The TB7100A1000 MultiPRO™ Multispeed and Multipurpose Thermostat provides electronic control of 24 Vac
heating and cooling systems.
See Table 1 for a description.
Table 1. TB7100A Thermostat Description.
FeatureDescription
Powering Methods • Battery only
System Types• Conventional (1 Heat, 1 Cool stages)
ChangeoverManual or automatic changeover selectable
System SettingHeat-Off-Cool-Auto
Fan SettingAuto, On
Fan SpeedsLow, Medium, High
Remote SetbackRemote Setback Input for occupancy sensor or DDC setback
Fan Ramping
Algorithm
• 24 Vac only
• 24 Vac with battery backup
• Heat Pump (up to 2 Heat,1 Cool stages)
• 2 Pipe Fan Coil
• 2 Pipe Fan Coil with Auxiliary Heat
• 4 Pipe Fan Coil
• PTAC (up to 2 Heat, 1 Cool)
VersaSpeed™ Fan Ramping Algorithm for automatic fan speed selection (fan coil and
PTAC applications)
If this control is replacing a control that
contains mercury in a sealed tube, do not
place your old control in the trash. Dispose of
properly.
Contact your local waste management
authority for instructions regarding recycling
and the proper disposal of an old control.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to fol-
low them could damage the product or cause a
hazardous condition.
2. Check ratings given in instructions and on the
product to ensure the product is suitable for
your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
CAUTION
5 FEET
[1.5 METERS]
YES
NO
M22258
NO
NO
M22268
DRILLED
HOLES (2)
WALL
ANCHORS (2)
MOUNTING
SCREWS (2)
WALLPLATE
SC
Install Wallplate (See Fig. 3)
Electrical Shock or Equipment Damage
Hazard.
Can shock individuals or short equipment
circuitry.
Disconnect power supply before installation.
Select Thermostat Location
Select a location for the thermostat about 5 ft (1.5m)
above the floor in an area with good air circulation at
average temperature. See Fig. 1.
Fig. 1. Select thermostat location.
Do not install the thermostat where it can be affected
by:
— Drafts or dead spots behind doors and in corners.
— Hot or cold air from ducts.
— Radiant heat from sun or appliances.
— Concealed pipes and chimneys.
— Unheated (uncooled) areas such as an outside wall
behind the thermostat.
Mount the thermostat horizontally on the wall:
1. Pull the wires through the wire hole on the wall-
2. Position the wallplate on the wall with the arrow
3. Use a pencil to mark the mounting holes.
4. Remove the wallplate from the wall and drill two
5. Pull the wires through the wire hole on the wall-
6. Insert the mounting scre ws into the wall anchors
WIRING
IMPORTANT
Separate Wallplate from
Thermostat
1. Separate the wallplate from the thermostat. See
Fig. 2.
WALLPLATE
WIRE HOLE
62-0273—072
THERMOSTAT
Fig. 2. Separate wallplate from thermostat.
M22267
NOTES:
1. Select set of terminal identifications that corre-
Fig. 4. Terminal identifications for system type.
plate.
pointing up. Level the wallplate for appearance
only.
3/16 in. holes in the wall (if drywall) as marked.
For firmer material such as plaster, drill two 7/
32 in. holes. Tap the wall anchors (provided) into
the drilled holes until flush with the wall.
plate and position the wallplate over the wall
anchors.
and tighten.
Fig. 3. Install wallplate.
— All wiring must agree with applicable codes,
ordinances and regulations.
— Use 18 gauge thermostat wire. Shielded cable
is not required.
—Sensor wires must have a cable separate
from the thermostat control cable.
—Refer to Table 2 for terminal designation
descriptions.
—See Fig. 6 through 17 for wiring diagrams
for specific equipment applications.
spond to your system type (conventional or heat
pump). (See Fig. 4).
REW
TERMINALS
C
G
Y
O/B
RC
R
W1
G2
G3
S1
S2
M27415
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
WALLPLATE
M22266
WALL OPENING
WIRE
SHADED AREA
2. Loosen screw terminals used for the application.
3. Insert the wires into the terminal block and
tighten each screw terminal.
