FIXED ORIFICE, FLARE CONNECTIONS
TBEX 0.5 - 4.5 two-way
TBEX 0.5 - 4.5 angle
Application
Thermostatic expansion valves series TBE are used in plants
with one or more refrigerant circuits, especially for series
installations mobile air-conditioning and cooling units with
flare connection, e. g. bus AC, train AC, transport cooling.
Materials
Body
Thermal head
Connections
brass
stainless steel
brass
Series TBE
THERMOSTATIC EXPANSION VALVES
PRODUCT DATA
Features
• TBE: with internal pressure equalisation; for single
injection in installations with one or more cooling
circuits.
• TBEX: with external pressure equalisation; for optimal
evaporation effectiveness in all applications.
Obligatory for multiple injection by liquid distributors.
• Combi adsorber charge as standard
The same valve can be used for different
refrigerants (see table on page 2)
Controller charge is high sensitive and responsive
thus lowest possible level of superheat can be
achieved
Charge is not sensitive to effects of temperature on
the capillary tube and valve head
damping characteristic results in stable control
behaviour
• Optional available with gas charge and MOP
• Adjustable superheat for two-way construction
• Fixed superheat setting for angle construction
• Warm thermal head provides best reliability
• Flare connections
• Extreme durable due to stainless steel head and
stainless steel diaphragm welded using protective gas
• Fixed orifice
• Refrigerants: R134a, R401A, R12
R22, R407C, R407A, R422D
R404A, R507A, R402A, R407B, R502
Further refrigerants on request.
Specification
Nominal capacity range
Evaporating temperature
range
Maximum pressure PS
Maximum test pressure PF
Max. ambient temperature
Max. bulb temperature
Static superheat
Length of capillary tube
Bulb diameter
0.99 to 17.0 kW R22
(small orifice graduation for
optimal control behaviour)
see table on page 2
see table on page 2
see table on page 2
100 °C
140 °C
approx. 3 K
1.5 m
12 mm
Copyright © 2009 Honeywell GmbH • Subject to change without notice EN0H-1906GE23 R0709
SERIES TBE
Thermal Charges and Temperature Ranges
1. Adsorber charge
Refrigerant
R134a, R401A,
R12
R22, R407C,
R407A, R422D
R404A, R507A,
R402A, R407B,
R502
Further refrigerants on request.
Thermal systems with adsorber charge are completely
insensitive to effects of temperature on the capillary tube and
valve head. It reacts only according to the temperature of the
bulb.
Thus, Honeywell TBE(X) valves with combi adsorber charge
work absolutely reliable, even in icy condition or while
defrosting using hot gas.
2. Adsorber charge with pressure limiting performance (MOP)
Refrigerant
R134a,
R401A,
R12
R22,
R407C,
R407A,
R422D
R404A,
R507A,
R402A,
R407B,
R502
Further refrigerants and MOP on request
Evaporation
temperature
range
+5 °C to -30 °C MOP A +15 °C 34 37.4
-10 °C to -30 °C MOP A ±0 °C 29 31.9
+5 °C to -45 °C MOP A +15 °C 36 39.6
-10 °C to -45 °C MOP A ±0 °C 29 31.9
-27 °C to -45 °C MOP A -18 °C 29 31.9
-10 °C to -50 °C MOP A ±0 °C 36 39.6
-20 °C to -50 °C MOP A -10 °C 34 37.4
-27 °C to -50 °C MOP A -18 °C 34 37.4
Evaporation
temperature range
+15 °C to -30 °C 34 37.4
+15 °C to -45 °C 36 39.6
±0 °C to -50 °C 36 39.6
MOP PS
PS
(bar(a))
(bar(a))
PF
(bar(a))
PF
(bar(a))
Capacities
3. Gas charge
Refrigerants and MOP on request.
With gas charged valves and MOP it is under all operating
conditions necessary that the bulb is always colder than the
capillary tube and the thermal head!
With the Honeywell TBE series the thermal head is heated
advantageously by the liquid refrigerant. The warm thermal
head is on the safe side at any time.
Type Orifice size
0.5 0.69 0.99 0.95 0.67 0.68 0.69
0.7 1.0 1.4 1.3 0.92 0.97 0.98
1.0 1.4 2.0 1.9 1.3 1.4 1.4
TBE
TBEX
* Capacities are based on t0 = +4 °C, tc = +38 °C and 1 K subcooled liquid refrigerant entering the valve.
For other operating conditions see capacity charts in Honeywell catalogue or consult the Honeywell software.
EN0H-1906GE23 R0709 2 Honeywell GmbH • Subject to change without notice
1.5 2.2 3.2 3.1 2.2 2.2 2.3
2.0 2.9 4.0 3.9 2.7 2.8 2.9
2.5 4.0 5.8 5.6 3.9 4.1 4.1
3.0 6.6 9.3 8.9 6.3 6.5 6.6
3.5 8.7 12.2 11.7 8.3 8.6 8.7
4.5 11.8 17.0 16.4 11.3 12.0 12.1
R134a R22 R407C R422D R404A R507A
Nominal capacity (kW)*