4. Remove the wallplate from the wall and drill two
3/16 in. holes in the wall (if drywall) as marked. For
firmer material such as plaster, drill two 7/32 in.
holes. Tap the wall anchors (provided) into the
drilled holes until flush with the wall.
NO
YES
NO
NO
5 FEET
[1.5 METERS]
M22258
5. Pull the wires through the wire hole on the wallplate
and position the wallplate over the wall anchors.
6. Insert the mounting screws into the wall anchors
and tighten.
Fig. 1. Select thermostat location.
Do not install the thermostat where it can be affected by:
— Drafts or dead spots behind doors and in corners.
— Hot or cold air from ducts.
— Radiant heat from sun or appliances.
— Concealed pipes and chimneys.
— Unheated (uncooled) areas such as an outside wall
behind the thermostat.
MOUNTING
HOLES
MOUNTING
SCREWS (2)
Separate Wallplate from Thermostat
1. Separate the wallplate from the thermostat. See
Fig. 2.
WALLPLATE
WIRE HOLE
THERMOSTAT
M22267
Fig. 2. Separate wallplate from thermostat.
Install Wallplate (See Fig. 3)
Mount the thermostat horizontally on the wall:
1. Pull the wires through the wire hole on the wallplate.
2. Position the wallplate on the wall with the arrow
pointing up. Level the wallplate for appearance only.
3. Use a pencil to mark the mounting holes.
WIRING
IMPORTANT
— All wiring must agree with applicable codes,
ordinances and regulations.
— Use 18 gauge thermostat wire. Shielded cable is
not required.
NOTES:
—Sensor wires must have a cable separate
from the thermostat control cable.
—Refer to Table 2 for terminal designation
descriptions.
—See Fig. 7 through 17 for wiring diagrams for
specific equipment applications.
1. Select set of terminal identifications that correspond
to your system type (conventional or heat pump).
(See Fig. 4).
Y2
L
A
W1
S1
S2
Fig. 4. Terminal identifications for system type.
2. Loosen screw terminals used for the application.
You can choose from three methods to power the
thermostat:
• Batteries only (AAA alkaline).
• 24 Vac direct connection only.
• 24 Vac direct connection with battery backup (AAA
alkaline).
Wiring 24 Vac Common
• Single-Transformer System—Connect the common
side of the transformer to the C screw terminal of the
thermostat wallplate. Leave the metal jumper wire in
place between Rc and R.
• Two-Transformer System—Connect the common side
of the cooling transformer to the C screw terminal of
the thermostat wallplate. Remove the metal jumper
wire between Rc and R.
Installing Batteries
1. Install three AAA alkaline batteries on the back of
the thermostat as marked. See Fig. 22.
BATTERIES (3)
Fig. 22. Installing batteries.
2. Locate and remove the tab labeled Remove. See
Fig. 23.
M19918
IMPORTANT
This tab must be removed in order to set the
real-time clock.
REMOVE
TAB
INSTALLATION
REMOVE DURING
INSTALLATION
REMOVE DURING
M19920
Fig. 23. Remove tab labeled REMOVE from
thermostat back.
Setting Calendar and Time
Setting Calendar
This thermostat is designed to, under normal use,
automatically keep current time and day in memory for up
to ten years once the calendar is set. There are two ways
to set the calendar for this thermostat:
SETTING CALENDAR WHEN THERMOSTAT IS FIRST POWERED
When the thermostat is first powered, the display is ready
to set the calendar and time. The thermostat proceeds
through a sequence of setup screens. See Fig. 24.
SETTING CALENDAR AFTER THERMOSTAT IS ALREADY
FUNCTIONING
See steps 1 through 4, in the Advanced Settings section,
to set year, month and day.
SET CURRENT DAY
SET MONTH
TUE WED
THU
FRI
MON
OK TO PICK MULTIPLE DAYS SCREEN LOCKED
CHANGE FILTER UV LAMP HUMIDIFIER PAD
DONE
SUN
USE ARROWS TO SET YEAR AND TIME
Fig. 24. Setting calendar and time after initial powerup.
Mount Thermostat to Wallplate
1. Align the terminal screw blocks with the pins on the
back of the thermostat.
2. Push the thermostat straight onto the wallplate until
62-3070—038
WED
THU
FRI
PM
MON
OK TO PICK MULTIPLE DAYS SCREEN LOCKED
CHANGE FILTER UV LAMP HUMIDIFIER PAD
The thermostat has advanced settings to match the HVAC
system. These settings can be adjusted to match specific
needs. Access to these settings is obtained as follows:
1. From the main screen, press SYSTEM. Five blank
touch keys show on the bottom of the screen
between DONE and CANCEL.
2. Press and hold the two blank keys on either side of
the center blank key for approximately five seconds.
(See Fig. 26.)
3. The Setup Number displays to the lower-left area of
the screen. It is a four-digit code beginning with
zero. The current setting is displayed to the right.
NOTE: To cycle through the Setup Numbers, press the
up or down arrow.