4. Push excess wire back into the wall opening and
restrict wires to the shaded area. See Fig. 5.
5. Plug the wall opening with nonflammable insulation to prevent drafts from affecting the thermostat.
Fig. 5. Restrict wires to shaded area of wire hole.
Table 2. Terminal Designation Descriptions.
Ter min al
DesignationDescription
RC (see Note 1)Power for cooling—connect to secondary side of cooling system transformer.
R (see Note 1)Power for heating—connect to secondary side of heating system transformer.
YCompressor output.
C (see Note 2)Common wire from secondary side of cooling system transformer.
W1Heat relay. Auxiliary heat relay to heat pump, PTAC.
GFan relay. Low fan speed for Fan Coil and PTAC applications.
G2Fan relay. Medium fan speed for Fan Coil applications only.
G3Fan relay. High fan speed for Fan Coil and PTAC applications.
O/B (see Note 3)Changeover valve for heat pumps.
S1 (see Note 4)Indoor remote sensor, remote setback, or changeover input.
S2 (see Note 4)Indoor remote sensor, remote setback, or changeover input.
NOTES:
1.When used in a single-transformer system,
leave metal jumper wire in place between
RC and R. If used on a two-transformer system, remove metal jumper wire between RC
and R.
2.Common wire is optional when thermostat
is used with batteries. When using separate transformers for heating and cooling,
the common must come from the cooling
transformer.
3.If t hermo stat i s conf igur ed for a heat p ump
in the Installer Setup, configure changeover valve for cool (O-factory setting) or
heat (B).
4.Sensor wires must have a cable separate
from the thermostat control cable.
Standard Heat/Cool (1H/1C)6, 7
Heat Only8
Heat Only with Fan9
Cool only10
Heat Pump (No Auxiliary Heat)
(1H/1C)
Heat Pump (with Auxiliary Heat )
(2H/1C)
4 Pipe Fan Coil13
2 Pipe Fan Coil (with Auxiliary
Heat)
2 Pipe Fan Coil (no Auxiliary Heat) 15
PTAC 1H/1C (High speed, Low
speed fan)
PTAC 2H/1C (High speed, Low
speed fan)
Table 3. Wiring Diagrams.
System Type
Wiring Diagram
11
12
14
16
17
Multiple TR21 Sensors18, 19, 20
Multiple C7189U Sensors21
Figure
362-0273—07
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
COMPRESSOR CONTACTOR
M27417
HEAT RELAY
FAN RELAY
COOLING
TRANSFORMER
HEATING
TRANSFORMER
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
REMOVE FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION
IS OPTIONAL. WHEN USED, THE COMMON MUST CONNECT
TO THE COOLING TRANSFORMER SECONDARY.
1
3
2
3
L1
(HOT)
L2
1
24 VAC
L1
(HOT)
L2
1
24 VAC
C
G
Y
O/B
RC
R
2
INDOOR TEMPERATURE
SENSOR/REMOTE
SETBACK
W1
G2
G3
S1
S2
M27418
HEAT RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS
OPTIONAL.
1
2
3
L1
(HOT)
L2
1
24 VAC
C
G
Y
O/B
RC
R
2
W1
G2
G3
S1
S2
INDOOR TEMPERATURE
SENSOR/REMOTE
SETBACK
3
M27419
HEAT RELAY
FAN RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION
IS OPTIONAL.
1
2
3
3
L1
(HOT)
L2
1
24 VAC
2
C
G
Y
O/B
RC
R
W1
G2
G3
S1
S2
INDOOR TEMPERATURE
SENSOR/REMOTE
SETBACK
Conventional System Wiring
1
L1
(HOT)
24 VAC
L2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
1
PROTECTION AS REQUIRED.
2
FACTORY INSTALLED JUMPER.
3
WHEN USING BATTERIES, THE 24V COMMON CONNECTION
IS OPTIONAL.
Fig. 6. Typical wiring of single transformer
C
G
Y
O/B
RC
R
COMPRESSOR CONTACTOR
FAN RELAY
HEAT RELAY
1H/1C system.
