Honeywell VC2010zz00, VC2011zz00, VC2012zz00, VC2611zz00, VC4012zz00 Quick Start Manual

...
Page 1
On-Off Actuator for VC Series Balanced Hydronic Valves
These 2-position (open/close) control actuators are used with VCZ 1000, 1100, 6000 and 6100 series hydronic valves in a normal indoor environment to provide quick opening/closing to control the flow of hot and/or chilled water or glycol solution to 60% concentra­tion. They are designed for on-off "zone" control of heating/cooling systems, or to control individual fan coil, baseboard radiator or convector applications.
Depending on the model selected, the actuator can be controlled by a low or line voltage SPST or SPDT controller, such as a room thermostat, aquastat or flow switch.
VC80 series valve actuators are designed to be used with hard­wired electronic thermostats with series anticipator or power­stealing thermostats. Recommended control thermostats include T8601D, T8401C, T8380 and T8360 families.
VC actuators use cam-operated cartridge travel to resist water hammer. Internal limit switches prevent motor overrun. Some of these actuators have conformally coated printed circuit boards for humidity resistance.
VC2, VC4, VC60, VC8

SPECIFICATIONS

The specifications following are nominal and conform to generally accepted industry standards. Honeywell is not responsible for damages resulting from misapplication or misuse of its products.
Voltage: Label Colour Code
24V 50Hz ; 24V 60Hz Models Blue 100-130 V 50-60 Hz Model Black 200-240 V 50-60 Hz Model Red
Power consumption:
6 Watts Max. at nominal Voltage (during valve position change). Use 24 V Class 2 transformer. Provide 6 VA per valve for transformer and connection wire sizing.
Maximum Duty Cycle: 15% Nominal timing: Valve opens in 6 seconds @ 60 Hz (20% longer @
50 Hz)
Electrical termination: Available in 3 versions:
(1) Molex™ (header # 39-30-1060). Requires mating
connector (receptacle/housing # 39-01-2060). OR (2) integral 1 meter [nominal 39"] leadwire cable. (3) 5 feet [1.5 meter] plenum-rated cable per UL94-5V.
Includes plastic adapter for use with 3/8" flexible conduit.
End switch rating :
2.2 A inductive from 5 to 110 Vac,
1.0 A inductive above 110 to 277 Vac. Min. DC switching capability: 5 mA @ 24 Vdc
Operating ambient temperature:
0 to 65°C [32 to 150°F]
Humidity Rating: 5-95% RH (non-condensing) Fluid temperatures: 34 to 203°F [1 to 95°C] Shipping & storage temperature: -40 to +65°C [-40 to +150°F] Atmosphere: non-corrosive, non-explosive Nominal Dimensions (Actuator only):
3-23/32" width x 2-11/16" depth x 2-3/4" height 94 mm width x 68 mm depth x 70 mm height
Accessories:
272866B Valve Flushing Cap
2003.02.24 © Honeywell Limited.
Form No. 95C-10920
Page 2
MODELS:
94 [3-3/4]
68 [2-3/4]
94 [3-3/4]
A
B
B
AB
A
D
90 [3-9/16]
C
C
n
Actuator Only: VC2, VC4, VC60, VC8 (See Table 1) Bodies (Order Separately): VCZ..., (See 95C-10919)
Actuators
Model No. Power