M19919
INSTALLER SETUP NUMBERS, SETTINGS, AND TESTS (TABLE 4)
Installer System Tests
Use the Installer System Test to test the heating, cooling
and fan. Refer to the latter portion of Table 4.
T
Advanced Settings
Insi
DON
t T
Followin
CANC
CAUTION
Equipment Damage Hazard.
Minimum compressor off time is bypassed
during Installer System Test
Avoid cycling compressor quickly.
IMPORTANT
Use Installer System Test to test heating, cooling
and fan. The setting chosen for System Type
(Installer Setup Number 0170) can prevent some
System Test Numbers from appearing.
M19923
Fig. 26. Entering Installer Setup.
Table 4. Installer Setup Menu.
Installer
Setup
Number
0120Date (Year Upper) 2020—20xx
Installer Setup
Name
Default
SettingAll SettingsNotes
21—21xx
Available year range: 2001 - 2178
0130Date (Year Lower) 0400-99Available year range: 2001 - 2178
Averaging would not include on-board sensor. It is
accomplished by series/parallel combinations.
2 applies only to Heat Pump applications (allowing
compressor lockout while displaying temperature).
Only shown for heat pump systems with more heat
stages than cool selected and remote sensor
selection is outdoor for control.
Must enforce a dead band between this and
Auxiliary Lockout
Only shown for heat pump systems with more heat
stages than cool selected and remote sensor
selection is outdoor for control.
Must enforce a dead band between this and Heat
Pump Compressor Lockout.
0 means no limit
Does not appear if Non-programmable is chosen.
Applies to all days of the week. With 2 selected the
“Cancel Period” option does not appear on the
display.
Only shown if system has cool stages.
Not displayed with fan set to fossil or with cool-only
systems
Only shown if system has cool stages.
Unlocked: All functions accessible.
Partial 1: Locks all but Holiday, Override, and Up/
Down.
Partial 2: Locks all but Holiday and Override.
Full: Entire interface locked/non-functional.
Only shown if system has heat stages.
Only integral gains affected. Affects control
operation in all control regimes (not just recovery
or setpoint change).
More Aggressive stops signal prior to reaching the
setpoint. (For use with oversized equipment.)
0 disables ramped recovery (step setpoint change
at period start time).
1—Heat Stage 1
2—Heat Stage 1 and 2
3—Heat Stage 1,2 and 3
00—Auxiliary Heat Off
1—Auxiliary Heat On
00—TOD/Economizer Off
1—TOD/Economizer On
Only shown if system has cool stages.
Only integral gains affected. Affects control
operation in all control regimes (not just recovery
or setpoint change).
More Aggressive stops signal prior to reaching the
setpoint. (For use with oversized equipment.)
0 disables ramped recovery (step setpoint change
at period start time).
This offset applies to both the control temperature
and to the display temperature for indoor sensor
(and remote indoor sensor).
Resets all ISU parameters to default values and
resets the schedule to default Energy Star. Retains
only calendar settings and time.
OPERATION
System Settings
Heat—Thermostat controls the heating system.
Off—Both heating and cooling systems are off.
Cool—Thermostat controls the cooling system.
Auto—Thermostat automatically changes between heat
and cool operation, depending on indoor temperature.
Fan Settings
Auto —Fan runs only when heating/cooling system is on.
On—Fan runs continuously.
Table 5 shows default program settings. See Owner’s
Guide for complete instructions to change the program.
Minimum-Off Timer Compressor
Protection
The thermostat has an adjustable Minimum-Off Timer that
can be set from zero to five minutes (Factory Setting—five
minutes). The Minimum-Off Timer can be bypassed
through the Installer System Test or it can be bypassed
permanently by setting the Minimum-Off Timer to 0
62-3070—0312
aThe thermostat default setting is two period only. To use
minutes in the Installer Setup. The Minimum-Off Timer is
activated after the compressor turns off:
— If the thermostat is system powered (common wire),
— If there is a call for cooling or heating during the
Table 5. Energy Star Default Program Settings.
(21°C)
(10°C)
Setpoints
78°F
(25.5°C)
85°F
(29.5°C)
SettingHeatCool
Auto
Auto
Fan
Schedule
PeriodTime
Occ18:00am70°F
Unocc110:00pm 55°F
a
Occ2
Unocc2
four periods, change the appropriate setup parameter.
the Minimum-Off Timer is also activated upon initial
startup and after power interruptions.
— When the Minimum Off Timer expires, “Cool On” or
“Heat On” (heat pumps only)” appears solidly in the
display and the compressor and fan turn on.
Outdoor or Indoor Temperature Sensor
Allow outdoor or indoor temperature sensor to absorb the
air for a minimum of five minutes before taking a reading.
See the Sensor instructions for more information.
Economizer/TOD Logic (Table 6)
Table 6. Operation of Terminal A.
