The V4055 Gas Valve Actuator in combination
with a V5055 Gas Valve controls the gas supply to
commercial and industrial burners.
V4055A,B,D,E
■ The V4055 Actuator, when used with the V5034 or
V5055 Valve, is rated for final safety shutoff service.
■ The V4055 Actuator may be used with the character-
ized guide model of the V5055 gas valve to enhance
lightoff smoothness.
■ The standard model has an opening time of 26 sec at
60 Hz, or 32 sec at 50 Hz. A fast-opening model, is
available with timings of 13 sec at 60 Hz, or 16 sec at
50 Hz.
■ Maximum closing time is 1 sec, which meets code/
standard/insurer requirements.
■ Models with damper shaft available, with or without
spring return; shaft extends out both sides and rides
in Teflon-like, Delrin bushings; used with standard
7616BR Damper Crank Arm.
■ Red OPEN indicator attached to the actuator stem
shows when valve is even slightly open; yellow
SHUT indicator on valve stem shows only when gas
valve is fully closed.
■ Ambient temperature rating is -40°F to 150°F
[-40°C to 66°C] for 60 Hz models; -10°F to 158°F
[-23°C to 70°C] for 50 Hz and 50/60 Hz models.
■ Valve and actuator combination may be mounted in
any position.
■ Models available with factory installed SPDT field
adjustable auxiliary switch. Field addable auxiliary
switch kits are also available.
■ Standard enclosure meets NEMA 1 general purpose
requirements; models available with NEMA 4
weather proof enclosure.
■ V4055D and high pressure V4055E with proof-ofclosure switch and V5055C or E with valve seal
overtravel interlock (double seal) to meet specific
code/standard/insurer requirements.
V4055A,B,D,E
SPECIFICATIONS • ORDERING INFORMATION
Specifications
MODELS:
NOMINAL OPENING TIME (SECONDS):
V4055A actuator with V5055 gas valves provide on-off
control of fuel. With proper adapter (see Accessories),
it replaces the V4034 actuator on a V5034 gas valve.
V4055B is a high pressure model of the V4055A.
V4055D is identical to the V4055A but incorporates a
proof-of-closure switch. Used with V5055C (double
seal) for valve seal overtravel interlock.
V4055E is identical to V4055B but incorporates a proof-
of-closure switch. Used with V5055E (double seal)
for valve seal overtravel interlock.
NEMA 4 (weatherproof) models available.
Model50 Hz60 Hz
Standard3226
Fast-opening1613
MAXIMUM CLOSING TIME: One second when de-ener-
gized.
AMBIENT OPERATING TEMPERATURE RATING:
60 Hz MODELS: -40°F to 150°F [-40°C to 66°C].
50 Hz, 50/60 HZ MODELS: -10°F to 158°F [-23°C to
70°C].
MOUNTING: V4055 attached directly to V5055 valve with
two set screws positioned with 90 degrees separation.
PRESSURE RATINGS:
Combination is multipoise.
PRESSURE RATINGS OF VALVE-ACTUATOR COMBINATIONS.
Actuator
V4055A,D
b
Diff
ValvepsikPapsikPapsikPapsikPa
V5055A,C
3/4 to 3 in.
V5055A,C
4 in.
V5055B
3/4 to 3 in.
V5055B
4 in.
V5055D,E
3/4, 1-1/4, 1-1/2 in.
V5055D,E
2, 2-1/2, 3 in.
a
Use a V4055D or V4055E (with proof-of-closure switch) with a V5055C or V5055E (with double seal) for valve seal
534.515103.415103.415103.4
320.715103.4534.515103.4
534.515103.415103.415103.4
320.715103.4534.515103.4
534.575517.125172.475517.1
534.545310.315103.445310.3
a
Closeoff
V4055B,E
c
Diff
b
a
Closeoff
c
overtravel interlock.
b
Maximum operating pressure differential.
c
Maximum closeoff pressure without seat leakage. This is the maximum allowable pressure drop to which a valve may be
subjected while fully closed, and is independent of the valve body rating.
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the Tradeline
Catalog or price sheets for complete ordering number, or specify—
1. Order number.4. Damper shaft, with or without return spring, if required.
2. Voltage and frequency.5. NEMA 4 enclosure, if required.
3. Standard or fast opening time.6. Accessories, if desired.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Home and Building Control Sales Office (please check the white pages of your phone directory).
