On-Off Actuator for VC Series Balanced Hydronic Valves
These 2-position (open/close) control actuators are used with VCZ
1000, 1100, 6000 and 6100 series hydronic valves in a normal
indoor environment to provide quick opening/closing to control the
flow of hot and/or chilled water or glycol solution to 60% concentration. They are designed for on-off "zone" control of heating/cooling
systems, or to control individual fan coil, baseboard radiator or
convector applications.
Depending on the model selected, the actuator can be controlled
by a low or line voltage SPST or SPDT controller, such as a room
thermostat, aquastat or flow switch.
VC80 series valve actuators are designed to be used with hardwired electronic thermostats with series anticipator or powerstealing thermostats. Recommended control thermostats include
T8601D, T8401C, T8380 and T8360 families.
VC actuators use cam-operated cartridge travel to resist water
hammer. Internal limit switches prevent motor overrun. Some of
these actuators have conformally coated printed circuit boards for
humidity resistance.
VC2, VC4, VC60, VC8
SPECIFICATIONS
The specifications following are nominal and conform to generally
accepted industry standards. Honeywell is not responsible for damages
resulting from misapplication or misuse of its products.
Voltage: Label Colour Code
24V 50Hz ; 24V 60Hz Models Blue
100-130 V 50-60 Hz Model Black
200-240 V 50-60 Hz Model Red
Power consumption:
6 Watts Max. at nominal Voltage (during valve position change).
Use 24 V Class 2 transformer.
Provide 6 VA per valve for transformer and connection wire sizing.
Maximum Duty Cycle: 15%
Nominal timing: Valve opens in 6 seconds @ 60 Hz (20% longer @
50 Hz)
Electrical termination: Available in 3 versions:
(1) Molex™ (header # 39-30-1060). Requires mating
connector (receptacle/housing # 39-01-2060). OR
(2) integral 1 meter [nominal 39"] leadwire cable.
(3) 5 feet [1.5 meter] plenum-rated cable per UL94-5V.
Includes plastic adapter for use with 3/8" flexible conduit.
End switch rating :
2.2 A inductive from 5 to 110 Vac,
1.0 A inductive above 110 to 277 Vac.
Min. DC switching capability: 5 mA @ 24 Vdc
Operating ambient temperature:
0 to 65°C [32 to 150°F]
Humidity Rating: 5-95% RH (non-condensing)
Fluid temperatures: 34 to 203°F [1 to 95°C]
Shipping & storage temperature: -40 to +65°C [-40 to +150°F]
Atmosphere: non-corrosive, non-explosive
Nominal Dimensions (Actuator only):
3-23/32" width x 2-11/16" depth x 2-3/4" height
94 mm width x 68 mm depth x 70 mm height
[1] No adapters
[2] Suitable for use as15 mm compression fitting
[3] Dimensions shown with nuts and olives installed
[4] Some models not available in all countries
Table 2 - VC Valve assembled dimensions
MANUAL OPENER
The manual opener can be manipulated only when in the up position.
The motorized valve can be opened by firmly pushing the red manual
lever down to midway and in. This holds the valve in the open
position. This "manual open" position may be used for filling, venting,
draining the system or for opening the valve in case of power failure.
The valve can be restored manually to the closed position by
depressing the red manual lever lightly and then pulling the lever out.
The valve and actuator will return to the automatic position when
power is restored.
NOTE: If the valve is powered open (the lever is down), it can not be
manually closed unless actuator is removed.
INSTALLATION
WHEN INSTALLING THIS PRODUCT:
1. Read these instructions carefully. Failure to follow them could
damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to
make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. Always conduct a thorough checkout when installation is com-
E
pleted.
5. While not necessary to remove the actuator from the body, it can
be removed for ease of installation. The actuator can be installed
in any position to suit the most convenient wiring mode.
6. An extra 1" (25 mm) head clearance is required to remove the
actuator.
CAUTION:
!
Disconnect power supply before connecting wiring to prevent
electrical shock and equipment damage.