VC2010zz00 VC2011zz00 VC2012zz00 [1] VC2611zz00 VC4012zz00 VC4013zz00 VC4013zz11 [3] VC4613zz00 VC6012zz00 VC6013zz00 VC6013zz11 [3] VC6612zz00 VC6613zz00 VC8011zz00 VC8611zz00
VC2114zz11 [3] VC2714zz11 [3] VC4011zz11 [3] VC4013zz11 [3] VC8111zz11 [3] VC8114zz11 [3] VC8711zz11 [3] VC8714zz11 [3]
NOTE: [1] with Snubber circuit [2] Plenum rated with 1.5 meter cable
[3] Model number ending with "11" has conformal coated printed circuit
board for heating/cooling use.
[4] Some models are not available in all countries. Not all VC Actuator modes are shown.
INTERNATIONAL MODEL [4]
24V~50Hz 24V~50Hz 24V~50Hz
24V~50Hz 200-240V~50-60Hz 200-240V~50-60Hz 200-240V~50-60Hz 200-240V~50-60Hz 200-240V~50-60Hz 200-240V~50-60Hz 200-240V~50-60Hz 200-240V~50-60Hz 200-240V~50-60Hz
24V~50Hz
24V~50Hz
NORTH AMERICA MODELS [4]
24V~60Hz
24V~60Hz
120V~60Hz
200-240V~50-60Hz
24V~60Hz
24V~60Hz
24V~60Hz
24V~60Hz
Control
Table 1 - Actuator Model Identifiers
VC Valve Assembled dimensions for reference (Figure 1 & Table 2):
Figure 1 - Nominal dimensions in inches and millimetres
Auxiliary
Input
SPDT - - Molex SPDT - - Cable SPDT - - Molex SPDT Yes Cable SPST - - Molex SPST - - Cable SPST - - Cable SPST Yes Cable SPDT - - Molex SPDT - - Cable SPDT - - Cable SPDT Yes Molex SPDT Yes Cable SPST - - Cable SPST Yes Cable
SPDT - - Plenum[2] SPDT Yes Plenum[2] SPST - - Cable SPST - - Cable SPST - - Cable SPST - - Plenum[2] SPST Yes Cable SPST Yes Plenum[2]
Switch
Special
Features
[4] Dimensio
Pipe Fitting Sizes
1/2" BSPP (int.) [2] 1/2" BSPT (int.)
C D E
mm Inches mm Inches mm Inches
98 3-7/8 111 4-3/8 136 5-11/32
3/4" BSPP (int.) 3/4" BSPT (int.) 3/4" BSPP (ext.) 22mm Compression [3] 112 1" BSPP (int.) 94 1" BSPP (ext.) 1" BSPT (int.) 94 28mm Compression [3] 116
NORTH AMERICA STANDARD MODELS
3/8" FLARE [1] 98 1/2" SWEAT 89 1/2" FLARE [1] 1/2" INVERTED FLARE [1]
94 3-11/16
113 4-7/16
4-7/16
3-11/16
95 3-11/17 114 4-7/17 137 5-11/33
3-11/16
113 4-7/16
4-9/16
3-7/8 3-1/2 130 5-1/8
111 4-3/8
98 3-7/8 136 5-11/32 1/2" NPT (int.) 3/4" NPT (int.) 3/4" SWEAT 132 1" NPT (int.)
94 3-11/16 113 4-7/16
1" SWEAT 1-1/4" SWEAT 1-1/4" NPT (int.)
110 4-5/16 118 4-5/8 142 5-5/8
[1] No adapters [2] Suitable for use as15 mm compression fitting [3] Dimensions shown with nuts and olives installed [4] Some models not available in all countries
Table 2 - VC Valve assembled dimensions
MANUAL OPENER
The manual opener can be manipulated only when in the up position. The motorized valve can be opened by firmly pushing the red manual lever down to midway and in. This holds the valve in the open position. This "manual open" position may be used for filling, venting, draining the system or for opening the valve in case of power failure. The valve can be restored manually to the closed position by depressing the red manual lever lightly and then pulling the lever out. The valve and actuator will return to the automatic position when power is restored. NOTE: If the valve is powered open (the lever is down), it can not be manually closed unless actuator is removed.