2. Home and Building Control Customer Logistics
Honeywell, Inc., 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 (612) 951-1000
In Canada—Honeywell Limited/Honeywell Limitée, 740 Ellesmere Road, Scarborough, Ontario M1P2V9. International Sales and
Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico,
Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
60-2309—82
Ordering Information
Page 3
V4055A,B,D,E
SPECIFICATIONS
ELECTRICAL RATINGS: V4055A,D:
Voltage andOpening (Standard)Opening (Fast)Holding
Holding—9.5W, 0.16A, 19 VA.
AUXILIARY SWITCH AND PROOF-OF-CLOSURE
SWITCH RATINGS: 1/2 hp [0.37 kW]a:
MOUNTING DIMENSIONS: See Fig. 1.
DAMPER SHAFT: Models available with or without inte-
gral damper shaft. Shaft is 3/8 in. [9.5 mm] square, for use
with 7616 BR Damper Crank Arm (not included). Models available with or without damper shaft return spring.
MAXIMUM DAMPER SHAFT ROTATION: 52 angular
Load120V240V
Full Load9.8A4.9A
Locked Rotor58.8A29.4A
a
Maximum total connected power to both switches (if used)
is 1800 VA.
degrees.
DAMPER SHAFT MAXIMUM FORCE A 2-11/16 in.
[68.3 mm] RADIUS FOR 7616 BR DAMPER CRANK
ARM (ordered separately):
NOTE: Damper shaft drives damper crank arm in one direc-
tion only; optional return spring is available on damper
shaft to turn damper crank arm in opposite direction.
-40°F to 20°F [-40°C to -7°C]20°F to 150°F [-7°C to 66°C]
V4055 Modellb NlbN
Without return spring522.22089.0
With return spring522.21044.5
APPROVALS:
Underwriters Laboratories Inc. Listed: File No. MH1639,
Guide No. YIOZ.
Factory Mutual Approved.
International Approval Services (IAS, a joint venture of
AGA and CGA): 60 Hz only.
British Gas Corporation and Dutch Gas Institute Ap-
proved:
V4055 with several V5055A and V5055B models.
V4055D with V5055C models with an internal screen.
ACCESSORIES:
133533A Short Stem Adapter for mounting actuator on
133534A Long Stem Adapter for mounting actuator on
V5034 valve.
133568 Auxiliary Switch Bag Assembly.
133569 Valve-Closed Indication Switch Bag Assembly
(do not use with V5034 valve body).
7616BR Damper Crank Arm (damper arm and clip).
Q5055A1001 Adapter Assembly: Adapts ITT General
V710 Gas Valve to accept Honeywell gas valve
actuators. Replaces ITT General AH2 gas valve
actuators.
AVAILABLE MODELS:
V4055 with NEMA 4 enclosure (weatherproof).
V5034 valve.
360-2309—8
Page 4
V4055A,B,D,E
INSTALLATION
Fig. 1—Approximate Mounting Dimensions of V4055 Actuators and V5055 Valves, in in. [mm].
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous
condition.
2. Check the ratings given in the instructions and on the
product to make sure the product is suitable for your
application.
3. Installer must be a trained, experienced, flame safeguard control technician.
4. After installation is complete, check out product operation as provided in these instructions.
60-2309—84
Installation
CAUTION
1. Disconnect power supply before making wiring
connections to prevent electrical shock and
equipment damage.
2. Voltage and frequency of the power supply
connected to this control must agree with those
marked on the device.
3. Maximum total connected load to both switches
(if used) must not exceed 1800 VA.
Page 5
V4055A,B,D,E
INSTALLATION
INSTALL VALVE
The actuator is mounted directly on the valve bonnet
after the valve is installed in the gas supply line. Refer to the
instructions packed with the gas valve for installation details. When installing the valve, assure that:
1. Sufficient clearance is left for installation and service
of the actuator.
2. Ambient temperatures at the valve location will re-
main within -40° to 150°F [-40°C to 66°C] or -10°F to 158°F
[-23°C to 70°C] (see Specifications section).
3. Position of the valve permits hookup to the damper if
one is controlled.
INSTALL ACCESSORY SWITCHES (IF NEEDED)
A spdt auxiliary switch may be installed to operate a
load up to 1/2 hp [0.37 kW]. The switch may be adjusted to
operate at any point in the valve stroke.
A proof-of-closure switch may also be installed on any
V4055 actuator to provide a valve seal overtravel interlock
when used with a V5055C or E valve (with double seal).
The spdt proof-of-closure switch is installed to make or
break a circuit when the valve is in the closed position. The
switch is not adjustable.
NOTE: Mark the actuator or valve to indicate any changes
made.
4. Insert the proof-of-closure switch in the position shown
in Fig. 2. The switch mounts against the side of the actuator
housing. The mounting holes are spaced to mount the switch
only in the correct position. Fasten with two screws through
the actuator base. The proof-of-closure switch is not adjustable.
