HORNER X7 OCS, HE-X7 Quick Reference Sheet

X OCS MODEL: HE-X7 QUICK REFERENCE SHEET
MODEL A BUILT-IN I/O: 12 DIGITAL INPUTS, 12 DIGITAL OUTPUTS, 4 ANALOG INPUTS, 2 ANALOG OUTPUTS
GETTING STARTED
1 Read this document to fully understand the
X7 and safety requirements.
2 Use Section 4 and the mounting template to
install the product.
3 Connect 24VDC power and I-O according to
the quick start guide and data sheet.
4 Refer to the X7 User Manual for further
instructions: MAN1155.
1 - General Specifications
1.1 General
Primary Pwr. Range 24VDC +/- 20%
Typical power-backlight 100%
Power Backlight Off 123mA @ 24V
Inrush Current 30A ˂ 1ms
Real Time Clock Battery backed; lithium coin cell CR2450
Clock Accuracy +/- 90 Secs/Month
Relative Humidity 5 to 95% Non-condensing
Operating Temp. -10°C to +60°C
Storage Temp. -20°C to +70°C
Weight 20.8 oz./ 590 g
Included in Box
Certifications (UL/CE)
154mA @ 24V
Controller, 3 x I/0 connectors, 4 x mounting clips, 1 x power connector, Quick Reference Guide
USA: https://hornerautomation.com/certifications/ Europe: http://www.horner-apg.com/en/support/
certification.aspx
1.2 Connectivity
Serial Ports 1 x RS232, 1 x RS485
485 Terminations On-board, software controlled
USB Programming Support USB mini-B 2.0
CAN Hardware Non-isolated
CAN Port Connector RJ45 (red)
CAN Port Termination On-board, software controlled
Removable Memory In
Remote I/O
microSD (SDHC, SDXC IN FAT32 format, support for 32 GB max. Application Updates, Datalogging, more)
SmartRail, SmartStix, SmartBlock, SmartMod
1.3 User Interface / Control & Logic
Display 7” Color Transmissive
Resolution 480 x 272 pixels
Backlight White LED, 20,000 hrs.
Backlight Control Yes, software controlled (ON/OFF)
Control Language Support
Advanced ladder logic Full IEC 61131-3 languages
Indianapolis, USA | Cork, Ireland | Calgary, Canada | Bangalore, India | Oakleigh, Australia | Tianjin, China | Esteio, Brazil
Please visit our website for a complete listing and to learn more about certified Horner Automation products. This document is the property of Horner Automation Group, and is subject to change.
page 1 of 4
12/18/2018 | MAN1202-01-EN
2.1 - Port Connectors
1
1. Touch Screen
2. High Capacity microSD Slot
3. RS232/RS485 Serial Connector, CAN port (via RJ45), LAN Port (Ethernet)
4. USB Mini-B Port
5. Analog I/O, DC Inputs, DC Outputs
6. DC Power
3.1 - Installation Procedure
The X7 utilizes a clip installation method to ensure a robust and watertight seal to the enclosure. Please follow the steps below for the proper installation and operation of the unit.
1. Carefully locate an appropriate place to mount the X7. Be sure to leave enough room at the top of the unit for insertion and removal of the microSD™ card.
2. Carefully cut the host panel per the diagram on Page 1, creating a 174.63mm x 130.96mm +/- 0.1mm opening into which the X7 may be installed. If the opening is too large, water may leak into the enclosure, potentially damaging the unit. If the opening is too small, the OCS may not fit through the hole without damage.
3. Remove any burrs and or sharp edges and ensure the panel is not warped in the cutting process.
4. Install and tighten the four mounting clips (provided in the box) until the gasket forms a tight seal. For standard composite mounting clips (included with product), use a torque rating of 2-3 in-lbs (0.23-0.34 Nm). For optional metal mounting clips, use a torque rating of 4-8 in lbs (0.45-0.90 Nm).
5. Connect communications cables to the serial port, USB ports, and CAN port as required.
3
4
2
5
6
4.1 - Panel Cut-Out
The graphics below detail the dimensions and depth of the overall controller itself. The X7 panel cut-out measures 6.88” (174.63mm) wide x 5.16” (130.96mm) tall.