Honeywell VC PRODUCT DATA

BALANCED 2-WAY AND 3-WAY HYDRONIC VALVES
VC actuator
2-way
VC valve body
Design
VC Series zone valves consist of:
Spindle and cartridge assembly
Actuator with cable or Molex™ socket
Pipe fittings (most versions)
Materials
Valve housing made of bronze
Spindle made of stainless steel
Cartridge made of Ryton™ (polyphenylene sulphide) and
Noryl™ (polyphenylene oxide)
O-ring seals made of EPDM rubber
Actuator cover made of Noryl™ (94V-0)
Actuator base made of Ryton™ (94V-0)
3-way
VC valve body
VC Series
Zone Valves
PRODUCT DATA
Application
Honeywell VC Series balanced 2-position hydronic valves are used in domestic and small commercial heating and cooling applications to control the flow of hot and/or cold water. They consist of an actuator, valve and a cartridge assembly
2-way valves are designed for on-off zone control of domestic systems. 3-way valves can be piped for either diverting or mixing valve applications in domestic central heating and/or cooling systems. Both versions can be used to control indi­vidual fan coil, radiator, space heater or convector applica­tions. Depending on the model selected they can be con­trolled by a low or line voltage SPST or SPDT controller such as a room thermostat, aquastat or flow switch.
VC Series hydronic valves are designed to take advantage of sinusoidal valve actuator travel, and therefore operate silently and reduce water hammer. Through internal logic the actua­tor only takes power while driving the valve to the com­manded position.
The actuator head is removable without affecting the integrity of the water system. All actuator versions are interchangeable with any valve body, offering the highest flexibility for boiler production line assembly, and maintenance. The valve piston construction allows for port sealing that is independent of the differential pressure across the valve. Flow through the 2-way valve can be in either direction, so the ports are not desig­nated. 3-way valves are suitable for both diverting water from AB to A or B, and from A or B to AB.
Features
Rugged design
Control by a low or line voltage SPST or SPDT
controller
Minimal actuator power consumption
Pressure differential up to 4 bar
Double insulated actuator
Quick connect electrical connections
Quick and easy replacement of moving parts
Actuator head installation does not require draining of
the system
High flow rate capacity
Honeywell • All rights reserved EN0H-0327GE25 R0206
VC SERIES
Specifications
Medium Water or water-glycol mixture
pH-value 8...9.5
Operating temperature 1...95°C (34...203°F)
Ambient temperature max. 65°C (149°F)
Operating pressure max. 20 bar (290 psi) static
Differential pressure max. 4 bar (58 psi)
k
vs (cv)-values see chapter “Dimensions” below
Flow 2-way: flow can be in either
(max. 50% glycol content), quality to VDI 2035
120°C (248°F) short duration peak
max. 100 bar (1,450 psi) burst
direction. When actuator is not mounted valve is in closed position
3-way: bottom port is marked AB. End ports are marked A and B. When actuator is not mounted port A is closed.
Function
VC Series 2-position hydronic valves are used in domestic and small commercial applications to control the flow of hot and/or cold water. They consist of an actuator, valve and a cartridge assembly.All moving and sealing parts of the valve are constructed in the cartridge assembly. The ports are sealed with O-rings on the outer surface of the piston.
When the valve stem is driven down to open port A the water will flow through the hollow piston to the other port. In case of
2-way valve
With an SPDT (3-wire) actuator
On a call for heat, the NO controller contacts close and the valve opens. When the valve is fully open, the cam closes switch SW1 and opens switch SW2. When the need for heat is satisfied the NC controller contacts close, energising the valve through SW1 and closing the valve. When the valve is fully closed, the cam closes SW2 and opens SW1. The valve is ready for the next call for heat.
With an SPST (2-wire and common) actuator
On a call for heat, the controller contacts close, RLY1 is e­nergized making the NO contacts in switch SW3 causing the valve to open. When the valve reaches the fully open position the cam closes switch SW1 and opens switch SW2. When the need for heat is satisfied, the controller contacts open, RLY1 is de-energized and the valve motor is driven through SW1 and the NC contacts of SW3. When the valve reaches the fully closed position, the cam closes SW2 and opens SW1. The valve is ready for the next call for heat.
