Honeywell Home V4043, V4044, V8043, V8044 Installation Instructions Manual

95-6983EF-03
V4043, V4044, V8043 and
CAUTION
M10162A
VERTICAL PIPING
HORIZONTAL PIPING
V8044 Zone Valves
INSTALLATION INSTRUCTIONS

APPLICATION

These valves consist of an actuator motor and valve assembly for controlling the flow of hot and/or cold water. The V4043 and V8043 provide two-position, straight-through control of supply water. The V4044 and V8044 provide two-position, diverting control of supply water. The valves are designed for use with fan coil and other units requiring quiet, compact water valves. The V8043E and F also control supply water for baseboard radiators and convectors. The V4043E and V8043J provide straight-through control of steam only. Models are available with 125 or 300 psi operating pressure.

INSTALLATION

IMPORTANT
Use this valve in hydronic heating systems which do not contain dissolved oxygen in the system water. The dissolved oxygen, which is found in systems that have a frequent source of makeup water, causes the rubber plug inside the valve to deteriorate and eventually fail.
LOCATION
Install the valve in an area with adequate clearance to:
— Move the manual opening lever on the side of
the powerhead. — Remove the powerhead cover. — Wire the powerhead. — Replace the powerhead motor.

When Installing this Product...

1. Read these instructions carefully. Failure to fol-
low them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and
on the product to make sure the product is suit­able for your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
1. Disconnect power supply before connect­ing wiring to prevent electrical shock of equipment damage.
2. Normally it is not necessary to remove the powerhead from the valve body during installation. If the valve must be disas­sembled, be certain that it is reassembled with the water flow in the direction of the arrow. Reversal of the powerhead will result in damage to the gear train.
3. On 24V systems, never jumper the valve coil terminals even temporarily. This may burn out the heat anticipator in the ther­mostat.

MOUNTING

The valve can be mounted in any position on a vertical line. If the valve is mounted horizontally; the powerhead must be even with or above the center line of the piping. Make sure that enough room is provided above the powerhead to remove the cover for servicing.
Fig. 1. Mounting positions.
V4043, V4044, V8043 AND V8044 ZONE VALVES
OUT
STRAIGHT THROUGH
VALVES
IN
B
A
M35994
OUT
OUT
B
A
AB
IN
2 POSITION DIVERTING
VALVES
4-7/8 (124)
OUT
IN
1
END SWITCH
MAN OPEN
AUTO
MAN OPEN
AUTO
CLEARANCE FOR COVER REMOVAL
CONDUIT COVER FOR V8043F
TERMINAL BOARDLEADWIRES
A
B
F
C
A
D
B
C
B
OUT
IN
N
M R
S
L
K
H
J
G
SWEAT
3/8 FLARE
2
U
P
FNPT
CLEARANCE NECESSARY FOR COVER REMOVAL
FLAIR-TO-SWEAT UNION ADAPTER
1
2
M16851
DIMENSION IN INCHES (MM)
MODELS A B C D E F G H J
V8043C,D,G 2-3/8 (60) 3-3/4 (90) 7/8 (22) 3/4 (19) 5-1/4 (133) 3-7/16 (87) 5/8 (16)
V8043F 2-3/8 (60) 3-3/4 (90) 7/8 (22) 3/4 (19) 3-7/8 (98) 5-1/4 (133) 3-7/16 (87) 3/4 (19)
SWEAT MODELS K L
5/8 IN. I.D. (FOR 1/2 IN. COPPER TUBING) 3-1/8 (79) 1-9/16 (40)
7/8 IN. I.D. (FOR 3/4 IN. COPPER TUBING) 3-1/2 (89) 1-3/4 (44)
1-1/8 IN. I.D. (FOR 1 IN. COPPER TUBING) 3-7/8 (98) 1-15/16 (49)
FLARE MODELS M N
3/8 IN NPT ONLY 4-5/8 (117) 2-5/8 (59)
FNPT MODELS P U
3/4 IN. 3-5/8 (98) 1-13/16 (46)
FLARE-TO-SWEAT UNION ADAPTER R S
FOR 1/2 IN. COPPER 6-3/16 (157) 3-29/32 (99)
FOR 3/4 IN. COPPER 6-7/16 (164) 4-13/16 (106)
Mount the valve directly in the tube or pipe. Make sure that the flow through the valve is in the direction indicated by the arrow stamped on the valve body.
On diverting valves, the three fittings or ports are labeled on the bottom of the valve body casting. See Fig. 2. Port AB is the inlet port and is open at all times. Port A is closed when the valve is de-energized; port B is open when the valve is de-energized. Refer to the equipment manufacturer’s instructions to determine which port (A or B) should be connected to the coil bypass.
Fig. 2. Inlet and outlet ports on straight-through
and diverting valves.
FLARE FITTING MODELS
Use new, properly reamed pipe, free from chips. The valve body is threaded for standard 5/8 in. OD copper, 45 degree SAE flare fitting nuts. These nuts are not furnished with the valve and must be obtained separately.
SWEAT COPPER MODELS
1. Use new, properly reamed pipe, free from dents
or corrosion.
2. Place the valve onto the pipe. Set the manual
opening lever to MAN. OPEN position before applying heat. This protects the plug inside the valve by removing it from the seat.
3. Sweat the joints, keeping the outer surface free
from solder. DO NOT use silver solder because of the high melting temperature required.
95-6983EF—03 2
Fig. 3. Dimensions.
V4043, V4044, V8043 AND V8044 ZONE VALVES
CAUTION
L2
1
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
END SWITCH
TH
TR
24V TRANSFORMER
TH TR
M5952C
THERMOSTAT
R
W
TO BOILER TT
L1 (HOT)
B
OUT
OPEN POSITION
A
A
IN
B
OUT
CLOSED POSITION
B
A
IN
M5951