5. If only one switch is used, install the narrow barrier
included with the switch in the unused space.
6. Mount the actuator before making wiring connections
and adjustments to the auxiliary switch.
MOUNT ACTUATOR ON VALVE
Check the final position of the valve body to be sure that
the actuator will be in the proper position when mounted on
the valve. This is especially important if the actuator is used
to drive a damper.
If two smaller sized valves are mounted very closely
together, as in an Industrial Risk Insurers type valve train, it
may be necessary to mount the actuator off center to
provide adequate clearance.
Slip the bottom collar of the actuator over the valve
bonnet assembly. Rotate the actuator to the desired position and use a 5/32 inch Allen wrench to securely tighten
the two set screws. (50 to 60 lb/in [5.7 to 6.8 Nm]).
Connect the damper linkage, if used. Refer to the instructions packed with the damper arm.
Fig. 2—V4055 Actuator with cover removed.
133568
AUXILIARY
SWITCH
133569
PROOF-OFCLOSURE
SWITCH
ADJUSTING
SCREW FOR
AUXILIARY
SWITCH
EACH SWITCH
SECURED BY TWO
SCREWS FROM
BOTTOM OF BASE.
IF ONLY ONE SWITCH IS
USED, INSTALL BARRIER
IN OPEN POSITION.
M7326
To install the switches, proceed as follows:
1. Remove the actuator faceplate (two screws).
2. Remove the sliver-colored barrier to expose the actua-
tor stem.
3. Insert the auxiliary switch in the position indicated in
Fig. 2. Fasten with two screws through the actuator base.
TO REPLACE A V4034 ACTUATOR ON A V5034
VALVE
IMPORTANT: When replacing a standard (26 sec) V4034
actuator on a V5034 Valve, check the main burner
flame-establishing period (MFEP) of the burner primary safety control. If the MFEP is 10 sec, you must
use a fast-opening (13 sec) V4055 Actuator on the
older V5034 Valve.
The initial action of the V4055 Actuator does not
immediately open the V5034 Valve because of a difference in stroke length. The pilot may be shut off before
the main burner flame is established. The fast-opening
V4055 Actuator will open the V5034 Valve fast enough
to establish the main burner flame within the ten
second flame-establishing period.
If it is desirable to maintain the slower opening
characteristic of the standard V4034 Actuator, both
the V4034 Actuator and V5034 Valve should be replaced. Use a standard V4055 Actuator on a V5055
Valve.
Select the correct adapter, depending on whether the
V5034 has a long or short stem (Fig. 3). Fasten the adapter
to the V5034 Valve bonnet, and then mount the actuator on
the adapter. Follow the instructions for mounting the actuator on the valve.
If the V4034 being replaced is equipped with a heater,
there will be a low limit control connected in series with the
V4034 power supply to prevent actuator operation below
25°F [-4°C]. There will also be a constant source of the line
voltage power to the heater and its control thermostat.
560-2309—8
Page 6
V4055A,B,D,E
INSTALLATION
Fig. 3—Adapters permit use of V4055 Actuator
with V5034 Valve.
USE NO. 133534A
ADAPTER WITH
USE NO. 133533A
ADAPTER WITH
SHORT STEM V5034
LONG STEM V5034
M7325
The V4055 is rated for ambient temperature down to -
40°F [-40°C] for 60 Hz models, or -10°F [-23°] for 50 Hz
and 50/60 Hz models, and does not require a heater. Remove all the wiring associated with the heater. Disconnect
the power supply for the heater at its source and remove the
wires. See Fig. 4.
Fig. 4—Remove heater circuits, if installed,
when replacing V4034 Actuator.
BLACK
WHITE
HEATER
THERMOSTAT
HEATER
LOW
LIMIT
HEATER
CIRCUIT
REMOVE HEATER CIRCUIT
COMPLETELY AND
REMOVE LOW LIMIT
V4034
1
M7333
L1
(HOT)
L2
TO MAIN
VALVE TERMINAL
ON BURNER CONTROL
Fig. 5—7616BR Damper Crank Arm may be
attached to actuator shaft to drive a damper
when valve is opened.
7616BR
52 DEGREE
ANGULAR
ROTATION
5
2
16
MAXIMUM
TRAVEL
[59]
11
1
16
RADIUS
[68]
DAMPER
ARM
M7322
SHAFT
WIRING
Disconnect power supply before making electrical con-
nections to prevent electrical shock or equipment damage.
Wiring must comply with all applicable electrical codes,
ordinances, and regulations. Wiring to the actuator must be
NEC Class 1.
