Honeywell Home NK300SE-VE Product Specification Sheet

EN0H-1561GE23 R0219
Boiler Room Valves
NK300SE-VE
Refilling combination with heatwater treatment unit and demineralisation cartridge

APPLICATION

The demineralisation unit of the Honeywell NK300SE-VE facilitates the demineralisation of heating water according to VDI-guideline 2035, sheet 1 and 2. Lime scale and thereby caused damages and malfunction in hot water heating system (EN 12828) are avoided efficiently.
The refilling combination fitted on the inlet and based on a BA-type backflow preventer protects the drinking water supply against back flow of heating water according to EN 1717.

SPECIAL FEATURES

Integrated electronic smart monitoring system
simplifies the determination of cartridge exchange
Easy installation, programming and exchange of
cartridge without tools
Permanent connection with the drinking water supply in
accordance with EN 1717 by hose line or piping is possible
Optimal protection of the drinking water supply system
Pressure reducing valve with inlet pressure balancing -
inlet pressure fluctuation does not influence the outlet pressure
Outlet pressure adjustable and directly visible on the
pressure gauge

TECHNICAL DATA

Media
Medium: Water
Freshwater hardness range*: 0°dH-26°dH
0°fH-46,4 °fH 0 mmol/l - 4,64 mmol/l
Connections/Sizes
Connection size discharge: HT40
Connection size:
Connection ball valve backflow preventer:
Pressure values
Max. inlet pressure: 10 bar
Outlet pressure: 1.5 - 4 bar
Preset outlet pressure: 1.5 bar
Operating temperatures
Max. operating temperature medium:
1
/2" external thread
G 1/4"
30 °C
Specifications
Liquid category backflow preventer BA:
Installation position: horizontal pipework with
* In order to estimate the capacity of the cartridge for fresh water hardness > 26°dH/46,4 °fH/4.64 mmol/l a manual calculation method has to be used. (see Installation Manual of the P300 cartridges incl. in the packaging of the cartridges)
4 (toxic, highly toxic, tumourigenic, radioactive materials)
discharge connection directed downwards
Suitable for heating systems with the following materials: aluminium, aluminium alloys, steel, copper, copper alloys and plastics.
Treated water has modified corrosive chemical parameters. Conditioning by means of inhibitors is to be provided for separately.
Product Specification Sheet • EN0H-1561GE23 R0219 • Subject to change 1
NK300SE-VE - Refilling combination with heatwater treatment unit and demineralisation cartridge

CONSTRUCTION

Overview Components Materials
1 42
1 Integrated isolation valve,
3
15
6
7
inlet and outlet side
2 Backflow preventer type BA
with discharge valve, cartridge insert, integrated dirt trap on the inlet side, backflow preventer outlet side and three measuring points with sealing plugs
3 Pressure reducing valve with
pressure gauge
4 Integrated electronic smart
monitoring system
5 Bleed valve 6 Insulation shells EPP 7 Demineralisation cartridge Polypropylene
Not depicted components:
Adjustment spring Spring steel
Seals NBR, EPDM
Diaphragm Fibre-reinforced EPDM
Discharge valve, cartridge insert, valve insert, mechanical components of the refilling unit and spring bonnet
Hardness test-kit to determine water hardness
Fine filter mesh Stainless steel
Dezincification-resistant brass
High-quality plastic

METHOD OF OPERATION

In the first instance the water passes through the refilling combination which protects the system against back flow of heating water. It combines backflow preventer, pressure reducing valve and ball valves in one appliance.
The backflow preventer changes to shut-off position (back pressure) if the differential pressure between middle- and inlet chamber falls under 0.14 bar. The check valves are closed and the discharge valve is opened.
The pressure reducing valve reduces the inlet pressure to the desired set-pressure on the outlet side.
Inlet pressure fluctuation does not influence the outlet pressure, because the pressure reducing valves operate by means of a force equalising system (inlet pressure balancing).
The heatwater treatment unit (VE300S) installed directly below the refilling combination (NK300S) uses the ionic exchange principle to demineralise water and extracts all minerals from the water. Thereby the electric conductivity of the filling water is reduced.

TRANSPORTATION AND STORAGE

Keep parts in their original packaging and unpack them shortly before use.
The following parameters apply during transportation and storage:
Parameter Value
Environment: clean, dry and dust free
Min. ambient temperature: +5 °C
Max. ambient temperature: +40 °C
Min. ambient relative humidity: 25 % *
Max. ambient relative humidity: 75 % *
*non condensing