On 24 V systems, never jumper the valve coil terminals, even
temporarily. This may damage the thermostat.
2
130 5-1/8
140 5-1/2
136 5-11/32
136 5-11/32
147 5-13/16
136 5-11/32
130
5-1/8
5-3/16
136
5-11/32
Page 3
1
2
3
PLUMBING
5
Port "A"
4
1
*
AUX.SW.
3 2 1
3
Closed
Open
6
2
(3 WIRE)
*
Valve
5
46
MODELS
L
~
N
Port "A"
Closed
Open
L
~
N
* AUX.SW.
MODELS
1
( 2 WIRE +
COMMON)
*
Valve
5
3 12
46
2
5
4
6
3
Refer to the VC Series Cartridge Valve Installation and Instruction
sheet, form number 95C-10919, for plumbing instructions.
IMPORTANT:
For trouble-free operation of the product, good installation
!
practice must include initial system flushing, chemical
water treatment, and the use of a 50 micron (or finer)
system side stream filter(s). Remove all filters before
flushing.
Put the VC actuator manual lever in the manual open or the
fully open (down) position to allow initial system flushing with
the actuator mounted. This may be done without electrical
hook-up. Alternatively, reusable flush caps, part # 272866B,
may be purchased separately for use in initial flushing of dirty
hydronic systems.
Do not use boiler additives, solder flux and wetted
materials which are
oil, hydrocarbons, or ethylene glycol acetate
which can be used, with minimum 50% water dilution, are
diethylene glycol, ethylene glycol, and propylene glycol
(antifreeze solutions).
TO INSTALL ACTUATOR
Installation of the actuator does not require draining the system,
provided the valve body and valve cartridge assembly remain in the
pipeline. Wiring may be done either before or after the actuator is
installed.
1. The actuator head is automatically latched to the valve. Align the
coupling hole in the bottom of the actuator with the valve stem.
Press the actuator down towards the body with moderate hand force
and turn the actuator counter-clockwise by 1/8 turn (45 degrees) to
line up the actuator with the piping. The latch will click when
engaged. See Figure 2.
NOTE: The actuator can also be installed at right angles to the valve
body but in this position the latch mechanism will not engage.
2. Connect leadwires. See Figure 3 for flexible conduit installation
with plenum-cable models.
petroleum based
or contain
. Compounds
mineral
3
4
3/8" flex
conduit
2
Figure 3 - Flexible Conduit Attachment
1
WIRING
NOTE: Each 3-wire (SPDT) actuator must have individual spdt
controller. Use series 40 or 80 for single controller to control
multiple valves.
Figures 4, 5, 6 and 7 show wiring connections. Port "A"
closed
denote valve open and closed positions respectively. On
auxiliary switch models, terminal 4 (grey wire) contact makes at the
end of the Port A opening stroke. On Molex connector models, valve
& auxiliary switch boltage must be the same to meet approval
requirement. For mixed line voltage and 24 VAC (Safety Extra Low
Voltage) application, the cable version is recommended.
CAUTION:
!
Disconnect power supply before connecting wiring to prevent
electrical shock and equipment damage.
Figure 4 - Wire configuration for MOLEX™ models for
Figure 5 - Wiring color code for cable models for SPDT
SPDT controller. (Series 20 & 60).
WHITE
ORANGE
GREY
*
AUX.SW.
MODELS
controller. ( Series 20 & 60 )
Valve
*
(3 WIRE)
BROWN
BLACK
BLUE
Port "A"
Closed
Open
~
open
L
N
and
Figure 2 - Latch Mechanism to detach Actuator
Figure 6 - Wire configuration for MOLEX™ models for SPST
Figure 7 - Wiring color code for cable models for SPST
controller. (Series 40 & 80)
WHITE
ORANGE
GREY
*
AUX.SW.