Connect the power supply to terminals 1 and 2 on the
V4055 terminal strip. Refer to Fig. 6 for auxiliary switch
connections. For typical system hookups, refer to Fig. 7
and to instructions packed with device used to control
valve.
When all wiring connections are complete, replace the
actuator faceplate.
CAUTION
Label all wires prior to disconnection when servicing values.Wiring errors can cause improper and
dangerous operation.
Verify proper operation after servicing.
MOUNT AND ADJUST 7616BR DAMPER CRANK
ARM (IF USED)
IMPORTANT: When a damper crank arm is used with a
NEMA 4 actuator that is exposed to ice or sleet, a
suitable shield must be installed to prevent ice or sleet
buildup.
Follow installation and adjustment directions included
with damper crank arm. Maximum pushrod travel is 2-5/16
in. [58.7 mm] through a stroke of 52 degrees. See Fig. 5.
60-2309—86
NOTE: Pipe sealant is required on the conduit threads of
actuators with NEMA 4 enclosures.
ADJUST THE AUXILIARY SWITCH (IF USED)
The auxiliary switch is adjustable throughout the stroke
of the actuator. With the switch installed in the actuator,
turn the adjusting screw (Fig. 2) clockwise to cause
the switch to operate earlier in the stroke or counterclockwise to cause the switch to operate later in the stroke.
NOTE: The proof-of-closure switch is not adjustable.
Page 7
FIg. 6—External connections to the V4055 Actuator.
L1
HOT
2
1
PROOF-OF-CLOSURE
SWITCH
AUXILIARY
SWITCH
NC
NO
2
3
C
C
NC
NO
1
L2
2
3
1
POWER SUPPLY. PROVIDE OVERLOAD PROTECTION AND
DISCONNECT MEANS AS REQUIRED.
SWITCH BETWEEN THESE TWO LEADS IS CLOSED WHEN
2
VALVE IS SHUT (DE-ENERGIZED).
SWITCH BETWEEN THESE TWO LEADS IS OPEN WHEN
3
VALVE IS SHUT (DE-ENERGIZED).
V4055A,B,D,E
INSTALLATION
M7334
Fig. 7—Typical application of a V4055D/V5055C or V4055E/V5055E combination to meet Factory Mutual
or Underwriters Laboratories Inc. Requirements for a proof-of-closure switch (valve seal overtravel
interlock).
B
R
W
SERIES 90
CONTROLLER
120V, 60 HZ
POWER
SUPPLY
2
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
1
PROTECTION AS REQUIRED.
USE ALL NEC CLASS 1 WIRING.
2
PROOF-OF-CLOSURE SWITCH IN PREIGNITION INTERLOCK CIRCUIT;
3
SWITCH IS CLOSED NC-C WHEN ACTUATOR IS DE-ENERGIZED.
C7027A, C7035A, OR
C7044A, ULTRAVIOLET
FLAME DETECTOR
OR
C7012A, C, E,F
OR C7076A
ULTRAVIOLET
FLAME DETECTOR
5
6
7
8
G
YELLOW
M7335
760-2309—8
Page 8
V4055A,B,D,E
CHECKOUT AND SERVICE
Checkout and Service
CAUTION
Only a trained, experienced, flame safeguard control service technician should check out and service
this control.
CHECKOUT
After the installation is complete, cycle the valve several
times with the manual fuel shutoff cock closed before
testing the system in actual operation.
SERVICE
The actuator is not field repairable except for replacing
the auxiliary switch or proof-of-closure switch. See Installation section for procedure. Do not disassemble the valve
actuator.
If the actuator should fail to operate properly, replace it.
Home and Building ControlHome and Building ControlHelping You Control Your World
Honeywell Inc.Honeywell Limited—Honeywell Limitée
1985 Douglas Drive North740 Ellesmere Road
Golden Valley, MN 55422Scarborough, Ontario
60-2309—88
Printed in U.S.A.
M1P 2V9
QUALITY IS KEY
Page 9
Industrial Gas Valves
The V5055 Gas Valves are used with the V4055,
V4062, and V9055 Fluid Power Actuators to control gas flow to commercial and industrial burners.
V5055A-E
■ Used with natural or liquefied petroleum (LP) gases.
■ V5055 normally closed valves are rated for final
shutoff service (safety shutoff).
■ V5055A,C,D,E Valves are for On-Off service.
■ V5055B Valve has a characterized guide and in
combination with the V4055, V4062, and V9055
Fluid Power Actuators, provides slow-opening, hi-
lo-off, and modulating functions respectively.