WIRING

Disconnect the power supply before connecting wiring to prevent electrical shock or equipment damage.
All wiring must comply with local codes and ordinances. Connections to the individual valves are shown in Fig. 4-5.
THERMOSTAT
R
W
1
L1 HOT L2
24 TRANSFORMER
MOTOR
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
Fig. 4. Typical wiring for V8043E, V8044E.
YELLOW LEADS
AUXILIARY SWITCH
TO BOILER TT
RED LEADS
M5953B
spring-return mechanism drives the valve to the closed position as shown in Fig. 6B. The valve can also be opened with no electrical power by moving the manual opening lever over the stop and pushing slowly and firmly to the MAN. OPEN position. The stop permits the valve to be locked in the open position. The valve will return to the automatic position when the valve is energized.
Auxiliary switch is not energized when the valve is manually opened.
NORMALLY OPEN MODELS
When the powerhead is de-energized, a spring-return mechanism drives the valve to the open position (Fig. 6A). When energized, the valve is closed as shown in Fig. 6B. A reverse-acting thermostat is required to control a normally open valve.
NOTE: Inlet Port is stamped “A”, Outlet Port is
stamped “B” on the valve body.
Fig. 6. V8043 operation for normally closed valve.

Checkout

1. Raise the setpoint on the zone thermostat above
the room temperature to initiate a call for heat.
2. Observe all control devices—the valve should
open and the auxiliary switch should make the circuit to the circulator or other valve at the end of the opening stroke.
3. Lower the setpoint on the zone thermostat below
the room temperature.
4. Observe the control devices. The valve should
close and the auxiliary equipment should stop.

OPERATION AND CHECKOUT

NORMALLY CLOSED MODELS
With the manual opener set to AUTO and the powerhead energized, the valve is opened as shown in Fig. 6A. When the powerhead is de-energized, a
Fig. 5. Typical wiring for V8043F.
On 24 V systems, never jumper the valve coil terminals even temporarily. This may burn out the heat anticipator in the thermostat.

Service

This valve should be serviced by a trained, experienced service technician.
1. If the valve is leaking, drain the system and
check to see if the O-ring needs replacing.
2. If the gear train is damaged, replace the entire
powerhead assembly. See the Installation sec­tion. If the motor is burned out, replace the motor.
NOTE: Resideo zone valves are designed and tested
for silent operation in properly designed and installed systems. However, water noises may occur as a result of excessive water velocity or piping noises may occur in high temperature (over 212° F [100° C]) systems with insuffi­cient water pressure.
NOTE: These hydronic valves are not suitable for use
in open loop systems where there is air expo­sure.
3 95-6983EF—03
Loading...
+ 5 hidden pages