INSTALLATION

WHEN INSTALLING THIS PRODUCT:
1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. Always conduct a thorough checkout when installation is com-
E
pleted.
5. While not necessary to remove the actuator from the body, it can be removed for ease of installation. The actuator can be installed in any position to suit the most convenient wiring mode.
6. An extra 1" (25 mm) head clearance is required to remove the actuator.
CAUTION:
!
Disconnect power supply before connecting wiring to prevent electrical shock and equipment damage.
On 24 V systems, never jumper the valve coil terminals, even temporarily. This may damage the thermostat.
2
130 5-1/8
140 5-1/2 136 5-11/32
136 5-11/32 147 5-13/16
136 5-11/32
130
5-1/8
5-3/16
136
5-11/32
Page 3
1
2
3

PLUMBING

5
Port "A"
4
1
*
AUX.SW.
3 2 1
3
Closed
Open
6
2
(3 WIRE)
*
Valve
5
46
MODELS
L
~
N
Port "A"
Closed
Open
L
~
N
* AUX.SW.
MODELS
1
( 2 WIRE + COMMON)
*
Valve
5
3 12
46
2
5
4
6
3
Refer to the VC Series Cartridge Valve Installation and Instruction sheet, form number 95C-10919, for plumbing instructions.
IMPORTANT:
For trouble-free operation of the product, good installation
!
practice must include initial system flushing, chemical water treatment, and the use of a 50 micron (or finer) system side stream filter(s). Remove all filters before flushing.
Put the VC actuator manual lever in the manual open or the fully open (down) position to allow initial system flushing with the actuator mounted. This may be done without electrical hook-up. Alternatively, reusable flush caps, part # 272866B, may be purchased separately for use in initial flushing of dirty hydronic systems.
Do not use boiler additives, solder flux and wetted materials which are
oil, hydrocarbons, or ethylene glycol acetate
which can be used, with minimum 50% water dilution, are diethylene glycol, ethylene glycol, and propylene glycol (antifreeze solutions).
TO INSTALL ACTUATOR
Installation of the actuator does not require draining the system, provided the valve body and valve cartridge assembly remain in the pipeline. Wiring may be done either before or after the actuator is installed.
1. The actuator head is automatically latched to the valve. Align the coupling hole in the bottom of the actuator with the valve stem. Press the actuator down towards the body with moderate hand force and turn the actuator counter-clockwise by 1/8 turn (45 degrees) to line up the actuator with the piping. The latch will click when engaged. See Figure 2. NOTE: The actuator can also be installed at right angles to the valve body but in this position the latch mechanism will not engage.
2. Connect leadwires. See Figure 3 for flexible conduit installation with plenum-cable models.
petroleum based
or contain
. Compounds
mineral
3
4
3/8" flex conduit
2
Figure 3 - Flexible Conduit Attachment
1

WIRING

NOTE: Each 3-wire (SPDT) actuator must have individual spdt controller. Use series 40 or 80 for single controller to control multiple valves.
Figures 4, 5, 6 and 7 show wiring connections. Port "A"
closed
denote valve open and closed positions respectively. On auxiliary switch models, terminal 4 (grey wire) contact makes at the end of the Port A opening stroke. On Molex connector models, valve & auxiliary switch boltage must be the same to meet approval requirement. For mixed line voltage and 24 VAC (Safety Extra Low Voltage) application, the cable version is recommended.
CAUTION:
!
Disconnect power supply before connecting wiring to prevent electrical shock and equipment damage.
Figure 4 - Wire configuration for MOLEX™ models for
Figure 5 - Wiring color code for cable models for SPDT
SPDT controller. (Series 20 & 60).
WHITE
ORANGE
GREY
*
AUX.SW.
MODELS
controller. ( Series 20 & 60 )
Valve
*
(3 WIRE)
BROWN
BLACK
BLUE
Port "A"
Closed
Open
~
open
L
N
and
Figure 2 - Latch Mechanism to detach Actuator
Figure 6 - Wire configuration for MOLEX™ models for SPST
Figure 7 - Wiring color code for cable models for SPST
controller. (Series 40 & 80)
WHITE
ORANGE
GREY
*
AUX.SW.
MODELS
controller. ( Series 40 & 80)
Valve
*
( 2 WIRE + COMMON)
BROWN
BLACK
BLUE
Port "A"
Closed
Open
~
L
N
3
Page 4