■ V5055C,E Valves have a double seal and are used
with V4055D,E Actuators to provide proof-of-clo-
sure switch and valve seal overtravel interlock.
■ V5055D,E Valves are for high pressure applications
(see Table 1).
■ Seven valve sizes from 3/4 to 3 inches have NPT
threaded connections. Models are available with
BSP-PL threads. V5055A,B,C Valves are available
in a 4 inch size and have flange connections.
■ Most models have 1/4 inch upstream and down-
stream top and plug. BSP-PL thread models have
1/4 inch upstream tap and plug.
■ Valve body rating of 75 psi (517.1 kPa).
■ Yellow SHUT indicator attached to the valve stem
provides an indication of the valve closed position.
V5055B Industrial Gas Valve with characterized guide
for slow opening, HI-LO-OFF, or modulating service.
V5055C: Same as V5055A but incorporates a double
seal. Used with the V4055D Actuator to a provide
proof-of-closure switch and a valve seal overtravel
interlock.
V5055D: Same as V5055A but for high pressure appli-
cations.
V5055E: Same as V5055C but for high pressure appli-
TYPE OF GAS: Natural or liquefied petroleum (LP) only.
PIPE SIZE: 3/4, 1, 1-1/4, 1-1/2, 2, 2-1/2, 3, and 4 in. (only
V5055A,B,C available in 4 in. size).
PIPE THREADS: NPT or BSP-PL Threads (equivalent to
ISO R7 and DIN 2999). Available on inlet and outlet of
3/4 to 3 inch valves. Four inch valves have flange connec-
tions.
PRESSURE RATINGS: See Table 1.
VALVE BODY RATING: 75 psi (517.1 kPa).
VALVE CAPACITIES: A.G.A. ratings at 1 in. (0.25 kPa)
pressure drop; based on gas with specific gravity of 0.64.
cations.
TABLE 1—PRESSURE RATINGS OF VALVE-ACTUATOR COMBINATIONS.
Actuator
V4055A,D
ValvepsikPapsikPapsikPapsikPapsikPapsikPa
V5055A,C
3/4 to 3 in.
V5055A,C
4 in.
V4055B
3/4 to 3 in.
V5055B
4 in.
V5055D,E
3/4, 1, 1-1/4, 1-1/2 in.
V5055D,E
2, 2-1/2, 3 in.
a
Maximum operating pressure differential.
b
Maximum close-off pressure without seal leakage. This is the maximum allowable pressure drop to which a valve may be
534.515103.415103.415103.4534.514103.4
320.715103.4534.515103.4320.715103.4
534.515103.415103.415103.4534.515103.4
320.715103.4534.515103.4320.715103.4
534.575517.125172.475517.1534.575517.1
534.545310.315103.445310.3534.545310.3
c
V4055B,E
c
V4062,V9055
c
subjected while fully closed, and is independent of the valve body rating.
c
Use a V4055D, V4055E, V4062D, or V9055D (with proof-of-closure switch) with a V5055C or E (with double seal) for valve
seal overtravel interlock.
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE
Catalog or price sheets for complete ordering number, or specify—
1. Order number
2. Pipe size.
3. NPT or parallel BSP threads (except for 4 in. models with flanges).
4. Optional additional tapping and plug—1/8 in downstream and/or 1/2 in. upstream.
5. Replacement parts, if desired.
If you have additional questions, need further information, or would like to comment on our products or services, please write
or phone:
1. Your local Home and Building Control Sales Office (please check the white pages of your phone directory).
2. Home and Building Control Customer Logistics
Honeywell Inc.
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 (612) 951-1000
In Canada—Honeywell Limited/Honeywell Limitée, 740 Ellesmere Road, Scarborough, Ontario M1P2V9. International Sales and
Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico,
Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
Fig. 3—Approximate dimensions of the 4 in. V5055 Valves with valve actuator in in. (mm).
3
(171.5)
6
4
23
(94.5)
3
32
27
(21.4)
32
of gas used.
3. Find the capacity in cf/h. If the capacity is listed in
Btu/h, convert to cfh by the following formula:
Capacity in cf/h =
Btu/h (from burner nameplate)
Btu/cu ft (from gas utility)
5 (127)
KNOCKOUT
FOR1/2 INCH
CONDUIT (4)
1
5
14
32
(360)
11
(285)
25
5
32
(147)
5
9
32
(233)
1
12 (318)
2
1 ALLOW 2 IN. (51 mm) CLEARANCE ABOVE V4055 SO IT MAY BE REMOVED FROM VALVE.
2
DIMENSIONS ON DIN-APPROVED VALVES: 1/4 - 19 BSP.PL UPSTREAM PLUG (2),
.71 IN (18 mm) DIAMETER BOLT HOLE (16), 7.087 IN (180 mm) DIAMETER BOLT CIRCLE.