MODELS
controller. ( Series 40 & 80)
Valve
*
( 2 WIRE +
COMMON)
BROWN
BLACK
BLUE
Port "A"
Closed
Open
~
L
N
3
Page 4
OPERATION
Actuator
3-WIRE
(for SPDT
controller)
2 + COM.
(for SPST
controller)
WHEN USED WITH SPDT (3-WIRE) CONTROLLER
a call for heat, the NO thermostat contacts close, the valve opens.
When the valve reaches the fully open position, the cam actuated
SW1 closes and SW2 opens. When the need for heat is satisfied
the NC thermostat contacts close, energizing the valve through
SW1 to close the valve. When the valve reaches the fully close
position, the cam actuated SW2 closes and SW1 opens anticipating
the next call for heat cycle.
In a power failure the valve will stay at whatever position it was in
when the power was interrupted. When power is restored, the valve
will respond to the controller demand.
CONTROLLER
Blue & Brown energised
Black de-energized
Blue & Black energised
Brown de-energized
Blue & Brown energised
Blue & Brown energised
S.P.D.T.
BROWN
NC
NO
Black open
Black closed
BLACK
L
~
N
Figure 8 - Actuator wiring for SPDT controller
NOTE: VC2114 and VC8114 actuators must be used with sepa-
rately-powered (hardwired) electronic controllers. Their sustained
current draw is too low for power stealing (parasitic power)
thermostats or series anticipators of electromechanical thermostats.
WHEN USED WITH SPST CONTROLLER
heat, RLY1 is energized making the NO contacts in SW3, the valve
opens. When the valve reaches the fully open position the cam
operated SW1 closes and SW2 opens. When need for heat is
satisfied,
BLUE
Connection
Pin #2 & #3 energised Pin
Pin #2 & #6 energised Pin
Pin #2 & #3 energised Pin
Pin #2 & #3 energised Pin
TM
Model
#6 de-energised Closes
#3 de-energised Opens
#3 & #6 open Closes
#3 & #6 closed Opens
(Figure 8): On
Valve
Close
3
Open
6
2
SW1
SW2
CW
CAM
AC
MOTOR
"VC "HYDRONIC VALVE
(Figure 9): On a call for
Valve
MovementType Cable Model Molex
the thermostat contacts open, RLY1 is de-energized and the valve
motor is driven closed through SW1 and the NC contacts of SW3.
When the valve reaches the fully closed position, the cam operated
SW2 closes and SW1 opens anticipating the next call for heat
cycle.
Valve
3
Close
SW1
NC
SW3
Open
6
SW2
CW
NO
AC
MOTOR
CAM
2
RLY1
L
~
N
BROWN
S.P.S.T
CONTROLLER
BLACK
BLUE
.
"VC" HYDRONIC VALVE
Figure 9 - Actuator wiring for SPST controller
CHECKOUT
1. Raise the set point of the thermostat above room temperature to
initiate a call for heat. Red valve position lever should move
downward to the open position.
2. For auxiliary switch models, observe all control devices. The valve
should open and the auxiliary switch (if present) should close and
make at the end of the opening stroke to activate auxiliary
equipment.
3. Lower the set point of the zone thermostat below room temperature.
4. Observe the control devices. The valve should close and all auxiliary
equipment should stop.
SERVICE
This valve should be serviced by a trained, experienced service
technician.
1. If the valve is leaking, drain system OR isolate valve from the
system.
2. Check to see if the cartridge needs to be replaced.
3. If the motor or other internal parts of the actuator is damaged,
replace the entire actuator assembly.
NOTE: Honeywell hydronic valves are designed and tested for silent
operation in properly designed and installed systems. However, water
noises may occur as a result of excessive water velocity. Piping noises
may occur in high temperature (over 212°F [100°C]) systems with
insufficient water pressure.
Automation and Control Solutions
Environmental Control Products
1985 douglas Drive North
Golden Valley, MN 55422-3992
U.S.A.
In Canada:
Honeywell Limited-Limitee
35 Dynamic Drive
Toronto, ON M1V 4Z9
Canada
Printed in Canada
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.