OPERATION

Actuator
3-WIRE
(for SPDT
controller)
2 + COM. (for SPST
controller)
WHEN USED WITH SPDT (3-WIRE) CONTROLLER
a call for heat, the NO thermostat contacts close, the valve opens. When the valve reaches the fully open position, the cam actuated SW1 closes and SW2 opens. When the need for heat is satisfied the NC thermostat contacts close, energizing the valve through SW1 to close the valve. When the valve reaches the fully close position, the cam actuated SW2 closes and SW1 opens anticipating the next call for heat cycle. In a power failure the valve will stay at whatever position it was in when the power was interrupted. When power is restored, the valve will respond to the controller demand.
CONTROLLER
Blue & Brown energised
Black de-energized
Blue & Black energised
Brown de-energized
Blue & Brown energised
Blue & Brown energised
S.P.D.T.
BROWN
NC
NO
Black open
Black closed
BLACK
L
~
N
Figure 8 - Actuator wiring for SPDT controller
NOTE: VC2114 and VC8114 actuators must be used with sepa-
rately-powered (hardwired) electronic controllers. Their sustained current draw is too low for power stealing (parasitic power) thermostats or series anticipators of electromechanical thermo­stats.
WHEN USED WITH SPST CONTROLLER
heat, RLY1 is energized making the NO contacts in SW3, the valve opens. When the valve reaches the fully open position the cam operated SW1 closes and SW2 opens. When need for heat is satisfied,
BLUE
Connection
Pin #2 & #3 energised Pin
Pin #2 & #6 energised Pin
Pin #2 & #3 energised Pin
Pin #2 & #3 energised Pin
TM
Model
#6 de-energised Closes
#3 de-energised Opens
#3 & #6 open Closes
#3 & #6 closed Opens
(Figure 8): On
Valve
Close
3
Open
6
2
SW1
SW2
CW
CAM
AC
MOTOR
"VC "HYDRONIC VALVE
(Figure 9): On a call for
Valve
MovementType Cable Model Molex
the thermostat contacts open, RLY1 is de-energized and the valve motor is driven closed through SW1 and the NC contacts of SW3. When the valve reaches the fully closed position, the cam operated SW2 closes and SW1 opens anticipating the next call for heat cycle.
Valve
3
Close
SW1
NC
SW3
Open
6
SW2
CW
NO
AC
MOTOR
CAM
2
RLY1
L
~
N
BROWN
S.P.S.T
CONTROLLER
BLACK
BLUE
.
"VC" HYDRONIC VALVE
Figure 9 - Actuator wiring for SPST controller

CHECKOUT

1. Raise the set point of the thermostat above room temperature to initiate a call for heat. Red valve position lever should move downward to the open position.
2. For auxiliary switch models, observe all control devices. The valve should open and the auxiliary switch (if present) should close and make at the end of the opening stroke to activate auxiliary equipment.
3. Lower the set point of the zone thermostat below room temperature.
4. Observe the control devices. The valve should close and all auxiliary equipment should stop.

SERVICE

This valve should be serviced by a trained, experienced service technician.
1. If the valve is leaking, drain system OR isolate valve from the system.
2. Check to see if the cartridge needs to be replaced.
3. If the motor or other internal parts of the actuator is damaged, replace the entire actuator assembly.
NOTE: Honeywell hydronic valves are designed and tested for silent operation in properly designed and installed systems. However, water noises may occur as a result of excessive water velocity. Piping noises may occur in high temperature (over 212°F [100°C]) systems with insufficient water pressure.
Automation and Control Solutions Environmental Control Products
1985 douglas Drive North Golden Valley, MN 55422-3992 U.S.A.
In Canada:
Honeywell Limited-Limitee 35 Dynamic Drive Toronto, ON M1V 4Z9 Canada
Printed in Canada
Loading...