9
1
32
7
32
3
4
DIAMETER
(16)
1/4 - 18 NPT
UPSTREAM
PLUG (2)
(33)
(19)
45° (16)
1
7 (191)
2
4 (102)
DIAMETER
2
DIAMETER
M9584
560-2307—10
Page 14
V5055A-E
SPECIFICATIONS • INSTALLATION
4. For gases with specific gravities other than 0.64,
multiply the burner cfh by the proper conversion factor:
Type of Gassp gr (average) Multiply cf/h by
LP—Propane1.530.647
LP—Butane1.980.569
5. Use the corrected capacity in cf/h when determining
the gas valve size in Fig. 1.
6. Determine the maximum pressure drop across the
valve and draw a horizontal line at this pressure in Fig. 1.
7. Draw a vertical line in Fig. 1 at the capacity (cf/h)
previously determined. Use the corrected capacity for a gas
with a specific gravity other than 0.64.
IMPORTANT: The V5055 Valve is designed to provide
control of gaseous fuel (natural and LP gas) flow in
applications in which there is minimal exposure to
water. V5055 Valves used in maritime, beverage, food
processing, outdoor and other installations in which
occasional exposure to water is experienced may be
subject to valve stem and spring corrosion. The presence of corrosion decreases the operating life of the
valve. V5055 Valves used in such installations should
be inspected at least annually and should have the
valve bonnets replaced if corrosion is noted.
A V4055 Valve Actuator with a NEMA 4 rating is also
recommended for such installations. The water-tight
design of the NEMA 4 rated V4055 Actuator prevents
water from entering the V4055 valve stem and spring
chamber through the actuator. Under certain conditions, some water may be retained by the external
upper portion of the valve body. The retained water is
effectively excluded from the valve stem and spring
chamber by a functional seal that is incorporated into
the NEMA 4 rated actuator.
WHEN INSTALLING THIS PRODUCT…
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous
condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for your
application.
3. Installer must be a trained, experienced, flame safeguard control technician.
4. After installation is complete, check out product
operations as provided in these instructions.
8. Use the valve size at the intersection of the horizontal
and vertical lines. If the intersection is between valve sizes,
use the next higher size to the right.
TO SIZE TWO IDENTICAL VALVES PIPED IN
SERIES
1. Find the cf/h for the type of gas used.
2. Consider both valves as one unit. Determine the total
maximum pressure drop across the unit.
3. Find the pressure drop across the first valve by assuming it to be 45 percent of the total pressure drop.
4. Find the valve size from Fig. 1.
5. The second valve will be the same size as the first
valve.
Installation
CA UTION
1. Turn off gas supply before starting installation.
2. Disconnect power supply for valve actuator
before beginning installation to prevent electrical shock and equipment damage.
3. Be sure the valve is installed so the arrow on the
valve points in the direction of gas flow. (Gas
pressure helps to close the valve.)
LOCATION
Install the valve in the gas supply line downstream from
the pressure regulator. The valve and actuator may be
mounted in any position that allows sufficient clearance for
installation and for repair or replacement.
1. The valve position indicators should be easily visible
with the valve and actuator in the final position.
2. The final position of the valve and actuator must allow
for damper linkage, if used.
IMPORTANT: Allow room for turning the valve body
(actuator not attached) onto the gas piping. Swing
dimensions, measured from the center of the pipe are:
3/4 through 1-1/2 in. valves: 4 in. (101.6 mm).
2 through 3 in. valves: 5 in. (127.0 mm).
4 in. valves: 7 in. (177.8 mm).
MOUNTING (Figs. 4 through 6)
WARNING
If flow is not in the direction of the arrow on the
valve body, the valve may not shut off.
60-2307—106
Page 15
V5055A-E
INSTALLATION
1. Use new, properly reamed, pipe, free from chips.
2. Do not thread pipe too far (Fig. 4). Valve distortion or
malfunction may result from excess pipe in the valve.
Fig. 4—Preparing the pipes.
TWO CLEAN
THREADS,
MODERATE
AMOUNT
OF DOPE
CORRECT:
NORMAL
FULL
THREAD
CORRECT:
NORMAL
FULL
THREAD
1
USE PIPE DOPE RESISTANT TO ACTION OF LP GAS.
