Honeywell VVT, VVT-HC User Manual

VVT, VVT-HC (T641A,C)
Floating Control Thermostats
Installation Instructions for the Trained Service Technician.
Application
The VVT and VVT-HC Thermostats provide spdt outputs to control floating actuators in applications such as variable air volume (VAV) terminal units.
thermostat.
—VVT-HC (T641C): provides manual heat/cool
changeover switch.
Operation
FLOATING CONTROL
The control provided by the thermostat is conventionally called floating control . During floating control, a variation of two-position control, the thermostat provides a three output control, which is Advance motor, Reverse motor, and Hold.
On a change in temperature, the thermostat drives the actuator to an intermediate position and then opens the circuit to the actuator. The actuator remains in this position until there is a temperature change at the thermostat. The actuator is said to float between the limits of the thermostat to satisfy various load requirements.
VAV SYSTEMS
VAV systems control the temperature within a space by varying the volume of supply air. Air is delivered to the space at a fixed temperature. The volume of supply air is controlled by the space thermostat modulating the supply air damper. When full heating and cooling flexibility is required in a zone, it is handled by perimeter heating, or reheat capability in the air terminal units. As individual zones shut down, the total air flow in the system is regulated by a central duct static pressure controller. The fan system is sized to handle an average peak load, not the sum of the individual peaks. Because each zone peaks at a different time of day, extra air is borrowed from the off-peak zones. This transfer from low-load to high-load zones occurs only in true VAV systems.
Pressure dependent systems do not incorporate an indi­vidual zone air flow sensor and depend on a stable system pressure to maintain flow. These systems require slower motors such as the seven minute dampers, which are typically controlled by the VVT (T641A) or VVT-HC (T641C) Ther­mostats.
HEAT ANTICIPATION/COOL ANTICIPATION
Control of heating or cooling units with a thermostat does not allow for the temperature to remain exactly at the thermo­stat set point, but varies within a certain temperature range. Anticipation is added to the thermostat to reduce this range.
The anticipator is a small resistive heater in the thermostat that heats when the system is on or off. The heat produced by the anticipator raises the internal bimetal temperature slightly faster than the surrounding room temperature. The thermo­stat anticipates the need to shut off the heating system sooner than it would if affected by room temperature only. The VVT (T641A) or VVT-HC (T641C) have fixed or voltage antici­pation.
Installation
WHEN INSTALLING THIS PRODUCT…
1. Read these instructions carefully. Failure to follow
them could cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained experienced service technician.
4. After installation is complete, check out product op­eration as provided in these instructions.
CAUTION
!
1. Disconnect power supply to prevent electrical shock or equipment damage.
2. To prevent interference with the thermostat link­age, keep wire length to a minimum and run wires as close as possible to the subbase.
3. Do not overtighten thermostat captive mounting screws, because damage to subbase threads can result.
4. Do not short across coil terminals on relay. This can burn out the thermostat heat anticipator.
IMPORTANT: An incorrectly leveled thermostat will cause
the temperature control to deviate from set point. It is not a calibration problem.
J. H. • 7-92 • © Honeywell Inc. 1992 • Form Number 69-0726
LOCATION
Install the thermostat about 5 ft. [1.5 m] above the floor in an area with good air circulation at average temperature. Do not install the thermostat where it may be affected by—
— drafts or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas behind the thermostat, such
as an outside wall.
MOUNTING AND WIRING
IMPORTANT: The VVT (T641A) and VVT-HC (T641C)
are electrically compatible and designed to operate with actuators that have seven minute timings for a full stroke of 90° (angular). Using with motors that have timings less than seven minutes (90° full stroke) will result in unstable temperature control.
The thermostat can be mounted on a horizontal outlet box or directly on the wall. Choose the method that best fits your installation.
In replacement applications, check the existing thermo­stat wires for cracked or frayed insulation. Replace any wires in poor condition. All wiring must comply with local codes and ordinances. The thermostat utilizes a four-wire opera­tion, so an additional transformer common wire must be present for correct wiring and operation. See Fig. 1 for functional schematic of thermostat. Screw terminals are located on the back of the thermostat. See Fig. 2.
The Honeywell part no. 221618 Cover Plate is available when replacing a competitive device that has left marks on the wall. See Fig. 3.
1. Grasp the thermostat cover at the top and bottom with one hand. Pull outward on bottom edge of the cover until it snaps free of the thermostat base. Carefully remove and save the packing material surrounding the mercury switches. See Fig. 3.
2. Run wiring from the actuator (if necessary) to the location. If the wiring is plastered into the wall, make a hole next to the cable and loosen the wires so they can be pushed back into the wall later. Thread wires through hole in packing material saved in step 1. Connect the wires to the terminals on the back of the thermostat. See Fig. 4.
3. Push the excess wire back through the hole and plug any opening with packing material to prevent drafts that may affect thermostat performance.
4. Through the thermostat two middle mounting holes, use the screws provided to loosely secure the thermostat to the wall or outlet box.
5. Level the thermostat exactly using a spirit level or plumb line. Tighten the two mounting screws in the middle of the device. See Fig. 3.
IMPORTANT: An incorrectly leveled thermostat will cause
the temperature control to deviate from set point. It is not a calibration problem.
6. Install two screws in top mounting holes and tighten.
7. Replace the thermostat cover.
WARNING
!
Because the cooling anticipator operates con­tinuously in the floating band, the VVT (T641A) and VVT-HC (T641C) Thermostats incorporate a factory offset that calibrates the thermostat. The offset causes the thermostat to appear to be switch­ing 10.5°F lower when not powered compared to actual operation. The cooling anticipator is needed to provide proper thermostat cycling by matching the current draw of the damper actuator. To ensure proper thermostat calibration and operation, the C terminal must be used.
Fig. 1—Functional equivalent anticipator circuit of thermostat.
SOLID STATE RELAY
HEAT
FALL
RISE
1
HEAT ANTICIPATOR
COOL ANTICIPATOR
COOL
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
N.O.
SOLID STATE RELAY
N.C.
2
W
C
Y
R
DAMPER CONTROL
DRIVE CLOSED COIL
DRIVE OPEN COIL
1
L1 (HOT)
L2
M6112
Loading...
+ 2 hidden pages