3
2
INDOOR TEMPERATURE
SENSOR/REMOTE
SETBACK
W1
G2
G3
S1
S2
M27416
Fig. 8. Typical hookup of heat-only system.
Fig. 9. Typical hookup of heat-only system with fan.
Fig. 7. Typical hookup of dual transformer
62-0273—074
1H/1C system.
1
L1
(HOT)
24 VAC
L2
COMPRESSOR CONTACTOR
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2
FACTORY INSTALLED JUMPER.
3
WHEN USING BATTERIES, THE 24V COMMON CONNECTION
IS OPTIONAL.
C
G
Y
O/B
RC
R
FAN RELAY
3
2
INDOOR TEMPERATURE
SENSOR/REMOTE
SETBACK
Fig. 10. Typical hookup of cool-only system.
W1
G2
G3
S1
S2
M27420
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
COOLING RELAY
INDOOR TEMPERATURE
SENSOR/REMOTE
SETBACK
HEAT RELAY
LOW FAN RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS
OPTIONAL.
1
2
3
C
G
Y
O/B
RC
R
W1
G2
G3
S1
S2
2
3
L1
(HOT)
L2
1
24 VAC
M27423
HIGH FAN RELAY
MEDIUM FAN RELAY
INDOOR TEMPERATURE
SENSOR/REMOTE
SETBACK/CHANGEOVER
PIPE SENSOR
TWO PIPE HEAT/COOL RELAY
LOW FAN RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS
OPTIONAL.
1
2
3
C
G
Y
O/B
RC
R
W1
G2
G3
S1
S2
2
3
L1
(HOT)
L2
1
24 VAC
M27424
HIGH FAN RELAY
AUXILIARY HEAT RELAY
MEDIUM FAN RELAY
INDOOR TEMPERATURE
SENSOR/REMOTE
SETBACK/CHANGEOVER
PIPE SENSOR
TWO PIPE HEAT/COOL RELAY
LOW FAN RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS
OPTIONAL.
1
2
3
C
G
Y
O/B
RC
R
W1
G2
G3
S1
S2
2
3
L1
(HOT)
L2
1
24 VAC
M27425
HIGH FAN RELAY
MEDIUM FAN RELAY
Heat Pump System Wiring
L1
(HOT)
24 VAC
L2
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
1
PROTECTION AS REQUIRED.
2
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS
3
OPTIONAL.
4
"O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE
INSTALLER SETUP.
OPTIONAL INDOOR REMOTE SENSOR OR REMOTE SETBACK.
5
WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT
CABLE.
Fig. 11. Typical hookup of single-stage heat pump
L1
(HOT)
24 VAC
L2
1
COMPRESSOR CONTACTOR
FAN RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
1
PROTECTION AS REQUIRED.
2
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION
3
IS OPTIONAL.
4
"O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B"
IN THE INSTALLER SETUP.
OPTIONAL INDOOR REMOTE SENSOR OR REMOTE SETBACK.
5
WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT
CABLE.
Fig. 12. Typical hookup of single-stage heat pump
C
G
Y
O/B
4
RC
R
CHANGEOVER VALVE
COMPRESSOR CONTACTOR
with no auxiliary heat (1H/1C).
C
G
Y
O/B
4
RC
R
CHANGEOVER VALVE
with auxiliary heat (2H/1C).
2
FAN RELAY
2
3
3
INDOOR TEMPERATURE
AUXILIARY HEAT RELAY
W1
G2
G3
S1
S2
INDOOR TEMPERATURE
SENSOR/REMOTE
SETBACK
M27421
W1
G2
G3
S1
S2
SENSOR/REMOTE
SETBACK
Fan Coil System Wiring
5
Fig. 13. Typical wiring of 4 pipe fan coil.
5
Fig. 14. Typical wiring of 2 pipe fan coil with reheat.
M27422
Fig. 15. Typical wiring of 2 pipe fan coil without
562-0273—07
reheat.
Loading...
+ 11 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.