1
EXCESS DOPE MAY BLOCK
DISK OFF
VALVE
SEAT
LOOSE
CHIPS
REAM PIPE,
BLOW OUT
CHIPS (TO AVOID
LODGING ON SEAT)
INCORRECT:
TOO LONG,
DISTORTS
VALVE SEAT
INCORRECT:
TOO LONG,
DISTORTS
VALVE SEAT
M9571
8. Use two threaded companion flanges, two gaskets
(included with valve), and 16 bolts (with washers and nuts)
for mounting a 4 in.-V5055 Valve. Mount a threaded flange
and gasket on each end of the valve as shown in Fig. 6. Then
screw the pipes into the threaded flanges. Apply dope sparingly, and use wrenches and vises properly as shown in Fig.
4 and 5.
9. Make sure the power supply is disconnected from the
valve actuator. Then mount the actuator on the valve body
and complete the electrical and linkage connections following the instructions packed with the actuator.
Fig. 5—Installing a 3/4 through 3 in. V5055
Valve.
CORRECT:
VISE GRIPS END
NEXT TO PIPE
BEING INSERTED
3. Remove the protective caps from the ends of the valve.
Do not attach the valve actuator until the valve body installation is complete.
4. Apply good quality pipe dope resistant to action of LP
gas, putting a moderate amount on the male threads only.
Use dope sparingly; if pipe dope lodges on the valve seat, it
will prevent proper closure.
5. Install valve with the gas flow in the direction indicated by the arrow on the casting.
6. Apply a parallel jaw wrench only to the flat next to the
pipe being inserted (Fig. 5). A wrench applied to the valve
body itself, or to the end farthest from the pipe being inserted,
may distort the casting, causing a malfunction. Do not use the
valve for a lever.
7. Be sure the gas flow is in the same direction as the
arrow on the bottom of the valve body.
CORRECT:
WRENCH CORRECTLY
APPLIED NEXT
TO PIPE BEING
INSERTED
INCORRECT:
WRENCH HERE
STRAINS
VALVE BODY
M9580
760-2307—10
Page 16
V5055A-E
INSTALLATION • OPERATION AND CHECKOUT
Fig. 6—Installing a 4 in. V5055 Valve.
4 IN. VALVE
NUT AND WASHER
(NOT INCLUDED)
GASKET
(2 INCLUDED WITH VALVE)
THREADED COMPANION
FLANGE (2 - NOT INCLUDED)
OPERATION
A V5055 Industrial Gas Valve is operated by a V4055,
V4062, or V9055 Fluid Power Gas Valve Actuator. The
valve opens when the actuator is energized, and closes
when power is removed. When closed, the valve seals off
against the rated close-off pressure with no power applied.
For further information, refer to the Instructions for the
actuator.
CHECKOUT
WARNING
Do not allow fuel to accumulate in the combustion
chamber. If fuel is allowed to enter the chamber for
longer than a few seconds without igniting, an
explosive mixture could result.
5/8 X 3 IN. [76] BOLT
(16 - NOT INCLUDED)
4 IN. PIPEM9581
Operation and Checkout
CA UTION
1. Do not put the system into service until you
have satisfactorily completed the following
Valve Leak Test, all applicable tests described
in the Checkout section of the Instructions for
the flame safeguard control, and any other tests
required by the burner manufacturer.
2. All tests must be performed by a trained, experienced flame safeguard control technician.
3. Close all manual fuel shutoff valves as soon as
trouble occurs.
After the installation is complete, cycle the valve several
times with the manual fuel shutoff cock closed. Make sure
the valve and actuator function properly. Also perform the
Valve Leak Test that follows before putting the valve into
service.
60-2307—108
Page 17
V5055A-E
OPERATION AND CHECKOUT • SERVICE INFORMATION
VALVE LEAK TEST (Fig. 7)
This is a test for checking the closure tightness of a gas
safety shutoff valve. It should be performed by qualified
personnel during the initial startup of a burner system, or
whenever the valve or valve bonnet is replaced (see Service
Information section). It is recommended that this test also
be included in the scheduled inspection and maintenance
procedures. For a periodic inspection test, follow steps 1,
3, 4, 5, 8, 9, 10, 12, 13, 16, and 17.
1. De-energize the control system to assure that there is
no power to the safety shutoff valve (C) shown in Fig. 7.
2. Close the upstream manual gas cock (A).
3. Make sure the manual test petcock (F) is closed in the
leak test tap assembly (D).
4. Remove the leak test tap plug and connect the test
apparatus to the Leak Tap (D).
5. Close the downstream manual gas cock (E).
6. Open the upstream manual gas cock (A).
7. Run the safety shutoff valve (C) to its fully open
position (through the safety system); then immediately deenergize the system to close the valve.