Effective
Occupancy
Call for
Cool
Terminal A
EconomizerTOD
Occupied—EnergizedEnergized
Unoccupied YesEnergizedDe-energized
NoDe-energized De-energized
Override—EnergizedEnergized
Heat Pump Temperature Lockouts
Dual Fuel Heat Pump and Outdoor Sensor
In this operation, there is no external fossil fuel kit (dual
fuel kit) installed; the thermostat controls this function:
1. Choose correct heat pump application in Installer
Setup Number 0170.
2. Choose Outdoor Temperature Sensor for Heat
Pump Temperature Lockouts Option in Installer
Setup Number 0340.
3. Choose appropriate Balance Point Temperature
in Installer Setup Number 0350.
OPERATION IN HEAT MODE ABOVE BALANCE POINT
(OUTDOOR TEMPERATURE)
When the outdoor temperature is above the selected
Balance Point Temperature (ISU 0350), only the
compressor operates and the fan (G terminal) energizes
when the thermostat calls for heat.
OPERATION IN HEAT MODE BELOW BALANCE POINT
(OUTDOOR TEMPERATURE)
When the outdoor temperature is below the selected
Balance Point Temperature (ISU 0350), only the Fossil
Fuel (auxiliary heat) operates and the fan (G terminal)
does not energize when the thermostat calls for heat.
Heat Pump with Auxiliary (Backup) Heat and
Outdoor Temperature Sensor
1. Choose correct heat pump application in Installer
Setup Number 0170.
2. Choose Outdoor Temperature Sensor for
Control Option in Installer Setup Number 0340.
3. Choose Compressor Lockout Temperature in
Installer Setup Number 0350.
4. Choose Auxiliary Lockout Temperature in
Installer Setup Number 0360.
NOTE: There is a 5°F deadband between Compressor
and Auxiliary Heat lockout temperatures.
Operation in Heat Mode
When the outdoor temperature is:
— Below the Compressor Lockout Temperature, only the
Auxiliary Heat operates.
— Above the Auxiliary Lockout Temperature, only the
Compressor operates. See Fig. 31.
— Between the two temperatures, both the Compressor
Display does not come on.Thermostat is not being powered.Check for 24 Vac between C and Rc.
Temperature settings do not
change.
Heating or cooling does not
come on.
Thermostat is calling for Heat
(Heat on) or Cool (Cool on) but
no heating or cooling is
running.
Heat does not turn on (Heat
On is solid in the display).
Heat pump puts out cool air in
the heat mode and warm air in
the cool mode.
Both the heating and cooling
equipment are running at the
same time.
Cooling does not turn on (Cool
On is solid in the display).
The upper or lower temperature limits
were reached.
The keypad is fully locked.Check Installer Setup Number 0670 to
Thermostat minimum off-time is
activated.
System selection not set to Heat or
Cool.
System type Selection is incorrect.Check Installer Setup Number 0170 and
Heating or cooling equipment is not
operating.
Heating equipment failure.Check for 24 Vac at the equipment on the
Loose or broken wire connection
between thermostat and heating
equipment.
Changeover Valve (Installer Setup
Number 0190) is not configured to
match the changeover required by the
installed heat pump.
The heating equipment is not a heat
pump but the System Type (Installer
Setup Number 0170) is set to Heat
Pump.
Heating and cooling wires are shorted
together.
Cooling equipment failure.Check for 24 Vac at the equipment on the
Loose or broken wire connection
between thermostat and cooling
equipment.
Check that AAA batteries are installed
correctly and are good.
Check temperature setpoints.
Check Installer Setup Numbers 0600 and
0610; modify as needed.
change keypad locked options.
Wait up to five minutes for the system to
respond.
Set system Selection to correct position.
make sure correct System type is chosen.
Check wiring.
Check Installer Setup Number 0170 and
make sure correct system type is chosen.
Verify operation of equipment in System Test
mode.
secondary side of the transformer between
power and common. If voltage is not present,
check the heating equipment to find the
cause of the problem.
Check for 24 Vac between the heat terminal
(W) and transformer common. If 24 Vac is
present, the thermostat is functional. Check
the heating equipment to find the cause of
the problem.
Check for 24 Vac between the heat terminal
(W) and transformer common. If voltage is
not present, check wire connection (loose or
broken) between the thermostat and the
heating equipment.
Set Changeover Valve (Installer Setup
Number 0190) to match the changeover
required by the installed heat pump.
Set System Type (Installer Setup Number
0170) to match the installed heating and/or
cooling equipment.
Separate the shorted heating and cooling
wires.
secondary side of the transformer between
power and common. If voltage is not present,
check the cooling equipment to find the
cause of the problem.
Check for 24 Vac between the cool terminal
(Y) and transformer common. If 24 Vac is
present, the thermostat is functional. Check
the cooling equipment to find the cause of
the problem.
Check for 24 Vac between the cool terminal
(Y) and transformer common. If voltage is not
present, check the wire connection (loose or
broken) between the thermostat and the
cooling equipment.
62-3070—0314
SymptomPossible CauseAction
Fan does not turn on in a call
for heat (electric furnace).
Heating equipment is running
in the cool mode.
Heating equipment does not
turn off and heat temperature
setting is set below room
temperature (Heat On is not in
the display).