Honeywell VBF5011, VBF5013 Installation Instructions

VBF5011, VBF5013 Control Ball Valves With Flanged Connections
INSTALLATION INSTRUCTIONS

APPLICATION

The VBF5011 Two-Way and the VBF5013 Three-Way Control Ball Valve control hot and chilled water with glycol solutions up to 50% in heating, ventilating and air conditioning (HVAC) systems to provide two-position or modulating functions.
These valves can be used with Honeywell electronic actuators.

Application Notes

IMPORTANT
Valve sizing is important for correct system opera­tion. Undersized valves do not have sufficient capacity at maximum load. Oversized valves do not have sufficient authority over the load in modulat­ing applications. Oversized valves can cause excessive cycling and the seat and ball can be damaged because of the restricted opening.
Proper Use
These valves are only for use in cold, warm, and hot water systems. Not suitable for oil or combustible gases. For water application, they are designed for a medium temperature range from -22 to 250°F, at a maximum pressure of 360 psi for 2-1/2" & 3" valves and 240 psi for 4", 5", & 6" valves. The valves are to be operated with the appropriate Honeywell electronic actuators only. Water should be properly filtered, treated and conditioned according to local conditions and the recommendations of the boiler or chiller manufacturers. The installation of strainers and filters is recommended.
IMPORTANT
The presence of excessive iron oxide (red rust) in the system voids the valve warranty.
Required Torque
Honeywell electronic actuators can be utilized with the VBF5011 and VBF5013 valves. See Table 1, which lists the torque requirement for each valve size. See Table 2, which lists the close-off pressure rating for the valves with the different torque actuators. Larger torque actuators may be used, but there is no increase in close-off pressure rating.
Table 1. Torque Requirement
Torque Requirement
Type Size
2-way 2 1/2” 35
3” 35
4” 85
5” 85
6” * 140
3-way 2 1/2” 35
3” 85
4” 85
5” 85
6” * 140
*6" requires 140 in-lb actuator for flows up to 700 gpm.
For flow rates greater than 700 gpm a 200 in-lb actua­tor is recommended.
Table 2. Close-off Pressure Rating
Actuator Type
35 lb-in
Valve
Type
2-way 2-1/2”, 3”100
3-way 2-1/2” 40
3-way 3” 70 70 70 70
2-way, 3-way
2-way, 3-way
2-way, 3-way
Valve
4” 70 70 70 70
5” 70 70 70 70
6” 70 70
(4 Nm)
Size
88 lb-in (10 Nm)
Close-off pressure rating (psi)
175 lb-in
(20 Nm)
(in-lbs)
175 lb-in
(20 Nm)
2-position
300 lb-
in (34
Nm)
Flow Characteristics
VBF5011 Two-Way Control Ball Valves have:
• an equal percentage flow characteristic.
VBF5013 Three-Way Control Ball Valves have:
• between ports A and AB: an equal percentage flow characteristic.
• between ports B and AB: a linear flow characteristic.
62-2035-02
VBF5011, VBF5013 CONTROL BALL VALVES WITH FLANGED CONNECTIONS
CAUTION
M34652
D
H
C
B
A
E
G
F

INSTALLATION

When Installing this Product...

1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazard­ous condition.
2. Check ratings given in instructions and on the prod-
uct to ensure the product is suitable for your appli­cation.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.