8. Immerse a 1/4 in. tube vertically 1/2 in. (12.7 mm) into
a jar of water.
9. Slowly open the test petcock (F).
10. When the rate of bubbles coming through the water
stabilizes, count the number of bubbles appearing during a
ten-second period. Each bubble appearing during a tensecond period represents a flow rate of approximately
0.001 cfh.
To meet U.S. requirements, leakage must not exceed the
following values:
V5055
Pipe Size
(in.)
Allowable
Leakage
a
(cc/hr)
Number of
bubbles per
10 sec
3/4, 1, 1-1/4, 1-1/245816
2, 2-1/2, 375226
4100335
a
Based on air at standard conditions, test pressures provided by ANSI Z21.21, Section 2.4.2 and a maximum of
235 cc/hr per inch of seal-off diameter. Seal-off diameter
is not to be confused with pipe size.
NOTE: For international leak test requirements, contact the
office of the appropriate approval agency.
AFTER THE TEST:
11. Close the upstream manual gas cock (A).
12. Close the test petcock (F), remove the test apparatus,
and replace the leak test tap plug (D).
13. Open the upstream manual gas cock (A) and energize
the safety shutoff valve (C).
14. Test with soap bubbles to assure that there is no leak at
the test tap (D).
15. De-energize the safety shutoff valve (C).
16. Open the downstream manual gas cock (E).
17. Restore the system to normal operation. If two safety
shutoff valves are utilized, each 550V valve is to be checked
for tightness of closure.
Fig. 7—Valve Leak Test.
SSOV
D
LEAK
TEST
TAP
MANUAL
GAS COCK
BURNER
F
TEST
PETCOCK
JAR OR GLASS
WITH WATER
CUT AT
45 DEGREE
ANGLE
1
M9547
GAS
SUPPLY
ABCE
MANUAL
GAS COCK
MAY ALSO BE A PERMANENT PETCOCK.1
PRV
1/4 in. FLEXIBLE
TUBING
1/4 in. ALUMINUM
OR COPPER PILOT
TUBING
1
[12.7]
2
CAUTION
1. Before servicing, turn off the gas supply and disconnect all electrical power to the valve actuator.
2. Only qualified service technicians should attempt to service or repair flame safeguard controls and burner systems.
3. Do not disassemble the valve bonnet assembly;
the valve seat is not replaceable.
4. Failure to properly position and seat the seals in
the valve body may result in a hazardous gas
leak.
Service Inf ormation
SCHEDULED INSPECTION AND MAINTENANCE
Setup and follow a schedule for periodic inspection and
maintenance, including the burner, all other controls, and
the valve(s). It is recommended that the Valve Leak Test in
the Checkout section be included in this schedule. Refer to
the Instructions for the primary safety control for more
information.
VALVE BONNET REPLACEMENT
The entire valve bonnet may be replaced without removing the valve body from the gas line. Do not disassemble the valve bonnet assembly; the valve seat is not
replaceable.
960-2307—10
Page 18
V5055A-E
SERVICE INFORMATION
For part numbers, refer to Replacement Parts in the
Specifications section. Complete instructions for replacing
the bonnet assembly are included with the replacement
part.
REPLACEMENT OF SEALS (Fig. 8 or 9)
When removing the bonnet to inspect and clean the
valve, install new seals (see Replacement Parts in Specifications section). Coat the new seals with the grease provided, and position them in the valve body as shown in
Fig. 8 or 9.
Fig. 8—Proper positions of valve and bonnet
seals in 3/4 through 3 in. valves.
BONNET SEAL
Failure to properly position and seat the seals in the
valve body may result in a hazardous gas leak.
After the new bonnet assembly is installed, or the bonnet
is removed for any reason, check for gas leakage around the
bonnet seal. Turn on the gas at the manual valve. Paint the
seal area with a rich soap and water solution. Bubbles
indicate a gas leak. If a leak is detected, check to see that the
bonnet screws are tight. If necessary, turn off the gas again
and remove the bonnet to be sure the seals are properly
seated.
Fig. 9—Proper positions of valve and bonnet
seals in 4 in. valve.
LARGE SEAL
VALVE SEAL
M9578
SMALL SEAL
M9579
60-2307—1010
Page 19
1160-2307—10
Page 20
Home and Building ControlHome and Building ControlHelping You Control Your World
Honeywell Inc.Honeywell Limited—Honeywell Limitée
1985 Douglas Drive North740 Ellesmere Road
Golden Valley, MN 55422Scarborough, Ontario
60-2307—1012
Printed in U.S.A.
M1P 2V9