Voltage 24 V, 50-60 Hz (blue label)
200-240 V, 50-60 Hz (red label)
Power consumption 4 VA
(when valve position changes)
Auxiliary switch rating 1.0 A @ 250 V, 50-60 Hz
(minimum 0.05 A @ 24 Vdc)
Nominal timing Valve opens in 7 seconds
(20% faster for 60 Hz)
Electrical termination 1. Molex™ socket: requires
mating connector, alternatively
2. With integral 1 m leadwire
Shipping temperature -40…65°C (-40…149°F)
Humidity rating 5…95% RH (non-condensing)
Atmosphere non-corrosive, non-explosive
a 3-way valve with the piston driven down port B is sealed, allowing flow between port AB and port A. With the stem up the flow is between port AB and port B.
The valve family offers a variety of versions of pipe connecti­ons to suit the different applications. The valve pressure loss characteristic is dependent on the pipe connections/ dimensi­ons. For the actual valve rating please refer to the specificati­on section.
For both types of actuator a power failure will leave the valve at the position it was when interrupted. When power is resto­red, the valve will respond to controller demand.
Fig. 1. Fluid flow through 2-way VC valve
EN0H-0327GE25 R0206 2 Honeywell • All rights reserved
3-way diverter valve
With an SPDT (3-wire) actuator
On a call for heat, the NO controller contacts close, the valve closes port B and opens port A. When port A is in the fully open position the cam closes limit switch SW1 and opens limit switch SW2. When the need for heat is satisfied the NC controller contacts close, energising the valve through SW1, causing port A to close. When port A is fully closed the cam closes SW2 and opens SW1. The valve is ready for the next call for heat.
With an SPST (2-wire and common) actuator
On a call for heat the controller contacts close, RLY1 is ener­gized making the NO contacts in switch SW3, causing port B to close and port A to open. When port A reaches the fully open position the cam closes switch SW1 and opens switch SW2. When the need for heat is satisfied, the controller con­tacts open. RLY1 is de-energized making the NC contacts in SW3 and port A is driven closed through SW1 and the NC contacts of SW3. When port A is in the fully closed position the cam closes SW2 and opens SW1. The valve is ready for the next call for heat.
Wiring
Figures 3 and 4 show wiring connections for 2-way and 3-way valves. Port A open and closed denotes valve open and clo­sed for 2-way, and AB-A open and AB-B open for 3-way valves respectively. A means for disconnection from the supply having a contact separation of at least 3 mm in all
VC SERIES
For both types of actuator a power failure will leave the valve at the position it was in when interrupted. When power is restored, the valve will respond to controller demand.
Fig. 2. Fluid flow through 3-way VC valve
poles must be incorporated in the fixed wiring. On Molex™ connector models, actuator and auxiliary switch voltages must be the same to meet the approval requirement. For mixed voltages, the cable assembly version is recommended.
Fig. 3. Logic sequence diagram with 3-wire actuator for
SPDT contoller
Honeywell • All rights reserved EN0H-0327GE25 R0206
Fig. 4. Logic sequence diagram with 2-wire + common
actuator for SPST contoller
VC SERIES
Dimensions
Fig. 5. 2-way VC valve
Table 1. Dimensions and k
Body 2-way VC valve 3-way VC valve
C kvs-value C D kvs-value
15mm compression 98 3.4 98 136 4.3
22mm compression* 112 6.8 112 140 8.6
28mm compression* 112 7.7 112 140 8.6
1/2” BSPP (external) 98 3.4 98 136 4.3
3/4” BSPP 94 6.8 94 130 7.7
1” BSPP 94 7.7 94 136 8.6
1/2” sweat 98 3.4 98 136 4.3
3/4” sweat 94 6.8 94 132 8.6
1” sweat 94 8.6 94 136 8.6
NOTE: All dimensions in mm * Includes compression nuts and olives
vs-value
Fig. 6. 3-way VC valve
Ordering Information
Use the Valve Selection Chart to find the right version. The Valve Selection Chart provides the necessary information to put together the OS-No. (OS=Ordering System). Example with OS-No. VC6012MP6000E:
VC6012MP6000E
Product family. Always “VC”
Actuator specifier –
see Valve Selection Chart column A
Body specifier –
see Valve Selection Chart column B
Accessories and packing specifier – see Valve Selection Chart column E
Customisation specifier – see Valve Selection Chart column D
Cartridge specifier – see Valve Selection Chart column C
EN0H-0327GE25 R0206 4 Honeywell • All rights reserved
Valve Selection Chart
VC SERIES
Honeywell • All rights reserved EN0H-0327GE25 R0206
VC SERIES
Installation
WARNING
Installer must be a trained, experienced service person.
When installing this product:
Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous condition.
Check the ratings given in the instructions and on the
product to make sure it is suitable for your application.
Always conduct a thorough checkout after installation.