Preparation

Safety
The valves are to be installed by skilled personnel and in strict accordance with the installation instructions and local regulations. Honeywell assumes no responsibility for damages or injuries resulting from non-compliance with installation instructions or standard good practice when mounting, operating, or maintaining the valves, even if not explicitly mentioned in the installation instructions. Observe all safety practices.
Equipment Damage Hazard.
Foreign particles like dirt and metal chips can damage the ball seals.
For trouble-free operation of the product, good installation practice must include initial system flushing and chemical water treatment. Clean the lines upstream of particles larger than 1/16 inch diameter (welding slag, pipe scale, sand and other suspended particulate). Use of a 20 mesh system side stream filter is suggested. Remove all filters before flushing.
Do not use boiler additives, solder flux and wetted materials which are petroleum based or contain mineral oil, hydrocarbons or ethylene glycol acetate. Compounds which can be used, with minimum 50% water dilution, are diethylene glycol, ethylene glycol, and propylene glycol (antifreeze solutions).
If installing these valves in an addition to, or retrofitting an existing building, do not assume that the fluid in the existing piping meets these criteria.
IMPORTANT:
1. Hold valve with pipe wrench by hexagonal fitting ONLY. Do NOT handle the valve body with the pipe wrench; product damage may result.
2. Clean the lines upstream of particles larger than 1/16 in. diameter (welding slag, pipe scale and other contaminants).
3. Proceed with installation once the system specif­ics (expansion/contraction of the system and its medium as well as operating pressures) are within tolerances.
4. Eliminate air from system.
5. All the valves are marked to show proper direction.
6. Flow arrows must point in the direction of the flow for proper operation. If the valves are not installed in the correct orientation, improper flow or possi­ble system damage could occur.
Fig. 1. 2-way 2-1/2" & 3" valve dimensions
Table 3. 2-way 2-1/2" & 3" valve dimensions
Size in. Model Number A in. (mm) B in. (mm) C in. (mm) D in. (mm) E in. (mm) F in. (mm) G in. (mm) H in. (mm)
2-1/2 VBF5011A1734/U 9-1/2 (241) 7 (178) 12-3/8 (314) 8-3/4 (222) 4-5/16 (110) 5-1/2 (140) 3/4 (19) 3 (76)
3 VBF5011A1767/U 11 (279) 7-1/2 (191) 12-5/8 (321) 9 (229) 6 (152)
62-2035—02 2
VBF5011, VBF5013 CONTROL BALL VALVES WITH FLANGED CONNECTIONS
M34653
A
C
D
F
I
B
G
E
H
M34656
H
D
C
I
A
B
E
G
F
Fig. 2. 3-way 2-1/2" valve dimensions
Fig. 3. 3-way 3" valve dimensions
Size
in. Model Number
2-1/2 VBF5013B1003/U 9-1/2
(241)
3 VBF5013B1011/U 11
(279)
Table 4. 3-way 2-1/2" & 3" valve dimensions
A
in.
(mm)
B
in.
(mm)
7 (178)
7-1/2 (191)
C
in.
(mm)
15-5/16 (389)
13-1/8 (333)
D
in.
(mm)
8-3/4 (222)
10-5/16 (262)
3 62-2035—02
E
in.
(mm)
4-5/16 (110)
4-13/16 (122)
F
in.
(mm)
5-1/2 (140)
6 (152)
(mm)
3/4 (19)
G
in.
H
in.
(mm)
6-7/16 (164)
6-5/8 (168)
I
in.
(mm)
3 (76)
VBF5011, VBF5013 CONTROL BALL VALVES WITH FLANGED CONNECTIONS
F
G
H
M34655
B
A D
C
E
F
E
B
A
D
C
M34654
Fig. 4. 2-way 4", 5" & 6" valve dimensions
Table 5. 2-way 4", 5" & 6" valve dimensions
Size
in. Model Number
A
in. (mm)Bin. (mm)
C
in. (mm)
D
in. (mm)
4 VBF5011A1858/U 13 (330) 9 (229) 18-1/8 (460) 14-5/8
(371)
5 VBF5011A1882/U 15 (381) 10 (254) 18-13/16
(478)
6 VBF5011A1916/U 16-1/2
(419)
11 (279) 19-11/16
(500)
15-5/8 (397)
16 3/8 (416) 10-1/8
E
in. (mm)
F
in. (mm)
9-3/8 (238) 4-1/2 (114)
9-11/16 (246)
(257)
Fig. 5. 3-way 4", 5" & 6" valve dimensions
62-2035—02 4
VBF5011, VBF5013 CONTROL BALL VALVES WITH FLANGED CONNECTIONS
WARNING
CAUTION
Table 6. 3-way 4", 5" & 6" valve dimensions
B
Size
in. Model NumberAin. (mm)
4 VBF5013B1029/U 13 (330) 9 (229) 1- 13/16
5 VBF5013B1037/U 15 (381) 10
6 VBF5013B1045/U 16-1/2
(419)
in.
(mm)Cin. (mm)Din. (mm)Ein. (mm)
(478)
19-11/16
(254)
11 (279)
(500)
20-3/4 (527)
14-5/8 (371)
15-5/8 (397)
16-3/8 (416)
9-11/16 (246)
10-1/16 (256)
10-11/16 (271)
F
in. (mm)Gin. (mm)Hin. (mm)
8-11/16 (221)
9-5/8 (244) 14-5/8
10-11/16 (271)
1- 3/16 (335)
(371)
16-3/16 (411)
4-1/2 (114)

Valve Installation Location

Select a location where the valve and actuator will be accessible once installed. Allow sufficient space for servicing the valve and actuator. Clearance for valve installation is dependent on actuator size and the valve pipe size. See Figures 1 and 5 for valve body dimensions. Refer to actuator literature for actuator dimensions.
1. Clean the lines upstream of the valve to remove par-
ticles larger than 1/16 inch diameter (welding slag, pipe scale and other contaminants). Upstream installation of a 20 mesh strainer is recommended.
2. Air should be eliminated from the system so the
valves remain full of fluid during operation.
3. Straight sections of piping upstream and down-
stream of the valves are not necessary for proper operation. Reducing bushings or flanges may be attached directly to valves. Standard adapters are adequate for installation of flow control valves.
4. Proceed with installation once the system specifics
(expansion/contraction of the system and its medium as well as operating pressures) are within tolerances.
5. Do not lift the valve by holding the stem.
Severe Burn Hazard. Contact with hot liquid can lead to severe injury or cause death. Release system pressure and isolate or drain the valve pipe section so the medium (water or glycol solution) does not leak out of the valve body during installation (see Fig. 7).

Mounting Valve

1. Before installing the valve, rotate the valve stem to
make sure that the valve stem operates freely. Impaired stem operation can indicate that the stem was bent by rough handling. This condition can require replacing the valve.
2. Protect the stem from damage due to bending or
scratching.
3. For horizontal piping, install the valve so the actua-
tor is above the valve body. Install the valve in any position between vertical and horizontal. Do not install the valve with the stem below horizontal or upside down. For vertical piping, the actuator can be mounted in any orientation.
4. Hoist valve by its body only. Do not lift by stem, bon-
net, flanges, or flange holes. (See Fig. 6 for proper hoisting method.)
M13752
Fig. 6. Proper hoisting of VBF Valves
5. Mount the valve between aligned pipes. Mounting
the valve on pipes that are not aligned causes leak­age at the valve-to-pipe connection.
Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry.
Disconnect power supply to the actuator to prevent electrical shock and equipment damage, or remove and cap the air line to the actuator.
M22591
Fig. 7. Piping must prevent leakage
5 62-2035—02
Loading...
+ 11 hidden pages