Honeywell V4055F, V4055G User Manual

65-0029-02
V4055F,G Fluid Power Actuator with Manual Control
PRODUCT DATA
FEATURES
• Fast opening time of 13 seconds at 120 V, 60 Hz.
• Maximum closing time, is 1 second, which meets approval body requirements.
• Unit available with FM approved proof of closure switch.
• Red “OPEN” indicator attached to the actuator piston will show if the valve is even slightly open; yellow “SHUT” indicator on the valve stem will show only when the gas valve is fully closed.
• Ambient temperature rating of -40°F to +150°F (-40°C to +66°C).
• Valve and actuator may be mounted in any position.
• Optional, field-adjustable, spdt auxiliary switch, rated at 112 hp (0.37 kW), may be added in the field.
• Standard enclosure meets NEMA 1 (IP30) general purpose requirements.
• Red light indicates when valve is ready to open.
• Rocker switch allows manual operation of valve.
APPLICATION
• Valve closes on power loss.
The V4055F and G fluid power gas valve actuators are for use with the V5055 valve for gas safety shutoff applications to control the gas supply of commercial and industrial burners.
NOTICE: Per Industry standards, the actuator is required a conduit seal or a cable type that is sealed be installed in a device that can result in a flammable liquid flow through a conduit or cable to an electrical ignition source in the event of a seal leakage or diaphragm failure.
Contents
Application ........................................................................ 1
Specifications ................................................................... 2
Operation .......................................................................... 2
Ordering Information ........................................................ 2
Installation ........................................................................ 3
Wiring ............................................................................... 5
Checkout and Service ...................................................... 5
V4055F,G FLUID POWER ACTUATOR WITH MANUAL CONTROL
SPECIFICATIONS
Models: V4055G Fluid Power Actuator with Manual Control-for use with the V5055 valve. Provides ON-OFF control. Rated for 5 PSI.
V4055F-Same as V4055G except: for use with V5055C only. Meets UL and FM proof of closure requirements.
Table 1. Auxiliary Switch And Valve-closed Indication Switch
Ratings: 112 hp (0.37 kW)
LOAD 120 V 240 V
Full Load 9.8 A 4.9A
Locked Rotor 58.5 A 29.4 A
a
Maximum total connected power to both switches (if used) is 1800 VA.
Nominal Opening Time: 13 seconds:
Voltage and
Frequency
120/60 5.4 71.0 1.33 160 9.5 0.12 14
InrushWAVAWAVA
a
Table 2. Electrical Ratings.
Opening (Fast) Holding
OPERATION
1. The red READY TO OPEN light will be on if there is power to the actuator and the rocker switch is in the cen­ter position.
2. To open the valve depress the rocker switch to the VALVE OPEN position and hold until the valve is open (Red READY TO OPEN light turns off). The valve will close if the rocker switch is released from the VALVE OPEN position with the red READY TO OPEN light on.
Closing Time: 1 sec maximum when de-energized.
Ambient Operating Temperature Rating:
-40°F to +150°F (-40°C to +66°C) for 60 Hz models; -10°F to +158°F (-23°C to +70°C) for 50 Hz and 50/60 Hz models.
Mounting Means: Actuator mounts directly to valve bonnet with 2 setscrews,
positioned 90 angular degrees apart. Valve and actuator can be mounted in any position.
Mounting Dimensions: See Fig. 1.
Accessories: 133568 Auxiliary Switch Bag Assembly. 133569 Valve-Closed Indication Switch Bag Assembly.
Approvals: UL and FM. IRI Approvable.
Electrical Ratings: See Table 2.
3. To close the valve depress rocker switch to VALVE CLOSED position. The rocker switch stays in the valve closed position when released.
4. The valve automatically closes on power loss. It must be manually reopened using the rocker switch.
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Environmental and Combustion Controls Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care 1885 Douglas Drive North Minneapolis, Minnesota 55422-4386
3. http://customer.honeywell.com or http://customer.honeywell.ca
International Sales and Service Offices in all principal cities of the world. Manufacturing in Belgium, Canada, China, Czech Republic, Germany, Hungary, Italy, Mexico, Netherlands, United Kingdom, and United States.
65-0029-02 2
V4055F,G FLUID POWER ACTUATOR WITH MANUAL CONTROL
9-3/16
(233)
D
3/4 (19) BOLT HOLES [8] ON 3-3/4 (95) RADIUS
M23960A
3/4
1
1-1/4
1-1/2
2
2-1/2
3
4
VALVE
SIZE INCH
13-1/8
13-1/8
13-1/8
13-1/8
13-1/4
13-3/4
13-3/4
16-3/16
333.5
333.5
333.5
333.5
336.5
349.0
349.0
411.0
2-3/4
2-3/4
2-3/4
2-3/4
2-7/8
3-3/8
3-3/8
5-13/16
70.0
70.0
70.0
70.0
73.0
85.5
85.5
128.0
8-3/16
8-3/16
8-3/16
8-3/16
8-5/16
8-13/16
8-13/16
11-7/32
208.0
208.0
208.0
208.0
211.1
224.0
224.0
285.0
5-3/4
5-3/4
5-3/4
5-3/4
8-3/8
9-1/4
9-1/4
12-1/2
146.0
146.0
146.0
146.0
212.5
235.0
235.0
317.5
2-1/4
2-1/4
2-1/4
2-1/4
2-3/4
2-3/4
2-3/4
4-5/8
57.0
57.0
57.0
57.0
70.0
70.0
70.0
117.0
4-13/16
4-13/16
4-13/16
4-13/16
7-19/32
7-19/32
7-19/32
122.0
122.0
122.0
122.0
192.5
192.5
192.5
2-13/16
2-13/16
2-13/16
2-13/16
3-1/2
4-1/2
4-1/2
71.0
71.0
71.0
71.0
89.0
114.5
114.5
DIM A
IN. MM
DIM B
IN. MM
DIM C
IN. MM
DIM D
IN. MM
DIM E
IN. MM
DIM F
IN. MM
OCTAGON
IN. MM
B
E
F
C
D
A
1
1/8 OR 1/4 INCH NPT DOWNSTREAM TAP AND PLUG (OPTIONAL ON DOMESTIC MODELS)
1/4 INCH NPT UPSTREAM TAP AND PLUG (1/4 BSP ON INTERNATIONAL MODELS)
1
KNOCKOUT FOR1/2 INCH CONDUIT (4)
OCTAGON
5 (127)
27/32 (22)
3-23/32 (95)
6-3/4 (172)
ALLOW 4 INCHES (102 MM) CLEARANCE FOR ACTUATOR REMOVAL.
ADD 1/8 INCH (3 MM) TO DIMENSION FOR MODELS WITH NEMA 4 ENCLOSURE.
ADD 1/4 INCH (6 MM) TO DIMENSION FOR A MODELS WITH NEMA 4 ENCLOSURE.
1-9/32 (33)
1/2 INCH NPT UPSTREAM TAP AND PLUG (OPTIONAL ON DOMESTIC MODELS)
3
2
3
2
Fig. 1. Approximate mounting dimensions of V4055 actuators and V5055 valves, in inches. (mm).
INSTALLATION
When installing this product...
1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced, flame safeguard control technician.
After installation is complete, check out product operation as provided in these instructions.
NOTICE: Per Industry standards, the actuator is required a conduit seal or a cable type that is sealed be installed in a device that can result in a flammable liquid flow through a conduit or cable to an electrical ignition source in the event of a seal leakage or diaphragm failure.
4.
3 65-0029-02