Plumbing
Fig. 7. Plumbing
To install a replacement actuator head
Fig. 8. Latch mechanism
CAUTION
Disconnect power supply before wire connection to
prevent electrical shock and equipment damage.
It is advisable to remove the actuator head from the
valve body for ease of installation. Fit the actuator head in the most convenient position for wiring.
On sweat fitted valves, the cartridge is shipped loose
or is removed to avoid being damaged during the sol­der operation.
On 24 V systems, never short circuit the valve coil
terminals. This may burn out the heat anticipator in the thermostat.
To remove the actuator head 25 mm clearance is
needed above the actuator.
The valve may be plumbed in any angle but preferably not with the actuator head below the horizontal level of the valve body. Make sure there is enough room around the actuator head for servicing or replacement.
When used to form part of a central heating system, do not locate it where it will block the system vent, cold feed or any bypass when the valve is closed.
Mount the valve directly in the tube or pipe. Do not grip actuator head while making and tightening plumbing connections. Either hold valve body in your hand or attach adjustable spanner across the hexagonal or flat faces on the valve body.
Compression models
For compression fitted models, tighten the compression nuts enough to make a watertight seal. Take care not to overtighten.
Important
Installation of a new actuator head does not require draining the system providing the valve body and cartridge assembly remain in the pipeline.
1. Disconnect power supply before servicing to avoid electri­cal shock or equipment damage.
2. Disconnect leadwires to actuator head, or depress tab on Molex™ wires for rewiring.
3. The actuator head is automatically latched to valve (see figure 8). To remove, lift up on the latch mechanism lo­cated directly below the red manual open lever. Press the actuator head down towards the body with moderate hand force and turn counter-clockwise by 1/8 turn (45 degrees) simultaneously. Lift the actuator head off the valve body.
NOTE: Actuator can also be installed at right angles to valve
body but in this position latch mechanism is not engaged.
4. Install the new actuator head by reversing process in (3).
5. Reconnect leadwires or Molex™
6. Restore power.
connector and remove. Where appropriate, label
connector.
EN0H-0327GE25 R0206 6 Honeywell • All rights reserved
VC SERIES
Adjustment and Testing
Manual Opener
The manual opener can be manipulated when in the up position. The motorized valve can be opened by firmly pushing the red manual lever down to midway and in (only possible if the actuator is in the upper position). This holds all ports in the open position, and with auxiliary switch models the NO switch is closed. Ports A and B of 3-way valves are opened. This 'manual open' position may be used for filling, venting or draining the system, or for opening the valve in case of power failure. The valve can be restored manually to the closed position by depressing the red manual lever lightly and then pulling it out. The valve actuator returns to the automatic position when power is restored.
Checkout
1. Raise the set point of the thermostat above room tem­perature to initiate a call for heat. Valve position indicator should move downward to the open position.
2. For all auxiliary switch models, monitor the control de­vices. 2-way valve: check that the valve opens, the auxil­iary switch (if present) closes, and at the end of the open­ing stroke the circuit to the circulator or another valve is made. 3-way valve: check that port A opens, port B closes, the auxiliary switch (if present) operates, and at the end of the opening stroke the circuit to the circulator or another valve is made.
3. Lower the set point of the thermostat below room tem­perature.
4. Observe the control devices. 2-way valve: check that the valve closes and all auxiliary equipment stops. 3-way valve: check that port A closes and all auxiliary equipment stops.
Service
WARNING
This valve should be serviced by a trained, experienced service person.
1. If the valve is leaking, drain system or isolate valve from the system.
2. Check to see if the cartridge needs to be replaced.
3. If the gear train or the motor is damaged, replace the actuator assembly.
NOTE: Honeywell hydronic valves are designed and tested
for silent operation in properly designed and in­stalled systems. However, water noises may occur as a result of excessive water velocity. Piping noises may occur in high temperature (over 100 with insufficient water pressure.
°
C) systems
Honeywell • All rights reserved EN0H-0327GE25 R0206
VC SERIES
Flow Diagrams
Fig. 9. Valve pressure loss characteristic
Port flow (%)
Travel (%)
Fig. 10. Typical 3-way valve diverting characteristic at constant pressure on port AB
ACS Control Products
Honeywell GmbH
Möhnestraße 55
59755 Arnsberg, Germany
Phone: +49 (2932) 9880
Fax: +49 (2932) 988324
www.honeywell.com
EN0H-0327GE25 R0206 February 2006 © 2005 Honeywell International Inc. Subject to change • All rights reserved Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route du Bois 37, Switzerland or by its Authorized Representative.
Loading...