input
1 = Enable Input
5 Input/Output DATA
SmartMod Analog I/O utilizes both Modbus Registers (40001-40030) and Coils (1-11). It is possible to access all data using Registers only, because the Coils can be accessed through Register 40010.
The following tables lists all Modbus I/O data available.
I/O Register Data (Registers 40014-40022) Modbus Register Description
40010 40014
Mirror of Coil
Data
Cold Junction
Temperature
Access Minimum Maximum
Read/Write n/a n/a n/a
Read-only -1000 6000 0.01 degrees C
40015 Input 0 Read-only 40016 Input 1 Read-only 40017 Input 2 Read-only 40018 Input 3 Read-only 40019 Input 4 Read-only 40020 Input 5 Read-only
Depends
on Input
Type
Depends
on Input
Type
0.1C or 0.1 ohm
40021 Input 6 Read-only 40022 Input 7 Read-only
Modbus
Coil
Description Access
00001 Open Detect Input 0 Read/Write 00002 Open Detect Input 1 Read/Write
Watchdog Event & Power-up
Event Operation
If Coil 9 (Watchdog Enabled) is set,
00003 Open Detect Input 2 Read/Write 00004 Open Detect Input 3 Read/Write 00005 Open Detect Input 4 Read/Write 00006 Open Detect Input 5 Read/Write 00007 Open Detect Input 6 Read/Write 00008 Open Detect Input 7 Read/Write 00009 Watchdog Enabled Read/Write 00010 Watchdog Event Read/Write 00011 Power-up Event Read/Write
RTD Sensor Temperature Ranges
The Watchdog Timeout value is set in
Register 40009. When set, Coil 10 can be reset by the controller when
normal communications resumes.
The Power-up Event (Coil 11) is set
be cleared by the controller if desired.
RTD Sensor Type Minimum Temperature Maximum Temperature
Pt-100 -200 degrees C +850 degrees C
Ni-100 -80 degrees C +180 degrees C Pt-1000 -200 degrees C +200 degrees C Ni-1000 -60 degrees C +150 degrees C
6 Installation / safety
Warning: Remove power from the OCS controller, CAN port, and any peripheral equipment
connected to this local system before adding or replacing this or any module.
a. All applicable codes and standards should be followed in the installation of this product. b. Shielded, twisted-pair wiring should be used for best performance. c. Shields may be terminated at the module terminal strip. d. In severe applications, shields should be tied directly to the ground block within the panel. e. Use the following wire type or equivalent: Belden 8441.
For detailed installation and a handy checklist that covers panel box layout requirements and minimum clearances, refer to the hardware manual of the controller you are using.
When found on the product, the following symbols specify:
Warning: Electrical Shock Hazard.
Warning: Consult user documentation.
7 Technical Support
Technical Support at the following locations:
North America:
Tel: 317 916-4274 Fax: 317 639-4279 Web: http://www.heapg.com Email: techsppt@heapg.com
No part of this publication may be reproduced without the prior agreement and written permission of Horner APG, Inc. Information in this document is subject to change without notice.
Europe:
Tel: +353-21-4321266 Fax: +353-21-4321826 Web: http://www.horner-apg.com Email: tech.support@horner-apg.com
__________________________________________________________________________________________________________________________________________________________________
5/11/2009 Page 2 of 2 ECN #
950